Experimental and Numerical Study on a Dryexpansion Shell-and-Tube Evaporator Used in Wastewater Source Heat Pump (WWSHP)

Similar documents
Purdue e-pubs. Purdue University

A study of Transient Performance of A Cascade Heat Pump System

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

High Efficiency Heat Pump for Domestic Hot Water Generation

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

System Using Exhaust Heat from Residential GHPs

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Experimental Research of Air Source Heat Pump Frosting and Defrosting in a. Double Stage-Coupling Heat Pump

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

A TRNSYS Simulation Case Study on Utilization of Heat Pump For both Heating and Cooling

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

High Efficiency R-134a Compressor for Domestic Refrigerator

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Low GWP Refrigerants for Air Conditioning Applications

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Study of R161 Refrigerant for Residential Airconditioning

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of CO2 Cycles with a Two-Stage Compressor

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Investigation, Analysis and Solution of Higher Noise of Heat Pump Water Heater

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

The Use Of Attic Space For Cooling and Dehumidification

Experimental Study on the Performance of Twisted Capillary Tube

Compressor Capacity Control

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Investigation of Evaporator Performance with and without Liquid Overfeeding

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Efficiency of Non-Azeotropic Refrigerant Cycle

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Real Time Upright Freezer Evaporator Performance Under Frosted Conditions

Air-Cooled Heat Exchanger Performance for R410A

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Modelling the Performance of a Diffusion Absorption Refrigeration System

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Thermal Modelling for the Motor in Semi-hermetic Screw Refrigeration Compressor under Part-load Conditions

Dynamic Simulation of Liquid Chillers

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Optimization of Compressors used in Air Conditioning Units

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Development of Small-diameter Tube Heat Exchanger: Circuit Design and Performance Simulation

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Experimental and Numerical Study on a Dryexpansion Shell-and-Tube Evaporator Used in Wastewater Source Heat Pump (WWSHP) Chao Shen shenchao030647@163.com Yiqiang Jiang Yang Yao Xinlei Wang Follow this and additional works at: http://docs.lib.purdue.edu/iracc Shen, Chao; Jiang, Yiqiang; Yao, Yang; and Wang, Xinlei, "Experimental and Numerical Study on a Dry-expansion Shell-and-Tube Evaporator Used in Wastewater Source Heat Pump (WWSHP)" (2012). International Refrigeration and Air Conditioning Conference. Paper 1253. http://docs.lib.purdue.edu/iracc/1253 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2318, Page 1 Experimental and Numerical Study on a Dry-expansion Shell-and-Tube Evaporator Used in Wastewater Source Heat Pump (WWSHP) Chao SHEN 1,2, Yiqiang JIANG 1 * Yang YAO 1, Xinlei WANG 2 1 Harbin Institute of Technology, Department of Building Thermal Energy Engineering, Harbin, China Tel: 86-0451-86282123, Fax:86-451-86282123, Email: jyq7245@163.com 2 Department of Agricultural and Biological Engineering, University of Illinois at Urbana-Champaign, Urbana, IL, USA Tel: 1-217-3334446, Fax: 1-217-2440323, Email: xwang2@illinois.edu *Corresponding author: Yiqiang JIANG, Tel: 86-0451-86282123, Fax:86-451-86282123, Email: jyq7245@163.com ABSTRACT Aiming at the issue of bio-fouling build-up on heat exchanger s surface in wastewater source heat pump (WWSHP) systems, a novel dry-expansion shell-and-tube wastewater evaporator (DESTE) with defouling function was developed. Based on reasonable assumptions, a steady-state model of the DESTE was built to carry out the investigation, which was validated by comparing the simulation results with experimental data. The DESTE at different velocities of refrigerant and wastewater before and after cleaning was simulated. The simulation results, which included the distributions of refrigerant s pressure, enthalpy, void fraction, heat transfer coefficient and the temperature of wastewater and refrigerant along the flow-line before and after cleaning, suggested that the cleaning can improve the performance of the DESTE effectively. The effect of wastewater flow rate and the growth of fouling were studied as well. The results indicated that, for the DESTE designed in this paper, the minimum wastewater flow rate was 51 10-5 m 3 s -1 and the optimal wastewater flow rate was 63 10-5 m 3 s -1 ; the optimal fouling thermal resistance to defouling was R f =25 10-5. m 2. K. W -1. All these results can be used as a key reference for designing and operating waste bath water source heat pump systems in future. 1. INTRODUCTION In China, with the rapid development of economy and the improvement of people s living standard, energy shortage is getting more and more serious. Therefore, alternative energy sources or improved energy utilization methods should be more actively developed. In past decades, municipal wastewater with little temperature fluctuation has been widely used as heat source/sink of wastewater source heat pump (WWSHP) for space cooling and cooling (Yoshii, 2001). In comparison with air source heat pump (ASHP), the application of WWSHP system for cooling/heating can save 34% of energy consumption and reduce 68% of CO 2 emissions and 75% of the nitrogen oxides production (Baek et al., 2001). Beside municipal wastewater, in many special places, such as wastewater treatment plants, the bath and swimming pool (Baek, 2005; Lamand and Chan, 2001), oilfield (Tang and Zhuang, 2000), pharmaceutical factory, brewery, hospital, there are much high-temperature wastewater which contain much waste heat and can be used as heat source of heat pumps. The energy recovered from the wastewater can meet the heating/cooling requirements of all these plants economically (Holmgren, 2006). Unfortunately, during the waste heat recovery process, the performance of wastewater heat exchanger would be deteriorated by the bio-fouling build-up on heat exchanger s surface due to the dirt contained in wastewater. Currently, the majority of wastewater heat exchangers are cleaned through shutting down the system and removing the bio-fouling manually. Some wastewater heat exchangers have a mechanically cleaning function but for indirect-type WWSHP system. Indirect-type WWSHP system is not only complex but also low-efficient in energy utilization, because a circulating loop is requested. On the contrary, the direct-type WWSHP system is not only

2318, Page 2 simple but also with 7% higher energy efficiency than indirect system (Li and Chen, 2002), therefore, the direct-type system has become the development goal of the WWSHP system. In this paper, a novel dry-expansion shell-and-tube evaporator (DESTE) with defouling function is proposed for direct-type WWSHP system (Jiang, et al., 2009). It realizes heat exchange directly between refrigerant and wastewater and can remove the bio-fouling easily, thus cuts down the initial and operation costs. To research on the performance of the DESTE, a steady-state model was used to calculate the temperature distribution of wastewater and refrigerant along the flowing route, the variation of phase and heat transfer coefficient of refrigerant were also researched. The performance of DESTE at different flow rates of wastewater and refrigerant, different bio-fouling resistant were simulated. To test the physical validity of the calculation results, experimental study at different wastewater temperatures were performed. The heat exchange capacity of the DESTE during the long-term test and that after de-fouling were presented. 2. STRUCTURE DESCRIPTION The novel dry-expansion wastewater evaporator includes tube side and shell side, as shown in Figure 1. Refrigerant flows in tube side and wastewater flows in shell side. Heat exchange tubes are installed in and can be pulled out from the shell. Different from the conventional shell-and-tube heat exchanger, all baffles were not welded to the shell but connected onto a rotatable screw axis at the center of the DESTE unit. The screw axis was supported by bearings on both ends of the evaporator, and stretched out at the right end where a manual rotating wheel was installed. Each baffle was connected with the central screw axis through an embedded screw nut. Owing to the screw translation, the baffle could move along the tubes of the DESTE when turning the screw axis; meanwhile, the rubber layer of the baffle would accordingly scrape the bio-fouling off the tube s surface. Sewage Inlet Heat Transfer Tube Baffle Plate Sewage Outlet Sub-Dispenser Refrigerant Inlet Rotation Axis Refrigerant Outlet Shell (a) Front view (b) Profile Figure 1: Schematic representation of a novel dry-expansion shell-and-tube evaporator. 3. EXPERIMENTAL STUDY 3.1 Experimental setup and test instruments To research the performance of the DESTE, an experimental heat pump for water heating was developed (see

2318, Page 3 Figure 2). The experimental WWSHP consisted of four main sub-systems: wastewater collection, heat pump, hot water heating, and data acquisition and control. The heat pump used the novel evaporator with defouling function to recover heat from waste bath water. The detailed configuration of the setup is listed in Table 1. Major test instrument are listed as follows: Platinum-resistance thermometers (ºC ), Range: -50~500, Accuracy: ±0.1 Flow meter (m 3 h -1 ), Range: 0-10, Accuracy: ±2.0% Current sensor (A), Range: 0-20, Accuracy: ±0.2% Voltage sensor (V), Range: 0-400, Accuracy: ±0.2% Table 1: Detailed configuration of test equipment Name Type Specification Compressor Hermetic piston compressor Nominal supply current of 5.3-5.6A and voltage of 220-240V Condenser Brazed plate heat exchanger Heat transfer area: 0.032 m 2 per piece; total number of heat transfer plate: 36 pieces Expansion valve Thermal expansion valve Refrigerant 134a Hot water heating sub-system T 1 V 2 Heat pump sub-system 1 3 5 2 4 T 2 T 3 Water tank Wastewater collection sub-system Common bath room V 1 6 T 4 T 5 7 10 Water level controller Pressure sensor Temperature sensor 8 9 T 6 Flow meter Solenoid valve Data logger PC Data acquisition and control sub-system Figure 2: Schematic for the wastewater source heat pump 1-compressor; 2-expansion valve; 3-plate condenser; 4-hot water pump; 5- HWST; 6- dry-expansion shell-and-tube evaporator (DESTE) with defouling function; 7-wastewater pump I; 8- wastewater pump II; 9- WST; 10-filter A series of experiments were conducted in a spa center in China, Shenzhen. The operation performances of the DESTE at different flow rates, different wastewater temperatures were tested. 3.2 Long-term performance of the dry-expansion evaporator affected by bio-fouling build-up A 30-day test was conducted to investigate the performance of WWSHP affected by the bio-fouling build-up (Shen,

2318, Page 4 et al, 2012). Figure 3 shows the variation of daily averaged heat exchange capacity of the evaporator during the testing period. As seen, the capacity dropped from 8.2 to 5.8 kw over the 30-day test, i.e., a 29.3% reduction. This clearly demonstrated the negative effect of bio-fouling growth on heat exchange capacity. This result suggested that, the suspended substance and biological matter contained in the waste bath water would lead to bio-fouling on the heat exchanger surface, resulting in gradual reductions in both heat exchange capacity and the operating performance of this studied WWSHP. A regular cleaning for the heat exchanger surface would be necessary to ensure that the WWSHP was operated at its design capacity with a satisfactory COP. A cleaning operation was conducted immediately after the 30-day long testing period. To evaluate the effectiveness of removing bio-fouling build-up using the novel evaporator, the recorded operating parameters of the WWSHP in three consecutive water heating processes before and after the cleaning operation were comparatively analyzed. The heat exchange capacities of the novel evaporator before and after cleaning are compared in Figure 4. It can be found that the averaged heat exchange capacity increased from 5.8 kw before cleaning to 8.0 kw after cleaning, which was 97.6% of the daily averaged heat exchange capacity of 8.2 kw recorded on the first day of the 30-day testing. This suggested that the heat exchange capacity of the novel evaporator could also be basically restored after wiping off the bio-fouling from the evaporator surface. Figure 3: The variation of daily averaged heat exchange capacity of the novel evaporator during 30-day test Figure 4: The heat exchange capacity of the novel evaporator during three water heating processes before/after the cleaning Figure 5: The variations of operation parameters tested at different wastewater flow rates 3.3 Performance of the dry-expansion evaporator at different flow rates of wastewater Figure 5 shows the variations of operation parameters tested at different flow rates of wastewater passing through the DESTE, including evaporating temperature, temperature difference of the waster at the inlet and outlet of the

2318, Page 5 DESTE, heat exchange capacity of the DESTE and the COP of the WWSHP. It can be found that different flow rates of wastewater affected the performance of the DESTE greatly. 4. MATHEMATICAL MODEL DEVELOPMENT AND ITS VALIDATION A steady-state model was built based on the conservation equations of energy, mass and momentum (Shen, 2009) to carry out the numerical study on the DESTE. An algorithm to solve the model of the DESTE was developed as well (Shen, 2011). In order to verify the developed algorithm and model, a WWSHP test rig using the DESTE as an evaporator was built in the special-economic-zones of Shenzhen, China. The geometrical characteristics of the evaporator are presented in Table 2. Totally, 8 sets of data measured at different wastewater flow rates of the DESTE (shown in Figure 5), and 13 sets of experimental parameters tested at different wastewater and refrigerant temperatures at the inlet of DESTE (shown in Table 3) were compared with the calculated results. Table 2: Geometrical characteristics of the sample unit simulated Diameter of shell D ( m) 0.22 Length of each tube L ( m) 1.1 Total number of tubes 80 Baffle plates pitch B ( m) 0.07 Tube center distance S ( m) 0.02 Outer diameter of tube Inner diameter of tube d ( mm ) o 10 d ( mm ) i 8 Number of tube side 2 2 Heat-transfer area ( m ) 2.38 Table 3: Test conditions of the DESTE for validation of the model case Wastewater flow rate of the DESTE, (m 3 /s) Inlet temperature (ºC) Refrigerant 1 0.00075 4.1 18.2 2 0.00075 4.8 20.5 3 0.00075 5.2 21.5 4 0.00075 5.9 23.6 5 0.00075 5.7 23.3 6 0.00075 6.3 24.6 7 0.00075 6.2 24.1 8 0.00075 6.7 24.9 9 0.00075 7.4 26.7 10 0.00075 7.5 26.9 11 0.00075 8.4 29.3 12 0.00075 8.7 30.4 13 0.00075 9.2 31.8 wastewater Comparison between the calculated results and the experimental data (as shown in Figure 5(c)) shows that they are coincided with each other well with the maximum deviation was 8.3%, even though some factors were neglected in the model but unavoidable in the experiment. As indicated in Figure 6, the maximum deviation for the experimental and numerical refrigerant temperature at outlet of evaporator was ±2.4ºC. Meanwhile, Figure 7 shows that the numerical and experimental results for the heat exchange capacity lay within the ±3.8% in the range of 5.2-5.7 kw. These indicated an excellent agreement

between the experimental and numerical results, thus verifying the algorithm and model developed. Numerical outlet temperature of refrigerant/ 32 30 28 +2.4 26 24 22-2.4 20 18 16 14 14 16 18 20 22 24 26 28 30 32 Experimental outlet temperature of refrigerant/ Figure 6: Comparison between the experimental and calculated refrigerant temperature at outlet of DESTE Numerical heat transfer rate/kw 5.8 5.7 5.6 5.5 5.4 5.3 5.2 5.1 5. RESULTS AND DISCUSSION +3.8% -3.8% 5.0 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 Experimental heat transfer rate/kw 2318, Page 6 Figure 7: Comparison between the experimental and numerical heat exchange rate of DESTE A series of simulation study were carried out based on the verified model to investigate the operation performance of the DESTE, which are helpful for further insights for the DESTE but could not realized by experimental study. In this section, the numeral results are presented and analyzed. 5.1 Refrigerant performance with different refrigerant flow rates The steady-state model was used to simulate the performance of the DESTE unit with a defouling function. Its simulation conditions are presented in Table 4: Three cases at different refrigerant flow rates after cleaning. The results are shown in Figures 8-11. Case Table 4: Simulation conditions of the dry-expansion shell-and-tube evaporator (DESTE) Refrigerant flow rate (kg/s) Wastewater flow rate (m 3 /s) Evaporating temperature (ºC) Wastewater inlet temperature (ºC) After cleaning 1 0.0593 0.00075 9 24 2 0.0791 0.00075 9 24 3 0.0988 0.00075 9 24 Before cleaning Pressure/Pa 10 5 4.0125 4.0120 4.0115 4.0110 4.0105 4.0100 4.0095 4.0090 Mr=0. 0593 kg/ s Mr=0. 0791 kg/ s Mr=0. 0988 kg/ s 4.0085 0 5 10 15 20 25 30 Serial number along refrigerant flow-line Figure 8: The pressure of refrigerant along refrigerant flow-line. Void fraction 1 0.8 0.6 Mr=0. 0593 kg/ s 0.4 Mr=0. 0791 kg/ s Mr=0. 0988 kg/ s 0.2 0 0 5 10 15 20 25 30 Serial number along refrigerant flow-line Figure 9: The void fraction of refrigerant along refrigerant flow-line. Simulation results of the DESTE after cleaning, described in terms of the pressure of the refrigerant along the tube at three different refrigerant flow rates, are shown in Figure 8. As seen, the pressure drop of the refrigerant was in direct proportion to the refrigerant flow rate, which can be explained by that an elevated flow rate of refrigerant would cause an increased friction factor. However, when compared with the inlet pressure of refrigerant of 401.22 kpa, the maximum pressure drop 0.34 kpa was such small that it can be neglected. Therefore, the evaporating

2318, Page 7 temperature in the evaporator can be assumed to be constant. Average enthalpy/ J kg -1 4.5 105 4.0 3.5 3.0 2.5 Mr = 0.0593kg/ s Mr = 0.0791kg/ s Mr = 0.0988kg/ s Temperature/ ºC 18 16 14 12 10 Mr = 0.0593 kg/s Mr = 0.0791 kg/s Mr = 0.0988 kg/s 2.1 8 0 5 10 15 20 25 30 0 5 10 15 20 25 30 Serial number along refrigerant flow-line Serial number along refrigerant flow-line Figure 10: The average enthalpy of refrigerant along Figure 11: The temperature of refrigerant along refrigerant flow-line refrigerant flow-line Figure 9 shows the void fraction distribution of refrigerant along the tubes in the DESTE unit. According to the equation l v d dx, ( l v ), when x 0.1, l v. Hence, it was 2 x( ) x( ) 2 l v v l v v evident that in the inlet section of refrigerant, the void fraction increased to 0.9 (L=0.14m) rapidly. In the latter sections of the evaporator, the void fraction increased slowly but kept high, which was ( 0.9 ). The average enthalpy of the refrigerant distribution at different refrigerant flow rates is shown in Figure 10. It indicates that the average enthalpy of the refrigerant increased linearly in two-phase region (x<1) along the tube and the rate of increase was larger at a larger refrigerant flow rate. While in overheat region, it increased slowly and the rate of increase was much smaller than that in the two-phase region. Two reasons cause this phenomenon: one was the temperature difference between refrigerant and tube wall is small in overheat region; the other was the heat transfer coefficient in this region was lower than in tow-phase region (see Figure14). Figure 11 describes the refrigerant temperature distribution along the tube at different refrigerant flow rates. The larger the refrigerant flow rate was, the longer the two-phase region was, in correspondence to which, the shorter the overheat region became. When the refrigerant flow rate reached to 0.0988kg/s, the overheat region disappeared, indicating that it was the maximum flow rate of refrigerant for the DESTE designed in this paper. 5.2 Performance of the DESTE before and after cleaning The temperature distributions of refrigerant/wastewater and the variation of heat transfer coefficient of refrigerant before and after cleaning were investigated in this section. The simulation conditions are given in Table 4 (case 2). The fouling thermal resistance of 5.28 10-4 m 2 K/W was assumed before cleaning which was the maximum value recommended by the Tubular Exchanger Manufacturers Association, USA (TEMA). The results are presented in Figures 12 and 13. As seen in Figure 12, there was no overheat region of refrigerant in the whole evaporator before cleaning, however the overheat region appeared after cleaning with the same refrigerant flow rate. It indicates that fouling on the tube s surface affected the heat transfer seriously and an effective cleaning was necessary for the wastewater heat exchanger to ensure that the refrigerant was gaseous at the outlet of the evaporator, which was required to protect the long service life of the compressor. The temperature distributions of wastewater before and after cleaning are presented in Figure 13. As shown, the temperature of wastewater decreased before cleaning much faster than that after cleaning in the near-inlet sections of wastewater flow-line (serial number<18). It can be explained that although the thermal resistance of bio-fouling was removed after cleaning, due to the improved total heat transfer coefficient after cleaning the refrigerant at the near-outlet sections became gaseous (overheat region), where the heat transfer coefficient of the refrigerant was low. Thus the total heat transfer coefficient in the near-outlet sections of the refrigerant flow-line became lower. Therefore along the flow line of the wastewater, the wastewater passing through this area couldn t be chilled well

2318, Page 8 (shown in Figure 13: the overheat region). Totally, the temperature of wastewater was higher after cleaning than before cleaning in the near-inlet sections of the wastewater flow-line. In the latter sections (serial number >18) the wastewater temperature after cleaning decreased much faster than that before cleaning, till the wastewater temperature after cleaning was lower than before cleaning in the near-outlet sections of the wastewater flow-line (serial number >30). Temperature/ 14 13 12 11 10 After cleaning Before cleaning Gs=0. 00075 m 3 /s Mr=0.0791 kg /s Temperature/ 24 23 22 21 Overheat region After cleaning Before cleaning Gs=0. 00075m 3 /s Mr=0. 0791kg/s 9 20 8 0 5 10 15 20 25 30 Serial number along the refrigerant flow-line Figure 12: Temperature distributions of refrigerant along refrigerant flow-line before and after cleaning. 19 0 10 20 30 40 50 Serial number along the wastewater flow-line Figure 13: Temperature distributions of wastewater along wastewater flow-line before and after cleaning. The variations of heat transfer coefficient and dryness of the refrigerant along the refrigerant flow-line before and after cleaning were shown in Figure 14. The physical processes in the system could be interpreted as follows. After cleaning: The heat transfer coefficient of refrigerant decreased rapidly in the near-inlet sections of refrigerant flow-line (x<0.18), with the dryness increase (0.18<x<0.52) it decreased slowly, when x=0.52, the heat transfer coefficient reached the minimum value; when 0.52<x<0.92, the heat transfer coefficient of refrigerant increased with the increase of the dryness of refrigerant along the flow-line; when x increased from 0.92 to 1, the heat transfer coefficient decreased rapidly to a low value, when the refrigerant went into the overheat region. In the overheat region it kept a constant low value approximatively. The variation of heat transfer coefficient with the dryness (x) before cleaning was similar with that after cleaning. Because there was no overheat region before cleaning, the heat transfer coefficient of refrigerant kept being high relatively, but due to the thermal resistance of fouling existing outside the tube, the total heat transfer coefficient of the heat exchanger before cleaning was lower than that after cleaning. Heat transfer coefficient /Wm -2 K -1 3000 2500 2000 1500 1000 500 Gs = 0. 00075 m 3 /s Mr =0. 0791 kg/s x=0.92 x=0.52 x=0.18 1 0.8 0.6 0.4 0.2 Dryness 0 0 1 5 10 15 20 25 30 Serial number along refrigerant flow-line dryness before cleaning dryness after cleaning heat transfer coefficient after cleaning heat transfer coefficient before cleaning Figure 14: The heat transfer coefficient of refrigerant before and after cleaning 5.3 Performance of the DESTE with different wastewater flow rates As shown in Table 5, a larger heat exchange capacity can be obtained at a higher wastewater flow rate. When G s <63 10-5 m 3 s -1, the increasing rate of heat exchange capacity versus the wastewater flow rate was higher than that when G s >63 10-5 m 3 s -1. With the increase of wastewater flow rate, the wastewater temperature at the outlet of DESTE increased as well. As shown, the temperature and enthalpy of refrigerant at the outlet of the DESTE varied differently, when G s <51 10-5 m 3 s -1, it is in two-phase region, so the refrigerant temperature at the outlet kept 9ºC,

2318, Page 9 while the enthalpy at the outlet of the DESTE had an obvious positive proportion to the wastewater flow rate. When 51 10-5 m 3 s -1 <G s <63 10-5 m 3 s -1, the refrigerant temperature at the outlet of DESTE increased rapidly with the increasing of wastewater flow rate, and the outlet enthalpy of refrigerant increased slightly. When G s >63 10-5 m 3 s -1, both outlet temperature and enthalpy of refrigerant increased slowly with the increasing of wastewater flow rate, indicating that the maximum of the heat exchange capacity of the DESTE with the designed size was reached up to. According to the analysis above, for the DESTE with the designed size in this study at the refrigerant flow rate of 0.0791 kg.s -1, the minimum wastewater flow rate is 51 10-5 m 3 s -1 (ensuring the refrigerant at the outlet of the DESTE was gaseous) and the optimal wastewater flow rate is 63 10-5 m 3 s -1 (a larger wastewater flow rate couldn t enhance the heat exchange capacity obviously). Table 5: The performance of the DESTE under different wastewater flow rates after cleaning. (The temperatures of wastewater and refrigerant at the inlet of the DESTE were T s,in =24ºC and T r,in =9ºC, respectively) Case m r (kg.s -1 ) G s (10-5.m 3.s -1 ) Q (kw) Q (kw) T s,out (ºC) T r,out (ºC) H r,out (kj.kg -1 ) 1 0.0791 39 13.793 15.6 9 385.7 2 0.0791 42 14.29 0.497 15.9 9 392.1 3 0.0791 45 14.828 0.538 16.1 9 399.6 4 0.0791 48 15.118 0.29 16.5 9 403.4 5 0.0791 51 15.158 0.040 16.9 9 403.9 6 0.0791 54 15.226 0.068 17.3 9.4 404.3 7 0.0791 57 15.349 0.123 17.6 11.6 406.3 8 0.0791 60 15.403 0.054 17.9 12 406.6 9 0.0791 63 15.5 0.097 18.1 13.7 408.2 10 0.0791 66 15.501 0.001 18.4 14 408.2 11 0.0791 69 15.544 0.043 18.6 14 408.4 12 0.0791 72 15.545 0.001 18.8 14 408.4 13 0.0791 75 15.546 0.001 19.1 15.4 408.4 5.4 The effect of the growth of fouling on the performance of the DESTE Table 6: Performance of the DESTE with the growth of fouling (Wastewater flow rate: G s =63 10-5 m 3 s -1 ; Mass flux of refrigerant: m r =0.0791kg s -1 ; The wastewater/refrigerant temperatures at the inlet of DESTE: T s,in =24 ºC; T r,in =9ºC, respectively) R f (10-5. m 2. K. W -1 ) 0 5 10 15 20 25 30 35 40 45 50 x 1 1 1 1 1 0.99 0.98 0.96 0.95 0.92 0.9 Q(kW) 15.5 15.4 15.35 15.23 15.2 15.12 14.96 14.71 14.48 14.18 13.84 Q(kW) 0.1 0.05 0.12 0.03 0.08 0.16 0.25 0.23 0.3 0.34 H r,out ( kj kg -1 ) 408.2 406.6 406.3 404.3 404 403.2 400.9 397.7 394.62 389.68 385.9 The performance of the DESTE with the growth of fouling is presented in the Table 6. With operation time, more and more fouling grew outside the tubes, which affected the heat transfer between wastewater and refrigerant badly. The result shows that the heat exchange capacity decreased with the growth of the fouling. But when the thermal resistance of fouling R f <25 10-5. m 2. K. W -1, the effect of fouling on heat exchange was acceptable (the heat exchange capacity was reduced by 0.1-0.12 kw when the thermal resistance of fouling increased by 5 10-5. m 2. K. W -1 ). When R f >25 10-5. m 2. K. W -1, the effect of fouling was distinct (the heat exchange capacity, Q, was

2368, Page 10 reduced by 0.16-0.34kW when the thermal resistance of fouling increased by 5 10-5. m 2. K. W -1 ). This result could be explained by the dryness shown in Table 6. When R f <25 10-5. m 2. K. W -1, the outlet refrigerant was in overheat region, but when R f >25 10-5. m 2. K. W -1, the outlet refrigerant was in tow-phase region, caused by the growth of fouling which increased the total thermal resistance of the DESTE. The effect of fouling on the enthalpy of refrigerant at the outlet (H r,out ) was the same with that on the heat exchange capacity, which is also shown in Table 6. Above results show that to keep the evaporator work at maximum efficiency (at operation conditions given in Table 6 with the size designed in this study), the optimal fouling thermal resistance to defouling is R f =25 10-5. m 2. K. W -1. 5. CONCLUSIONS A novel shell-and-tube wastewater evaporator with defouling function, namely DESTE, was developed, and its performance was investigated based on experiment and simulation study. The key conclusions are as follows. Maximum refrigerant pressure drop in the DESTE was 0.34 kpa. The average enthalpy increased linearly in two-phase region and increased slightly in overheat region along the refrigerant flow-line. However, the void fraction increases rapidly at the near-inlet sections of refrigerant flow-line, but slowly in latter sections. Along the wastewater flow-line, the wastewater temperature decreased more slowly after cleaning than before cleaning in the near-inlet sections of wastewater flow-line, but in the other sections the wastewater temperature after cleaning decreased faster than that before cleaning. The wastewater temperature at the outlet of the DESTE after cleaning was lower than that before cleaning. For the DESTE with the designed size in this study, when the mass flux of refrigerant m r = 0.0791kg s -1, the minimum wastewater flow rate was 51 10-5 m 3 s -1 and the optimal wastewater flow rate was 63 10-5 m 3 s -1 ; when m r =0.0791kg s -1 and wastewater flow rate G s =63 10-5 m 3 s -1, the optimal fouling thermal resistance to cleaning was R f =25 10-5. m 2. K. W -1. REFERENCES Baek, N.C., et al., 2001. Development of off-peak electric water heater using heat pump, (1999-E-ID01_P11): p. 3-7. Baek, N.C., Shin, U.C., Yoon, J.H.. 2005, A Study on the Design and Analysis of a Heat Pump Heating System Using Wastewater as a Heat Source, Solar Energy, vol.78, no.3: p.427-440. Jiang, Y.Q., Yao, Y., Ma, Z.L., et al., 2009, A dry-expansion shell-and-tube heat exchanger with function of defouling, Patent no.200810136804.9, China. Holmgren, K., 2006, Role of a district-heating net work as a user of waste heat supply from various sources the ease of Goteborg, Applied Energy, vol. 83, no. 12: p.1352-1354. Lam, J.C., Chan, W.W., 2001, Life Cycle Energy Cost Analysis of Heat Pump Application for Hotel Swimming Pools, Energy Conservation and Management, vol.42, no.11: p.1299-1306. Li, Y.F., Chen, P., 2002, Recycle the heat from municipal wastewater using heat pump, Renewable Energy, vol.6:23-24. Shen, C., 2009, Development of high-efficiency blockage-proof dirt-removal wastewater heat exchanger and study on its characteristics of heat transfer. In: Master Thesis, Department of Building Thermal Energy Engineering, HIT, China. Shen, C., 2011, Model and algorithm for simulation of a novel dry-type shell-tube evaporator used in sewage source heat pump. 2011 International Conference on Computer Distributed Control and Intelligent Environmental Monitoring, Changsha, China: 446-449. Shen, C., Jiang, Y.Q., Yao, Y., Deng, S.M., 2012, Experimental performance evaluation of a novel dry-expansion evaporator with defouling function in a wastewater source heat pump, Applied Energy, Vol. 95: 202-209. Tang, G.H., Zhuang, Z.N., 2000, Analysis of the Energy-saving Plan of the Heaters in an Oil Refinery, Chemical Machinery, vol.6: p.352-354. Yoshii, T., 2001, Technology for Utilizing Unused Low Temperature Difference Energy. Journal of Japan Institute of Energy, vol. 8: p.696-706. ACKNOWLEDGMENTS The authors acknowledge the financial supports from the National Key Technology R&D Program in the 11th Five Year Plan of China ( No. 2006BAJ01A06).