Temperature Monitoring in Low-Voltage Switchgear

Similar documents
THERMAL DIAGNOSIS OF MV SWITCHBOARDS: A COST-EFFECTIVE, DEPENDABLE SOLUTION BASED ON AN OPTICAL SENSOR

Hunting the Mighty Milliwatt- The next Technology Step

Emerson s Pervasive Sensing strategies enable plants to realize full potential of Industrial IoT

Hunting the Mighty Milliwatt The next Technology Step

Moving to the Cloud: The Potential of Hosted Central Station Services

Smart Hub. Connecting people, connected care. What is it? Who is it for? How does it work?

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee

Monitoring of Electrical Equipment Failure Indicators and Alarming

Smart Sensing and Tracking with Video and Mote Sensor Collaboration

Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures

NEW HV/LV TRANSFORMER SUBSTATION WITHIN A BUILDING INTENDED FOR OTHER NON ELECTRICAL USES WITH ADVANCED FUNCTIONALITIES

Laird Thermal Systems Application Note. Bi-directional Microcontrollers Monitor and Protect Medical Equipment

THE SPOT* PERSONAL THERMAL COMFORT SYSTEM. A. Rabbani S. Keshav

Introducing the innovative ipids Indoor Outdoor Detection System MANUFACTURING SECURITY SOLUTIONS

Remote Monitoring of Offshore Structures using Acoustic Emission.

Design and Development of General Purpose Alarm Generator for Automated System

[Patil* et al., 5(7): July, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

Project Briefing Document. Section 3 Electrical Services design guide and specifications

Intelligent Fire Detection and Visual Guided Evacuation System Using Arduino and GSM

Managing Ex Asset Integrity

Design of Multi-Sensors Cooperation Control System for Intelligent Building

The Centron Presidio Monitoring System. Centron. Presidio. Rees Scientific. An ISO 9001:2008 Company

The Design of MLX90621 Based Intelligent Lighting Control System Hui-jiao Wang*, Meng-meng Liu and Cong-cong Shi

Arc Fault Protection System D1000

NFEC FIRE SAFETY SEMINAR Krish Mysore

The Legal Obligations of Employers to Maintain all Electrical Installations in a Safe Condition

Bringing Smarts to Methane Emissions Detection

D1000 Arc-fault Protection System

The Next Generation of VESDA Aspirating Smoke Detection Technology

VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage

ENACTMENT OF SCADA SYSTEM FOR JUDICIOUS DWELLING

Aspirating Smoke Detection PRODUCTS. Accessories Piping Conventional and Intelligent Detectors

Virtual Boundary System Using Passive Infrared Sensor

Boztek Solutions` PLAYSTATE

DIGITAL HOT WATER SOLUTIONS

Your specialist partner for total electrical compliance. Electrical Testing

Continuous, real-time detection, alarming and analysis of partial discharge events

Implementation of an Embedded Microcontroller-Based Intrusion Detection System

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Real Time Pipeline Leak Detection on Shell s North Western Ethylene Pipeline

Temperature and Calibration Capabilities

INTERNATIONAL STANDARD

Industrial and home safety Management using GSM

Temperature and Calibration Capabilities

A Forest Fire Warning Method Based on Fire Dangerous Rating Dan Wang 1, a, Lei Xu 1, b*, Yuanyuan Zhou 1, c, Zhifu Gao 1, d

Construction of An Automatic Power Switch using Infrared Motion Sensor

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.

Intrusion Detection System: Facts, Challenges and Futures. By Gina Tjhai 13 th March 2007 Network Research Group

United Electric Controls One Series Safety Transmitter Safety Manual

Smart Water Networks for Efficiency Gains

Fixed-Point Interface Profiling. Multi-Point Density Array (MDA) Solution for Separation Applications

Guide to Gate Safety Legislation & the Machinery Directive

2019 Price List. Company Overview. Gateways. Super Gateways. paragonrobotics.com GW3 GW10

Connected lighting components. Xitanium SR drivers EasyAir office sensors. Connected lighting components

Case Study. Custom Solutions for High Arc Flash Incident Energy and. Interlocked Electrical Enclosures. Overview: iriss.com

Performance Neuro-Fuzzy for Power System Fault Location

ELECTRICAL SAFETY for GAS ENGINEERS ACV. Do a GOOD JOB Take care of YOURSELF STAND OUT from the competition 2018 ISSUE 1. sterling4gas.co.

i-con Switchgear Condition Monitoring HV Switchgear Integrated Substation Condition Monitoring ISCM Answers for Infrastructure & Cities.

Guide to Gate Safety Legislation & the Machinery Directive. In Association with:

The safe way to verify the absence of voltage.

Speed and Frequency Seite 1 von 7

Totally Wireless Video Security

How many wireless networks does it take to optimize your plant?

NOVEL COMPACT SORPTION GENERATORS FOR HEAT PUMP APPLICATIONS

Altanium Temperature Controllers

GSM BASED GARBAGE AND WASTE COLLECTION BIN OVERFLOW INDICATOR

V3 Intelligent Damper Control and Monitoring System

SEC Signature Process Gas Analyzer

Bench Model of Electrical Control System for Inflatable Hemi- Spherical Structure

Open Source Home Security System

II. METHODS AND MATERIALS

Mass Sensors, Inc. Profile. Applications. Technology Baur Blvd, St. Louis, MO (314)

Remote Environment Monitoring & Detection Tribot

Fire Detection Using Image Processing

Safety Instrumented Systems

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

The water heater evolved. Hot water. Perfected.

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS

Surface Acoustic Wave Technology based Temperature Monitoring of High Voltage and High Current Switchgear Boxes

G-MAX IVS R123 Vibration Sensors Perimeter Intrusion Detection System

INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS: RESIDUAL CURRENT DEVICES

Permanent Infrared Hotspot Detection

Overview. Wireless Overview QLD NSW VIC Fundamentals. Operation. Features.

SITE SECURITY THE SMARTER WAY TO PROTECT REMOTE AND TEMPORARY SITES, 24 HOURS A DAY.

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

IOT ENABLED FOREST FIRE DETECTION AND ONLINE MONITORING SYSTEM

Products and systems

Connected Plant. SMARTLINE TRANSMITTERS So Smart, They Make Life Easy

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

15900 HVAC INSTRUMENTATION AND CONTROLS

Operation and use. Functions and characteristics

Reducing Arc Flash Risks with Electrical Maintenance Safety Devices - Part 2

The Mode of Urban Renewal Base on the Smart City Theory under the Background of New Urbanization

Integrated Security Solutions

Minimization of Mass Flow in District Heating Network Equipped with One Stage Domestic Hot Water Production Substations

Controllers, Indicators & Set Point Programmers

US Navy Leading the Way in Switchboard Protection

NEW. Innovative heating controls. Commercial boiler control systems. Control 8000 & MX25

Policy and Specification for the Interface with Independent Distribution Network Operators Installations

Transcription:

ISSN: 2516-6190 (Print) 2516-7219 (Online) http://sevenbridges.ncl-coll.ac.uk Temperature Monitoring in Low-Voltage Switchgear Andrew Turner Seven Bridges, Vol. 6 (2018) Published on: 05/07/2018 To cite this article: Turner, A. (2018) Temperature Monitoring in Low-Voltage Switchgear. Seven Bridges, 6, pp.75-81. View the full issue. Submit to Seven Bridges. Seven Bridges is published by: Newcastle College Rye Hill Campus Scotswood Road NE4 7SA

Temperature Monitoring in Low-Voltage Switchgear Andrew Turner BEng (Hons) Electrical Electronic Engineering Newcastle College ABSTRACT This article evaluates temperature monitoring solutions in low-voltage switchgear employing existing technologies, evaluating the effectiveness of an alternative, contemporary selfdiagnosing embedded solution. The design of the proposed system incorporated the monitoring of temperature-rise within low-voltage switchboards and emergency escalations to duty holders and end-users when electrical equipment has surpassed its thermal limits, predicting failure, rather than reacting to it. This intelligence in low-voltage switchgear will prove a key component in end-user asset management and integration into Smart Grid networks and Internet of Things (IoT). KEYWORDS: Condition Monitoring, Temperature Monitoring, Low-voltage Switchgear, Predictive Maintenance, Self-diagnostics. INTRODUCTION Low-voltage (LV) switchboards, are infrastructurally positioned at the centre of a building or site electrical distribution system. Armah Switchgear Ltd (ASL) is a specialist manufacturer of this integral piece of equipment. Switchboards are responsible for the supply and protection of electrical equipment throughout an installation from overload and short-circuit currents. Similarities can be drawn to the familiar consumer unit, fuse or circuit breaker distribution board, found in domestic dwellings, but on a larger and more complex scale. Example installations of the LV switchboards manufactured include: highintegrity data centres, manufacturing process plants within the motor industry, MoD sites, transport, prisons and hospitals, together with applications demanding robust redundancy to life safety equipment supplies (lifts, smoke ventilation, sprinkler pump systems, medical theatres). Continuity of supply, the lifespan of assets and operative safety are imperative within any electrical installation. Through rigorous laboratory testing of the product, full compliance with and beyond the requirements of the governing standard BS EN61439 (BSI, 2011) has been achieved with partner businesses. These are discussed in more detail hereinafter. The research evaluated existing temperature monitoring technologies to consider alternative improved methods for integration into intelligent LV switchgear systems, with several objectives set to identify existing sensor products and systems available within market. Technologies and methods used within existing products and systems for temperature monitoring electrical power 75

Andrew Turner distribution equipment have been evaluated. A concept has been developed for an improved approach/method of temperature monitoring of LV distribution equipment. This concept will be developed postresearch into a standard model and along with the methods of interpreting inputs within a closed-loop system and communication of data to a supervisory monitoring system. This report set out to explore the requirements of a predictive maintenance, closed-loop control system; utilising hardware and software, to warn, and if required, provide outputs to de-energise circuits to ensure safe operation within design parameters. These requirements cover the legal obligations of duty of the asset holders. MONITORING TECHNOLOGY The research motivation for developing an intelligent system for energy and temperature monitoring is rooted in the Smart Grid initiative, detailed in Figure 1 below. Figure 1. Features of Proposed Technology research is intended to ensure the ASL LV product is technologically prepared for dynamic condition reporting, so energy consumption and the correct operation within the thermal limits to which the assembly has been tested to can be monitored by an end-user s supervisory system. Figure 2. Remote Condition Monitoring of LV Switchgear TEMPERATURE MONITORING A popular method of switchgear temperature monitoring, to check for hotspots at cabling termination points or copper busbar connections such as joint fishplates, is by the use of an infrared (IR) thermal imaging camera, allowing inspection via special crystal or mesh viewing ports mounted on the switchboard s external coverings, Figure 3. Usually conducted annually, the inspection will most likely not highlight a problem area if load or ambient temperature in room is lower than occasionally sustained. Figure 3. Thermal imaging view ports (left/centre) and hotspot within fuse chamber (right) Smart Grid demands implementation of methods of continuous system monitoring, (as shown in Figure 2) through modernisation of existing electrical systems from grid to socket. This is achieved by use of information and technology to monitor and actively control generation and demand in near real-time (Ofgem, 2014). This Source: Yan, et al. (2017) DeGrate et al. (2015) describe the main limitations of thermal imaging to be the restrictive viewing angles available to 76

Seven Bridges Vol. 6 (2018) interrogate internal switchboard connection temperatures, those which are immediately behind coverings, as seen in Figure 4. Figure 4. Operative carrying out thermal survey of switchgear using IR thermal imaging camera through a crystal viewing port directly related to limits identified during design verification. The end-user, or the designer, will specify that requirements from the switchboard manufacturer must include compliance to the standard, BS EN 61439 (BSI, 2011), see Table 1. Design verification, the act of ensuring the assembly is compliant, must be carried out by the manufacturer. Source: Yan, et al. (2017) For intrusive access to continuously monitor temperature at all key locations, IR sensors and thermocouples are utilised, eliminating line-of-sight issues of thermal imaging windows (Durocher and Loucks, 2015). See Figure 5. Figure 5. IR sensors mounted within switchgear for monitoring all key locations within an assembly The standard allows design verification to be carried out by testing, calculation or by design rules. The data used within this study are derived from testing, conducted within controlled environments in verified laboratories in the UK and Europe within which assemblies have been tested, based on set assembly configurations and arrangements. Table 1. Extract: BS EN 61439-1, Annex D Characteristic to be verified Verification Options Available Test Calculation Design Rules Temperature-rise limits YES YES YES Source: Standard BS EN 61439-1 (BSI, 2011) Source: Calex (2018) SELF-DIAGNOSTICS TECHNOLOGY Existing condition monitoring systems monitor temperatures and signal alarm or trip signals when temperatures have surpassed safe operational levels. An intelligent approach must be able to continuously monitor working temperatures in-line with the temperature-rise limits of the tested arrangement s design, verified through standards testing. Early selfdiagnosis of premature aging or the initiation of failure of switchgear can be SENSOR SELECTION A range of sensors were considered in the selection process. The K-type thermocouple (Figure 6) is an inexpensive option with a unit price less than 10 and sufficiently accurate, at 0.5% or 2 C, whichever is greater (RS Components, 2018). However, the sensor is intrusive as it must be surface mounted to the material which it is monitoring. This introduces the potential for the tracking of leakage currents between conductors and instruments. It would not be possible to busbar mount with sensor in supplementary insulation as it may be detrimental to measurement accuracy. 77

Andrew Turner Figure 6. K-Type Thermocouple Sensor Source: RS Components (2018) The IR sensor is unintrusive, has no physical connection, compared to the K- type thermocouple. It is hardwired and expensive in comparison, at over 200 per sensor. Its accuracy is ±1% or 1 C, whichever is greater (Calex, 2018). Figure 7. Prototype IR Sensor Source: Calex (2018) The SAW passive sensor is unintrusive and requires no power; components are passive and excited via radio waves, it detects surface temperatures through dynamic response of a piezo crystal directly mounted to the surface of the material. SAW stands for surface acoustic wave ; the wave which is emitted from the piezo crystal upon radio wave excitation. The response of the crystal, picked up by a remote antenna, allows temperature to be measured as frequency responses vary, with an accuracy of ±2 C. Figure 8. Wireless SAW Sensor The IR sensor was selected for integration into the proposed system, albeit expensive, it allowed hard-wire connection, providing ease of compatibility, whilst offering unintrusive monitoring; no physical connection to conductors or surfaces is required. DATA ANALYSIS AND THEORY Data gathered from BS EN 61439 laboratory testing is utilised to gauge overall assembly and switchgear limits. This allows actual temperature inputs from IR sensors to be compared with expected temperatures or the set limits of the assembly and switchgear. It is important to note, that exceeding the design limit of the assembly may not trigger a traditional temperature monitoring system and would therefore not alert the end-user to exercise predictive measures, but only to reactive maintenance requirements, or potentially catastrophic failure of switchgear (see Figure 11). The theory detailing the relationship between electrical energy and thermal losses of switchgear is detailed below in Research and Findings section. LIMITATIONS OF RESEARCH The research presented by the author is a hypothesis utilising data gathered from laboratory testing. Software along with an embedded algorithmic formula to interpret continuous data inputs from real installations was used. Hardware selection has been considered suitable, site-based case studies and long-term data gathering is still to be gathered to confirm operation due to the incompletion of complementary deployable software. Source: IntelliSAW (2017) RESEARCH AND FINDINGS During laboratory verification, an assembly comprising a metalclad enclosure, a 78

Seven Bridges Vol. 6 (2018) supported copper busbar system and compartmentalised switchgear are all under test. The switchboard assembly connected to a supply at the Main Incomer (main switch to accept power from a stable source) and via the busbar system, the outgoing devices supply electrical power to a resistive load bank. This enables a simulation of the switchboard to be tested under load. During the tests, thermocouples (as per Figure 6) are strategically placed internal and external to the assembly. The temperature is monitored as the board is tested to its design load in amps, In. At In, the test load is sustained until a stable temperature measurement can be established by the test equipment. The manufacturer must specify to the laboratory what the maximum working temperature of the switchgear is, and the maximum expected ambient temperatures within which the assembly will be installed. The term Temperature Rise test describes to what magnitude of temperature the assembly s components can rise, whilst efficiently and compliantly delivering the required amount of energy, or more specifically current, to the load. The data gathered from these tests is the basis of the expected or maximum limit to which measured actual temperatures will be compared in real installations. THEORY AND CONTRIBUTING FACTORS Laboratory test data can inform the maximum operating temperature, of a given piece of switchgear operating at its maximum rated diversity factor (RDF). The RDF may be less than the full rating of the device depending on the temperature rise performance of the overall assembly. Neglecting the external factors which will affect temperature rise, the fundamental relationship between power loss, and current (load) is given by: Power Loss Algorithm P W = P N ( I 2 ) I n P W Calculated Power Loss P N Power Loss at Rated Current I Magnitude of Current (Load) I n Rated Current (RTD) of Circuit Breaker Source: Kilindjian (1997) Thus, power loss is proportional to the square of the current flowing through a circuit breaker. Figure 9 shows other actual contributing factors will need to be inputted into the final algorithm for comparison with test data. Figure 9. Proposed Algorithm Inputs SYSTEM OPERATION The IR sensor selected seen in Figure 7 can communicate samples to a monitoring relay every 2 seconds. This rate will be adjustable upwards to suit the final design, and when the amount of data which can be handled and stored by the supervisory is established. The system sequence of operation is depicted in Figure 10. Figure 10. Sequential System Operation 79

Andrew Turner The proposed algorithm shown in Figure 9. The inputs grouped to the right-hand side of the diagram are assumed as the key variables for this research, with other contributing measurables included which can also inform potential premature ageing of switchgear. CONCLUSIONS AND NEXT STEPS Although temperature monitoring in LV switchgear is a common offering throughout the industry, this research intends to demonstrate that the utilisation of the known limits of an assembly allows continuous monitoring of actual measurements to be compared with the limits of a derived design verified configuration. End-users will be able to better manage, monitor and potentially prolong, or better guarantee the life span of their power distribution assets by use of condition monitoring which alerts the user to variables exceeding those of the limits set by the tested arrangement, which can be seen in Figure 11 below: Figure 11. Condition Curve / Time. Predictive, Preventive and Reactive Maintenance Opportunities Source: IntelliSAW (2017) The chart shows a comparison curve of condition against time, and how early stage warnings better manage cost and risk in maintenance planning; catching failure at its initiation. It will allow for predicative maintenance, rather than preventive or reactive maintenance, rectification or complete replacement of an assembly. FURTHER RESEARCH Following post-study research, data will be presented against example tested arrangements. The theory will be developed to allow algorithm design to commence, with software and hardware selection fully identified, and key sensor locations identified for a generic installation. Further analysis will be presented of the requirements for compliance with BS EN 61439, to convey the significance of implementation of a system described within this article. The final system must be compatible with communications protocol Modbus over RS 485 to allow for compatibility with existing building management systems (BMS). DIRECTOR APPROVAL The author obtained director approval for the proposed system to be further developed and finalised as a new product offering, following initial research findings. ACKNOWLEDGEMENTS The research presented has been made possible by the ongoing support of the author s employer, Armah Switchgear Ltd, with support and the development tools provided by partner business, with the aim to make the proposed system a reality, sharing a common interest in ensuring the products are safe, reliable and beyond legislative requirements. 80

Seven Bridges Vol. 6 (2018) REFERENCES BSI (2011). BS EN 614392011 - Lowvoltage switchgear and controlgear assemblies. London: British Standards Institution. Calex. (2018). PyroMiniBus. [online] Available at: http://www.calex.co.uk/product/temperatur e-measurement/infrared-temperaturesensors/pyrominibus/ [Accessed 9 January 2018]. Craig, T. (2017). Condition Monitoring in Low Voltage Circuit Breaker. Glasgow: Terasaki. Malinowski, A. and Yu, H. (2011). Comparison of Embedded System Design for Industrial Applications. IEEE Transactions on Industrial Informatics, 7(2), pp. 244-254. Ofgem (2014). Smart Grid Vision and Route Map. London: Department of Energy & Climate Change. Piesciorovsky, E. and White, W. (2009). Building Heat Load Contributions from Medium and Low Voltage Switchgear Part II: Component and Overall Switchgear Heat Gains. ASHRAE Transactions, Atlanta, 115(2), pp.382-394. RS Components. (2018). RS Pro K Type Thermocouple. [online] Available at: https://uk.rsonline.com/web/p/thermocouples/ 3630294/ [Accessed 4 January 2018]. Yan, Y., Qi, D. and Gu, H. (2017) "A Real- Time IR-Fusion Switchgear Contact Monitoring System (SCMS)". IEEE Access, (5)1, pp.12114-12124. DeGrate, Payne and Belak (2015). Thermal Imaging: Just a note, not the whole tune. IEEE Industry Applications Magazine, 21(4) pp.1-8. Durocher, D.B. and Loucks, D. (2015). Infrared Windows Applied in Switchgear Assemblies: Taking Another Look. IEEE Transactions on Industry Applications, 51(6), pp.4868-4873. Eaton. (2017). Eaton Diagnose System. [online] Available at: www.eaton.eu/ [Accessed 12 February 2018]. IntelliSAW (2017). Critical Asset Monitoring (CAM) Platform. [online] Available at: www.emersonprocess.com/ [Accessed 11 January 2018]. Kilindjian, C. (1997). Cahier technique no. 145 - Thermal study of LV electric switchboards. Paris: Schneider Electric. 81