technical data air conditioning systems RMXS-E7V3B1 Super multi plus Split Sky Air

Similar documents
TABLE OF CONTENTS RMXS-E8V1B

TABLE OF CONTENTS ERSQ-AAY1

EEDEN technical data ERHQ AA. Altherma. Altherma

technical data air conditioning systems FDKS-CVMB Concealed ceiling, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems FDXS-CVMB Concealed Ceiling, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems Indoor Units FBQ-C7VEB

technical data air conditioning systems RZQ-B Pair/Twin/Triple/Double Twin Application, Inverter Controlled Unit Split Sky Air

TABLE OF CONTENTS ERHQ BAV3

Air Conditioners. Technical Data FBQ-C

Air Conditioning Technical Data RZAG-MV1

Air Conditioning Technical Data RZASG-MV1

EEDEN technical data. air conditioning systems RZQS71-140C7V1B. Split Sky Air

technical data air conditioning systems RZQ B8W1B Split Sky Air

EEDEN technical data. air conditioning systems RZQS-DV1. Split Sky Air

EEDEN technical data. air conditioning systems RZQ-DV1. Split Sky Air

Air Conditioning. Technical Data. Pair, Twin, triple, double twin EEDEN RZQ-C

Air Conditioners. Technical Data RZQG-L

Heating. Technical Data EEDEN ERRQ-AY1

technical data air conditioning systems FVXS-FV1B R-410A Split Sky Air

technical data air conditioning systems RZQ-B9V3B_RZQ-B8W1B Pair, Twin, Triple, Double Twin, Application, Inverter Controlled Split Sky Air

Air Conditioning. Technical Data EEDEN AZQS-BV1

technical data air conditioning systems RZQ C7Y1B Split Sky Air

Air Conditioning Technical Data AZAS-MY1

technical data air conditioning systems RR-B8V3B_RR-B8W1B Pair, Twin, Triple Application Split Sky Air

EEDEN technical data ERHQ AA

Air Conditioning. Technical Data. VRV IV heat recovery EEDEN14-200_4 REYQ-T

technical data air conditioning systems FTXG-C Wall Mounted, Inverter Controlled Unit Split Sky Air

1 Features. Outdoor Units R-410A RYN-E3V1B. Split Sky Air Outdoor Units

Heating. Technical Data. Daikin Altherma low temperature split EEDEN ERLQ-CW1

Air Conditioners. Technical Data FTXS-G

Ventilation. Technical Data. Outdoor air processing unit, ventilation and air processing EEDEN FXMQ-MF

technical data air conditioning systems Indoor Units FCQ-C8VEB

technical data air conditioning systems FHYKP-B Ceiling Mounted Corner Cassette Split Sky Air

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FXMQ-MB

Air Conditioning. Technical Data. Multi model application EEDEN MXS-E

Air Conditioning. Technical Data EEDEN RXS-F8

Air Conditioning. Technical Data EEDEN RZQG-L8/7V1

technical data air conditioning systems FHYP-B Ceiling Suspended Unit Split Sky Air

Air Conditioning. Technical Data EEDEN RZQSG-L(8)Y1

EEDEN technical data. air conditioning systems FTXS-G2V1B. Indoor units. Split - Sky Air

EDUS D Engineering Data RXYQ-TAYCU, 575 V. Heat Pump 60 Hz

Air Conditioning. Technical Data EEDEN RZQSG-L(3/8)V1

Air Conditioners. Technical Data. Heating only hydrobox for VR V HXHD-A

Heating. Technical Data. Daikin Altherma low temperature monobloc EEDEN EBLQ-BB6W1

Heating. Technical Data. Daikin Altherma low temperature monobloc EEDEN EDHQ-BB6V3

Air Conditioning. Technical Data. High temperature hydrobox for VRV EEDEN HXHD-A8

Service Manual. Air Cooled Refrigeration Condensing Unit

technical data air conditioning systems FHYCP-B7 4-way Blow Ceiling Mounted Cassette (950x950) Split Sky Air

Air Conditioning. Technical Data. VRV IV S-series compact heat pump EEDEN RXYSCQ-TV1

for small rooms in multi application

Air Conditioning. Technical Data. VRV IV S-series heat pump EEDEN16-200_2 RXYSQ-TV1

EEDE06-9. technical data. Altherma ERYQ A EKHBH007A / EKHBX007A EKSWW

January Engineering Data RXSQ24-60TAVJU. Heat Pump 208/230V / 60 Hz / 1 ph. Presales Manual DAIKIN NORTH AMERICA LLC

Chillers. Technical Data. EWYD-BZ 250~580 kw

Daikin air conditioners for your home, shops, restaurants and offices

EEDEN technical data EKRTR. Altherma. Altherma

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FDQ-C

Air Conditioning. Technical Data. Flexi type unit EEDEN FLXS-B(9)

technical data air conditioning systems FT(Y)S-B Wall Mounted Unit Split Sky Air

technical data air conditioning systems FTKS/FTXS-C FTKS/FTXS-B Wall Mounted, Inverter Controlled Unit Split Sky Air

TABLE OF CONTENTS EDLQ AA6V3

Air Conditioning. Technical Data. Ceiling suspended unit EEDEN AHQ-C

Air Conditioning. Technical Data. Concealed ceiling unit with high ESP EEDEN FDQ-B

TABLE OF CONTENTS EBLQ01-016AA6V3

Digital Inverter 4 series 8 & 10HP

Air Conditioning. Technical Data. Small concealed ceiling unit EEDEN FDBQ-B

your comfort. our world. Altherma Flex Type Renewable heat pump system for every environment

Air conditioners Heating & Cooling

Air conditioners, heating & cooling. for large spaces. air to air heat pumps. FDQ-B

Water-cooled chillers Remote condenser chillers NEW

Air Conditioners Technical Data

Air Conditioning. Technical Data. 4-way blow ceiling mounted cassette EEDEN ACQ-C

EDUS Heat Pump - D-Series

EWWD MBYN EWLD MBYN Applied systems

Air Conditioners Technical Data

Air Conditioners Technical Data

Air Conditioning. Technical Data. Wall mounted unit EEDEN FTX-J3

SUPERB TECHNOLOGY FOR SUPERB INTERIORS

Air conditioners, heating & cooling for the retailmarket and offices

Chillers EWAQ-E-/F- EWYQ-F- Air cooled multi-scroll chillers and heat pumps

Air Conditioning Technical Data FFA-A > FFA25A2VEB > FFA35A2VEB > FFA50A2VEB > FFA60A2VEB

Air Conditioners Heating & Cooling

Air Conditioning. Technical Data. Concealed ceiling unit EEDEN FDXM-F

where innovation meets creativity

Daikin air conditioners for your home

EEDEN technical data. Altherma ERHQ AA EKHBH007AC / EKHBX007AC EKSWW

Air conditioners, heating & cooling for shops,restaurants and offices

technical data air conditioning systems FH(Y)B-FK7 Concealed Ceiling Unit Split Sky Air

w w w. d a i k i n. e u ATXS-E

Air Conditioners Technical Data

for the retail market, hotels, restaurants and offices

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Commercial and Technical Data

Optimised for high ambient operation (up to 55 C ambient) EWAD-MZ. Air cooled chiller

Air Conditioners Heating & Cooling

Air Conditioners Heating & Cooling

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control...

Air conditioners Cooling only

Air Conditioners Technical Data

EWAD-TZ. Air cooled chiller with R-134a inverter driven screw compressor

Transcription:

technical data RMXS-E7V3B1 Super multi plus air conditioning systems Split Sky Air

Outdoor Units R-410A RMXS-E7V3B1 TABLE OF CONTENTS RMXS-E7V3B1 1 Features............................................................. 2 2 Specifications....................................................... 3 Nominal Capacity and Nominal Input............................... 3 Technical Specifications............................................. 3 3 Electrical data....................................................... 6 4 Options.............................................................. 7 5 Capacity tables..................................................... 8 Cooling capacity tables.............................................. 8 Heating capacity tables............................................. 14 Capacity correction factor........................................... 20 6 Dimensional drawing & centre of gravity....................... 22 Dimensional drawing................................................ 22 7 Piping diagram..................................................... 23 8 Wiring diagram..................................................... 24 Wiring diagram...................................................... 24 External connection diagram........................................ 25 9 Sound data......................................................... 26 Sound pressure spectrum........................................... 26 Sound power spectrum............................................. 28 10 Installation.......................................................... 29 Installation method.................................................. 29 11 Operation range................................................... 31 Split Sky Air Outdoor Units 1

i n y k 3 r 7 o t o 0- i d 1 l t 4 pu- Outdoor Units R-410A RMXS-E7V3B1 1 Features 1 BU S V A E S X M O RS The RMXS gives you a high-capacity multi split system which combines the power and easy installation of a VRV outdoor unit with the quiet operation of residential - use indoor units. The Super Multi Plus has more than enough power to drive up to 9 indoor units, including a 7,1 kw class unit. An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures. A 135-meter piping length means there are now no restrictions on the choice of installation position for indoor units, greatly improving planning flexibility. 1 2 Split Sky Air Outdoor Units

2 Specifications Outdoor Units R-410A RMXS-E7V3B1 2-1 NOMINAL CAPACITY AND NOMINAL INPUT RMXS112E7V3B1 RMXS140E7V3B1 RMXS160E7V3B1 Capacity Cooling Standard kw 11.2 14.0 15.5 (Conditions Heating Standard kw 12.5 16.0 17.5 specified in 1) For combination EER Cooling 3.20 2.75 2.87 indoor units + outdoor units COP Heating 3.18 3.07 3.22 Max. number of connectable indoor units (BP to be connected) 6 8 9 Min. / Max. total capacity index of I/U to be connected 50/130 62.5 / 162.5 70 /182 2 2-2 TECHNICAL SPECIFICATIONS RMXS112E7V3B1 RMXS140E7V3B1 RMXS160E7V3B1 Casing Colour Daikin white Material Painted galvanised steel plate Dimensions Unit Height mm 1345 1345 1345 Width mm 900 900 900 Depth mm 320 320 320 Packing Height mm 1524 1524 1524 Width mm 980 980 980 Depth mm 420 420 420 Weight Unit kg 125 125 125 Packed Unit kg 130 130 130 Heat Exchanger Dimensions Length mm 857 857 857 Nr of Rows 2 2 2 Fin Pitch mm 2 2 2 Nr of Passes 10 10 10 Face Area m² 1.131 1.131 1.131 Nr of Stages 60 60 60 Tube type Hi-XSS(8) Fin Type Non-symmetric waffle louvre Treatment Corrosion resistant Fan Type Propeller Discharge direction Horizontal Quantity 2 2 2 Air Flow Rate Cooling m³/min 106 106 106 (nominal at 230V) Heating m³/min 102 105 105 Motor Quantity 2 2 2 Model Brushless DC motor Motor Speed (nominal) Cooling rpm 850/815 Heating rpm 820/785 840/805 840/805 Fan Motor Output W 70 70 70 Compressor Quantity 1 1 1 Motor Model JT100G-VDL@T2 Type Hermetically sealed scroll compressor Speed rpm 6480 6480 6480 Motor Output W 2.5 3000 3500 Crankcase W 33 33 33 Heater Starting Method Direct on line Operation Range Cooling Min CDB -5-5 -5 Max CDB 46 46 46 Heating Min CWB -15-15 -15 Max CWB 20 20 20 Sound Level Cooling Sound Power dba 67 68 70 (nominal) Sound Pressure dba 51 52 54 Heating Sound Pressure dba 53 54 55 Sound Level (Night quiet) Sound Pressure dba Step 1: 47Step 2: 44Step 3: 41 step 1: 47step 2: 44step 3: 41 step 1: 47step 2: 44step 3: 41 Split Sky Air Outdoor Units 3

2 Specifications Outdoor Units R-410A RMXS-E7V3B1 2 2-2 TECHNICAL SPECIFICATIONS RMXS112E7V3B1 RMXS140E7V3B1 RMXS160E7V3B1 Refrigerant Type R-410A Charge kg 4.0 4.0 4.0 Control Expansion valve(electronic type) Nr of Circuits 1 1 1 Refrigerant Oil Type Daphne FVC68D Charged Volume l 1.5 1.5 1.5 Piping connections Liquid (OD) Quantity 1 1 1 Type Flare connection Diameter (OD) mm 9,52 Gas Quantity 1 1 1 Type Braze connection Diameter (OD) mm 19,1 Drain Quantity 3 3 3 Type Hole Diameter (OD) mm 26x3 Piping Length System total m 115 135 145 Piping Length Total OU - BP m 55 55 55 BP - IU m 60 80 90 1 room BP - IU m 15 15 15 Piping connections Height difference OU - BP m 30 30 30 OU - IU m 30 30 30 BP-BP/IU-IU m 15 15 15 Additional Refrigerant Charge kg/m Refer to installation manual Refere to installation manual Refer to installation manual Installation height difference Maximum m 30 30 30 Max. internunit level difference m 15 15 15 Heat Insulation Both liquid and gas pipes Defrost Method Reverse cycle Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method Inverter controlled Capacity control Cooling Minimum 24 24 24 Maximum 100 100 100 Heating Minimum 24 24 24 Maximum 100 100 100 Safety Devices High pressure switch Fan motor thermal protector Inverter overload protector PC board fuse Standard Item Gas connection pipe Accessories Quantity 3 3 3 Item Installation manual Quantity 1 1 1 Item Operation manual Drain socket Drain socket Quantity 1 1 1 Item Drain socket Drain cap Drain cap Quantity 1 2 2 Item Drain cap Drain receiver Drain receiver Quantity 2 3 3 Item Drain receiver Insulation Insulation Quantity 3 1 1 Item Insulation Operation manual Operation manual Quantity 1 1 1 4 Split Sky Air Outdoor Units

2 Specifications Outdoor Units R-410A RMXS-E7V3B1 2-2 TECHNICAL SPECIFICATIONS RMXS112E7V3B1 RMXS140E7V3B1 RMXS160E7V3B1 Notes * Nominal cooling capacities are based on : indoor temperature : 27 CDB, 19 CWB, outdoor temperature : 35 CDB, equivalent piping length: outdoor - BP: 5m / BP - indoor: 3m / level difference: 0m. * Nominal heating capacities are based on : indoor temperature : 20 CDB, outdoor temperature : 7 CDB, 6 CWB, equivalent piping length: outdoor - BP: 5m / BP - indoor: 3m / level difference: 0m. The sound power level is an absolute value indicating the power which a sound source generates. Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to sound level drawings of this chapter. Sound values are measured in a semi-anechoic room. 2 Split Sky Air Outdoor Units 5

3 Electrical data Outdoor Units R-410A RMXS-E7V3B1 3 Power supply Current Voltage range Wiring connections Power supply intake RMXS112EVB RMXS140EV3B RMXS160EV3B Name V3 Phase 1 Frequency Hz 50 Voltage V 230 Nominal running current (RLA) A 15.9 20.2 22.2 Starting current (MSC) A 15.9 20.2 22.2 Min. Circuit Amps (MCA) A 27.0 Max. Fuse Amps (MFA) A 32.0 Total overcurrent amps (TOCA) A 27.0 Full Load Amps (FLA) A 0.3 + 0.3 (Fan motor) Min. V 207 Max. V 264 For power supply Quantity 3 Remark Earth wire included For connection with BP Quantity 2 Remark F1+F2 Both BP unit and outdoor unit 3TW27601-4 SYMBOLS MCA : Min. Circuit Amps TOCA : Total Over-current Amps MFA : Max. Fuse Amps (see note 6) RLA : Rated Load Amps (A) FLA : Full Load Amps MSC : Starting current (see note 7) NOTES 1 RLA is based on the following conditions: Indoor temperature 27 CDB/19 CWB Outdoor temperature 35 CDB 2 TOCA means the total value of each OC set. 3 Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits 4 Maximum allowable voltage variation between phases is 2% 5 Select wire size based on the larger value of MCA or TOCA. 6 Instead of fuse, use circuit breaker MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). 7 MSC means the maximum current during start up of the compressor. 8 For more details concerning conditional connections, see http://extranet.daikineurope.com, select E-Data Books. Finally, click on the document title of your choice. 6 Split Sky Air Outdoor Units

Outdoor Units R-410A RMXS-E7V3B1 4 Options RMXS-EV N Item RMXS112 RMXS140 RMXS160 1 Drain plug KKPJ5F180 2 Refnet joint KHRQ22M20TA 3 Branch provider (2 rooms) BPMKS967B2 4 Branch provider (3 rooms) BPMKS967B3 4 *Note: all options are kits 4TW26791-2B Split Sky Air Outdoor Units 7

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-1 Cooling capacity tables 5 RMXS112EV- Cooling capacity Combination % Outdoor air temp. CDB Indoor air temp.: CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 3D052905 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. 8 Split Sky Air Outdoor Units

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-1 Cooling capacity tables RMXS112EV- Cooling capacity Combination % Outdoor air temp. CDB Indoor air temp.: CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 3 5 3D052905 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. Split Sky Air Outdoor Units 9

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-1 Cooling capacity tables 5 RMXS140EV- Cooling capacity Combination % Outdoor air temp. CDB Indoor air temp.: CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 3D052906 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. 10 Split Sky Air Outdoor Units

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-1 Cooling capacity tables RMXS140EV- Cooling capacity Combination % Outdoor air temp. CDB Indoor air temp.: CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 5 3D052906 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. Split Sky Air Outdoor Units 11

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-1 Cooling capacity tables 5 RMXS160EV- Cooling capacity Combination % Outdoor air temp. CDB Indoor air temp.: CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 3D052907 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. 12 Split Sky Air Outdoor Units

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-1 Cooling capacity tables RMXS160EV- Cooling capacity Combination % Outdoor air temp. CDB Indoor air temp.: CWB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 5 3D052907 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. Split Sky Air Outdoor Units 13

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-2 Heating capacity tables 5 RMXS112EV- Heating capacity Combination % Outdoor air temp. CDB Indoor air temp.: CDB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 3D052908 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. 14 Split Sky Air Outdoor Units

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-2 Heating capacity tables RMXS112EV- Heating capacity Combination % Outdoor air temp. CDB Indoor air temp.: CDB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 3 5 3D052908 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. Split Sky Air Outdoor Units 15

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-2 Heating capacity tables 5 RMXS140EV- Heating capacity Combination % Outdoor air temp. CDB Indoor air temp.: CDB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 3D052909 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. 16 Split Sky Air Outdoor Units

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-2 Heating capacity tables RMXS140EV- Heating capacity Combination % Outdoor air temp. CDB Indoor air temp.: CDB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 5 3D052909 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. Split Sky Air Outdoor Units 17

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-2 Heating capacity tables 5 RMXS160EV- Heating capacity Combination % Outdoor air temp. CDB Indoor air temp.: CDB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 3D052910 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. 18 Split Sky Air Outdoor Units

Outdoor Units R-410A RMXS-E7V3B1 5 Capacity tables 5-2 Heating capacity tables RMXS160EV- Heating capacity Combination % Outdoor air temp. CDB Indoor air temp.: CDB 14 C 16 C 18 C 19 C 22 C 24 C TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw 3 5 3D052910 Symbols: TC: Total capacity (kw) PI: Power input (kw) Notes: 1. This table shows outdoor unit cooling capacity and power input. 2. Q Is specified point. 3. PI of indoor units is not included in the table. Split Sky Air Outdoor Units 19

5 Capacity tables 5-3 Capacity correction factor Outdoor Units R-410A RMXS-E7V3B1 Capacity correction factor by the length of refrigerant piping (Reference) Rate of change in capacity by the main piping length Rate of change in cooling capacity 5 Main piping length 5 10 15 20 25 30 35 40 45 50 55 Rate of change in cooling capacity 100.0% 98.6% 97.2% 95.9% 94.7% 93.5% 92.3% 91.2% 90.1% 89.1% 88.1% Rate of change in heating capacity Main piping length 5 10 15 20 25 30 35 40 45 50 55 Rate of change in heating capacity 100.0% 99.5% 99.1% 98.6% 98.2% 97.7% 97.3% 96.9% 96.4% 96.0% 95.6% Rate of change in capacity by the main piping length Rate of change in capacity (%) Rate of change in cooling capacity Rate of change in heating capacity Main piping length (m) L1 In both cases, the outdoor unit is in inferior or superior position for the indoor unit, the rate of change in capacity is the same. Rate of change in capacity by the branch piping length (1) Refrigerant piping connection diameter liquid J6.4 gas J15.9 Rate of change in capacity Piping length Cooling Heating 3 100.0% 100.0% 5 99.6% 99.9% 10 98.7% 99.6% 15 97.9% 99.3% (3) Refrigerant piping connection diameter liquid J6.4 gas J9.5 Rate of change in capacity Piping length Cooling Heating 3 100.0% 100.0% 5 98.0% 98.8% 10 93.4% 96.0% 15 89.3% 93.5% (2) Refrigerant piping connection diameter liquid J6.4 gas J12.7 Rate of change in capacity Piping length Cooling Heating 3 100.0% 100.0% 5 99.1% 99.5% 10 96.9% 98.2% 15 94.8% 97.0% Piping size for field connection (mm) (KW) RA SA liquid gas liquid gas 25 J9.5 J9.5 35 J6.4 50 J6.4 J12.7 60 J15.9 71 J15.9 J9.5 Notes 1 These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under standard conditions. Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures. 2 With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out. System layout of piping Outdoor unit Piping length: L1 = 5m L2 = 3m BP unit Indoor unit 20 Split Sky Air Outdoor Units

5 Capacity tables 5-3 Capacity correction factor Outdoor Units R-410A RMXS-E7V3B1 (1) Refrigerant piping connection diameter liquid: J6.4 gas: J15.9 Cooling Heating 5 Rate of change in capacity (%) Branch piping length (m) L2 (2) Refrigerant piping connection diameter liquid: J6.4 gas: J15.9 Cooling Heating Rate of change in capacity (%) Branch piping length (m) L2 (3) Refrigerant piping connection diameter liquid: J6.4 gas: J15.9 Cooling Heating Rate of change in capacity (%) Branch piping length (m) L2 Method of calculating cooling / heating capacity: Total capacity from capacity tables x (Rate of change in capacity by main piping length x rate of change in capacity by branch piping length). Split Sky Air Outdoor Units 21

Outdoor Units R-410A RMXS-E7V3B1 6 Dimensional drawing & centre of gravity 6-1 Dimensional drawing 6 RMXS-EV Model A Hole for anchor bolt 4-M12 RMXS112E7V3B RMXS140E7V3B RMXS160E7V3B RXYSQ4P7V3B RXYSQ5P7V3B RXYSQ6P7V3B U-4ML4DPQ U-5ML4DPQ U-6ML4DPQ J19.1 Brazing J19.1 Brazing J19.1 Brazing J15.9 flare J15.9 flare J19.1 Brazing J15.9 flare J15.9 flare J19.1 Brazing In case of Panasonic 1 Gas pipe connection A 2 Liquid pipe connection - J9.5 flare 3 Service port (in the unit) (x2) 4 Electronic connection and grounding terminal MS (in switch box) 5 Refrigerant piping intake 6 Power supply wiring intake (knock hole J34) 7 Control wiring intake (knock hole J27) 8 Drain outlet 3TW27604-1 22 Split Sky Air Outdoor Units

7 Piping diagram Outdoor Units R-410A RMXS-E7V3B1 RMXS-EV Electronic expansion valve Double pipe heat exchanger Electronic expansion valve Filter Pressure regulating valve Heat exchanger 7 Filter Service port 4-way valve Capillary tube Service port Filter Low pressure sensor High pressure sensor Solenoid valve Filter Capillary tube Oil separator Filter Compressor High pressure switch Capillary tube Solenoid valve Accumulator Stop valve (with service port on field piping side J 7.9mm flare connection) 3D052712 Split Sky Air Outdoor Units 23

8 Wiring diagram 8-1 Wiring diagram Outdoor Units R-410A RMXS-E7V3B1 8 RMXS-EV Cool / Heat selector S1S : Selector switch (Fan/Cool - Heat) S2S : Selector switch (Cool - Heat) Connector of option adaptor X37A : Connector (Note 4) (option adaptor power supply) A1P : Printed circuit board (Main) A2P : Printed circuit board (INV.) A3P : Printed circuit board (Noise filter) A4P : Printed circuit board (C/H selector) BS1 BS5 : Push button switch (Mode, set, return, test, reset) C1 C4 : Capacitor DS1 : Dip switch E1HC : Crankcase heater F1U,F4U : Fuse (T 6.3A/250V) F6U : Fuse (T 5.0A/250V) FINTH : Thermistor (fin) H1P H8P : Light emitting diode (service monitor orange) : Prepare test ----------- Flickering [H2P] : Malfunction detection--- Light up HAP Light emitting diode (service monitor green) (A1P) HBP : INV. pilot lamp (service monitor green) (A1P) K1M : Magnetic contactor (M1C) K2R : Magnetic relay (K1M) K1R : Magnetic relay (Y1S) K2R : Magnetic relay (Y2S) K4R : Magnetic relay (Y3S) K5R : Magnetic relay (E1HC) L1R : Reactor M1C : Motor (compressor) M1F : Motor (fan) (upper) M2F : Motor (fan) (lower) PS : Switching power supply Q1DI : Field earth leak detector (30mA) R1 : Resistor R2 : Resistor R1T : Thermistor (Air) R2T : Thermistor (Discharge) R3T : Thermistor (Suction 1) R4T : Thermistor (Heat exchanger) R5T : Thermistor (Suction 2) R6T : Thermistor (subcooling HEX) R7T : Thermistor (Liquid pipe) S1NPH : Pressure sensor(high) S1NPL : Pressure sensor(low) S1PH : Pressure switch (High) V1R : Power module V2R,V3R : Diode module V1T : IGBT X1M : Terminal strip (Power supply) X2M : Terminal strip (Control) Y1E : Electronic expansion valve (Main) Y3E : Electronic expansion valve (Subcool) Y1S : Solenoid valve (4 way valve) Y2S : Solenoid valve (Hot gas) Y3S : Solenoid valve (U/L circuit) Z1C Z7C : Noise filter (ferrite core) Z1F Z4F : Noise filter Outdoor Position of compressor terminal Wire entrance Notes: 1. This wiring diagram only applies to the outdoor unit 2. L: Live, N: Neutral, : Field wiring 3. : Terminal strip : Connector : Connection Protective earth : Relay connector : (screw) : Noiseless earth : Terminal 4. When using the option adaptor, refer to the installation manual 5. Refer to the wiring diagram sticker (on back of front plate) on how to use BS1 - BS5 and DS1, DS2 switch 6. Do not operate the unit by short-circuiting protection device S1PH 7. Refer to the installation manual for connection wiring to PB unit - outdoor unit transmission F1-F2 8. When using the central control system, connect outdoor-outdoor transmission F1-F2. 9. Colours: WHT: White / RED: Red / BLU: Blue / BRN: Brown / GRN: Green / YLW: Yellow Cool / Heat selector Cool C/H selector Heat Air control To BP unit (Note 8) BP unit To out/d unit (Note 9) Outdoor Component location (Back) (Note 4) (Front) 2TW27606-1A 24 Split Sky Air Outdoor Units

8 Wiring diagram Outdoor Units R-410A RMXS-E7V3B1 8-2 External connection diagram RMXS112-160EV Outdoor unit Power supply 8 Fuse 2 wires cable Transmission line 2 wires cable Transmission line 2 wires cable Transmission line Power supply Power supply Power supply Fuse 3 wires cable Power line Fuse 3 wires cable Power line Fuse 3 wires cable Power line BP units 4 wires cable Power line and transmission line 4 wires cable Power line and transmission line 4 wires cable Power line and transmission line Indoor units When the power source is suppled to each BP unit individually. NOTES 1 All wiring, components and materials to be produced on the site must comply with the applicable local and national codes. 2 Use copper conductors only. 3 See wiring diagrams for details. 4 Install circuit breakers for safety. 5 All field wiring and components must be installed by a licensed electrician. 6 Units shall be grounded in compliance with applicable local national codes. 7 Wiring shown are general points-of-connection guides only and are not intended for or to include all details for a specific installation. 8 Be sure to install the switch and the fuse to the power line of each equipment. Outdoor unit Power supply Fuse 2 wires cable Transmission line 2 wires cable Transmission line 2 wires cable Transmission line Power supply Fuse 3 wires cable Power line 3 wires cable Power line 3 wires cable Power line BP units 4 wires cable Power line and transmission line 4 wires cable Power line and transmission line 4 wires cable Power line and transmission line Indoor units When the power source is connected in series between the units. Split Sky Air Outdoor Units 25

9 Sound data 9-1 Sound pressure spectrum Outdoor Units R-410A RMXS-E7V3B1 RMXS112EV- Cooling RMXS112EV- Heating 9 Octave band sound pressure level db:(0db = 0.0002 μ bar) Octave band sound pressure level db:(0db = 0.0002 μ bar) approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise 4D054137A NOTES Octave band center frequency (Hz) 4D054141A NOTES Octave band center frequency (Hz) 1 The operating sound is measured in anechoic chamber, if it is measured under the actual installation conditions, it is normally over the set value due to enviromental noise and sound reflection. 2 Measuring place: anechoic room 1 The operating sound is measured in anechoic chamber, if it is measured under the actual installation conditions, it is normally over the set value due to enviromental noise and sound reflection. 2 Measuring place: anechoic room Location of microphone Location of microphone RMXS140EV- Cooling RMXS140EV- Heating Octave band sound pressure level db:(0db = 0.0002 μ bar) Octave band sound pressure level db:(0db = 0.0002 μ bar) approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise 4D054138A NOTES Octave band center frequency (Hz) 4D054142A NOTES Octave band center frequency (Hz) 1 The operating sound is measured in anechoic chamber, if it is measured under the actual installation conditions, it is normally over the set value due to enviromental noise and sound reflection. 2 Measuring place: anechoic room 1 The operating sound is measured in anechoic chamber, if it is measured under the actual installation conditions, it is normally over the set value due to enviromental noise and sound reflection. 2 Measuring place: anechoic room Location of microphone Location of microphone 26 Split Sky Air Outdoor Units

Outdoor Units R-410A RMXS-E7V3B1 9 Sound data 9-1 Sound pressure spectrum RMXS160EV- Cooling RMXS160EV- Heating 3 Octave band sound pressure level db:(0db = 0.0002 μ bar) Octave band sound pressure level db:(0db = 0.0002 μ bar) 9 approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise 4D054139A NOTES Octave band center frequency (Hz) 4D054143A NOTES Octave band center frequency (Hz) 1 The operating sound is measured in anechoic chamber, if it is measured under the actual installation conditions, it is normally over the set value due to enviromental noise and sound reflection. 2 Measuring place: anechoic room 1 The operating sound is measured in anechoic chamber, if it is measured under the actual installation conditions, it is normally over the set value due to enviromental noise and sound reflection. 2 Measuring place: anechoic room Location of microphone Location of microphone Split Sky Air Outdoor Units 27

9 Sound data 9-2 Sound power spectrum Outdoor Units R-410A RMXS-E7V3B1 RMXS112EV RMXS140EV 9 Sound power level (db) Sound power level (db) 3TW27607-3 NOTES Octave band center frequency (Hz) 3TW27617-3 NOTES Octave band center frequency (Hz) 1 dba = A-weighted sound power level (A-scale according to IEC) 2 Refernece acoustic intensity 0dB = 10E-6μW/m_ 3 Measured according to ISO 3744 1 dba = A-weighted sound power level (A-scale according to IEC) 2 Refernece acoustic intensity 0dB = 10E-6μW/m_ 3 Measured according to ISO 3744 RMXS160EV Sound power level (db) 3TW27627-3 NOTES Octave band center frequency (Hz) 1 dba = A-weighted sound power level (A-scale according to IEC) 2 Refernece acoustic intensity 0dB = 10E-6μW/m_ 3 Measured according to ISO 3744 28 Split Sky Air Outdoor Units

10 Installation 10-1 Installation method Outdoor Units R-410A RMXS-E7V3B1 Required installation space The unit of the values is mm. (2) Where there is an obstacle on the discharge side (a) No obstacle above (1) Stand-alone installation 1. Where there is an obstacle on the suction side (a) No obstacle above 1 Stand-alone installation + Obstacle on the suction side only. (2) Series installation (2 or more) 500 or more 10 100 or more + Obstacle on both sides. 1000 or more (b) Obstacle above, too. 500 or less 100 or more 100 or more 100 or more 1 Stand-alone installation 1000 or more 2 Series installation (2 or more). + Obstacle on both sides 2 Series installation (2 or more). 500 or more 1000 or more 500 or less 200 or more 300 or more 1000 or more (b) Obstacle above, too. 500 or less 1000 or more 1000 or more 1 Stand-alone installation + Obstacle on the suction side,. 100 or more 3. Where there are obstacles on both suction and discharge sides: Pattern 1 + Obstacle on the suction side and both sides. 500 or less 1000 or more Where the obstacles on the discharge side is higher than the unit. (There is no height limit for obstructions on the intake side.) (a) No obstacle above. 1 Stand-alone installation. 150 or more 150 or more 150 or more 100 or more 500 or more 2 Series installation (2 or more). 2 Series installation (2 or more). + Obstacle on the suction side and both sides. 500 or less 1000 or more 1000 or more 300 or more 200 or more 300 or more 1000 or more Split Sky Air Outdoor Units 29

10 Installation 10-1 Installation method Outdoor Units R-410A RMXS-E7V3B1 (b) Obstacle above, too 1 Stand-alone installation. 1 Series installation. 10 The relations between H, A and L are as follows. L A 0<L 1/2 H 750 L H 1/2H<L H 1000 H < L Set the stand as:l<=h Close the bottom of the installation frame to prevent the discharged air from being bypassed. 2 Series installation (2 or more). The relations between H, A and L are as follows. L A 0<L 1/2 H 1000 L H 1/2H<L H 1250 H < L Set the stand as:l<=h Close the bottom of the installation frame to prevent the discharged air from being bypassed. Only two units can be installed for this series. Pattern 2 Where the obstacle on the discharge side is lower than the unit. (There is no height limit for obstructions on the intake side.) (a) No obstacle above. 1 Stand-alone installation. L H 2 Series installation (2 or more). The relations between H, A and L are as follows. L A 0<L 1/2 H 250 1/2H<L H 300 (b) Obstacle above, too. 1 Stand-alone installation. The relations between H, A and L are as follows. L A 0<L 1/2 H 100 L H 1/2H<L H 200 H < L Set the stand as:l<=h 500 or less 500 or less 1000 or more 1000 or more 100 or more 500 or more 1500 or more 500 or less 250 or more 300 or more 100 or more The relations between H, A and L are as follows. L A 0<L 1/2 H 250 L H 1/2H<L H 300 H < L Set the stand as:l<=h Close the bottom of the installation frame to prevent the discharged air from being bypassed. Only two units can be installed for this series. 4. Double-decker installation (a) Obstacle on the discharge side. Close the gap A (the gap between the upper and lower outdoor units) to prevent the discharged air from being bypassed. Do not stack more than two unit.. (b) Obstacle on the suction side only. Close the gap A (the gap between the upper and lower outdoor units) to prevent the discharged air from being bypassed. Do not stack more than one unit.. 5. Multiple rows of series installation (on the rooftop, etc.). (a) One row of stand-alone installation. (b) Rows of series installation (2 or more). 1000 or more 200 or more 500 or less 2000 or more 1500 or more 1000 or more 300 or more Drain piping construction dimension 100 or more 1000 or more Drain piping construction dimension 3000 or more Close the bottom of the installation frame to prevent the discharged air from being bypassed. 1000 or more 1500 or more 600 or more The relations between H, A and L are as follows. L A 0<L 1/2 H 250 L H 1/2H<L H 300 H < L Cannot be installed 3D049376B 30 Split Sky Air Outdoor Units

11 Operation range Outdoor Units R-410A RMXS-E7V3B1 RMXS-EV Cooling (50/60Hz) Heating 11 Outdoor temp. ( CDB) Continuous operation Pull-down period Outdoor temp. ( CWB) Warming up period Continuous operation Indoor temp. ( CWB) Indoor temp. ( CDB) Notes: The graphs are based on the following conditions: + Equivalent piping length From outdoor unit to BP unit 5 m Total from BP unit to indoor unit 3 m + Level difference 0 m + Air flow rate high 3D049096C Split Sky Air Outdoor Units 31

Split - Sky Air The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V.. ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment. Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. Daikin units comply with the European regulations that guarantee the safety of the product. Daikin Europe N.V. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products. Zandvoordestraat 300 B-8400 Ostend - Belgium www.daikineurope.com EEDE06-1/3(PART2) 09/2006 Prepared in Belgium by Lannoo ÉEEDE06-1/3(PART2):ËÍ