PRE-PRINT APPENDIX E GREEN MECHANICAL CODE SUPPLEMENT

Similar documents
READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)

COMcheck Software Version Mechanical Compliance Certificate

2009 IECC Commercial Mechanical Requirements

SESSION Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE ( ) ASHRAE Detroit Members:

COMcheck Software Version Review Mechanical Compliance Certificate

HVAC Mandatory Provisions Part II, Page 1

COMcheck Software Version Mechanical Compliance Certificate

2006 Washington State Nonresidential Energy Code Compliance Form Washington State Nonresidential Energy Code Compliance Forms Revised July 2007

August 15, 2013 Page 1 of 19

COMMERCIAL ENERGY EFFICIENCY

COMcheck Software Version Mechanical Compliance Certificate

Application of the 2012 North Carolina Energy Conservation Code

COMcheck Software Version Mechanical Compliance Certificate

COMMERCIAL ENERGY EFFICIENCY

COMcheck Software Version Interior Lighting Compliance Certificate

Mechanical Compliance Certificate

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC

COMcheck Software Version Interior Lighting Compliance Certificate

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

AHRI Certification Program Scopes - COOLING

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

1 - This title will copy onto other forms Date

Ventilation for New Low-Rise Residential Buildings July 20, 2015

ONTARIO BUILDING CODE AND SUPPLEMENTARY STANDARD SB-10 PROJECT INFORMATION. Mechanical Designer Information*

COMcheck Software Version Mechanical Compliance Certificate

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

Equipment Specifications and Required Information Quantity Rebate

Inspection Phase Three. Mechanical, Electrical & Plumbing Section 503

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

INDEX. ADDITIONS AND ALTERATIONS Defined Requirements ADMINISTRATION AND ENFORCEMENT... Chapter 1 AIR ECONOMIZERS

ASHRAE/IESNA Standard

ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

CHAPTER 4. HVAC DELIVERY SYSTEMS

COMMERCIAL ENERGY EFFICIENCY

SECTION AIR-SOURCE UNITARY HEAT PUMPS

Address Account # Member # Equipment Specifications Quantity Rebate. ENERGY STAR Appliances

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P Edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

NAHB Green Home Building Guidelines. 3.1 Prerequisites. ResCheck. Energy Efficiency

High Performance Building Guide 1

COMcheck Software Version Mechanical Compliance Certificate

Job Name Control Systems Description Date

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

SECTION/SUBSECTION (scroll down to view more listings; this list is arranged alphabetically) SCOPE. AHRI Section-Subsection Scopes

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

COMcheck Software Version

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Dehumidifying with Dedicated Outdoor Air

AHRI Product Section and Subsection Scopes

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION

Deemed Savings, Installation & Efficiency Standards

HVAC Equipment Access Equipment Location

Massachusetts Energy Code Compliance Support Commercial Energy Code Building Mechanical & Service Water Heating Provisions

August 27, Section 3.2 Definitions. On page 11 delete the following definition:

Snohomish County PUD #1 HEAT PUMP SYSTEM INSTALLATION STANDARDS

wattsmart New Homes Contractor-Certified HVAC Quality Assurance (HVAC-QI)

2019 Smart Energy Existing Homes Program Manual

ASHRAE JOURNAL ON REHEAT

Energy-Efficiency Measures List

Appendix 13. Categories of Cooling and Heating systems

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

2012 INTERNATIONAL FUEL GAS CODE VENTS

IMC Significant Changes Summary Tier I

2016 BUILDING ENERGY EFFICIENCY STANDARDS RESIDENTIAL HVAC ALTERATIONS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

General HVAC Recommendations

Inspection Checklist Mechanical Rough in

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

LEED for Homes V4 Provisional Alternative Compliance Paths for the Canadian market March, 2017

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

ENGINEERING. Edition No. 13 October 2002

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

Chapter FUEL GAS CODE*

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

SPECIFIC APPLIANCES CHAPTER 6

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

COMMERCIAL HVAC EQUIPMENT Indoor Self-Contained Units

Submittal Data Performance Data Electrical Data

Inspection Checklist Mechanical Final

Section 42. Lead Paint Risk Factor NONE WATER HEATER STORAGE GAS

C.E.P., C.E.M, C.I.P.E.

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

GARCIA GALUSKA DESOUSA Consulting Engineers

DUCT LEAKAGE (Page 1 of 3)

DIVISION 15 MECHANICAL

b.) Technical Information:

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

Transcription:

GREEN MECHANICAL CODE SUPPLEMENT E 101.0 General. E 101.1 Scope Applicability. The purpose of this appendix is to provide a comprehensive set of technically sound provisions that encourage sustainable practices and works towards enhancing the design and construction of mechanical systems that result in a positive long-term environmental impact. This appendix is not intended to circumvent the health, safety, and general welfare requirements of this code. E 101.2 Definition of Terms. For the purposes of this code, these definitions shall apply to this appendix. No attempt is made to define ordinary words, which are used in accordance with their established dictionary meanings, except where a word has been used loosely and it is necessary to define its meaning as used in this appendix to avoid misunderstanding. The definitions of terms are arranged alphabetically according to the first word of the term. E 201.0 Definitions. E 201.1 Cycles of Concentration for Cooling Towers. Cycles of concentration equals the specific conductance of the water in the cooling tower basin divided by the combined flow weighted average specific conductance of the makeup water(s) to the cooling tower. E 201.2 Energy Star. A joint program of the U.S. Environmental Protection Agency and the U.S. Department of Energy. Energy Star is a voluntary program designed to identify and promote energy-efficient products and practices. E 201.3 Geothermal. Renewable energy generated by deep-earth. E 201.4 Heating Seasonal Performance Factor (HSPF). The total heating output of a heat pump during its normal annual usage period for heating (in Btu) divided by the total electric energy input during the same period. E 201.5 Integrated Energy Efficiency Ratio (IEER).A single number figure of merit expressing cooling part-load EER efficiency for commercial unitary air-conditioning and heat pump equipment on the basis of weighted operation at various load capacities for the equipment. E 201.6 Integrated Part-Load Value (IPLV). A singlenumber figure of merit based on part-load EER, COP, or kw/ton expressing part-load efficiency for air-conditioning and heat pump equipment on the basis of weighted operation at various load capacities for the equipment. E 201.7 Maintenance. The upkeep of property or equipment by the owner of the property in compliance accordance with the requirements of this appendix. E 201.8 Minimum Efficiency Reporting Value (MERV). Filter minimum efficiency reporting value, in accordance with ASHRAE 52.2. E 201.9 Multi-Occupant Spaces. Indoor spaces used for presentations and training, including classrooms and conference rooms. E 201.10 Recirculation System. A system of hot water supply and return piping with shutoff valves, balancing valves, circulating pumps, and a method of controlling the circulating system. E 201.11 Seasonal Energy Efficiency Ratio (SEER). The total cooling output of an air conditioner during its normal annual usage period for cooling (in Btu) divided by the total electric energy input during the same period (in Wh). E 301.0 General Regulations. E 301.1 Installation. Mechanical systems covered by this appendix shall be installed in a manner conforming in accordance with to this code, other applicable codes, and the manufacturer s installation and operating instructions. E 301.2 Qualifications. Where permits are required, the Authority Having Jurisdiction shall have the authority to require contractors, installers, or service technicians to demonstrate competency. Where determined by the Authority Having Jurisdiction, the contractor, installer or service technician shall be licensed to perform such work. E 302.0 Disposal of Liquid Waste. E 302.1 Disposal. It shall be unlawful for a person to cause, suffer, or permit the disposal of liquid wastes, in a place or manner, except through and by means of an approved drainage system, installed and maintained in accordance with the provisions of the plumbing code. E 302.3 Connections to Plumbing System Required. Equipment and appliances, used to receive or discharge liquid wastes or sewage, shall be connected properly to the drainage system of the building or premises, in accordance with the requirements of the plumbing code and this appendix. E 303.0 Abandonment. E 303.1 General. An abandoned system or part thereof covered under the scope of this appendix shall be disconnected any from remaining systems, drained, plugged, and capped in an approved manner. E 401.0 Water Conservation and Efficiency. E 401.1 General. The provisions of this section establish the means of conserving potable and nonpotable water used in and around a building. 281

E 402.0 Meters. E 402.1 Required. A water meter shall be required for buildings connected to a public water system, including municipally supplied reclaimed (recycled) water. In other than single-family houses, multi-family structures of three stories or fewer above grade, and modular houses, a separate meter or submeter shall be installed in the following locations: (1) The makeup water supply to cooling towers, evaporative condensers, and fluid coolers. (2) The makeup water supply to one or more boilers collectively exceeding 1 000 000 British thermal units per hour (Btu/h) (293 kw). (3) The water supply to a water-using process where the consumption exceeds 1000 gallons per day (gal/d) (0.0438 L/s), except for manufacturing processes. (4) The makeup water supply to an evaporative cooler having an air flow exceeding 30 000 cubic feet per minute (ft 3 /min) (14 158.2 L/s). E 402.2 Consumption Data. A means of communicating water consumption data from submeters to the water consumer shall be provided. E 402.3 Access. Meters and submeters shall be accessible. E 403.0 HVAC Water Use. E 403.1 Once-Through Cooling. Once-through cooling using potable water is prohibited. E 403.2 Cooling Towers and Evaporative Coolers. Cooling towers and evaporative coolers shall be equipped with makeup water and blow down meters, conductivity controllers, and overflow alarms. Cooling towers shall be equipped with efficiency drift eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counterflow towers and 0.005 percent for cross-flow towers. E 403.3 Cooling Tower Makeup Water. Not less than five cycles of concentration is required for air-conditioning cooling tower makeup water having a total hardness of less than 11 grains per gallon (gr/gal) (188 mg/l) expressed as calcium carbonate. Not less than 3.5 cycles of concentration is required for air-conditioning cooling tower makeup water having a total hardness equal to or exceeding 11 gr/gal (188 mg/l) expressed as calcium carbonate. Exception: Air-conditioning cooling tower makeup water having discharge conductivity range not less than 7 gr/gal (120 mg/l) to 9 gr/gal (154 mg/l) of silica measured as silicon dioxide. E 403.4 Use of Reclaimed (Recycled) and On-Site Treated Nonpotable Water for Cooling. Where approved for use by the water/wastewater utility and the Authority Having Jurisdiction, reclaimed (recycled) or onsite treated nonpotable water shall be permitted to be used for industrial and commercial cooling or air-conditioning. E 403.4.1 Drift Eliminator. A drift eliminator shall be utilized in a cooling system, utilizing alternate sources of water, where the aerosolized water is capable of coming in contact with employees or members of the public. E 403.4.2 Disinfection. A biocide shall be used to treat the cooling system recirculation water where the recycled water is capable of coming in contact with employees or members of the public. E 501.0 Heating, Ventilation and Air-Conditioning Systems and Equipment - Energy Efficiency. E 501.1 Scope. The provisions of this section shall establish the means of enhancing energy efficiency associated with mechanical systems in a building. E 502.0 Heating, Ventilation, and Air-Conditioning Low-Rise Residential Buildings. E 502.1 General. The heating, ventilating, air-conditioning, for single-family houses, multi-family structures of three stories or fewer above grade, and modular houses shall be in accordance with Section E 502.2 through Section E 502.12. The heating, ventilation, and air-conditioning system of other buildings shall be in accordance with Section E 503.0. E 502.2 Heating, Ventilating, and Air-Conditioning Systems and Equipment. This section shall regulate equipment using single-phase electric power, air conditioners, and heat pumps with rated cooling capacities less than 65 000 British thermal units per hour (Btu/h) (19.0 kw), warm air furnaces with rated heating capacities less than 225 000 Btu/h (66 kw), boilers less than 300 000 Btu/h (88 kw) input, and heating-only heat pumps with rated heating capacities less than 65 000 Btu/h (19.0 kw). [ASHRAE 90.2:6.2] E 502.2.1 Non-Residential Type Systems and Equipment. Heating, ventilating, and air-conditioning systems and equipment that does not fall under the requirements in of Section E 502.0 shall be in accordance comply with the applicable requirements of Section E 503.0. E 502.3 Balancing. The air distribution system design, including outlet grilles, shall provide a means for balancing the air distribution system unless the design procedure provides a system intended to operate within ± 10 percent of design air quantities. [ASHRAE 90.2:6.3] E 502.3.1 Balancing Dampers. Balancing dampers shall be installed in branch ducts and the axis of the damper must shall be installed parallel to the direction of airflow in the main duct. E 502.4 Ducts. Ducts shall be sized, installed, and tested in accordance with Section E 502.4.1 through Section E 502.4.4. E 502.4.1 Insulation for Ducts. Portions of the air distribution system installed in or on buildings for heating and cooling shall be R-8. Where the mean outdoor dewpoint temperature in a month exceeds 60ºF (16ºC), vapor retarders shall be installed on conditioned-air supply ducts. Vapor retarders shall have a water vapor permeance not exceeding 0.5 perm [2.86 x 10-11 kg/(pa s m 2 )] where tested in accordance with Procedure A in ASTM E 96. Insulation is not required where the ducts are within the conditioned space. [ASHRAE 90.2:6.4] 282

E 502.4.2 Ducts and Register Penetrations. Joints, seams, and penetrations of duct systems shall be made airtight by means of mastics, gasketing, or other means in accordance with this code. Register penetrations shall be sealed to the wall or floor assemblies. Where HVAC duct penetrates a conditioned space, the duct penetration shall be sealed to the wall or floor assembly to prevent leakage into an unconditioned space. E 502.4.3 Duct Leakage Test. For systems with a duct or air handler outside of the conditioned space, a duct leakage test shall be performed in accordance with Section E 502.4.3.1. E 502.4.3.1 Duct Leakage Verification Test. Ductwork shall be tested to the maximum permitted leakage in 1 cubic foot per minute (ft 3 /min)/per 100 square feet (0.05 L/s/m 2 ) of duct surface area in accordance with the SMACNA Air Duct Leakage Test Manual. Register penetrations shall be sealed during the test. The test shall be conducted with a pressure differential of 0.1 inch water gauge (0.024 kpa) across the tested system. E 502.4.4 Duct Sizing. Duct systems shall be sized in accordance with ACCA Manual D or other methods approved by the Authority Having Jurisdiction with the velocity in the main duct not to exceed 1000 feet per minute (ft/min) (5 m/s) and the velocity in the secondary branch duct not to exceed 600 ft/min (3.05 m/s). E 502.5 Insulation for Piping. HVAC system piping installed to serve buildings and within buildings shall be thermally insulated in accordance with Table E 502.5. [ASHRAE 90.2:6.5] E 502.6 Ventilation and Combustion Air. E 502.6.1 Ventilation Air. The building shall be designed to have the capability to provide the ventilation air specified in Table E 502.6.1. Mechanical ventilation shall be calculated in accordance with Equation E 502.6.1. [ASHRAE 90.2:6.3.1] Mechanical Ventilation = [(0.35 Summer) Volume] / 60 (Equation E 502.6.1) Where: Mechanical Ventilation = required mechanical ventilation rate to supplement summer infiltration, cfm Summer = summer design infiltration rate, ach Volume = volume of conditioned space, ft 3 E 502.6.21 Combustion Air. Combustion air for fossil fuel heating equipment shall be in accordance comply with this code or with one of the following: nnatural gas and propane heating equipment, NFPA 54; oil heating equipment, NFPA 31; or solid fuel burning equipment, NFPA 211. [ASHRAE 90.2:6.3.2] E 502.7 Electric Heating Systems. Electric heating systems shall be installed in accordance with the following requirements. [ASHRAE 90.2:6.7] E 502.7.1 Wall, Floor, or Ceiling Electric-Resistance Heating. Where wall, floor, or ceiling electricresistance heating units are used, the structure shall be zoned and heaters installed in each zone in accordance with the heat loss of that zone. Where living and sleeping zones are separate, the number of zones shall not be less than two. If Where two or more heaters are installed in one room, they shall be controlled by one thermostat. [ASHRAE 90.2:6.7.1] E 502.7.2 Electric Central Warm Air Heating. When Where electric central warm air heating is to be installed, an electric heat pump or an off-peak electric heating system with thermal storage shall be used. [ASHRAE 90.2:6.7.2] Exceptions: (1) Electric resistance furnaces where the ducts are located inside the conditioned space, and not less than two zones are provided where the living and sleeping zones are separate. (2) Packaged air-conditioning units with supplemental electric heat. E 502.8 Bath Ceiling Units. Bath ceiling units providing a combination of heat, light, or ventilation shall be provided with controls permitting separate operation of the heating function. [ASHRAE 90.2:6.8] E 502.9 HVAC Equipment, Rated Combinations. HVAC system equipment and system components shall be furnished with the input(s), the output(s), and the value of the appropriate performance descriptor of HVAC products in accordance with federal law or as specified in Table E 502.9, as applicable. These shall be based on newly produced equipment or components. Manufacturer s recommended maintenance instructions shall be furnished with and attached to the equipment. The manufacturer of electric-resistance heating equipment shall furnish full-load energy input over the range of voltages at which the equipment is intended to operate. [ASHRAE 90.2:6.9] E 502.10 Controls. E 502.10.1 Temperature Control. Each system or each zone within a system shall be provided with not less than one thermostat capable of being set from 55ºF (13ºC) to 85ºF (29ºC) and capable of operating the system s heating and cooling. The thermostat or control system, or both, shall have an adjustable deadband, the range of which includes a setting of 10ºF (-12ºC) between heating and cooling where automatic changeover is provided. Wallmounted temperature controls shall be mounted on an inside wall. [ASHRAE 90.2:6.10.1] E 502.10.1.1 Initial Control Setting. The control shall initially be set for a maximum heating temperature of 70ºF (21ºC) and a cooling temperature of not less than 78ºF (26ºC). E 502.10.2 Ventilation Control. Each mechanical ventilation system (supply, exhaust, or both) shall be equipped with a readily accessible switch or other means for shutoff. Manual or automatic dampers installed for the purpose of isolating outside air intakes and exhausts from the air distribution system shall be designed for tight shutoff. [ASHRAE 90.2:6.10.2] 283

FLUID DESIGN OPERATING TEMPERATURE RANGE (ºF) INSULATION CONDUCTIVITY Btu inch/(h ft 2 ºF) MEAN RATING TEMPERATURE (ºF) TABLE E 502.5 MINIMUM PIPE INSULATION THICKNESS 1, 5 [ASHRAE 90.1 TABLE 6.8.3] NOMINAL PIPE DIAMETER (inches) <1 1 TO 1 1 4 1 1 2 TO 3 1 2 4 TO 6 EQUAL TO OR GREATER THAN 8 HEATING SYSTEMS (STEAM, STEAM CONDENSATE, AND HOT WATER) 2, 3 201 250 0.27 0.30 150 1.5 1.5 2.0 2.0 2.0 141 200 0.25 0.29 125 1.0 1.0 1.0 1.5 1.5 105 140 0.22 0.28 100 0.5 0.5 1.0 1.0 1.0 COOLING SYSTEMS (CHILLED WATER, BRINE, AND REFRIGERANT) 4 40 55 0.22 0.28 100 0.5 0.5 1.0 1.0 1.0 Below 40 0.22 0.28 100 0.5 1.0 1.0 1.0 1.5 For SI Units: t/ºc= (t/ºf-32)/1.8, 1000 British thermal unit = 1055 J 0.293 kw, 1 inch = 25 mm, 1 square foot = 0.0929 m 2 Notes: 1 For insulation outside the stated conductivity range, the minimum thickness (T) shall be determined as follows: T = r{(1 + t/r)k/k 1} Where: T = minimum insulation thickness (inches). r = actual outside radius of pipe (inches). t = insulation thickness listed in this table for applicable fluid temperature and pipe size. K = conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature [Btu inch/(h ft 2 ºF)] k = the upper value of the conductivity range listed in this table for the applicable fluid temperature. 2 These thicknesses are based on energy efficiency considerations only. Additional insulation is sometimes required relative to safety issues/surface temperature. 3 Piping insulation is not required between the control valve and coil on run-outs when where the control valve is located within 4 feet (1219 mm) of the coil and the pipe size is 1 inch (25 mm) or less. 4 These thicknesses are based on energy efficiency considerations only. Issues such as water vapor permeability or surface condensation sometimes require vapor retarders, additional insulation or both. 5 For piping exposed to outdoor air, increase insulation thickness by 1 2 of an inch (12.7 mm). The outdoor air is defined as any portion of insulation that is exposed to outdoor air. For example, attic spaces and crawlspaces are considered exposed to outdoor air. TABLE E 502.6.1 VENTILATION AIR [ASHRAE 90.2: TABLE 6.1.1] CATEGORY MINIMUM REQUIREMENT CONDITIONS Mechanical ventilation 1 50 ft 3 /min outdoor air When Where summer design infiltration rate calculated in accordance with reference standard A or B is less than 0.35 ach 2 Kitchen exhaust 100 ft 3 /min intermittent All conditions Bath exhaust intermittent All conditions For SI units: 1 cubic foot per minute = 0.00047 m 3 /s. Notes: 1 Calculate in accordance with Equation E 502.6.1. 2 Reference standards: (A) ACCA Manual J (B) ASHRAE GRP-158 E 502.10.3 Humidity Control. E 502.10.3.1 Heating. Where additional energy-consuming equipment is provided for adding moisture to maintain specific selected relative humidities in spaces or zones, a humidistat shall be provided. This device shall be capable of being set to prevent energy from being used to produce relative humidity within the space above 30 percent. [ASHRAE 90.2:6.10.3.1] E 502.10.3.21 Cooling. Where additional energyconsuming equipment is provided for reducing humidity, it shall be equipped with controls capable of being set to prevent energy from being used to produce a relative humidity within the space below 50 percent during periods of human occupancy and below 60 percent during unoccupied periods. [ASHRAE 90.2:6.10.3.2] 284

TABLE E 502.9 MINIMUM REQUIREMENTS FOR NON-FEDERALLY COVERED HVAC EQUIPMENT [ASHRAE 90.2: TABLE 6.9] EQUIPMENT TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE Groundwater source heat pump* Cooling Mode 11.0 EER @ 70ºF Ent. Water 11.5 EER @ 50ºF Ent. Water ARI 325 Heating Mode 3.4 COP @ 70ºF Ent. Water 3.0 COP @ 50ºF Ent. Water ARI 325 Unitary A/C Water cooled split system 9.3 EER @ 85ºF Ent. Water 8.3 IPLV @ 75ºF Ent. Water ARI 210/240 Evaporatively cooled split system 9.3 EER @ 95ºF Out. Amb. 8.5 IPLV @ 80ºF Out. Amb. ARI 210/240 For SI units: t/ºc = (t/ºf-32)/1.8 * Performance for electrically powered equipment with capacity less than 65 000 Btu/h (19.0 kw) when where rated in accordance with ARI Standard 325. E 502.10.4 Freeze Protection Systems. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self-regulating heat tracing, shall include automatic controls capable of shutting off the systems where outdoor air temperatures are above 40ºF (4ºC) or where the conditions of the protected fluid will prevent freezing. Snow- and ice-melting systems shall include automatic controls capable of shutting off the systems where the pavement temperature is above 50ºF (10ºC) and no precipitation is falling and an automatic or manual control that will allow shutoff when where the outdoor temperature is above 40ºF (4ºC) so that the potential for snow or ice accumulation is negligible. [ASHRAE 90.1:6.4.3.8] E 502.10.5 Other Controls. Where setback, zoned, humidity and cooling controls and equipment are provided, they shall be designed and installed in accordance with Section E 502.10. [ASHRAE 90.2:6.10.3.3] E 502.11 Whole House Fans. Whole house exhaust fans shall have insulated louvers or covers which close where the fan is off. Covers or louvers shall have a insulation value of not less than R-4.2, and shall be installed in accordance with the manufacturer s installation instructions. The attic openings shall be sufficient to accommodate the ventilation capacity of the whole house fan. The operation of the whole house fan shall be considered in determining the adequacy of providing combustion air in accordance with this code. E 502.12 Dampers. Dampers shall be installed to close off outdoor air inlets and exhaust outlets where the ventilation system is not operating. E 503.0 Heating, Ventilation, and Air-Conditioning Other Than Low-Rise Residential Buildings. E 503.1 General. The heating, ventilation, and air-conditioning in buildings, other than single-family houses, multifamily structures of three stories or fewer above grade, and modular houses, shall be in accordance with this section. E 503.1.1 Scope. E 503.1.1.1 New Buildings. Mechanical equipment and systems serving the heating, cooling, or ventilating needs of new buildings shall be in accordance with the requirements of this section as described in Section E 503.2. [ASHRAE 90.1:6.1.1.1] E 503.1.1.2 Additions to Existing Buildings. Mechanical equipment and systems serving the heating, cooling, or ventilating needs of additions to existing buildings shall be in accordance with the requirements of this section as described in Section E 503.2. Exception: Where HVAC to an addition is provided by existing HVAC systems and equipment, such existing systems and equipment shall not be required to be in accordance with this appendix. However, new systems or equipment installed must shall be in accordance with specific requirements applicable to those systems and equipment. [ASHRAE 90.1:6.1.1.2] E 503.1.1.3 Alterations to Heating, Ventilating, and Air-Conditioning in Existing Buildings. E 503.1.1.3.1 New HVAC equipment as a direct replacement of existing HVAC equipment shall be in accordance with the specific minimum efficiency requirements applicable to that equipment. [ASHRAE 90.1:6.1.1.3.1] E 503.1.1.3.21 New Cooling Systems. New cooling systems installed to serve previously uncooled spaces shall be in accordance with this section as described in Section E 503.2. [ASHRAE 90.1:6.1.1.3.2] E 503.1.1.3.32 Existing Cooling Systems. Alterations to existing cooling systems shall not decrease economizer capability unless the system is in accordance with Section E 503.5.1. [ASHRAE 90.1:6.1.1.3.3] E 503.1.1.3.43 Ductwork. New and replacement ductwork [insulation of] shall be in accordance comply with Section E 503.4.4.1 and Section E 503.4.4.2. [ASHRAE 90.1:6.1.1.3.4] E 503.1.1.3.54 Piping. New and replacement piping shall be in accordance comply with Section E 503.4.4.1. [ASHRAE 90.1: 6.1.1.3.5] Exceptions: Compliance shall not be required for the following: (1) Equipment that is being modified or repaired but not replaced, provided that such modifications, repairs for the following or both will not result in an increase in the annual energy consumption of the equipment using the same energy type. 285

(2) Replacement or alteration of equipment requires extensive revisions to other systems, equipment, or elements of a building, and such replaced or altered equipment is a like-for-like replacement. (3) Refrigerant change of existing equipment. (4) Relocation of existing equipment. (5) Ducts and pipes where there is insufficient space or access to meet these requirements. E 503.2 Compliance Path(s). E 503.2.1 Compliance with Section E 503.0 shall be achieved by meeting requirements for Section E 503.1, General; Section E 503.6, Submittals; Section E 503.7, Minimum Equipment Efficiency Tables; and either: (1) Section E 503.3, Simplified Approach Option for HVAC Systems. (2) Section E 503.4, Mandatory Provisions; and Section E 503.5, Prescriptive Path. [ASHRAE 90.1:6.2.1] Exception: Projects using the Energy Cost Budget Method of Section 11 of ASHRAE 90.1, provided such projects are in accordance with Section E 503.4, the mandatory provisions of this section, as a portion of that compliance path. E 503.3 Simplified Approach Option for HVAC Systems. E 503.3.1 Scope. The simplified approach is an optional path for compliance where the following conditions are met: (1) Building is two stories or fewer in height. (2) Gross floor area is less than 25 000 square feet (2323 m 2 ). (3) Each HVAC system in the building is in accordance with the requirements listed in Section E 503.3.21. [ASHRAE 90.1:6.3.1] E 503.3.21 Criteria. The HVAC system must shall meet the following criteria: (1) The system serves a single HVAC zone. (2) The equipment must shall meet the variable flow requirements of Section E 503.4.3.10. (3) Cooling shall be provided by a unitary packaged or split-system air conditioner that is either air-cooled or evaporatively cooled with efficiency meeting the requirements shown in Table E 503.7.1(1) (air conditioners), Table E 503.7.1(2) (heat pumps), or Table E 503.7.1(4) (packaged terminal and room air conditioners and heat pumps) for the applicable equipment category. (4) The system shall have an air economizer where indicated in Table E 503.5.1, with controls as indicated in Table E 503.5.1.1.3(1)2(1) and Table E 503.5.1.1.3(2)2(2) and with either barometric or powered relief sized to prevent overpressurization of the building. Where the cooling efficiency meets or exceeds the efficiency requirement in Table E 503.3.21, no economizer is required. Outdoor air dampers for economizer use shall be provided with blade and jamb seals. (5) Heating shall be provided by a unitary packaged or split-system heat pump that meets the applicable efficiency requirements shown in Table E 503.7.1(2) (heat pumps) or Table E 503.7.1(4) (packaged terminal and room air conditioners and heat pumps), a fuel-fired furnace that meets the applicable efficiency requirements shown in Table E 503.7.1(5) (furnaces, duct furnaces, and unit heaters), an electric resistance heater, or a baseboard system connected to a boiler that meets the applicable efficiency requirements shown in Table E 503.7.1(6) (boilers). (6) The outdoor air quantity supplied by the system shall be less than or equal to 3000 (cubic feet per minute) ft 3 /min (1415.8 L/s) and less than 70 percent of the supply air quantity at minimum outdoor air design conditions unless an energy recovery ventilation system is provided in accordance with the requirements in Section E 503.5.710. (7) The system shall be controlled by a manual changeover or dual setpoint thermostat. (8) Where a heat pump equipped with auxiliary internal electric resistance heaters is installed, controls shall be provided that prevent supplemental heater operation where the heating load is capable of being met by the heat pump alone during both steady-state operation and setback recovery. Supplemental heater operation is permitted during outdoor coil defrost cycles. Two means of meeting this requirement are: (a) A digital or electronic thermostat designed for heat pump use that energizes auxiliary heat where the heat pump has insufficient capacity to maintain setpoint or to warm up the space at a sufficient rate. (b) A multistage space thermostat and an outdoor air thermostat wired to energize auxiliary heat on the last stage of the space thermostat and where outside air temperature is less than 40ºF (4ºC). Heat pumps whose minimum efficiency is regulated by NAECA and whose HSPF rating both meets the requirements shown in Table E 503.7.1(2) and includes usage of internal electric resistance heatitng are exempted from the control requirements of this part [Section E 503.3.21(7)]. (9) The system controls shall not permit reheat or other form of simultaneous heating and cooling for humidity control. (10) Systems serving spaces other than hotel/motel guest rooms, and other than those requiring continuous operation, which have both a cooling or heating capacity greater than 15 000 Btu/h (4.4 kw) and a supply fan motor power greater than 3 4 horsepower (hp) (0.6 kw), shall be provided with a time clock that: (a) Can start and stop the system under different schedules for seven different day-types per week. (b) Capable of retaining programming and time setting during a loss of power for a period of not less than 10 hours. 286

(c) Includes an accessible manual override that allows temporary operation of the system for up to two hours. (d) Capable of temperature setback down to 55ºF (13ºC) during off hours. (e) Capable of temperature setup to 90ºF (32ºC) during off hours. (11) Except for piping within manufacturer s units, HVAC piping shall be insulated in accordance with Table E 503.7.31(11). Insulation exposed to weather shall be suitable for outdoor service (e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover). Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation. (12) Ductwork and plenums shall be insulated in accordance with Table E 503.7.21(19) and Table E 503.7.21(210) and shall be sealed in accordance with Table E 503.4.4.2(1). (13) Construction documents shall require a ducted system to be air balanced in accordance with industryaccepted procedures. (14) Where separate heating and cooling equipment serves the same temperature zone, thermostats shall be interlocked to prevent simultaneous heating and cooling. (15) Exhausts with a design capacity of over 300 ft 3 /min (142.0 141.6 L/s) on systems that do not operate continuously shall be equipped with gravity or motorized dampers that will automatically shut when where the systems are not in use. SYSTEM SIZE (kbtu/h) (16) Systems with a design supply air capacity greater than 10 000 ft 3 /min (4719.4 L/s) shall have optimum start controls. [ASHRAE 90.1:6.3.2] E 503.3.32 Climate Zone Determination. Climate zones identified in this appendix shall be determined in accordance with Section 5.1.4 of ASHRAE 90.1. Exception: If Where recorded historical climatic data are available for a construction site, it is permitted to be used to determine compliance if where approved by the Authority Having Jurisdiction. E 503.4 Mandatory Provisions. E 503.4.1 Equipment Efficiencies, Verification, and Labeling Requirements. E 503.4.1.1 Minimum Equipment Efficiencies Listed Equipment Standard Rating and Operating Conditions. Equipment shown in Table E 503.7.1(1) through Table E 503.7.1(7) shall have a minimum performance at the specified rating conditions where tested in accordance with the specified test procedure. Where multiple rating conditions or performance requirements are provided, the equipment shall satisfy stated requirements, unless otherwise exempted by footnotes in the table. Equipment covered under the Federal Energy Policy Act of 1992 (EPACT) shall have no minimum efficiency requirements for operation at minimum capacity or other than standard rating conditions. Equipment used to provide water heating functions as part of a combination system shall satisfy stated requirements for the appropriate space heating or cooling category. TABLE E 503.3.21 ELIMINATE REQUIRED ECONOMIZER BY INCREASING COOLING EFFICIENCY [ASHRAE 90.1: TABLE 6.3.2] MANDATORY MINIMUM EER 1 UNITARY SYSTEMS WITH HEAT PUMP HEATING CLIMATE ZONES 5 to 8 4 3 2 MINIMUM COOLING EFFICIENCY REQUIRED (EER) 1 65 and <135 10.1 N/A 2 12.1 11.6 11.1 135 and <240 9.3 N/A 2 11.3 10.8 10.4 240 and <760 9.0 N/A 2 10.9 10.5 10.0 SYSTEM SIZE (kbtu/h) MANDATORY MINIMUM EER 1 OTHER UNITARY SYSTEMS CLIMATE ZONES 5 to 8 4 3 2 TEST PROCEDURE 3 ARI 340/360 TEST PROCEDURE 3 MINIMUM COOLING EFFICIENCY REQUIRED (EER) 1 65 and <135 10.3 N/A 2 12.5 12.0 11.5 135 and <240 9.7 N/A 2 11.5 11.1 10.6 ARI 340/360 240 and <760 9.5 N/A 2 11.2 10.7 10.3 For SI units: 1000 British thermal units per hour = 0.293 kw. Notes: 1 Each EER shown should be reduced by 0.2 for units with a heating section other than electric resistance heat. 2 Elimination of required economizer is not allowed. 3 Section 12 of ASHRAE 90.1 contains complete specification of the referenced test procedure, including the referenced year version of the test procedure. 287

Tables are as follows: (1) Table E 503.7.1(1) Air Conditioners and Condensing Units. (2) Table E 503.7.1(2) Heat Pumps. (3) Table E 503.7.1(3) Water-Chilling Packages (see Section E 503.4.1.2 for water-cooled centrifugal waterchilling packages that are designed to operate at nonstandard conditions). (4) Table E 503.7.1(4) Packaged Terminal, Room Air Conditioners and Heat Pumps. (5) Table E 503.7.1(5) Furnaces, Duct Furnaces, and Unit Heaters. (6) Table E 503.7.1(6) Boilers. (7) Table E 503.7.1(7) Heat Rejection Equipment. Furnaces with input ratings of 225 000 Btu/h (66 kw), including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75 percent of the input rating. [ASHRAE 90.1:6.4.1.1] E 503.4.1.2 Minimum Equipment Efficiencies Listed Equipment Nonstandard Conditions. Water-cooled centrifugal water-chilling packages that are not designed for operation at ARI Standard 550/590 test conditions (and, thus, cannot be tested to meet the requirements of Table E 503.7.1(3)) of 44ºF (7ºC) leaving chilled-water temperature and 85ºF (29ºC) entering condenser-water temperature with 3 gallons per minute per ton (gal/min/t) (0.0002 L/s/kg) condenserwater flow shall have a maximum full-load and NPLV ratings. Adjusted using the following equation: Adjusted maximum full-load kw/ton rating = (fullload kw/ton from Table E 503.7.1(3))/Kadj (Equation E 503.4.1.2) Adjusted maximum NPLV rating = (IPLV from Table E 503.7.1(3))/Kadj Where: Kadj = 6.174722 0.303668(X) + 0.00629466(X) 2 0.000045780(X) 3 X = DTstd + LIFT DTstd = (24 + (full-load kw/ton from Table E 503.7.1(3) x 6.83)/Flow Flow = Condenser water flow (gpm)/cooling fullload capacity (tons) LIFT = CEWT CLWT CEWT = Full-load condenser entering water temperature, (ºF) CLWT = Full-load leaving chilled-water temperature, (ºF) The adjusted full-load and NPLV values are applicable over the following full-load design ranges: (1) Leaving Chiller-Water Temperature: 38ºF (3ºC) (2) Entering Condenser-Water Temperature: 102ºF (39ºC) (3) Condenser-Water Flow: 1 to 6 gal/min/t (6 x 10-5 L/s/kg to 0.000378 L/s/kg) (4) X 39ºF (4ºC) and 60ºF (16ºC) Chillers designed to operate outside of these ranges or applications utilizing fluids or solutions with secondary coolants (e.g., glycol solutions or brines) with a freeze point of 27ºF (-3ºC) or lower for freeze protection are not covered by this appendix. [ASHRAE 90.1:6.4.1.2] Example: Path A 600 ton (600 000 kg) centrifugal chiller Table E 503.7.1(3) efficiencies as of 1/1/2010 Full Load = 0.570 kw/ton IPLV = 0.539 kw/ton CEWT = 80ºF (27ºC) Flow = 2.5 gal/min/t (16x10-5 L/s/kg) CLWT = 42ºF (6ºC) LIFT = 80 42 = 38ºF (3ºC) DT = (24 + 0.570 6.83)/2.5 = 11.16ºF (-12ºC) X = 38 + 11.16 = 49.16ºF (10ºC) Kadj = 6.174772 0.303668(49.16) + 0.00629466(49.16) 2 0.00004578 (49.16) 3 = 1.020 Adjusted full load = 0.570/1.020 = 0.559 kw/ton NPLV = 0.539/1.020 = 0.528 kw/ton For SI units: 1 metric ton = 1000 kg, 1000 Btu/h = 0.293 kw, 1 gal/min = 0.0631 L/s,ºC = (ºF-32)/1.8 E 503.4.1.31 Equipment Not Listed. Equipment not listed in the tables referenced in Section E 503.4.1.1 and Section E 503.4.1.2 shall be permitted to be used. [ASHRAE 90.1:6.4.1.3] E 503.4.1.42 Verification of Equipment Efficiencies. Equipment efficiency information supplied by manufacturers shall be verified as follows: (1) Equipment covered under EPACT shall be in accordance with U.S. Department of Energy certification requirements. (2) Where a certification program exists for a covered product, and it includes provisions for verification and challenge of equipment efficiency ratings, then the product shall be listed in the certification program. (3) Where a certification program exists for a covered product, and it includes provisions for verification and challenge of equipment efficiency ratings, but the product is not listed in the existing certification program, the ratings shall be verified by an independent laboratory test report. (4) Where no certification program exists for a covered product, the equipment efficiency ratings shall be supported by data furnished by the manufacturer. (5) Where components such as indoor or outdoor coils from different manufacturers are used, the system designer shall specify component efficiencies whose combined efficiency meets the minimum equipment efficiency requirements in Section E 503.4.1. 288

(6) Requirements for plate type liquid to liquid heat exchangers are listed in Table E 503.7.1(8). [ASHRAE 90.1:6.4.1.4] E 503.4.1.53 Labeling. E 503.4.1.5.1 Mechanical Equipment. Mechanical equipment that is not covered by the U.S. National Appliance Energy Conservation Act (NAECA) of 1987 shall carry a permanent label installed by the manufacturer stating that the equipment is in accordance with the requirements of ASHRAE 90.1. [ASHRAE 90.1:6.4.1.5.1] E 503.4.1.5.23(A) Packaged Terminal Air Conditioners. Nonstandard size packaged terminal air conditioners and heat pumps with existing sleeve having an external wall opening of less than 16 inches (406 mm) high or less than 42 inches (1067 mm) wide and having a crosssectional area less than 670 square inches (62 0.432 m 2 ) shall be factory labeled as follows: Manufactured for nonstandard size applications only not to be installed in new construction projects. [ASHRAE 90.1:6.4.1.5.2] E 503.4.2 Load Calculations. Heating and cooling system design loads for the purpose of sizing systems and equipment shall be determined in accordance with generally accepted engineering standards and handbooks acceptable to the adopting authority (e.g., ASHRAE/ACCA Standard 183 or ASHRAE Handbook Fundamentals). [ASHRAE 90.1:6.4.2] E 503.4.3 Controls. E 503.4.3.1 Zone Thermostatic Controls. E 503.4.3.1.1 General. The supply of heating and cooling energy to each zone shall be individually controlled by thermostatic controls responding to temperature within the zone. For the purposes of Section E 503.4.3.1, a dwelling unit shall be permitted to be considered a single zone. [ASHRAE 90.1:6.4.3.1.1] Exceptions: Independent perimeter systems that are designed to offset building envelope loads shall be permitted to serve one or more zones also served by an interior system provided: (1) The perimeter system includes at least one thermostatic control zone for each building exposure having exterior walls facing one orientation for 50 contiguous feet (15 240 mm) or more. (2) The perimeter system heating and cooling supply is controlled by a thermostatic control(s) located within the zones(s) served by the system. Exterior walls are considered to have different orientations if where the directions they face differ by more than 45 degrees (0.79 rad). E 503.4.3.1.2 Dead Band. Where used to control both heating and cooling, zone thermostatic controls shall be capable of providing a temperature range or dead band of not less than 5ºF (-15ºC) within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. [ASHRAE 90.1:6.4.3.1.2] Exceptions: (1) Thermostats that require manual changeover between heating and cooling modes. (2) Special occupancy or special applications where wide temperature ranges are not acceptable (such as retirement homes, process applications, museums, some areas of hospitals) and are approved by the Authority Having Jurisdiction. E 503.4.3.2 Setpoint Overlap Restriction. Where heating and cooling to a zone are controlled by separate zone thermostatic controls located within the zone, means (such as limit switches, mechanical stops, or, for DDC systems, software programming) shall be provided to prevent the heating setpoint from exceeding the cooling setpoint minus an applicable proportional band. [ASHRAE 90.1:6.4.3.2] E 503.4.3.3 Off-Hour Controls. HVAC systems shall have the off-hour controls required by Section E 503.4.3.3.1(A) through Section E 503.4.3.3.4(D). [ASHRAE 90.1:6.4.3.3] Exceptions: (1) HVAC systems intended to operate continuously. (2) HVAC systems having a design heating capacity and cooling capacity less than 15 000 Btu/h (4.4 kw) that are equipped with readily accessible manual ON/ OFF controls. E 503.4.3.3.1(A) Automatic Shutdown. HVAC systems shall be equipped with one of the following: (1) Controls that can start and stop the system under different time schedules for seven different day-types per week, are capable of retaining programming and time setting during loss of power for a period of not less than 10 hours, and include an accessible manual override, or equivalent function, that allows temporary operation of the system for up to 2 hours. (2) An occupant sensor that is capable of shutting the system off where no occupant is sensed for a period of up to 30 minutes. (3) A manually operated timer capable of being adjusted to operate the system for up to 2 hours. (4) An interlock to a security system that shuts the system off where the security system is activated. [ASHRAE 90.1:6.3.3.1] Exception: Residential occupancies shall use controls that can start and stop the system under two different time schedules per week. E 503.4.3.3.2(B) Setback Controls. Heating systems located in climate zone 2 through zone 8 shall be equipped with controls that have the capability to automatically restart and temporarily 289

operate the system as required to maintain zone temperatures above a heating setpoint adjustable down to 55ºF (13ºC) or lower. Cooling systems located in climate zones 1b, 2b, and 3b shall be equipped with controls that have the capability to automatically restart and temporarily operate the system as required to maintain zone temperatures below a cooling setpoint adjustable up to 90ºF (32ºC) or higher or to prevent high space humidity levels. [ASHRAE 90.1:6.4.3.3.2] Exception: Radiant floor and ceiling heating systems. E 503.4.3.3.3(C) Optimum Start Controls. Individual heating and cooling air distribution systems with a total design supply air capacity exceeding 10 000 ft 3 /min (4719.4 L/s), served by one or more supply fans, shall have optimum start controls. The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied setpoint and the amount of time prior to scheduled occupancy. [ASHRAE 90.1:6.4.3.3.3] E 503.4.3.3.4(D) Zone Isolation. HVAC systems serving zones that are intended to operate or be occupied nonsimultaneously shall be divided into isolation areas. Zones may shall be permitted to be grouped into a single isolation area provided it does not exceed 25 000 square feet (2323 m 2 ) of conditioned floor area nor include more than one floor. Each isolation area shall be equipped with isolation devices capable of automatically shutting off the supply of conditioned air and outdoor air to and exhaust air from the area. Each isolation area shall be controlled independently by a device meeting the requirements of Section E 503.4.3.3.1(A), Automatic Shutdown. For central systems and plants, controls and devices shall be provided to allow stable system and equipment operation for a length of time while serving the smallest isolation area served by the system or plant. [ASHRAE 90.1:6.4.3.3.4] Exceptions: Isolation devices and controls are not required for the following: (1) Exhaust air and outdoor air connections to isolation zones where the fan system to which they connect is 5000 ft 3 /min (2360 L/s) and smaller. (2) Exhaust airflow from a single isolation zone of less than 10 percent of the design airflow of the exhaust system to which it connects. (3) Zones intended to operate continuously or intended to be inoperative where other zones are inoperative. E 503.4.3.4 Ventilation System Controls. 503.4.3.4.1 Stair and Shaft Vents. Stair and elevator shaft vents shall be equipped with motorized dampers that are capable of being automatically closed during normal building operation and are interlocked to open as required by in accordance with fire and smoke detection systems. [ASHRAE 90.1:6.4.3.4.1] E 503.4.3.4.2(A) Gravity Hoods, Vents, and Ventilators. Outdoor air supply and exhaust hoods, vents, and ventilators shall be equipped with motorized dampers that will automatically shut where the spaces served are not in use. [ASHRAE 90.1:6.4.3.4.2] Exceptions: (1) Gravity (nonmotorized) dampers are acceptable in buildings less than three stories in height above grade and for buildings of any height located in climate zone 1 through zone 3. (2) Ventilation systems serving unconditioned spaces. E 503.4.3.4.3(B) Shutoff Damper Controls. Both outdoor air supply and exhaust systems shall be equipped with motorized dampers that will automatically shut when where the systems or spaces served are not in use. Ventilation outdoor air dampers shall be capable of automatically shutting off during preoccupancy building warmup, cool down, and setback, except when where ventilation reduces energy costs (e.g., night purge) or when where ventilation must shall be supplied to meet the requirements of this code. [ASHRAE 90.1:6.4.3.4.3] Exceptions: (1) Gravity (nonmotorized) dampers are acceptable in buildings less than three stories in height and for buildings of any height located in climate zone 1 through zone 3. (2) Gravity (nonmotorized) dampers are acceptable in systems with a design outdoor air intake or exhaust capacity of 300 ft 3 /min (142.0 L/s) or less. E 503.4.3.4.4(C) Dampers. Where outdoor air supply and exhaust air dampers are required by Section E 503.4.3.4, they shall have a maximum leakage rate where tested in accordance with AMCA 500 as indicated in Table E 503.4.3.4.4(C). [ASHRAE 90.1:6.4.3.4.4] TABLE E 503.4.3.4.4(C) MAXIMUM DAMPER LEAKAGE [ASHRAE 90.1: TABLE 6.4.3.4.4] MAXIMUM DAMPER LEAKAGE OF DAMPER AREA (1.0 inch water gauge per ft 3 /min per ft 2 ) CLIMATE ZONES MOTORIZED NONMOTORIZED 1, 2, 6, 7, 8 4 Not allowed All others 10 20* For SI units: 1 inch = 25.4 mm, 1 cubic foot per minute = 0.06 L/s, 1 square foot = 0.929 m 2, 1 inch water gauge = 0.249 kpa * Dampers smaller than 24 inches (610 mm) in either dimension shall be permitted to have leakage of 40 (ft 3 /min)/ft 2 per square feet (203 L/s/m 2 ). 290

E 503.4.3.4.5(D) Ventilation Fan Controls. Fans with motors greater than 0.75 hp (0.6 kw) shall have automatic controls in accordance with Section E 503.4.3.3.1(A) that are capable of shutting off fans where not required. [ASHRAE 90.1:6.4.3.4.5] Exception: HVAC systems intended to operate continuously. E 503.4.3.5 Heat Pump Auxiliary Heat Control. Heat pumps equipped with internal electric resistance heaters shall have controls that prevent supplemental heater operation where the heating load can be met by the heat pump alone during both steady-state operation and setback recovery. Supplemental heater operation is permitted during outdoor coil defrost cycles. [ASHRAE 90.1:6.4.3.4.15] Exceptions: Heat pumps whose minimum efficiency is regulated by U.S. National Appliance energy Conservation Act (NAECA) and whose HSPF rating both meets the requirements shown in Table E 503.7.1(2) and includes usage of internal electric resistance heating. E 503.4.3.6 Humidifier Preheat. Humidifiers with preheating jackets mounted in the airstream shall be provided with an automatic valve to shut off preheat when where humidification is not required. [ASHRAE 90.1:6.4.3.6] E 503.4.3.7 Humidification and Dehumidification. Where a zone is served by a system or systems with both humidification and dehumidification capability, means (such as limit switches, mechanical stops, or, for DDC systems, software programming) shall be provided capable of preventing simultaneous operation of humidification and dehumidification equipment. [ASHRAE 90.1:6.4.3.7] Exceptions: (1) Zones served by desiccant systems, used with direct evaporative cooling in series. (2) Systems serving zones where specific humidity levels are required, such as museums and hospitals, and approved by the Authority Having Jurisdiction. E 503.4.3.8 Freeze Protection and Snow/Ice Melting Systems. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self-regulating heat tracing, shall include automatic controls capable of shutting off the systems where outdoor air temperatures are above 40ºF (4ºC) or where the conditions of the protected fluid will prevent freezing. Snow- and ice-melting systems shall include automatic controls capable of shutting off the systems where the pavement temperature is above 50ºF (10ºC) and no precipitation is falling and an automatic or manual control that will allow shutoff where the outdoor temperature is above 40ºF (4ºC) so that the potential for snow or ice accumulation is negligible. [ASHRAE 90.1:6.4.3.8] E 503.4.3.9 Ventilation Controls for High- Occupancy Areas. Demand control ventilation (DCV) is required for spaces larger than 500 square feet (46.45m 2 ) and with a design occupancy for ventilation of greater than 40 people per 1000 square feet (93 m 2 ) of floor area and served by systems with one or more of the following: (1) An air-side economizer. (2) An automatic modulating control of the outdoor air damper. (3) A design outdoor airflow greater than 3000 ft 3 /min (1416.0 L/s). [ASHRAE 90.1:6.4.3.9] Exceptions: (1) Systems with energy recovery in accordance with Section E 503.5.7.10. (2) Multiple-zone systems without DDC of individual zones communicating with a central control panel. (3) Systems with a design outdoor airflow less than 1200 ft 3 /min (566.3 L/s). (4) Spaces where the supply airflow rate minus a makeup or outgoing transfer air requirement is less than 1200 ft 3 /min (566.3 L/s). E 503.4.3.10 Single Zone Variable-Air-Volume Controls. HVAC systems shall have variable airflow controls as follows: (1) Air-handling and fan-coil units with chilled-water cooling coils and supply fans with motors greater than or equal to 5.36 hp (4 kw) shall have their supply fans controlled by two-speed motors or variable speed drives. At cooling demands less than or equal to 50 percent, the supply fan controls shall be able to reduce the airflow to no greater than the larger of the following: (a) One half of the full fan speed. (b) The volume of outdoor air required to meet the ventilation requirements of ASHRAE 62.1. (2) Air-conditioning equipment and air-handling units with direct expansion cooling and a cooling capacity at ARI conditions greater than or equal to 43.3 hp (32.329 kw) that serve single zones shall have their supply fans controlled by two-speed motors or variable-speed drives. At cooling demands less than or equal to 50 percent, the supply fan controls shall be able to reduce the airflow to no greater than the larger of the following: (a) Two-thirds of the full fan speed. (b) The volume of outdoor air required to meet the ventilation requirements of ASHRAE 62.1. [ASHRAE 90.1:6.4.3.10] E 503.4.3.11 Outdoor Heating. Radiant heat systems shall be used to provide heat outdoors. 291