Experimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after the Condenser Using Sub Colling of Refregaring Fluid

Similar documents
Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System

Waghmare Tushar Ramrao, D.S.Nakate

INTERNATIONAL JOURNAL OF ADVANCED RESEARCH IN ENGINEERING AND TECHNOLOGY (IJARET)

[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Performance Assessment of Water Cooled Condenser Refrigeration System

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Fabrication of Hot and Cold Water Dispenser

VCR SYSTEM USING R-600a/ POE OIL/MINERAL OIL/NANO-SiO 2 AS WORKING FLUID: AN EXPERIMENTAL INVESTIGATION

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

Design & Fabrication of Hybrid Cooler

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

Design and Development of Water Cooled Condenser for Domestic Refrigerator

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Performance of an Improved Household Refrigerator/Freezer

Design of solar powered vapour absorption refrigeration system

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

To Improve Cop of Domestic Refrigerator with the Help of Water Cooling Condenser

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Enhancement of COP in Vapour Compression Refrigeration System

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Sarthak Thakar, 2 R.P.Prajapati 1

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 04, 2016 ISSN (online):

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Performance Enhancement of Mini Refrigerator with Phase Change Materials

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015


"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

HVAC Fundamentals & Refrigeration Cycle

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Experimental Study of Modified Refrigerator Cum Air Conditioning and Water Cooler System

Closed Loop Pulsating Heat Pipe with a Hydrocarbon as Working Fluid: A Review

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 12 May 2015 ISSN (online):

ISSN Vol.08,Issue.21, November-2016, Pages:

Soil Stabilization by Using Fly Ash

Refrigerator and Heat Pump Objectives

Performance Optimization of the Evaporative Condenser Design

Experimental Investigation on R 290 and R 600a In a Vapor Compression Refrigeration

Refrigeration and Air Conditioning

Evaluation of Available Heat at the Exhaust of Automotive Engine for Air Conditioning by Vapor Absorption System

Pressure Enthalpy Charts

EXPERIMENTAL INVESTIGATION OF VAPOUR ABSORPTION SYSTEM

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

Performance Evaluation of Coil Heat Exchanger inside PCM Bed

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM

4th IIR International Conference on Thermophysical Properties and Transfer Processes of Refrigerants 2013

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

EXPERIMENTAL ANALYSIS ON THE CONDENSER FINS FOR HOUSEHOLD REFRIGERATED SYSTEM

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM

Cost-Effective COP Enhancement of a Domestic Air Cooled Refrigerator using R-134a Refrigerant

[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Performance Analysis of Solar Assisted Cascade Refrigeration System of Cold Storage System

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

NABTEB Past Questions and Answers - Uploaded online

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

Design and development of vapor absorption refrigeration system for rural dwellers. Adekeye, T. Oyedepo, S.O and Oyebanji, J.A

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

Chapter 9. Refrigeration and Liquefaction

DESIGN, DEVELOPMENT AND TESTING OF CROSS FLOW CIRCULAR HEAT PIPE TO COOLING OF OIL

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

Transcription:

IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 12, Issue 2 Ver. V (Mar - Apr. 2015), PP 63-67 www.iosrjournals.org Experimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after the Condenser Using Sub Colling of Refregaring Fluid E Saidulu *, G.S.Guru Dattatreya ** * Asst.prof, Mechanical Engineering Department, Siddhartha institute of technology & sciences,ghatkesar, Hyderabad, India, ** Asst. prof, Mechanical Engineering Department, Siddhartha institute of technology & sciences, Ghatkesar, Hyderabad, India, Abstract: Majority of refrigerator works on vapor compression refrigeration system. The system consists of compressor, condenser, expansion valve and evaporator. The performance of the system depends on the performance of all components of the system. The main objective of the present study is to study the performance of a domestic refrigerator by placing shell and tube type heat exchanger immediately after the condenser to extract more amount of heat by sub cooling process by using ammonia as an external cooling media. Keywords: Sub cooling, Ammonia, Shell and tube heat exchanger, Coefficient of performance. I. Introduction: The term sub cooling refers to a liquid existing at a temperature below its normal saturation temperature. The sub cooling technology not only provides for additional capacity but also can reduce compressor power leading to higher overall system efficiency besides saving energy. The strategic placement of sub cooler for cooling in the liquid zone allow the operating pressure and temperature of the refrigerator system to be reduced and the refrigerant in the system to provide the highest cooling effect in the evaporator. Fig. 1.1 vapor compression refrigeration system Sub cooling desirable, reasons: It increases the efficiency of the system since the amount of heat being removed per kilogram of refrigerant circulated is greater. In other words we pump fewer refrigerants through the system to maintain the refrigerated temperature you want. This reduces the amount of time that the compressor must run to maintain the temperature. Sub cooling is beneficial because it prevents the liquid refrigerant from changing to a gas before it gets to the Evaporator. Pressure drops in the liquid piping and the vertical risers can reduce refrigerant pressure to the point where it will boil or flash in the liquid line. The change of phase causes the refrigerant to absorb heat before it reaches the evaporator. Inadequate sub cooling prevents the expansion valve from properly metering liquid refrigerant in to the evaporator, resulting in poor system performance. Selection of tube material: The tube material plays an important role in the design of refrigeration and air conditioning system. The tube material should have good thermal conductivity, as heat is transferred from hot to a cold side through the tubes, there is a temperature difference. Because of the tendency of the tube material the material is DOI: 10.9790/1684-12256367 www.iosrjournals.org 63 Page

thermally expands differently at various temperatures, and also thermal stresses will also occur during operation. All of these requirements call for careful selection of strong, thermally conductive, corrosion resistant, high quality tube material, typically metals including copper alloy, stainless steel, galvanized iron, carbon steel, nickel etc. Poor choice of tube material could result in a leak through the tube between shell and tube sides causing fluid cross-contamination and possibly loss of pressure. Fig.1.2: Shell and tube heat exchanger Shell and tube heat exchanger: A shell and tube heat exchanger is a class of heat exchanger designs. It is the most common type of heat exchanger and is suited for high pressure applications. As its name implies, this type of the heat exchanger consists of a shell with bundle of tubes inside it. One fluid runs through the tubes, another fluid flows over the tubes to transfer heat between the two fluids. The set of tubes is called tube bundle, and may be composed of Several types of tubes. 101.7 Pm 107.8 0 Properties of ammonia: Molecular formula NH3 Molar mass 17.031 g/mol Appearance Colorless gas Odour strong pungent odour Density 0.86 kg/m3 (1.013 bar ) Melting point 77.73 C Boiling point 33.34 C Solubility in water 47% (0 C) Solubility soluble in chloroform, ether, ethanol, methanol Structure: Molecular formula NH3 Molar mass 17.031 g/mol Appearance Colorless gas Odour strong pungent odour Density 0.86 kg/m3 (1.013 bar ) Melting point 77.73 C Boiling point 33.34 C Solubility in water 47% (0 C) Solubility soluble in chloroform, ether, ethanol, methanol Structure Molecular shape Trigonal pyramid Thermo chemistry Flash point flammable gas (see text) Explosive limits 15 28% DOI: 10.9790/1684-12256367 www.iosrjournals.org 64 Page

Ammonia, or azane, is a compound of nitrogen and hydrogen with the formulae NH3. It is a colorless gas with a characteristic pungent smell. NH3 boils at 33.34 C ( 28.012 F) at a pressure of one atmosphere, so the liquid must be stored under pressure or at low temperature. Household ammonia or ammonium hydroxide is a solution of NH3 in water. Measured in units of the Baumé scale (density), with 26 degrees baumé (about 30% (by weight) ammonia at 15.5 C or 59.9 F) being the typical high-concentration commercial product. Solvent properties: Ammonia is miscible with water. In an aqueous solution, it can be expelled by boiling. The aqueous solution of ammonia is basic. The maximum concentration of ammonia in water (a saturated solution) has a density of 0.880 g/cm3 and is often known as '.880 ammonia'. Ammonia does not burn readily or sustain combustion, except under narrow fuel-to-air mixtures of 15 25% air. One of the most characteristic properties of ammonia is its basicity. II. Experimental Setup The experimental test rig has a vapor refrigeration cycle working with refrigerant R-134a it consists of a compressor, evaporator, air cooled condenser, receiver, expansion valve and two shell and tube heat exchangers, One placed after condenser and the other after the evaporator. In the present work on the domestic refrigerator placing of shell and tube heat exchanger after the condenser contains ammonia that absorbs the heat from the refrigerating fluid coming from condenser. Sub cooling will occur and allow the operating pressure and temperature to be lowered. The net refrigeration effect and overall performance of the system will increase. The ammonia that is present in the modified shell and tube heat exchanger is converted from liquid to vapor state. The vaporized ammonia exchanges heat with the refrigerant coming out from the heat exchanger placed immediately after the evaporator is converted in to liquid.the cooled ammonia returns back to shell and tube heat exchanger after the condenser. Modifications made to the existing system Heat exchanger (HE-1) placed after the expansion valve in which liquid ammonia converts to vapor ammonia. Heat exchanger (HE-2) placed after the evaporator in which vapour ammonia converts to liquid. The ammonia continuously transferred from HE-1 to HE-2 and vice-versa. Fig 1.3: Proposed System Fig 1.4: Shell and Tube Heat Exchanger DOI: 10.9790/1684-12256367 www.iosrjournals.org 65 Page

Performance with Suction pressure (bar) Discharge pressure(bar) Temperature of vapour refrigerant before shells(0c) Inlet temperature of compressor(0c) Outlet temperature of compressor(0c) Condenser outlet temperature before shell SS0shell(0C Condenser outlet temperature after shell (0C) () Evaporator temperature(0c) Coefficient of performance Experimental Investigation on Domestic Refrigerator by Shell and Tube Heat Exchanger after In the above fig.1.4 the liquid - vapor phase refrigerant flows through the tube and the Ammonia flows outside the tubes but inside the shell (the shell side). Heat is transferred from refrigerant to Ammonia through the tube walls, either from tube side to shell or vice versa III. Tabular Column: Base line 0.9 18.0-19.1 78.2-42.9 2.6 5.16 Ammonia 0.6 11.0 18.1 25.0 69.5 42.0 39.5 1.7 6.11 Graph 1 Comparison of Heat Rejection Rate for Existing System and Proposed System Graph 2 Comparison of net refrigeration effect for existing system and proposed system Graph 3 Comparison of power input per tone of refrigeration for existing system and proposed system DOI: 10.9790/1684-12256367 www.iosrjournals.org 66 Page

Graph 4 Comparison of coefficient of performance for existing system and proposed system IV. Result And Discussions: By placing shell and tube heat exchanger after condenser the refrigerant is sub cooled by 2.5 0C when ammonia is used as coolant. Due to sub cooling the net refrigeration effect is increased and the C.O.P of the system is increased. The increase in coefficient of performance is 18.4% when ammonia is used as coolant. Coefficient of performance of refrigerator will be more with ammonia when compared with existing system References: [1]. Akintunde, M.A. 2004b. Experimental Investigation of The performance of Vapor Compression Refrigeration Systems. Federal University of Technology, Akure, Nigeria. [2]. Eckert, E.R.G.; Goldstein, R.J.; Ibele, W.E.; Patankar, S.V.; Simon, T.W.; Strykowski, P.J.; Tamma, K.K.; Kuehn, T.H.; Bar- Cohen, A.; Heberlein, J.V.R.; (Sep 1997), Heat transfer- a review of 1994 literature, International Journal of Heat and Mass Transfer 40-16, 3729-3804. [3]. Performance enhancement of a household refrigerator by addition of latent heat storage International Journal of Refrigeration, Volume 31, Issue 5, August 2008, Pages 892-901 Azzouz, K.; Leducq, D.; Gobin, D. [4]. Akintunde, M.A. 2004b. Experimental Investigation of The performance of Vapor Compression Refrigeration Systems. Federal University of Technology, Akure, Nigeria. [5]. Kays WM, London AL. Compact heat exchangers. New- York: McGraw-Hill, 1984. [6]. Seshimo Y, Fujii M. An experimental study of the performance of plate fin and tube heat exchangers at lowreynolds numbers. ASME/JSME Thermal Engineering Proceedings, ASME 1991;4:449 54. [7]. James R. lines. ly Coiled Heat Exchangers offer Advantages GRAHAM MANUFACTURI DOI: 10.9790/1684-12256367 www.iosrjournals.org 67 Page