Nitin Ventures FZE. (A Division of Nitin Fire Protection Industries Ltd.)

Similar documents
mechanical. OPERATION Rapidrop Global

ALARM VALVE MODEL: SDH-AVA TECHNICAL DATA : OPERATION DESCRIPTION. Flange X Groove Groove X Groove Bar (250 PSI)* WORKING PRESSURE

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

SPRINKLER ALARM TECHNICAL DATA SPRINKLER ALARM MODEL - GA

FOAM MAKER MODEL - FMA & FMA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA INSTALLATION, TESTING AND MAINTENANCE APPLICATION SPECIFICATION

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

Instructions for Installation, Operation, Care and Maintenance

TECHNICAL DATA. Wet 26a. February 22, 2009

WATER POWERED OSCILLATING MONITOR

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION

FOAM CHAMBER MODEL - FCA & FCA-S TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100. Stainless Steel Construction

FOAM CHAMBER MODEL - FCA & FCA-S TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100. Stainless Steel Construction

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

AIC Series Float & Thermostatic Steam Trap Installation and Maintenance Instructions

Discontinued Product

Series 759 FireLock Alarm Check Valve

TECHNICAL DATA OBSOLETE

TITAN FLOW CONTROL, INC.

ICS Float and Thermostatic Steam Trap Installation and Operation Manual

Technical Data. Installation

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA. 319a. January 27, 2012

SH-2000, SH-2500, AB-3000 Bimetallic Steam Traps Installation and Operation Manual SH-2000

Model DDX Deluge Valve

BERMAD Fire Protection

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

OPEN SPRINKLER SYSTEM

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

BROCHURE COMMERCIAL FIRE SPRINKLER CONNECTIONS. Product Submittal A PART OF

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

SERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK

Design Criteria. Installation

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

(Alarm Valve) & ' ( ()& * +,, & +-,. /0-

Installation and Testing of Inverted Bucket Steam Traps Manual

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

SH-300, SH-900, SH-1500, SH-1600 and SH-1700 Bimetallic Steam Trap Installation and Operation Manual

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314)

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Read and save these instructions! DRANE-KOOLER. Water tempering device Installation, operation and maintenance manual

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

The Series LFII (TY3596) Residential

INSTRUCTION MANUAL HS-229G

QUICK PRIME INSTALLATION AND SERVICE MANUAL

Installation Instructions PP-AS20 Anti-Scale System

MaxLite LED MICRO-T PANEL

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

Installation and Maintenance "L" and "LS" Series

IMPORTANT INFORMATION - PLEASE READ CAREFULLY

Instructions for Installation, Operation, Care and Maintenance

Series LFII Residential Flush Pendent Sprinklers 4.2 K-factor General Description

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-Factor General Description

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

Additional Bulletins applicable to all F1RES LL Sprinklers Wall Wetting - Bulletin 007 Design and Installation - Bulletin 140

Battery Powered In-line Valve with Watering Timer RBC 7000

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

Sprinkler Identification Number TY ECLH HSW, 8.0K, 3/4"NPT

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

PNLDII-28 Condensate Drain Instruction Manual

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

Model/Sprinkler Identification Numbers

Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Tempered Water Outlet. Hot Water Inlet.

INSTALLATION ADJUSTMENT SERVICE

INSTALLATION, OPERATION & MAINTENANCE AVANTCO SERIES 177AG OWNER S MANUAL

Model F1 Residential Sprinklers for Design Density of.10 gpm/ft 2

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

Installation, Operation and Maintenance Manual for Model 8331 Condensate Accumulator

Model/Sprinkler Identification Number (SIN) Technical Data

Ace Heaters LLC INSTALLATION and MAINTENANCE INSTRUCTIONS for ACE STORAGE TANKS INSTALLATION AND HOOKUP

Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General Description

Installation, Operation and Maintenance Guide AP3900 Series Thermostatic Mixing Valves

ZC450-IB-09/13-01 US. Instruction Booklet. Zonecheck 450

Installation & Maintenance Instructions

DRY-PAK INDUSTRIAL AIR DRYER Installation and Instruction Manual

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Ace Heating Solutions, LLC INSTALLATION and MAINTENANCE INSTRUCTIONS for ACE STORAGE TANKS INSTALLATION AND HOOKUP

IMPORTANT INFORMATION - PLEASE READ CAREFULLY

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

HIGH EFFICIENCY CIRCULATOR INSTRUCTION, INSTALLATION, MAINTENANCE AND REPAIR MANUAL

Transcription:

Model : A TECHNICAL DATA : Model Nominal Size Maximum Service Pressure Threaded Opening Mounting Flange Connection Trim Factory Hydrostatic Test Pressure Frictional Loss in Terms of Equivalent Length of Pipe (C-120) Approximate Net Weight without Trim A 200, 150, 100 & 80 NB 12 Bar (175 Psi) BSPT (NPT Optional) Vertical ANSI B16.1 FF #125 (Optional IS:1538) Steel with brass valves 25Kg./Sq.cm. (355 psi) 200NB-13.00Mtrs.(42.6 ft) 150NB- 7.50Mtrs.(24.6 ft) 100NB- 6.46Mtrs.(21.2 ft) 80NB- 3.65Mtrs.(12.0 ft) 200NB 86 Kg. 150NB 52 Kg. 100NB 36 Kg. 80NB 28 Kg. Fire Red Epoxy painted. UL Listed Size of Valve, Flange Connection & Trim details Finish Approval Ordering Information Reference NFPA 13 and NFPA 25 GENERAL DESCRIPTION Alarm Valve is a double seated clapper check valve with grooved seat design, which ensures positive water flow for alarm operation and is designed for installation in wet pipe sprinkler system. External bypass prevents false alarm under all supply pressure condition. In the event of variable pressure condition, false alarms are prevented with the provision of retard chamber, thus the design allows for installation under both variable and constant supply pressure condition. Operation of one or more automatic fire sprinklers, the water flows into the sprinkler system and the alarm valve opens, allowing continuous flow of water into the system and transmittal of alarm, both electrical and mechanical.

OPERATION The fire protection system initially when being pressurised, will allow water to flow into the system until the water supply and system pressure is equalised and the clapper closes the waterway. Once the pressure is stabilised, the fire protection system is ready to be placed in service and then the alarm control valve must be opened. Under normal condition, the water pressure gauge connected to the system side of the alarm valve would show a higher or equal pressure reading than the water pressure gauge connected to the supply side of the valve. This occurs because the 20 NB bypass line connecting downstream and upstream side of the alarm valve, which allows water pressure surge to pass without lifting the valve clapper off it's seat, thereby causing excessive high pressure surge entrapped in the system side due to presence of a check valve, which generally prevents false alarm. Sudden high pressure surge, as might be encountered by the start-up of a large fire pump may lead the valve clapper to lift momentarily, allowing water to flow through grooves in the valve seat to the retarding chamber. The water in the alarm line is automatically drained out, which helps to prevent false alarm due to successive transient surge in supply pressure. Restriction assembly located beneath the retarding chamber consists of an inlet and drain restriction orifice, which are established by considering the volume of the retarding chamber to meet the listing and approval requirement with regard to time-to-alarm. These requirements represent a balancing of the need to reduce the possible false alarm due to a transient surge in supply pressure and to achieve desired minimum time-toalarm following a sprinkler operation. In constant pressure installation, the retarding chamber is not required and the water passing through the groove in the alarm valve seat flows directly through restriction nozzle assembly to activate the mechanical and electrical alarm. INSTALLATION 1. Nitin Sprinkler Alarm Valve, Model-A must be installed vertically. 2. The alarm valve must be installed in a readily visible and accessible location and provision to be made in such a way that alarm line drain is visible and accessible. 3. Where water pressure fluctuates, the variable pressure trim with retarding chamber must be used. Under non-fluctuating water pressure condition, the constant pressure trim, which does not include retarding chamber may be used. 4. The valve must be installed with trim in accordance with the trim data. Failure to follow the appropriate trim connection guidelines may prevent the device from functioning properly as well as void listing, approval and the manufacturer's warranty. 5. Care must be exercised while installing the check valve in the trim to ascertain that they are located with the arrow mark on the check valve body and pointed in proper direction. 6. The contraction and expansion associated with an excessive volume of trapped air could

cause the waterway clapper to cycle open and shut. This may result in false alarm or an intermittent alarm. To avoid these, it is recommended to have breather valve in the system piping network and a vent valve at the extreme end of the system to bleed-off the air. 7. The ball valve provided on the alarm line must be kept open and strapped in set position of the alarm valve. 8. Pipe connecting the retarding chamber and sprinkler alarm bell must be supported properly to avoid loading on the retarding chamber. 9. All the newly installed system pipes must be flushed properly before alarm valve is put into service. INSPECTION AND MAINTENANCE A qualified and trained person must commission the system. After few initial successful tests an authorised person must be trained to perform inspection and testing of the system. It is recommended to carry out physical inspection of the system at least twice a week. The inspection should verify that all the control valves are in proper position as per the requirement of the system and no damage has taken place to any component. It is recommended that the alarm valve and it's accessories should be examined and performed for following at least quarterly or as demanded by local authorities to ensure reliable and trouble free operation and service. 1. Inspection and testing is to be carried out only by an authorised person. DO NOT TURN OFF the water supply valve to undertake repair work or to test the valve, without placing a roving fire patrol in the area covered by the system. The patrol should continue until the system is back into service. Also do inform the local security personnel and alarm control station, so that a false alarm is not signalled. 2. Open the alarm test valve. Verify that the sprinkler alarm bell and/or the pressure alarm switch/electric alarm properly actuate. Close the alarm test valve and verify that water has ceased to flow from the alarm line drain. 3. Clean the 20 NB (3/4") strainer provided on the sprinkler alarm bell line. 4. Clean the strainer of restriction assembly. 5. Inspect the 20 NB (3/4") check valve clapper located on the bypass line. FALSE ALARM 1. Inspect the valve rubber clapper face. If worn or damaged, replace it. Be certain that dirt, stone or any other foreign object have not accumulated under the clapper face and lodged in the groove or holes. Clean the clapper face thoroughly. If the seat ring surface is nicked or scoured, it might be possible to repair the same using lapping compound. If not, replace the complete valve or return it to the manufacturer's works for repair. 2. If sprinkler alarm bell is not functioning or the impeller is jammed, please follow the maintenance guideline provided in the catalogue for sprinkler alarm bell. 3. If pressure alarm switch gives a steady signal, but sprinkler alarm generates an intermittent alarm, check sprinkler alarm bell shaft. If both the sprinkler alarm bell and pressure alarm switch are generating intermittent alarm then check for the possible air which is trapped within the sprinkler system. Trapped air is to be bled-off. Also the intermittent alarm may occur due to sudden pressure drop and increase in the system. These problems can be corrected by maintaining a steady supply. NOTE The listing of UL, approvals & manufacturer's warranty are valid only when the alarm valve is installed with HD trim set and installed as per trim installation guidelines.

LIMITED WARRANTY Products manufactured are warranted against defects in material and workmanship for a period of Two (2) years from the date of shipment. Nitin Group s obligation under this warranty is limited to replace or repair the products or its parts, which are shown to Nitin Group's examination to be in a defective condition attributable to Nitin. No warranty is given for products or components which have been subject, to misuse, improper installation, corrosion, wear and tear, improper storage, modification or repaired. If the defect attributable to Nitin Group cannot be rectified by repair or replacement, then Nitin Group may elect to refund the purchase price of the equipment in complete discharge of its obligation under this Limited Warranty. IN NO EVENT SHALL NITIN GROUP OF INDUSTRIES BE LIABLE IN CONTRACT, STRICT LIABILITY OR ANY OTHER LEGAL THEORY, FOR INCIDENTAL, IN-DIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING DAMAGES. FOR INJURY TO PERSON OR DEATH OR DAMAGE TO PROPERTY AND OR PENALTIES RESULTING FROM ANY PRODUCTS OR COMPONENT MANUFACTURED OR ASSEMBLED BY NITIN GROUP. THIS IS LIMITED WARRANTY ONLY. NITIN DISCLAIMS WITH RESPECT TO THE PRODUCTS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. THERE IS NO WARRANTY OF ANY NATURE MADE BY NITIN BEYOND AS STATED ABOVE. NOTICE : The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the provision of government codes or ordinances wherever applicable. The information provided by us are to the best of our knowledge and belief, and are general guidelines only. Site handling and installation control is beyond our reach. Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or damages due to our product.