Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Similar documents
Low Global Warming Refrigerants For Commercial Refrigeration Systems

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

A Review of Household Compressor Energy Performance

Experimental and Numerical Steady-State Analysis of a Top-Mount Refrigerator

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Investigation of Evaporator Performance with and without Liquid Overfeeding

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Low GWP Refrigerants for Air Conditioning Applications

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

An Experimental-Numerical Procedure to Characterize Compressor Performance under Cycling Operating Conditions of Refrigerators

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Evaluation of HCFC Alternative Refrigerants

Exploring the Performance Characteristics of CO2 Cycles in a Breadboard-Type Test Facility

Study of R161 Refrigerant for Residential Airconditioning

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Performance of an Improved Household Refrigerator/Freezer

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Purdue e-pubs. Purdue University

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Experimental Mapping of the Thermodynamic Losses in Vapor Compression Refrigeration Systems

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

Adsorption refrigeration system using waste heat

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

Alternative Refrigerants For Household Refrigerators

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

Dynamic Models of a Home Refrigerator

Optimisation Of Expansion Valve Control In Refrigeration Appliances Under Cyclic Operation

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge

System Modeling of Gas Engine Driven Heat Pump

Modeling And Testing Of R23/R134a Mixed Refrigerant System With Water Cooled Separator For Low Temperature Refrigeration

POTENTIAL OF NON - AZEOTROPIC REFRIGERANT MIXTURE AS WORKING REFRIGERANT IN HOT WATER HEAT PUMPS. FJ Smit and JP Meyer

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Dynamic Simulation of Liquid Chillers

Efficiency of Non-Azeotropic Refrigerant Cycle

Experimental comparison of a cascade refrigeration system operating with R744/R134a and R744/ R404a.

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Compendium DES July 2016, CARN

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

*Corresponding author;

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

INFLUENCE OF REFRIGERANT CHARGE AND AIR INLET TEMPERATURES ON THE PERFORMANCE OF AN AUTOMOTIVE AIR CONDITIONING SYSTEM

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Performance investigation of Air-conditioning system using ejector as expansion device

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

1.1. SCOPE OF THE WORK:

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Theoretical analysis of low GWP mixture R600a/ R1234ze as a possible alternative to R600a in domestic refrigerators

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Dynamic Simulation of HFC-134a Flow Through Adiabatic and Non-Adiabatic Capillary Tubes

Transcription:

568, Page Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors Jose N. FONSECA *, Rodrigo KREMER, Thiago DUTRA 2 EMBRACO, Research & Development Group, Joinville, Santa Catarina, Brazil Jose_Fonseca@embraco.com.br Rodrigo_kremer@embraco.com.br 2 Department of Mechanical Engineering, Federal University of Santa Catarina Florianópolis, SC, Brazil dutra@polo.ufsc.br * Corresponding Author ABSTRACT In a conventional cooling system, refrigerant superheating inside the compressor is largely responsible for overall energy losses, increasing the compression specific work and decreasing the cooling capacity. In heat pump applications, superheating not only affects the compression loss, but also the specific heating capacity of the system, since the inlet temperature of the condenser depends on the final temperature of compression. Kremer et al. (20) proposed a new approach to identify and understand the superheating losses in compressors submitted to heat pump applications. In this paper, a more accurate approach is proposed and the effects of refrigerant superheating are analyzed using a compressor thermal model. Different configurations of compressors are experimentally and numerically evaluated in order to validate the theoretical model. The obtained results follow the trend establied by the theoretical purpose.. INTRODUCTION The heating systems grounded on the vapor compression principle have become more and more attractive due to its higher efficiency levels. Thus, the demand for high efficiency heat pumps has increased significantly and motivates researches to continually develop this type of systems. The compressor is one of the most studied components of a heat pump system. Horn (976) identified some characteristics of the compressor that impacts the heat pump systems performance. Several critical issues were pointed out, such as: liquid handling, external oil circulation, high mean load of bearings and operating time. Squarer et al. (976) mentioned the necessity of redesigning reciprocating compressors for heat pump applications, especially for low evaporating temperatures. The authors presented a numerical analysis, comparing the reference compressor with a modified one. Among all modifications suggested, the suction gas insulation seemed to be the main source of performance gain (5% to 5%), under low back pressure (LBP) conditions. Giuffrida (984) presented a compressor-condenser concept as a high efficiency solution for heat pump applications. The layout guarantees the compressor cooling by the water flow inside the heat-exchanger. According to the author, it is possible to obtain an improvement between 0% and 5% on the heating COP due to the discharge heat recovery and superheating reduction. It is well known that, for household refrigeration compressors, a significant portion of the energy losses is associated with refrigerant superheating before (i.e., along the suction gas path inside the compressor) and during the vapor

568, Page 2 compression process (Possamai & Todescat, 2004). Such a useless superheating provides a reduction of the refrigerant mass flow rate, and an increase of the specific compression work (Gosney, 982). Kremer et al. (20) analyzed the relationip between the compressor superheating and the system performance as the compressor is submitted to heat pump and refrigeration applications. In addition, a new approach to identify the superheating losses in the heat pump system was suggested. Therefore, part of this study will be presented here and a more accurate approach will be proposed. Figure illustrates the decrease of COP as a function of the initial compression temperature for a single stage (7.2 o C/54.4 o C) refrigeration system operating with R-34a. The COP, Capacity and Power Consumption were calculated considering a refrigeration cycle with: a) isentropic compression in a specified initial temperature; b) No pressure drop and no subcooling at the condenser; c) Isenthalpic expansion; d) No pressure drop and outlet temperature equal to 20ºC in the evaporator. The COP is normalized with respect to the COP of a reference cycle in which the initial compression temperature is 20 o C. In other words, the reference cycle presents no superheating inside the compressor, until the refrigerant is compressed. It is also observed that the compression power remains almost constant and the refrigerating capacity decrease as the useless superheating is varied. It is clear that useless suction gas superheating provides a compressor performance decrease for a refrigeration system. However, regarding to heat pump applications, such a performance behavior is not the same. To ensure this statement, the following analysis is proposed: consider a compressor with a fixed loss in bearings and electrical motor. Figure 2 ows the COP and the heating capacity when that loss is not used to increase the initial compression temperature (20 C) and when this loss is 00% used to increase the initial temperature (40 C). The COP and the capacity were normalized with respect to the COP and capacity of a cycle in which the initial compression temperature is 20 o C and there are no losses in bearings and electrical motor. This is the ideal situation (COP/COP cycle = ) and when the loss is considered, COP/COP cycle is lower than. On the other hand, if this loss is used to superheat the refrigerant gas upstream the compression, the COP increases, but it does not reach the reference cycle COP level (i.e. without losses). Hence, it is reasonable to drag out some benefit of the unavoided compressor losses. Moreover, when the suction gas superheating is provided by the discharge system heat, the heat pump performance is affected in a different manner. Figure 3 presents the COP decrease as a function of the initial compression temperature, similarly with the refrigeration case. In this situation, the suction gas superheating is given at the expense of the heating capacity. In addition, there is also a reduction of the mass flow rate. Therefore, the heating capacity decreases as the initial compression temperature increases..02 Normalized Values 0.98 0.96 0.94 0.92 CAP/CAP cy cle POT/POT cy cle COP/COP cy cle 0.9 20 24 28 32 36 40 Initial Compression Temperature [ C] Figure : Effect of superheating on COP, capacity and power (refrigeration application)

568, Page 3.05.045 0.65 0.648 Capacity Normalized.04.035.03.025.02.05.0 CAP/CAP cycle COP/COP cycle 0.645 0.642 0.639 0.636 0.633 0.63 0.627 0.624.005 0.62 20 24 28 32 36 40 Initial Compression Temperature [ C] Figure 2: Effect of superheating caused by motor and bearings heat on COP and heating capacity (heat pump application).02 COP normanized Normalized Values 0.98 0.96 0.94 0.92 CAP/CAP cy cle POT/POT cy cle COP/COP cy cle 0.9 20 24 28 32 36 40 Initial Compression Temperature [ C] Figure 3: Effect of superheating caused by discharge heat transfer on COP, heating capacity and power (heat pump application) The current analysis is intended to ow that the refrigerant gas superheating along the suction path may be beneficial or harmful to the compressor performance, depending on the heat source. Thus, for heat pump applications, it is not possible to assess the superheating loss only by evaluating the cylinder inlet temperature. 2. THEORETICAL DEVELOPMENT A traditional way of analyzing the compressor performance is dividing the energy losses in an inventory of losses. Thus, the effects of several solutions can be seen and, bottlenecks become easily identifiable. From an energetic point of view, the power consumption supplied to the electrical motor is converted into electrical losses and mechanical power. The last one is delivered to the compressor aft and part of this energy is dissipated by bearings

568, Page 4 and compression mechanism. The remaining energy is converted into thermodynamic energy, which is used to provide the mass flow of the refrigerant gas and elevation of its pressure inside the compression chamber. There are several losses involved in this thermodynamic compression process, such as pumping losses (regarded to valves and muffler losses), suction gas superheating and leakage. Nevertheless, only the superheating of the refrigerant gas is considered. Indeed, the present paper deals with to approach the superheating losses impact on compressor performance for heat pump applications. The superheating losses can be estimated by: & = & & () W Ws Ws, where the W & s,, W & s are isentropic compression powers which take and do not take into account the suction gas superheating, respectively. Both terms are referenced to the capacity computed from the superheating situation. Figure 4: Representative P-h diagram for heat pump/refrigeration application (Klein, 200) 2. Effect of the Superheating on Compressors for Cooling For refrigeration systems, W & s can be calculated using the ideal coefficient of performance. Hence, eq. () becomes: and, & m& (2) 3 W, cooling = m& 2, s,, COPs, cooling 2, s 3 COPs, cooling = (3) then, m ( h h ) & = & & (4) W, cooling m 2, s 2, s,, Physical properties are calculated from Lemmon et al. (2002). Regarding to heat pump applications, eq. (4) is unable to provide the superheating impact on the heat pump performance, because it only considers the compression power variation. In these cases, the superheating also affects the specific heating capacity.

568, Page 5 2.2 Effect of the Superheating on Compressors for Heating Since superheating modifies the compression final temperature, the discharge line temperature is altered and, therefore, the specific heating capacity of a heat pump system. Due to that, thermal management solutions may affect the specific heating capacity. In this way, it is very important to identify the superheating losses correctly. For heat pump systems, W & s can be calculated using the ideal coefficient of performance, similarly to the refrigeration application. Thus, eq. () is rewritten as: and, then, eq. () becomes: & m& (5) out 3 W, heating = m& 2, s,, COPs, heating ( h2, s h3 ) COPs, heating = (6) 2, s ( h2, s h ) ( hout h3 ) m& & (7) W, cooling = m& 2, s,, 2, s 3 Comparing eq. (4) and eq. (7), one notices that the first term of the right hand side of eq. (7) presents a term to assess the superheating impact on the specific heating capacity. 3. RESULTS AND DISCUSSIONS A 60 Hz reciprocating compressor operating with R34a was selected for the analysis. The compressor was submitted to an operating condition, represented by a pair of evaporation and condensation temperatures, 7.2ºC/54.4ºC. The tests were conducted in a calorimeter facility following refrigerating conditions establied by standards, with environment and compressor inlet temperatures controlled. Typical uncertainty values are about ±2 C for temperature and ±2% for mass flow rate and electrical power measurements. Further details of the experimental facility can be found in Dutra (2008). By default, the selected compressor operates according to the indirect suction concept, which consists in a nonalignment of the compressor inlet tube with the muffler inlet. Due to this configuration, the refrigerant gas is forced to flow into the compressor cavity (where motor, discharge system and bearings are placed) before entering the suction muffler. Further this standard configuration, two additional ones were purposed to provide the superheating assessment: i. semi-direct suction, where the suction tube is aligned with the muffler inlet, and ii. insulation of the compressor body combined with the semi-direct suction concept. A computational program was employed to simulate the operation of the selected compressor, aiming to obtain its thermal profile and performance parameters. Such a program consists on a coupling between thermal and thermodynamic models and is based on an integral formulation (Lumped Parameter Methodology), firstly presented by Todescat et al. (992). The thermal model was calibrated for the semi-direct suction configuration by adjusting the global thermal conductance between components. To simulate the indirect suction configuration, the thermal conductance of the suction muffler was considered as being 0 times higher than the semi-direct configuration. Furthermore, the ell was set up as ideally insulated to simulate the insulated compressor with semi-direct suction situation. Table ows the thermal profile most important points. The temperatures for the indirect suction compressor had a good agreement comparing to the experimental results. On the other hand, the numerical result for the insulated case predicts higher temperature levels because the ell was considered ideally insulated and this is a very difficult condition to be experimentally achieved.

568, Page 6 Comparing the three configurations, one notices that the lowest muffler outlet temperature is found at the semidirect suction configuration. Additionally, the numerical simulations compute the initial compression temperature. Actually, such a temperature is the one which better represents the suction superheating level, because the suction process is ended inside the compression chamber as the suction valve closes. The semi-direct suction configuration presents the lowest value of initial compression temperature, as observed for the muffler outlet temperature. Indeed, this result is expected, since the refrigerant gas enters the compressor and is directly driven to the muffler inlet. Such a lower temperature provides the highest mass flow rate among the three configurations of the numerical result, as Fig. 5 ows. In a typical refrigeration analysis, the cooling capacity depends only on the mass flow rate, which gives the highest value in the semi-direct suction. However, regarding to heat pump systems, the heating capacity depends also on the compressor discharge temperature. Therefore, as Fig. 5 depicts, the highest heating capacity level is observed at the insulated compressor combined with semi-direct suction configuration. Error! Reference source not found. and Error! Reference source not found. ow the performance parameter results obtained by experiment and numerical simulation, respectively. Both methodologies indicate that the highest COP heating level is found at the semi-direct + insulated configuration. On the other hand, the highest COP cooling was noticed at the semi-direct suction configuration. These results reflect the importance of the criteria employed to select a compressor to be adopted in a heat pump application. Since a compressor is the best to be used in a refrigeration system is not a guarantee that it is also the best choice for an equivalent heat pump application. Table : Thermal Profile, in C. Indirect Suction Semi-direct Suction Insulated Compressor Temperatures Exp. Num. Exp. Num. Exp. Num. Compressor Inlet 35.0 35.0 34.9 35.0 35.0 35.0 Muffler Outlet 68.5 68.6 5.9 5.9 59.2 68. Initial Compression - T_ --- 78.6 --- 62.8 --- 78.8 Cylinder 89.8 96.8 86. 86. 93. 02.4 Discharge Chamber 24. 26.6 2.3 2.3 9.9 28.2 Compressor Discharge 99.6 02.8 96.2 96.2 04.8 4.4 Electrical Motor 69.9 78.5 86.5 86.5 02.8 0.8 Shell 44.8 44.0 47.2 47.2 77. 85.2 32 3 Mass Flow Heating Capacity Cooling Capacity 900 800 Mass Flow Rate [kg/h] 30 29 28 27 700 600 500 400 Capacity [W] 26 300 25 REFERENCE Semi-direct Suction SD + Insulated Compressor Figure 5: Mass Flow vs Capacity Numerical results 200

568, Page 7 Still regarding Error! Reference source not found., one observes that superheating losses behave differently in refrigeration and heat pump applications, as already noticed in COP. In cooling, the lowest superheating loss is found at the semi-direct suction configuration, which means that this is the best configuration in terms of superheating. Indeed, the COP cooling outcome agreed with that. In heating, the lowest superheating loss is indicated in the semi direct + insulated configuration. This parameter also agreed with the COP heating result. It ould be mentioned that the negative value attributed to the superheating loss is due to a measurement difficulty: temperature measurement inside the compression chamber. As already commented, the suction process ends as the suction valve closes and the gas is superheated inside the compression chamber until the compression process start. Hence, the initial compression temperature ould be used rather than the muffler outlet one to calculate h in eq. (6). Tab. 3 ows that no negative superheating losses are found, because the initial compression temperature is assessed in numerical simulations. Finally, numerical and experimental results owed the same trends. The compressor insulation combined with a semi-direct suction was found to be the best configuration to heat pump. The most probable explanation for that is that the compressor insulation hindered the heat release through the ell, which increased the amount of heat absorbed by the suction system. In this situation, the compressor insulation brought an improvement of the performance because the superheating was provided in majority by bearings and electrical motor losses. Table 2: Performance parameters experimental results REFERENCE Semi-direct SD + Insulated Suction Compressor Heating Capacity [W] 576 608 689 Cooling Capacity [W] 22 259 265 COP/COP ref heating.000.006.09 COP/COP ref cooling.000.025 0.993 c 0.69 0.65 0.77 Superheating Loss - Cooling [W] 35.3 8.9 26.9 Superheating Loss - Heating [W] 5. 2.7 -.6 Pumping Loss [W] 06.2 06.5 8.2 Bearing Losses [W] 5 5 5 Electric Motor Loss [W] 95 9 94 Table 3: Performance parameters numerical results REFERENCE Semi-direct SD + Insulated Suction Compressor Heating Capacity [W] 708 740 8 Cooling Capacity [W] 292 363 293 COP/COP ref heating.000.0.06 COP/COP ref cooling.000.047.002 c 0.78 0.70 0.97 Superheating Loss - Cooling [W] 48.5 33.2 48.7 Superheating Loss - Heating [W] 22.2 5.7 5.6 Pumping Loss [W] 05.8 08.8 05.8 Bearing Losses [W] 5 5 5 Electric Motor Loss [W] 02.9 02.0 99.2 3. CONCLUSIONS The present work presented a theoretical analysis of the superheating effect in a reciprocating compressor adopted for a heat pump application. Experimental and numerical results supported the analysis with good agreement.

568, Page 8 In the theoretical analysis, it was proposed a different way to treat the suction gas superheating when the compressor is employed in heating systems. The superheating losses impact the power consumption and also heating capacity. The effects related in the theoretical analysis were also noticed in the experimental and numerical tests, where the results owed a COP improvement as the compressor was insulated and the suction gas superheating was increased. It is important to emphasize that COP gain is possible only when the heat sources are bearings, electrical motor or any other, except the discharge line. The agreement between theoretical and experimental results brings a clear evidence of the importance of how to address the superheating issue in heat pump applications. It was also noticed the importance of using the COP heating as a criterion to select a compressor for this application, instead of only analyzing the COP cooling. NOMENCLATURE COP coefficient of performance (-) Subscripts h specific enthalpy (J/kg) cooling refrigeration m& mass flow rate (kg/s) system W & power (W) heating heat pump system out discharge line s isentropic superheating REFERENCES () Squarer, D., Sisk, F. J., Veyo, S. E., 976. Conceptual Design of a Better Heat Pump Compressor for Northern Climates. International Compressor Engineering Conference at Purdue University, West Lafayette, IN, USA. (2) Possamai FC, Todescat ML, 2004, A review of household compressor energy performance, Proc. 7th Int. Compressor Engineering Conference at Purdue, CD-ROM. (3) Lemmon EL, McLinden MO, Huber ML, 2002, REFPROP 7.0, NIST, USA. (4) Kremer, R. Fonseca Jr., J. N., Dutra, T., 20. Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. 7 th International Conference on Compressors and Their Systems, London. (5) Horn, J., 976. Design Considerations for Heat Pumps Compressors. International Compressor Engineering Conference at Purdue University, West Lafayette, IN, USA. (6) Gosney WB, 982, Principles of Refrigeration, Cambridge University Press. (7) Giuffrida, G., 984. High Efficiency Compressor Condenser in a Single Hermetic Component for Heat Pumps. International Compressor Engineering Conference at Purdue University, West Lafayette, IN, USA. (8) Klein, S. A., 200. Engineering Equation Solver. (9) Dutra, T., 2008. Experimental Investigation of the Heat Transfer in Reciprocating Compressors Adopted for Household Refrigeration. M.Sc. Thesis, PPGEM, Federal University of Santa Catarina. The authors thank Embraco for support. ACKNOWLEDGEMENT