Fusion 200, 300 & 500

Similar documents
TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data Electrical Details Connection Details Dimensions Standing Losses

Extreme Domestic Hot Water Loading System TECHNICAL DOCUMENTATION. Issue 11/09

30 SD & 45 SD CONDENSING BOILERS

MAXI & MAXI PLUS Floor mounted Pressure manager TECHNICAL DOCUMENTATION. Issue 06/14

1 Dimensions Installation Mains/boosted cold water inlet Connection to the system Drain Dimension for fixing 6

extreme HIGH EFFICIENCY HOT WATER SYSTEMS

ferroli Boiler Replacement Maxima 35C- Modena HE

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE:

Baxi System 100 HE Plus. User s Operating Instructions. Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data

Mikrofill Ethos Condensing combination boiler

Greenstar 12i/24i System

Mikrofill Ethos Condensing combination boiler

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data

Clyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw

Baxi Bahama 100. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

INSTALLATION & TECHNICAL MANUAL

Installation, operating and servicing instructions

Baxi Maxflow Combi WM

Baxi Combi 80Eco. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

USER INSTRUCTIONS & CUSTOMER CARE GUIDE Si II SERIES

Baxi Maxflow Combi FS

Cast Iron Boilers. G Series ( kW)

Multi-Elec COMPACTE BOILER

Performa 24. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions

capriz 25 capriz 28 Condensing Wall Mounted Combination Boiler Installation, Servicing & User Instructions

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

Baxi Combi 133 HE Plus Baxi Combi 100 HE Plus Baxi Combi 80 HE Plus. User s Operating Instructions

PLEASE LEAVE THIS INSTRUCTION WITH THE USER. Ecomfort 30 HE. User instructions

INSTALLATION & TECHNICAL MANUAL

Installation and Servicing Instructions. Alpha FlowSmart

Alpha FlowSmart 25 and 50

Installation, Operation and Maintenance Instructions Electric Flow Heater OM009

ecotec Instructions for installation and servicing Wall hung room sealed fan assisted condensing boiler For the installer

Greenstar 25Si/30Si USER INSTRUCTIONS & CUSTOMER CARE GUIDE

Instructions for Use Installation and Servicing

ELECTRIC COMBINATION BOILER. (European Patent No: Design Right Protected.) TH12-450U MRK 2

SEALED THERMAL STORE

Installation, Operation and Maintenance Instructions for Electric Storage Calorifier

DOMESTIC HEATING CONTROLS ARE EASY PART 1 - THE BASICS

Vote for your Installer of the year at. 9/14, 14/19 & 19/24CBi. Worcester supports the Benchmark code of practice

Performa System 12e, 18e, 24e & 28e

Compact HE. High efficiency combi boiler. Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

WALL-HUNG HIGH EFFICIENCY GAS BOILERS. Elegant, efficient and intelligent

Remeha Avanta Plus. Remeha Avanta Plus. Installation and service manual. Remeha Avanta Plus 28c. Remeha Avanta Plus 35c. Remeha Avanta Plus 39c

Assessment Schedule - TS.6

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

AquaNova. Water heater. Users Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

Osprey 2 CFL

User Guide and Important Warranty Information. Suprima HE Range. Condensing Central Heating Boiler. You can rely on

Fitting & Commissioning Instructions. EcoBlue Combi and System Range. Outdoor Sensor Kit. Kit Part No (System) Kit Part No.

R e m e h a P Technical Information. Remeha P 300. Pressurized boiler. Heat output: kw

USER INSTRUCTIONS & CUSTOMER CARE GUIDE HIGHFLOW 400 ELECTRONIC SERIES

Linea HE. High efficiency combi boiler. Users Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

CONDENSING COMBINATION BOILER. Installation, Servicing and User Instructions

ADVANCE ECB ELECTRIC COMBINATION BOILER

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600

MAX O GAZ. Condensing water heater TECHNICAL MANUAL

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

Installation and Servicing Instructions. Alpha GasSaver GS-2

User Guide. Promax SL Condensing Central Heating Boiler

STREAMLINE OVERSINK. Fitting Instructions and User Guide _iss_05.indd 1 15/09/ :46:30

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw

INSTALLATION INSTRUCTIONS FOR FLUE KIT

General safety precautions English

Installation and Commissioning Manual

ADVANCE ELECTRIC THERMAL STORE

Stored Water District Heating Interface Units. Heat Interface Units

Heat 45 & 55. User Instructions FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

Installation and Servicing Instructions. Alpha GasSaver GS-1

Clyde CK40. Cast Iron Boiler. Engineering Data Sheet 663/8 May Natural gas Class D oil Dual Fuel. 350 kw to 500 kw

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Streamline Undersink. Fitting Instructions and User Guide

British Gas 330+ High Efficiency Condensing Boiler. Instructions for Use. To b e l e f t w i t h t h e u s e r. British Gas Service Tel:

Baxi Combi 80 Maxflue

Alpha CombiMax 350 and 600

FASTflo. Working towards a cleaner future

This is a Wall Mounted Powered Flue Condensing Combination Boiler Gas Fired Central Heating Unit.

Installation and Servicing Instructions

Dovre 250 Cast Iron Gas Stove

UNIQ HEAT BATTERIES REFERENCE MANUAL_V2.2. Version: 2018_07_19_v2.2

ADVANCE STAINLESS STEEL UNVENTED HOT WATER SYSTEMS

Hamworthy. Dorchester DR-SA & DR-SE Fully Automatic and Permanent Pilot Direct Gas-Fired Storage Water Heaters. Exceeds Minimum Requirements

INSTRUCTION MANUAL T30 1MN0107 REV. 0. operates with ISO9001 certified quality system

24CDi, 28CDi & 35CDi II COMBI

Dene Bath Shower Mixer

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

Unvented Electric Water Heater 10/15 litre Undersink

With a power output ranging from 13kW to 24kW, they provide the flexible answer for the majority of traditional installation scenarios.

Performa 24 Eco HE. User Guide and Important Warranty Information. Condensing Combination Boiler

Operating instructions

Installation, Operation and Maintenance Instructions Thermaflow E Plate Heat Exchanger Package OM013

Baxi Combi 105 HE. User s Operating Instructions. Gas Fired Wall Mounted Condensing Boiler

Bath Shower Mixer

Open Vented Condensing Boilers

GREENSPRING CWi47 INSTALLATION AND OPERATING INSTRUCTIONS WALL HUNG RSF GAS CONDENSING INSTANTANEOUS WATER HEATER FOR MAINS FED DOMESTIC HOT WATER

Installation & Service Manual Remeha Avanta Range. 24c 28c 35c 39c 18s 24s 30s

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw

Transcription:

Fusion 200, 300 & 500 Installation and Operating Manual Issue 07/07 Part of The Mikrofill Group

Contents 1 Fusion 2 1.1. Safety Provisions 3 1.2. Delivery 3 1.3. Hydraulic system Diagram 3 1.4. 2 Fusions in Parallel 3 1.5. Maintenance 3 Installation 2.1. Siting the Fusion 4 2.2. DHWS Connections 4 2.3. Gas Connections 4 2.4. Condense drain connection 4 3 Commissioning 3.1. Filling and Venting the DHWS System 6 3.2. Settings 6 3.3. Altering the Temperature Setting 6 4 Fault Conditions 4.1. Explanation of Fault Codes 7 4.2. Fault Diagnosis 7 5 Technical Specifications 5.1. System Performance 8 2.5. Flue Gas / Air Intake Connection 4 2.6. Dimension Details 4 6 Guarantee 9 2.7. Heating Connection 5 2.8. Electrical connections 5 This manual should be used in conjunction with the Ethos 54C Combination boiler manual. This document has been put together with as much care as possible. All right reserved. 1

Safety Provisions Conditions Mikrofill Systems shall not be liable for any damages caused by non-compliance with the assembly instructions. Only original Mikrofill parts must be used for service purposes. It is a statutory requirement that all gas appliances are installed in accordance with the manufactures instructions and all current regulations in force, all instructions should be fully read before installing or using the appliance. All installations should be carried out by competent persons as described in the Gas Safety (Installation & Use) Regulations. i.e. CORGI registered and holding current certification. The work must be carried out by a competent person as described in the I.S. 813 Domestic Gas Installations with reference to the following codes of practices. The Manufacturers instructions MUST NOT be taken in any way as overriding statutory obligations. This boiler has been tested and certified to comply with all necessary European directives, latest building regulations and efficiency requirements for the SEDBUK scheme and as been approved with an efficiency band rating of A and is CE marked and complies with 92/42/EEC Efficiency of Hot Water Boilers Directive 90/396/EEC Gas Appliance Directive 93/68/EEC Low Voltage Directive (was 73/23) 92/31/EEC Electromagnetic compatibility Directive I.S. 813 Domestic Gas Installations The Fusion should be installed in compliance with The building regulations (Scotland-consolidated) Building Regulations (Northern Ireland) Building Regulations Water fittings regulations or water bylaws in Scotland Local water company bylaws The boiler should not be modified in any way. Any modifications will invalidate the gas approval and invalidate the warranty. Codes of Practice BS 7593:1992 Treatment of water in domestic hot water central heating systems BS5546:1990 installation of hot water supplies for domestic purposes BS5440 part 1: 2000 flues BS5440 part 2: 2000 Ventilation BS5449:1990 Forced circulation hot water systems BS6798:2000 installation of gas fired hot water boilers of rated inputs not exceeding 70kW BS6891:1989 Installation of low pressure gas pipe up to 28mm BS7671:2001 IEE wiring regulations BS4814:1990 Specification for expansion vessels BS5482:1994 installation of LPG BS7671 requirements for electrical installations BS5955-8 plastic pipe work installations ATTENTION: High Voltage Before opening the boiler casing for maintenance or servicing the 230VAC main supply to the boiler must be disconnected!! 2

1 Fusion 1.1 The Fusion The Fusion is a standalone DHW charging system that consists of a buffer tank and a combination boiler. The System is suitable for use in any building with medium to large water usage, such as swimming pools, gyms, sports clubs, fitness centres etc. The Fusion has been designed for ease of installation. For the unit to provide DHW a minimum of the following is required to be installed from the system to the unit: 1. 230Vac electrical supply 2. Mains cold water supply 3. DHWS secondary flow pipework 4. DHWS secondary return pipework 5. Gas supply pipework 6. Condense drain pipework 7. Flue gas outlet & Air intake pipework 1.3 Delivery The Fusion is delivered with the following components Fusion Fusion Installation Manual Ethos 54C Operating and Maintenance Manual 1.4 Installing 2 Fusions in parallel The Fusion is a standalone unit that functions exceptionally. Where there is a high demand for hot water there is an option to connect two units together in parallel. It is essential that the units are connected such that flow is distributed evenly through both units Ensure that pipework is equal from both units to the system flow connection. 1.2 Hydraulic System Diagram Fusion Fusion T4 Plan View of two Fusions in parallel T1 P3 P1 T3 T2 P2 T5 Legend: P1: Loading Pump P2: DHWS Recirculation Pump P3: Boiler Pump The capacity of the built in water recirculation pump is 600 l/hr at the 20 kpa setting. The maximum loss of the flow and recirculation system occurs at 65 C flow and 60 C return (3.kw). A greater loss will cause a lower return temperature and therefore a longer loading period. T1: Buffer tank upper temperature T2: Loading temperature T3: Shut down temperature T4: DHWS recirculation temperature T5: Buffer tank lower temperature 3

2000 mm Clearance 2 Installation 2.1 Siting the Fusion The Fusion should be sited on a flat stable floor, adjustable legs are provided for leveling the unit on uneven surfaces. It is recommended that a distance of 900mm is left free in front of the unit for maintenance purposes. The Fusion should be connected to the mains water supply, the concentration of chloride in the water supply should be less than 200mg/l. Should the hardness be measured at more than 14 dh then a softener should be installed to bring the hardness down to between 6 dh and 8 dh. The right hand side of the unit should be left accessable for the the hot water secondary recirculation pump. A 230 Vac supply is required adjacent to the unit. When installing the Fusion a main water kit must be used. The DHWS flow connection should be protected against a vacuum by use of an air valve. 2.3 Gas Connection All gas pipework should be installed by a competent person and in accordance with all current standards and regulations. All gas pipework should be tested fo gas tightness. At the planning stages it may be necessary to contact the local gas supplier to ensure an adequate supply of gas is available The boilers gas pipe should be calculated and sized to supply adequate gas working inlet pressure of 20mbar (minimum) for natural gas and 37mbar for LPG. Fill and drain valve Only pressure test the gas supply pipe as far as the boiler isolation valves. The gas valve cannot withstand high test pressures, since it was designed for a maximum working pressure of 60mbar. Before switching on the power supply ensure that the central heating side of the boiler is filled with water ( see page 5 for details), filling can be achieved through the fill and drain valve shown above. Connections 2.4 Condense drain connection All condensate pipework should be installed in a suitable plastic pipe material, metal pipe MUST NOT be used. All condensate pipework should have a fall of 2.5 or 44mm per metre.any condensate pipework that is subject to frost or freezing conditions should treated as external and be insulated. This pipework should be increased in size to a minimum of 32mm with a continuous fall to a suitable drain or soakaway. Type Fusion 230 VAC Switched fused spur MCWS DHWS RECIRC 200 1 1 3 /4 300 1 1 /4 1 1 /4 500 1 1 /2 1 1 /2 3 /4 3 /4 2.5 Flue Connections When deciding on the diameter and length of the flue gas pipe and the air inlet pipe please consult the ETHOS 54C Operating and Maintenance manual. 2.6 Dimensional details 1400 mm Clearance l 15 mm gas l 80/125 mm Flue gas outlet/ Air intake Free area for maintenance Model Length Width Height Weight Fusion 200 1368 mm 113 kg Fusion 300 1898 mm 130 kg Fusion 500 1975 mm 148 kg 4 Plan view of Fusion

2.7 Heating Connections The Fusion has been designed as a domestic hot water supply system, however it is possible to use the unit to supply a heating system. The following must be taken into account when adding a heating system. A suitable expansion vessel must be installed. Only Volt free control can be used. Connecting to the heating (Before filling the central heating) Remove pipework between heating flow and return on the boiler Connect the central heating flow to the left hand connection on the boiler (22mm) Connect the central heating return to the right hand connection on the boiler (22mm) Connect volt free controls to terminals 3 & 4 on the boiler Fill and vent the system once all joints are made and tightened. Flush the system thoroughly prior to operation of the unit Do not connect opentherm room thermostats and the room thermostat limit is 10ohm. 2.8 Electrical connections Failure Enabling Flush J K 21 22 23 24 25 26 21-22 Closed 24-25 Closed 15 13 pomp sensoren F G H I E A T4 Sensor B Boiler OpenTherm connection C 230 VAC Electrical supply D DHW Recirculation pump E Load pomp F T1 Sensor G T5 Sensor H T3 Sensor I T2 Sensor Optional Circuits J Fault Relay K Enabling Flush Relay L Input external signal high temperatur 2 3 4 5 6 7 N L 8 9 10 11 A L B C D BR-S-U2/Wiring diagram 5

3 Commissioning Ensure the central heating and domestic hot water pipework has been filled and vented correctly. The loading process will stop when the sytem has reached the required temperature During the loading process the pumps speed will be altering this can lead to a pulsing sound from the pumps but is not damaging to their operation 3.1 Filling and venting the domestic hot water system Step 1: Open the furthest outlet from unit Step 2: Open the mains cold water supply until all the air has been eliminated from the outlet Step 3: Open the valve on the reciculation circuit, when all of the air has been eliminated close the outlet Step 4: Check pipework for leaks Display codes during use: The display will show various codes during operation including the unit flow temperaure and one of the following: of; The Fusion hot water circuit is switched off nl; Normal loading in operation nr; The Fusion has reached its normal loading temperature hl; Anti legionella program in operation hr; The Fusion has reached its anti legionella temperature 3.2 Further Commissioning Once the system has been completely filled and vented the unit can be connected to the electrical supply. All DHWS settings are pre-set. 3.3 Temperature Setting The Fusion is factory set at 65 C DHW flow and 60 DHW return the temperature can only be adjusted with specialist equipment Ensure the following are operating correctly. The recirculation pump should operate continuously, ensure the pump is running The load pump will operate intermittently, ensure the pump turns freely The boiler should operate when the loading pocess has started 6

4 Faults 4.1 Fault codes If there is a fault in te system one of the following codes should appear The diagnosis settingcan be exited by holding the button for 5 seconds or if the button is not depressed for 10 minutes. 01 T1 Sensor fault 02 T2 Sensor fault 03 T3 Sensor fault 04 T4 Sensor fault 05 T5 Sensor fault 06 Low temperature for extended period 07 Frost protection active 08 Boiler fault 09 No communication with boiler 4.2 Diagnosis It is possible to view the operational data of each of the Fusion i.e. temperatures, this is achieved by holding the button on the controller for more approximately 5 seconds. The diagnosis number is shown for 1 second then the value for 3 seconds. So D0 D1 D2 D3 D4 D5 D6 D7 Ex software version Operating Status Current T1 temperature Current T2 temperature Current T3 temperature Current T4 temperature Current T5 temperature Load pump P1 speed (rpm) Recirculation pump P2 speed (rpm) Previous errors The last 10 errors or faults will be logged by the system. The oldest error or fault will be at the end of the list and the most recent at the start. For boiler faults please refer to Ethos 54C Boiler O&M manual. 7

5 Technical Specification 5.1 System Performance System Load Maximum 10 min. 60 min. 120 min. l/m/65 C l/m/65 C l/m/65 C l/m/65 C l/m/65 C Fusion 200 12 50 300 900 1620 Fusion 300 12 57 390 990 1710 Fusion 500 12 72 570 1170 1890 5.2 Electrical connections Failure Enabling Flush J K 21 22 23 24 25 26 21-22 Closed 24-25 Closed 15 13 pomp sensoren F G H I E A T4 Sensor B Boiler OpenTherm connection C 230 VAC Electrical supply D DHW Recirculation pump E Load pomp F T1 Sensor G T5 Sensor H T3 Sensor I T2 Sensor Optional Circuits J Fault Relay K Enabling Flush Relay L Input external signal high temperature 2 3 4 5 6 7 N L 8 9 10 11 A L B BR-S-U2/Wiring diagram C D 5.3 Dimensional details Model Fusion 200 Fusion 300 Fusion 500 Length Width Height Weight 1368 mm 113 kg 1898 mm 130 kg 1975 mm 148 kg 8

6 Guarantee Our delivery conditions and other conditions are specified in the following articles: Buffer Tank Guarantee The total guarantee for the tank spans for 10 years from the date of registration. Boiler, Pump and Controls Guarantee The total guarantee for the boiler, pump and controls spans for 2 years from date of purchase Dealing with claims Claiming the guarantee must always be done through Mikrofill Systems Exceptions The following will void any guarantee: In case of the system being used or installed in manner not described in the installation manuals The defect was caused by high pressure, low pressure or if the temperature was too hot, or the system has been damaged by frost. The data badge has been removed or damaged to an extent that it cannot be read When there is damage caused by corrosion from water leakage or agressive liquids or gasses from an external source A detailed version of the terms and conditions can be provided to you if you should require them. 9

Mikrofill Systems Ltd. West Court Merse Road North Moons Moat Industrial Estate Redditch West Midlands B98 9HL T 00 44 (0) 8452 606020 F 00 44 (0) 8452 606021 I www.mikrofill.com