FIREYE FLAME SCANNERS

Similar documents
Distributed By: M&M Control Service, INC

FIREYE FLAME SCANNERS

FIREYE FLAME SCANNERS

Fireye FLAME SCANNERS

FIREYE FLAME SCANNERS

MBCE-110/230UV Flame Sensor Module

DESCRIPTION AND INSTALLATION

Distributed By: M&M Control Service, INC

DESCRIPTION AND INSTALLATION

SOLID STATE Burner Management Controls SERIES D40-41

DESCRIPTION AND INSTALLATION

MBCE-110/230FR Flame Sensor Module

FIREYE C9707A ALL FUEL SCANNER

Eclipse 90 UV Scanner Model A Version 1

MBCE-110/230FR Flame Sensor Module

UV Scanner. Model Specification. Introduction. 854 Instruction Manual

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

MBUV-100D, MBUVS-100D MBIR-100D, MBFR-100D DIN RAIL MOUNT FLAMEWORX MODULES

55UV5 SCANNER MODEL 1010

NXM2G Installation and Operating Manual

Solid State Burner Management Controls Series D10-20 for Automatic Burners

FLAME SAFEGUARD FOR BURNER MANAGEMENT SYSTEMS

ED510 DISPLAY MODULE. FOR USE WITH FIREYE FLAME-MONITOR AND MicroM BURNER MANAGEMENT CONTROLS DESCRIPTION INSTALLATION APPROVED

FIREYE E210/211 FLAME-MONITOR

Eclipse Self-Check UV Scanner

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

FIREYE NXF4000 ADVANCED BURNER MANAGEMENT SYSTEM with INTERNAL FLAME SAFEGUARD

SIL3. C7961E,F Dynamic Self-Check Ultraviolet Flame Detector. Capable APPLICATION FEATURES PRODUCT DATA. Contents

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7915A Infrared Flame Detector

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7061C/F ULTRA VIOLET FLAME DETECTOR FEATURES APPLICATION PRODUCT HANDBOOK. Contents

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

UV Flame Supervision System

FLAME SAFEGUARD & COMBUSTION CONTROLS. Preface

E340 BOILER CONTROL INSTALLATION MANUAL

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

C7007A, C7008A, C7009A Flame Rod Holder & Flame Rod Assemblies

FIREYE FLAME SAFEGUARD CONTROLS DESCRIPTION

E110 FIREYE FLAME-MONITOR BURNER MANAGEMENT CONTROL FOR USE WITH THE MICROPROCESSOR-BASED EP AND EPD STYLE PROGRAMMER MODULES

OPERATING AND MAINTENANCE MANUAL

LAE10 LFE10. Use. Series 02

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas

IN TEXAS CALL (800) FIREYE. CONTRACT No. TXMAS (800)

North American Flame Detector Adapters 8832 through 8839 and Series R

24 VAC SYSTEM CONTROL KIT Model: CK-91F and CK-91FG

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

C7061A Dynamic Self-Check Ultraviolet Flame Detector

FLAME DETECTOR ADAPTERS 8832 through 8839 and Series R Bulletin 8832

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071

ECLIPSE INFORMATION GUIDE

Fire Bowls and Fire Bowl Inserts (Automated Operation) Operating and Maintenance Instructions

Columbia Boiler Company

C7012A,C,E,F,G Solid State Purple Peeper Ultraviolet Flame Detectors

Fire-Water Bowls Model 100

RK / RK Methane Detector Operator s Manual

TYPE 85UVF/IRF Integrated Flame Scanner with Internal Flame Relay

Burner Company. Flame Safeguard Systems. Bulletin IG-1. Bulletin FS-1

FIREYE MODULAR M-SERIES II

CINCINNATI, OH USA

FIREYE BurnerPRO MICROPROCESSOR-BASED INTEGRATED BURNER MANAGEMENT CONTROL DESCRIPTION. with UV & FR Flame Amplifiers

INDITHERM. Low temperature gas burners

1.03 DELIVERY, STORAGE, AND HANDLING Heater will be stored to secure against damage and handled per manufacturer s recommendations.

Flame Safeguards LFE10. Building Technologies HVAC Products

Interrupted Ignition Series Oil Primary Control

PRODUCT: SEL-SV-MCQ-O5- K6 VERSION TECHNICAL SHEET 1/5 SAC

Flame Safeguards LFE10. Building Technologies HVAC Products

TYPE 105F1-1 Integrated Flame Scanner and Temperature Analyzer

TJERNLUND PRODUCTS, INC.

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS DU/DUH DUAL OUTPUT RANGE INFRARED TUBE HEATERS

FIREYE MODULAR MicroM FLAME SAFEGUARD CONTROLS

GRAND EFFECTS Fire-Water Bowls Model 100

SECTION GAS-FIRED RADIANT HEATERS

Flame Rod Manual. Publication Rev A

RK-05 Combustible Gas Transmitter Operator s Manual

FIREYE EPD260, EPD261, EPD270 PROGRAMMER MODULES

RK/ RK Combustible Gas Detector Operator s Manual

INFRARED RADIANT HEATERS

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

S55XB and S55XBE Series Viewing Heads

AUR300C, AUR350C. Advanced Ultraviolet Burner Controller

SIL3. C7012A,C,E,F,G Solid State Purple Peeper Ultraviolet Flame Detectors. Capable FEATURES APPLICATION PRODUCT DATA. Contents C7012A,E,G C7012C,F

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

Flame Safeguard Fault Code Diagnostics

Tox-COMB/ANA Combustible Gas Transmitter Operator s Manual

TYPE 95IR/95UV/95DS. Integrated Flame Scanner with Internal Flame Relay TUV SIL2 DESCRIPTION MODEL S1, S2. RoHS Compliant to EU Directive 2002/95/EC

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

ABB. Measure IT Uvisor System Flame scanner for fuel oil and coal flame. UR600 IR Mod flame scanner Product Data Sheet (rev.

AUR300C. Advanced Ultraviolet Burner Controller

Model TL104 MANTL104. Test Lamp for Flame Detection

Instruction Manual E4 ChamberIR Heater

UV - flame detector dual fuel burners for intermittent burner operations

VMS-3. Part Number: Ultraviolet Systems VMS-3. Installation, Operation & Maintenance

1500 SERIES SMALL CAPACITY ULTRA 2 LOW NO X TM BURNER

Single stage operation oil burner

RK Transmitter Technical Notice

7800 SERIES Relay Modules

QRA10... QRA53... QRA55...

Transcription:

UV90 SC-102 MAY 2002 FIREYE SCANNERS UV1A UV8A UV non self-checking Scanner Models: UV1A3, UV1A6, UV8A, UV2, UV2A6, UV2C,45UV2, 45UV3, UV90-3. UV90-6, UV90-9 For UV self-check Scanners refer to SC-101 For Infrared Photocell Scanners refer to SC-103 APPROVED 45UV2 DESCRIPTION 45UV3 The UV1A3/6, UV2/UV2A6/UV2C, 45UV2, 45UV3, UV90-3/6/9 Scanners are used with the M-Series, M-Series II, MicroM, FlameWorx, MB-2, P, C, and D-Series controls as well as the Fireye -MONITOR and Nexus System. The UV1A3/6 scanners come with 3 ft. and 6 ft. shielded flexible cables. The UV2 scanner comes with 36 inch (915mm) shielded flexible cable. The UV2C comes with 36 inch (915mm) unshielded lead wires. The UV90-3/6/9 is available with 3 ft., 6 ft. and 9 ft. shielded flexible cables. The UV8A Scanner is a 90 right angle ultraviolet flame scanner used in conjunction with the M-Series, M-Series II, MicroM, FlameWorx, MB-2, P, C and D series controls as well as the Fireye -MONITOR TM. It is available only with 72 inch (1830mm) unshielded lead wires. The 45UV2 Scanner is a non self-checking scanner in a die cast aluminum housing with a 1 inch NPT threaded mount. The 45UV3 Scanner has a rugged cast housing that mounts on a 3/4 inch pipe with sleeve and setscrew. The replaceable UV tube is mounted in a vertical position for greater sensitivity. Non selfchecking. The UV90 Series Scanners are designed for front and lateral (90 ) mounting which, in some applications allow the scanners to obtain a clearer view of the flame. The UV90, with its exclusive snug-fit mounting block, eliminates the need for a threaded sight pipe. The UV tube is made of quartz and is filled with a gas that ionizes when struck by UV radiation from the flame. In the absence of UV radiation, the gas acts as an insulator between two electrodes which are mounted inside the tube. These electrodes are energized continuously by a high voltage. During combustion, UV radiation ionizes the gas, causing current pulses to flow between the electrodes. These current pulses result in a flame signal which is transmitted to the amplifier in the control, where it is processed to energize or hold in the flame relay. WARNING: When installing or replacing UV scanners, a minimum pilot turndown test on pilot ignited burners and a spark pickup test on all burners must be performed. Refer to bulletins E-1101, C-4000 or MC-5000 for recommended procedures. 1

APPLICATION UV scanners are recommended for detecting flames from standard fuel gases, some waste gases and light oil fuels such as No. 2 oil. Flames from heavier oils can be detected with UV scanners but the unburned fuel shroud and/or atomization shroud can block passage of the UV from the flame zone to the UV tube, causing nuisance burner/boiler trips. Infrared detection is recommended for fuel oil heavier than No. 2, and some installations where waste gases are burned together with natural gas as a main flame. NOTE: Certain safety codes and regulations require the use of self-checking ultraviolet scanners. For information on self-checking UV scanners, refer to Bulletin SC-101. SPECIFICATIONS IMPORTANT NOTE Operating Voltage: APPLICATION REFERENCE (S1-S2): 560-610 VAC 50/60 Hz Operating Temperature Limits: Maximum: 200 F (94 C) Minimum: -40 F (-40 C) Humidity: 85% RH maximum non-condensing UV1A3: 36 in. (915mm) shielded leads UV1A6: 72 in. (1830mm) shielded leads UV8A: 72 in. (1830mm) unshielded leads, 90 right angle mount UV2: 36 in. (915mm) shielded leads UV2A6: 72 in. (1830mm) shielded leads UV2C: 36 in. (915mm) unshielded leads 45UV2-1020 1 in. NPT Mount 60 Hz, 72 in. (1830mm) unshielded leads 45UV3-1050 3/4 in. Sleeve/Setscrew Mount, 72 in. (1830mm) unshielded leads UV90-3 36 in. (915mm) shielded leads UV90-6 72 in. (1830mm) shielded leads UV90-9 108 in. (3660mm) shielded leads For scanner dimensions refer to Figures 2 and 4. The information provided in this bulletin is directed to assist boiler and combustion service technicians who are experienced in the installation and operation of Fireye Flame Safety equipment. Persons not familiar with Fireye products should contact the nearest Fireye representative or other qualified service group. The UV1A, UV2, UV8A, 45UV2, 45UV3 and UV90 as well as all other Fireye scanners, are designed to be used exclusively with the appropriate Fireye Flame safeguard and Burner Management controls. The application of these scanners to other than Fireye equipment should be reviewed for approval by Fireye. UV1A, UV2, UV8A, 45UV2, 45UV3 and UV90 can be used only with the following FIREYE flame safeguard controls. FIREYE -MONITOR MB-2 SERIES MicroM M-SERIES I &II D SERIES PFM ADAPTOR KITS WORX NEXUS OTHER To be used with EUV1 Amplifier Card Use with 61-3359 UV Amplifier MAUV1 MAUV1T MEUV1 MEUV4 All D-Series using 72DUV1 Amplifier PFM2UV PFM3UV MBUV-300D MBUV-310D NX3000 NX3100 NX4000 NX4100 C-Series P-Series 2

CAUTION: The UV1A, UV2, UV8A, 45UV2, 45UV3 and UV90 ultra-violet flame scanners and associated amplifier modules are non-self checking UV systems and should be applied only to burners that cycle often (e.g.: a minimum of once per 12 hours) in order for the safety checking circuit to be exercised. If component checking is required during burner operation for constantly fired burners, utilize the self-checking ultra-violet flame scanners (45UV5) with associated amplifier module (EUVS4), (MEUVS) or (MBUVS) or the infrared flame scanner (48PT2) with associated Auto Check amplifier (E1R1, E1R2, E1R3, MEIR1, MEIR4). FIGURE 1. TYPICAL SCANNER MOUNTING FRONT PLATE 1/2'' SWIVEL MOUNT 1/2'' SWIVEL MOUNT #60-302 UV1A #60-302 STANDARD MOUNTING AIR ENTRY (PURGE AND COOLING) STANDARD MOUNTING WITH PURGING/COOLING AIR UV1A 1/2'' SIGHT PIPE 1/2'' SWIVEL MOUNT #60-302 UNION COUPLING #60-1257 WITH QUARTZ WINDOW #60-1290 WITH QUARTZ LENS UV1A ALTERNATE STANDARD MOUNTING (NOT ADJUSTABLE) MOUNTING FOR EXCESSIVE FURNACE OR WINDBOX PRESSURE 1/2'' SWIVEL MOUNT #60-302 HEAT INSULATOR #35-69 UV1A MOUNTING WITH HEAT INSULATING NIPPLE NOTE: UV1A AND UV8A SCANNERS MOUNT ON 1/ NPT PIPE, UV2 AND UV2C SCANNERS MOUNT ON 3/8" NPT PIPE. FIGURE 2. SCANNER MOUNTING FOR UV90 1.406" (35.7mm) POSITION SCANNER FOR OPTIMUM VIEW OF TIGHTEN SCREW TO SECURE SCANNER IN MOUNTING BLOCK TO A MINIMUM OF 6 IN/LB.TORQUE DRILL (2).1065 IN FOR #6/32 SELF TAPPING SCREWS 0.880" (22.3mm) 1.90" (48.2mm) UV90 MOUNTING BLOCK (INCLUDED WITH UV90) 1.48" (37.6mm) 0.875" (37.6mm) 3.75" (95.7mm) 0.5" (12.7mm) UV90 3

ACCESSORIES PART NUMBER DESCRIPTION 60-302 1 / 2 in. Swivel Mount 35-69 Heat Insulator 1 / 2 in. NPT threads each end, (male x female). 60-1257 1 / 2 in. NPT Union with quartz window 60-1290 1 / 2 in. NPT Union with quartz lens to increase sensitivity 4-314-1 Replacement UV tube for 45UV2, 45UV3 INSTALLATION OF UV1A, UV2, UV8A, 45UV2, 45UV3, UV90 SCANNERS WARNING: THE LEADS FROM THE UV8A AND UV2C SCANNER TO THE CONTROL MUST BE SHIELDED TO PREVENT ELECTRICAL NOISE FROM GENERATING A FALSE SIGNAL TO THE CONTROL. Where possible, obtain the Burner Manufacturer s Instructions for mounting the scanner. This information is available for most standard burners. The scanner mounting should comply with the following General Instructions: 1. The quartz UV tube is brittle. Care must be exercised to avoid dropping or otherwise striking the scanner with force. Keep the scanner protected until mounted. 2. Position the UV scanner within 36 inches of the flame to be monitored. 3. Select a scanner location that will remain within the ambient temperature limits of the UV Scanner (200 F). If cooling is required, use an insulating coupling (Fireye P/N 35-69). 4. The UV Scanners are designed to seal off against pressures up to 1 PSI. To seal against higher pressures, install a union coupling with quartz window (P/N 60-1257). Add cooling air to reduce the scanner sight pipe temperature. (Not applicable to UV90). 5. Install the scanner on a standard 1/2 in. NPS (3/8 in. for UV2/UV2A6/UV2C, 1 in. NPT for 45UV2, 3/4 in. for 45UV3) pipe whose position is rigidly fixed. If the scanner mounting pipe sights through the refractory, do not extend it more than halfway through. Swivel flanges are available if desired (P/N 60-302). The sight pipe must permit an unobstructed view of the pilot and/or main flame, and both pilot and main flames must completely cover the scanner field of view. Oil and gas flames radiate more ultraviolet energy from the base of the flame than from further out in the flame. This fact should be considered when installing the scanner sight pipe. SCANNER MUST HAVE UNOBSTRUCTED VIEW OF MUST COMPLETELY COVER SIGHT OPENING NOT THIS NOT THIS BUT THIS NOT THIS NOT THIS BUT THIS 6. Since the radiated energy from an electric spark ignitor is very rich in the UV region, the field of view should be aimed so that it does not see an electric spark ignitor nor any reflector that is close to the spark. CAUTION: The unprotected leads must be run in electrical conduit in order to eliminate pickup of electrical noise which could present an unsafe condition. To prevent spark pickup by the UV detector, close and/or disconnect all pilot and main fuel valves. Operate the control through a burner startup cycle to determine that ignition spark cannot be detected. Burner will not ignite if spark is detected. 7. Avoid running the scanner cables or conduit in close proximity to hot surfaces at the burner. 8. Avoid running the scanner conduit in close proximity to high energy ignition wires. 4

9. Smoke or unburned combustion gases absorb ultraviolet radiation. On installations having negative pressure combustion chamber, a small hole drilled in the scanner sight pipe will assist in keeping the pipe clean and free of smoke. For positive pressure furnaces, provide clean air to pressurize the sight pipe, if necessary. 10. Two UV Scanners may be installed on one burner if it is necessary to view two areas to obtain reliable detection of the flame. They should be wired in parallel. 11. To increase scanner sensitivity with the UV Scanners, a quartz lens permits location of the scanner at twice the normal distance. (Union w/quartz lens P/N 60-1290). 12. Request the assistance of any Fireye Field Office for recommendations of a proper scanner installation on a non-standard application. CAUTION: Ultra-violet tubes can simulate flame when exposed to high levels of X and GAMMA radiation. The table below indicates the maximum dose of radiation that a UV tube can be exposed to safely. SOURCE MAXIMUM DOSE Cobalt 60 (CO 60 ) 7.5mR/Hr Iridium 192 (IR 192 ) 1.0mR/Hr X-Ray 4mR/Hr 150kV @ 0.2mA X-Ray 1mR/Hr 150kV @ 5mA Minimum Pilot Test This test assures that the flame detector will not detect a pilot flame too small to reliably light off the main flame. The test should be made on every new installation and following any repositioning of the flame detector. THE MINIMUM TESTS MUST BE ACCOMPLISHED BY A TRAINED AND QUALIFIDED TECHNICIAN. FIGURE 3. REFRACTORY REFRACTORY REFRACTORY SCANNER SCANNER SCANNER INSUFFICIENT MINIMUM NORMAL SPARK REJECTION TEST. CAUTION: The scanner must not sight the ignition spark directly or any part of the burner that can reflect the spark back to the scanner. the scanner must not see a a pilot flame that is too small to reliably ignite the main flame. Test procedures vary according to the control used. See procedures as described in the technical bulletin for the control being installed. 5

WIRING - UV SCANNERS To connect the scanner to the control, the UV1, UV2 and UV90 Scanners are supplied with up to 96" of flexible cable. The 45UV2 and 45UV3 are supplied with 72 in. (1830mm) lead wires. Install them in a suitable length of flexible armor cable and connect it to the control. A conduit connector is supplied with the scanner. Connect black wires (UV tube) of the 45UV2 to terminals 14 & 15 of the appropriate P- Series and for the 45UV3, to terminals S1 & S2. If it is necessary to extend the scanner wiring, the following instructions apply: Scanner wires should be installed in a separate conduit. The wires from several scanners may be installed in a common conduit. Selection of Wire 1. Use #14, 16, or 18 wire with 75 C, 600 volt insulation for up to 100 foot distances (signal loss approximately 20% at 100 feet). 2. For extended scanner wiring up to 500 feet, or for shorter lengths to reduce signal loss, use a shielded wire (Belden 8254, RG-62/U coaxial cable, or equal) for each scanner wire. The ends of the shielding must be taped and not grounded. 3. Asbestos insulated wire should be avoided. 4. Multiconductor cable is not recommended. 5. High voltage ignition wiring should not be installed in the same conduit with flame detector wires. CAUTION: Keep scanner leads well clear of ignition high voltage wiring or any other high voltage or high current wiring in order to prevent false signal pickup in the scanner leads. WARNING: Protective filtered lenses should be worn when viewing flame. Infrared and ultraviolet energy can be damaging to the eyes. TENANCE Ultraviolet Scanners The viewing area of the scanner must be kept clean. Even a small amount of contamination on the lens will reduce the flame signal reaching the detector by a measurable amount. Wipe the viewing area routinely using a soft cloth dampened with concentrated detergent, then wipe dry. Flame Signal Strength Routine observation of the flame signal strength will forewarn any deterioration in the capability of the flame detector or its application. Periodic Safety Check It is recommended that a procedure be established to test the complete flame safeguard system at least once a month,. This test should verify the proper operation of all limit switches and safety interlocks as well as flame failure protection and fuel safety shutoff valve tightness. Rotation It is recommended that control and scanner units purchased as spares be installed periodically to ensure proper operation. 6

TROUBLESHOOTING NON SELF-CHECKING UV SCANNERS ZERO OR LOW SIGNAL 1. Zero volts at test jacks on control. Make sure scanner has good view of the first 1 / 3 of flame. Reposition scanner for best flame signal. If no signal... 2. Check for approximately 500-610 VAC across S1-S2 on control, with no flame present, as follows: Use meter with 20k ohms/volt sensitivity. Deenergize control. Close and secure all fuel valves. Energize control and measure voltage across S1-S2. 3. If voltage across S1-S2 is acceptable... With control energized, remove scanner from burner and bring it to within a few inches of a UV source such as a gas lighter or propane torch. Check for flame signal at control. 4. If no flame signal... Make sure scanner lens is clean and dry. Deenergize control and check continuity of leads between scanner and control. Replace scanner Replace amplifier or control. 5. If voltage across S1-S2 is low, check L1-L2 for proper line voltage. If line voltage is good: Deenergized control, remove scanner lead wires from terminals S1 and S2. Energize control and recheck for proper voltage across S1 and S2. If voltage across S1 and S2 is good, replace scanner or lead wires. If voltage across S1 and S2 is low, replace amplifier or control. FALSE SIGNAL 1. Control will not start burner. Check control wiring, all limits and interlocks. Verify flame signal at test jacks upon energizing control. 2. Flame signal appears at test jacks when no flame is in combustion chamber. Deenergize control to remove scanner leads from S1-S2. Close and secure all fuel valves. Energize control. Check for induced voltage pickup to amplifier. 3. Burner starts up with scanner removed from S1-S2. Deenergize control and connect scanner to S1-S2. Energize control. Check scanner for runaway condition. Look for a blue glow in the UV tube. If glow is present, replace scanner. If no glow is present, check to see that scanner leads are well clear of ignition or other noise carrying lines. 4. Burner does not start up even with scanner removed from S1-S2. Check control wiring, all limits and interlocks. Replace control/amplifier. 7

FIGURE 4. UV SCANNER OUTLINE DIMENSIONS UV8A 1/ NPT 2 1/4" (57.2mm) UV1A3/6 (50.8mm) 3/8" NPT (9.5mm) UV2/UV2C/UV2A6 (50.8mm) 1 1/ (38.1mm) 1" OD (25.4mm) 0.70" Dia. fitting (17.8mm) for water-tight conduit Shielding of 7 (1830mm) leads is required UV1A3-36" (915mm) Flexible Cable UV1A6-7 (1830mm)Flexible Cable 7/8" (22.2mm) UV2 UV2C 36" (915mm) Flexible Cable 36" (915mm) Lead Wire (shielding required) HOLE FOR 3/4 (19mm) SIGHTING PIPE 2 7/8" (73mm) 3 1/4" (82mm) SCREW, 1/4" - 20 THD 72 LEAD 1830mm) 2 (51mm) CLEARANCE REQUIRED TO REMOVE UV NON SELF-CHECK SCANNER TYPE 45UV5/45UV2 MODEL 1020 8 1/4" (210mm) (51mm) 4" (102mm) 1 11/16" HEX (43mm) UV SCANNER TYPE 45UV3 MODEL 1050 (50.8mm) 1 5/8" (41mm) 3/8" - 18 NPT FOR PURGE AIR CONNECTION 1" - 11 NPT FOR SIGHT TUBE WARNING: The leads from the UV1A, UV8A, UV2C and UV90 Scanners to the control must be shielded to prevent electrical noise from generating a false flame signal to the control. NOTICE WARRANTIES When Fireye products are combined with equipment manufactured by others and/or integrated into systems designed or manufactured by others, the Fireye warranty, as stated in its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the combined system or its overall performance. FIREYE guarantees for one year from the date of installation or 18 months from date of manufacture of its products to replace, or, at its option, to repair any product or part thereof (except lamps, electronic tubes and photocells) which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order. THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANTABILITY OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED. Except as specifically stated in these general terms and conditions of sale, remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or repair as above provided. In no event shall Fireye be liable for consequential or special damages of any nature that may arise in connection with such product or part. FIREYE SC-102 3 Manchester Road MAY 2002 Derry, New Hampshire 03038 USA Supersedes March 2001 www.fireye.com 8