SERVICE MANUAL R410A. June 2014 AIR TO WATER HEAT PUMP. No. OCH562. Outdoor unit [Model Name] [Service Ref.] PUHZ-W112VHA PUHZ-W112VHA-BS CONTENTS

Similar documents
SERVICE MANUAL. R410A [Model Name]

PUHZ-SHW230YKA SERVICE MANUAL R410A. September 2012 SPLIT-TYPE, AIR TO WATER HEAT PUMP. No. OCH534. [Service Ref.] [Model name] CONTENTS

SERVICE MANUAL R410A. September 2008 AIR TO WATER HEAT PUMP. No. OCH439 REVISED EDITION-A. [Service Ref.] [model name]

SERVICE MANUAL R410A PUHZ-SP100VHA.UK PUHZ-SP125VHA.UK PUHZ-SP125VHA PUHZ-SP140VHA.UK PUHZ-SP140VHA PUHZ-SP100YHA.UK PUHZ-SP100YHA PUHZ-SP125YHA.

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

TECHNICAL & SERVICE MANUAL

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL PUHZ-ZRP250YKA3.UK R410A. No. OCH680. November 2017 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. Outdoor unit [Model Name]

R410A PUHZ-SW75VHA-BS.UK PUHZ-SW75VHAR3-BS.UK PUHZ-SW75VHAR4-BS.UK PUHZ-SW100VHA-BS.UK PUHZ-SW100VHAR3-BS.UK

PUHZ-SHW140YHA PUHZ-SHW230YKA

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL R410A SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. December No.OCH415 REVISED EDITION-F

TECHNICAL & SERVICE MANUAL

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL PUHZ-RP35VHA PUHZ-RP50VHA PUHZ-RP60VHA PUHZ-RP71VHA PUHZ-RP100VHA PUHZ-RP125VHA PUHZ-RP140VHA PUHZ-RP100YHA PUHZ-RP125YHA PUHZ-RP140YHA

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL. R410A Outdoor unit [Model Name] SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. December 2013

TECHNICAL & SERVICE MANUAL

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Wireless type Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A

PKA-RP60KAL.TH PKA-RP71KAL.TH PKA-RP100KAL.TH

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

TECHNICAL & SERVICE MANUAL

Part 3 Troubleshooting

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1

SERVICE MANUAL. R410A Outdoor unit [Model names] SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. September No.OCH526

SERVICE MANUAL MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-F.

SLZ-KF25VA.TH SLZ-KF35VA.TH SLZ-KF50VA.TH SLZ-KF60VA.TH

MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service manual MSZ-EF VE Series (OBH589)

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

SERVICE MANUAL MXZ-2A40VA - MXZ-2A52VA - MXZ-3A54VA - MXZ-3A54VA - MXZ-4A71VA - MXZ-4A71VA - MXZ-4A80VA - E1 OUTDOOR UNIT. No. OB377 REVISED EDITION-A

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA PEAD-RP100EA(2) PEAD-RP125EA PEAD-RP140EA

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA OUTDOOR UNIT. No. OBH543. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

PKA-RP35HAL PKA-RP35HALR1 PKA-RP35HALR1-ER PKA-RP50HAL PKA-RP50HALR1 PKA-RP50HALR1-ER

Outdoor unit SERVICE MANUAL

SUZ-SA71VA3.TH SUZ-SA100VA2.TH

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL R410A SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. May No.OCH425 REVISED EDITION-F. Outdoor unit [Model names]

SERVICE MANUAL MXZ-A18WV - MXZ-A26WV - MXZ-A32WV - E1 HFC. Inverter-controlled multi system Models SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG OUTDOOR UNIT. No. OBH767. Models HFC R32

AIR CONDITIONERS MODELS PQHY-P650YSHM-A PQHY-P700YSHM-A PQHY-P750YSHM-A PQHY-P800YSHM-A PQHY-P850YSHM-A PQHY-P900YSHM-A DATA BOOK

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

MUH-24RV - MSH-30RV -

TECHNICAL & SERVICE MANUAL SUZ-SA71VA.TH. R410A Outdoor unit SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. May 2014 HFC. No.OCH561 R410A CONTENTS

PKA-RP35HAL PKA-RP50HAL

SERVICE MANUAL OUTDOOR UNIT. No. OBH789

3.2 E1 Outdoor Unit PCB Abnormality E4 Actuation of Low Pressure Sensor E5 Compressor Motor Lock 3 52

PKFY-P15VBM-E PKFY-P20VBM-E PKFY-P20VBM-ER1 PKFY-P25VBM-E PKFY-P25VBM-ER1

TECHNICAL & SERVICE MANUAL. Wall Mounted. Series PKFY PKFY-P20VAM-A PKFY-P25VAM-A R407C R22 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MUX-A22WV - E1 HFC. Multi system type Model SPLIT-TYPE, AIR CONDITIONER. No. OB318 R410A CONTENTS. Revision A: MUX-A22WV -

Outdoor unit SERVICE MANUAL

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-SP100JA(L) PEAD-SP125JA(L) PEAD-SP140JA(L) Models PEAD-SP71JA(L) <indoor unit>

SERVICE MANUAL MUH-A18WV - MUH-A24WV - MUH-A30WV - E1. Wireless type Models HFC

SERVICE MANUAL MUZ-GB50VA - MUZ-GB50VA - E2 OUTDOOR UNIT. No. OB455 REVISED EDITION-D. Wireless type Models HFC

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E

SERVICE MANUAL MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. OB368 R410A CONTENTS

TABLE OF CONTENTS ERSQ-AAY1

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1. Wireless type Models HFC FLOOR AND CEILING TYPE AIR CONDITIONERS. No.

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH SUZ-A24VR.TH

TABLE OF CONTENTS RMXS-E8V1B

SERVICE MANUAL PKA-M60KA.TH PKA-M71KA.TH PKA-M100KA.TH PKA-M60KAL.TH PKA-M71KAL.TH PKA-M100KAL.TH R32/R410A. No. OCH661.

PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL PKH-P60FALH PKH-P71FALH PKH-P100FALH

Ceiling Cassettes PLH-3AKH1.UK PLH-3AKH.UK PLH-4AKHS1.UK PLH-4AKHS.UK PLH-5AKHS1.UK PLH-5AKHS.UK PLH-6AKHS1.UK PLH-6AKHS.UK

SERVICE MANUAL. R410A Outdoor unit [model names] SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS April 2007

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1

TECHNICAL & SERVICE MANUAL

1 TECHNICAL CHANGES. MUZ-A09NA MUZ-A09NA - 1 MUZ-A09NA - U1 MUZ-A09NA - U2 1. Refrigerant system diagram has been changed.

SEZ-KD25VAQ.TH SEZ-KD35VAQ.TH SEZ-KD50VAQ.TH SEZ-KD60VAQ.TH SEZ-KD71VAQ.TH

PMFY-P-VBM-E. Ceiling cassette (1-way flow type) R410A Data G8 1. SPECIFICATIONS EXTERNAL DIMENSIONS CENTER OF GRAVITY 1-100

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

PUHZ-P200YHA PUHZ-P250YHA PUHZ-P200YHA3 PUHZ-P250YHA3

SERVICE MANUAL MFZ-KA25VA - MFZ-KA35VA - MFZ-KA35VA - E1. Wireless type Models FLOOR-TYPE, HEAT PUMP AIR CONDITIONERS. No.

PKA-M35HA PKA-M50HA PKA-M35HAL PKA-M50HAL SERVICE MANUAL R32/R410A. No. OCH660

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 2010 SERVICE MANUAL PEA-RP200GAQ PEA-RP250GAQ PEA-RP400GAQ PEA-RP500GAQ. [Model names] CONTENTS

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

SiBE041010EA. Service Manual. Inverter Pair Wall Mounted Type J-Series. [Applied Models] Inverter Pair : Heat Pump

Digital Inverter 4 series 8 & 10HP

PKFY-P32VGM-E PKFY-P40VGM-E PKFY-P50VGM-E

Floor Standing PFFY-P20VKM-E PFFY-P20VKM-ER1 PFFY-P25VKM-E PFFY-P25VKM-ER1 PFFY-P32VKM-E PFFY-P32VKM-ER1 PFFY-P40VKM-E PFFY-P40VKM-ER1

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models

SiBE04-808_C. Service Manual. Inverter Pair Wall Mounted Type G-Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump

SERVICE MANUAL. Series PEA SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS CONTENTS

TECHNICAL DATA & SERVICE MANUAL

EDUS Heat Pump - D-Series

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*R07LGC AO*R09LGC AO*R12LGC AO*R14LGC

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

SUZ-KA25VA2.TH SUZ-KA35VA2.TH SUZ-KA50VA2.TH SUZ-KA60VA2.TH SUZ-KA71VA2.TH

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy MUZ-GA35VAH - E1

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No.

TECHNICAL DATA & SERVICE MANUAL

Transcription:

AIR TO WATER HEAT PUMP June 204 No. SERVICE MANUAL R40A Outdoor unit [Model Name] PUHZ-W2VHA Salt proof model PUHZ-W2VHA-BS [Service Ref.] PUHZ-W2VHA PUHZ-W2VHA-BS Note: This manual describes service data of outdoor unit only. CTENTS. SAFETY PRECAUTI... 2 2. SPECIFICATIS... 5 3. DATA... 7 4. OUTLINES AND DIMENSIS... 9 5. WIRING DIAGRAM... 0 6. WIRING SPECIFICATIS... 7. REFRIGERANT SYSTEM DIAGRAM... 2 8. TROUBLESHOOTING... 3 9. DISASSEMBLY PROCEDURE... 4 PARTS CATALOG (OCB562)

SAFETY PRECAUTI -. ALWAYS OBSERVE FOR SAFETY Before obtaining access to terminal, all supply circuits must be disconnected. Preparation before the repair service. Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker. Discharge the condenser before the work involving the electric parts. Precautions during the repair service. Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigerating cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to touch the live parts. -2. CAUTIS RELATED TO NEW REFRIGERANT Cautions for units utilizing refrigerant R40A Do not use refrigerant other than R40A. If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc. Use a vacuum pump with a reverse flow check valve. Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc. Use the following tools specifically designed for use with R40A refrigerant. The following tools are necessary to use R40A refrigerant. Tools for R40A Gauge manifold Vacuum pump adaptor Charge hose Electronic refrigerant charging scale Gas leak detector Torque wrench Handle tools with care. If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor. Do not use a charging cylinder. If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered. Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released. Charge refrigerant from liquid phase of gas cylinder. If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered. Use the specified refrigerant only. Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions. 2

[] Cautions for service () Perform service after recovering the refrigerant left in the unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. [2] Additional refrigerant charge When charging directly from cylinder Check that cylinder for R40A on the market is syphon type. Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.) Unit Gravimeter [3] Service tools Use the below service tools as exclusive tools for R40A refrigerant. No. Tool name Specifications Gauge manifold Only for R40A Use the existing fitting specifications. (UNF/2) Use high-tension side pressure of 5.3 MPa G or over. 2 Charge hose Only for R40A Use pressure performance of 5.09 MPa G or over. 3 Electronic scale 4 Gas leak detector Use the detector for R34a, R407C or R40A. 5 Adaptor for reverse flow check Attach on vacuum pump. 6 Refrigerant charge base 7 Refrigerant cylinder Only for R40A Top of cylinder (Pink) Cylinder with syphon 8 Refrigerant recovery equipment 3

-3. CAUTIS FOR REFRIGERANT PIPING WORK Tools for R40A (The following table shows whether conventional tools can be used or not.) Tools and materials Use R40A tools Can R22 tools be used? Can R407C tools be used? Gauge manifold Charge hose Gas leak detector Refrigerant recovery equipment Refrigerant cylinder Safety charger Tool exclusive for R40A Tool exclusive for R40A Tool for HFC refrigerant Tool exclusive for R40A Tool exclusive for R40A Tool exclusive for R40A Charge valve Vacuum pump Bender Pipe cutter Welder and nitrogen gas cylinder Refrigerant charging scale Vacuum gauge or thermistor vacuum gauge and vacuum valve Charging cylinder Air purge, refrigerant charge and operation check Gas leak check Refrigerant recovery Refrigerant charge Prevent compressor malfunction when charging refrigerant by spraying liquid refrigerant Prevent gas from blowing out when detaching charge hose Vacuum drying and air purge Bend the pipes Cut the pipes Weld the pipes Charge refrigerant Check the degree of vacuum. (Vacuum valve prevents back flow of oil and refrigerant to thermistor vacuum gauge) Refrigerant charge Tool exclusive for R40A Tools for other refrigerants can be used if equipped with adapter for reverse flow check Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tools for other refrigerants can be used Tool exclusive for R40A : Prepare a new tool. (Use the new tool as the tool exclusive for R40A.) : Tools for other refrigerants can be used under certain conditions. : Tools for other refrigerants can be used. (Usable if equipped with adapter for reverse flow) (Usable if equipped with adapter for reverse flow) -4. PRECAUTIS FOR SALT PROOF TYPE "-BS" MODEL Although "-BS" model has been designed to be resistant to salt damage, observe the following precautions to maintain the performance of the unit.. Avoid installing the unit in a location where it will be exposed directly to seawater or sea breeze. 2. If the cover panel may become covered with salt, be sure to install the unit in a location where the salt will be washed away by rainwater. (If a sunshade is installed, rainwater may not clean the panel.) 3. To ensure that water does not collect in the base of the outdoor unit, make sure that the base is level, not at angle. Water collecting in the base of the outdoor unit could cause rust. 4. If the unit is installed in a coastal area, clean the unit with water regularly to remove any salt build-up. 5. If the unit is damaged during installation or maintenance, be sure to repair it. 6. Be sure to check the condition of the unit regularly. 7. Be sure to install the unit in a location with good drainage. 4

2 SPECIFICATIS 2-. SPECIFICATIS PUHZ-W2VHA(-BS) Power supply (Phase, Voltage, Frequency) φ, 230V, 50Hz Nominal operating condition Nominal water flow rate (Heating mode) L/min 32. Heating(A7/W35) Heating C apacity kw.20 Outside air temperature (Dry-bulb) + 7 (A7/W35) C OP 4.47 Outside air temperature (Wet-bulb) + 6 P ower input kw 2.5 Water temperature (inlet/outlet) +30/+35 Heating Capacity kw.20 Heating(A2/W35) (A2/W35) C OP 3.34 Outside air temperature (Dry-bulb) + 2 P ower input kw 3.35 Outside air temperature (Wet-bulb) + Pressure difference (water circuit) kpa 6.3 Water temperature (inlet/outlet) -/+35 Heating pump input (based on EN45) kw 0.0 Cooling(A35/W7) N ominal water flow rate (Cooling mode) L/min 28.7 Outside air temperature (Dry-bulb) +35 Cooling C apacity kw 0.00 Outside air temperature (Wet-bulb) + 24 (A35/W7) E ER (COP) 2.80 Water temperature (inlet/outlet) +2/+ 7 Power input kw 3.57 Cooling(A35/W8) Cooling C apacity kw 0.00 Outside air temperature (Dry-bulb) +35 (A35/W8) E ER (COP) 4.50 Outside air temperature (Wet-bulb) + 24 P ower input kw 2.22 Water temperature (inlet/outlet) +23/+8 Pressure difference (water circuit) kpa 5 Cooling pump input (based on EN45) kw 0.0 Note: "COP" and "Power input" in the above table are values that contains the "pump input (based on EN 45) ". Outdoor unit specifications Model name Running current Heating(A7/W35) A Cooling(A35/W7) A Power factor Heating(A7/W35) % Cooling(A35/W7) % Max. current A Breaker size A Outer casing External finish Refrigerant control Compressor Model Motor output kw Start type Protection devices Crankcase heater Heat exchanger Fan Oil (Model) Air Water Fan(drive) No. L W Fan motor output kw Air flow m 3 /min (CFM) Defrost method Noise level (SPL) Heating db Cooling db Dimensions Width mm (in) Depth mm (in) Weight Refrigerant Height mm (in) kg (lb) Quantity kg (lb) Guaranteed operating Heating range (Outdoor) Cooling Outlet water temp. Heating (Max in heating, Min in cooling) Cooling Return water Heating temperature range Cooling Water flow rate range L/min PUHZ-W2VHA(-BS). 5.8 98 98 29.5 32 Galvanized plate Munsell 3Y 7.8/. Linear expansion valve Hermetic scroll ANB33FNMMT 2.5 Inverter HP switch/lp switch Discharge thermo Comp.surface thermo 900 (FV50S) - Plate fin coil Plate heat exchanger Propeller fan 2 0.074 x 2 00 (3,530) Reverse cycle * *2 *3 53 53 *2 020 (40-3/6) 330 +30 *4 (3+-3/6) 350 (53-/8) 33 R40A 4.0 (8.8) -20 *5 ~ +35-5 *6 ~ +46 +60 +5 +5 *7 ~ +59 +8 ~ +28 4.4 ~ 32. 5 Plate heat exchanger MITSUBISHI MWA2-46LM A:50mm B:466mm W:08mm H:522mm D:32mm 46 plates Ref. IN (Heating) Ref. OUT (Heating) Maximum outlet water temperature Maximum outlet water temperature [ ] 65 60 55 50 45 B W A Thermistor (TH32) D H Water OUT Water IN 40-20 -5-0 -5 0 5 0 * Hot gas with four-way valve *2 at distance of m from outdoor unit *3 A weighted sound power level in accordance with ISO964- for EN45 testing is 69 dba. *4 grill *5 Lower limit of use is -5 for EN45 testing purposes. *6 With the optional air outlet guide, min. operation temperature will be -5. *7 Lowest entering temperature is 2 for EN45 testing purposes.

2-2. AVAILABLE RANGE (WATER FLOW RATE, RETURN WATER TEMP.) Note: If using the unit out of the available range, the parts of unit might be damaged. <Heating> Return water temp [:] 25.0 23.0 2.0 Available range 9.0 7.0 5.0 3.0.0 9.0 7.0 5.0 4.0 9.0 24.0 29.0 34.0 39.0 Water flow rate [L/min] Table 3 <Applicable Models> PUHZ-W2VHA(-BS) <Cooling> Return water temp [:] 7.0 5.0 Available range 3.0.0 9.0 7.0 5.0 4.0 9.0 24.0 29.0 34.0 39.0 <Applicable Models> PUHZ-W2VHA(-BS) Water flow rate [L/min] Table 6 6

3 DATA 3-. NOISE CRITERI CURVES PUHZ-W2VHA PUHZ-W2VHA-BS 90 MODE SPL(dB) COOLING 53 HEATING 53 LINE OCTAVE BAND SOUND PRESSURE LEVEL, db (0 db = 0.0002 bar) 80 70 60 50 40 30 20 0 APPROXIMATE THRESHOLD OF HEARING FOR CTINUOUS NOISE 63 25 250 500 000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NC-70 NC-60 NC-50 NC-40 NC-30 NC-20 MICROPHE.5m m UNIT GROUND 7

3-2. STANDARD OPERATI DATA Mode Cooling (A35/W7) Heating (A7/W35) Total Electrical circuit Capacity W 0,000,200 Input kw 3.57 2.5 Outdoor unit PUHZ-W2VHA Phase, Hz, 50 Voltage V 230 Current A 5.8. Discharge pressure MPa 2.63 2.08 Refrigerant circuit Suction pressure MPa 0.83 0.67 Discharge temperature ºC 69 60 Condensing temperature ºC 45 36 Suction temperature ºC 9 6 Water conditions Flow volume L/min 28.7 32. Outlet water temperature ºC 7 35 Outdoor conditions Intake air temperature D.B. ºC 35 7 W.B. ºC 24 6 The unit of pressure has been changed to MPa based on international SI system. The conversion factor is: (MPa) = 0.2 (kgf/cm 2 ) 8

Ov m 00 5 er mm 0 m FREE Water IN Water OUT Handle for moving er Ov 59 0m m er Ov m 00 3 er Ov m Over 0 Service space 500 Over Over 300 Over Side Air Intake FOUNDATI <Foundation bolt height> Please secure the unit firmly with 4 foundation (M0) bolts. (Bolts and washers must be purchased locally.) Handle for moving Handle for moving Rear Air Intake 500 Dimensions of space needed The diagram below shows a for service access are basic example. shown in the below diagram. Explantion of particular details are given in the installation manuals etc. 30 FREE SPACE (Around the unit) Less than Handle for moving Handle for moving Side Air Intake 30 256 322 20 600 33 33 33 Earth terminal 020 Air Discharge Installation Feet Drain hole (5-{33) Power supply wiring hole (2-{27Knock Out) Handle for moving Terminal connections Left Power supply wiring Right Controller wiring Service panel 2-2 36 oval holes (Foundation Bolt M0) 20 2-U Shaped notched holes (Foundfation Bolt M0) 53 Rear Air Intake 47 3 FOUNDATI BOLTS 34 24 Front cover Detail Scale :6 ISO 228- G B 466 2 SERVICE SPACE 635 37 9 370 28 079 330 30 23 29 8 40 9 74 see Detail Air Intake 74 4 OUTLINES AND DIMENSIS PUHZ-W2VHA PUHZ-W2VHA-BS Unit: mm 350

5 WIRING DIAGRAM PUHZ-W2VHA PUHZ-W2VHA-BS SYMBOL NAME SYMBOL NAME TB MC MF, MF2 Terminal Block <Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor NI DCL, DCL2 IGBT Connection Terminal <N-Phase> Connection Terminal <Reactor> Power Module 2S4 Solenoid Valve (Four-Way Valve) EI, E2, E3, E4 Connection Terminal <Ground> 63H High Pressure Switch C. B. Controller Circuit Board 63L Low Pressure Switch SW Switch <Manual Defrost, Defect History, 63HS High Pressure Sensor Record Reset, Function Switch> TH3 TH4 Thermistor <Liquid> Thermistor <Discharge> SW2 SW5 Switch <Function Switch> Switch <Function Switch, Model Select> TH6 Thermistor <Plate HEX Liquid> SW6 Switch <Model Select> TH7 Thermistor <Ambient> SW7 Switch <Function Switch> TH8 Thermistor(internal) <Heat Sink> SW8 Switch <Function Switch> TH32 Thermistor <Inlet Water> SW9 Switch <Function Switch> TH33 Thermistor <Suction> CN3 Connector <Emergency Operation> TH34 Thermistor <Comp. Surface> CN5 Connector <Connection for Option> LEV-A, LEV-B DCL Linear Expansion Valve Reactor SS SV Connector <Connection for Option> Connector <Connection for Option> CB Main Smoothing Capacitor CNDM Connector <Connection for Option> CY, CY2 Capacitor LED3 LED <Operation/Inspection Indicators> P. B. U, V, W Power Circuit Board Connection Terminal <U/V/W-Phase> F, F2, F3, F4 Fuse <T6.3AL250V> X5, X52, X54 Relay LI Connection Terminal <L-Phase> * MODEL SELECT The black square ( )indicates a switch position. MODEL SW6 SW5-6 * 2 2V OFF 7 8 2. SW5 - to 5 : Function Switch * OFF MF MS 3~ MF2 MS 3~ 63H TH33 TH32 TH7TH6TH3 TH4 63L 63HS TH34 LEV-A LEV-B M M C. B. t t t t t t t CNF * 7(WHT) 3 2 4 2 2 3 2 5 5 3 5 TH33 TH32 TH7/6 TH3 TH4 3 63HS TH34 LEV-A LEV-B CNVMNTCNMNT * (YLW) (BLK) (RED) (WHT) (WHT) (WHT) (RED) (WHT) (RED) (WHT) (WHT) CNF2 63L (WHT) (RED) 7 3 CN52C 63H CN4 (RED) CN3 (YLW) (WHT) 2 3 3 CN2 2 TRANS (WHT) 7 2 LED3 3 CNDC (PNK) 3 F2 CNAC 7 F3 (WHT) 2 5 F F4 2S4 3 3 SV 3 SS 3 (GRN) (GRY) (WHT) 3 4 CNS (WHT) 2S4 X52 X54 X5 SW8SW5 SW6 SW SW7 SW9 SW2 CNDM (WHT) CN5 (WHT) 2 P. B. 2 CN4 (WHT) CN2 7 (WHT) CN52C 3 (RED) 52C WHT CB RED TH8 t N2 P2 2 CNDC (PNK) 3 IGBT E4 52C E3 CNAC2 (RED) 3 E2 3 CNAC (WHT) BLK BLK RED WHT W V U DCL2 DCL EI NI LI BLK WHT RED W V U MS 3~ BLK DCL WHT BLK BLK MC RED BLU GRN/YLW YLW ORN BRN CY CY2 L N S S2 S3 TB POWER SUPPLY ~/N 230V 50Hz 0 Interface unit / Flow temp. controller

6 WIRING SPECIFICATIS FIELD ELECTRICAL WIRING (power wiring specifications) Outdoor unit model 2V Outdoor unit power supply ~/N (single), 50 Hz, 230 V Outdoor unit Circuit Breaker capacity * 32A Outdoor unit power supply, earth 3 Min. 6 Interface unit/flow temp. controller-outdoor unit *2 3.5 (polar) Interface unit/flow temp. controller-outdoor unit earth *2 Min..5 Remote controller-interface unit/flow temp. controller 2 0.3 (Non-polar) Outdoor unit L-N (single) Outdoor unit L-N, L2-N, L3-N (3phase) *3 AC 230 V Interface unit/flow temp. controller-outdoor unit S-S2 *3 AC 230 V Interface unit/flow temp. controller-outdoor unit S2-S3 *3 DC 24 V Remote controller-interface unit/flow temp. controller *3 DC 2 V *. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV). Make sure that the current leakage breaker is one compatible with higher harmonics. Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter. The use of an inadequate breaker can cause the incorrect operation of inverter. *2. Max. 80 m *3.The figures are NOT always against the ground. S3 terminal has DC 24 V against S2 terminal. However between S3 and S, these terminals are NOT electrically insulated by the transformer or other device. Wiring Wire No. size (mm²) Circuit rating Caution: Be sure to install N-line. Without N-line, it could cause damage to the unit. Notes:. Wiring size must comply with the applicable local and national codes. 2. Power supply cables and the cables between Controller and Outdoor unit shall not be lighter than polychloroprene sheathed flexible cables. (Design 60245 IEC 57) 3. Be sure to connect the cables between Controller and Outdoor unit directly to the units (no intermediate connections are allowed). Intermediate connections may result in communication errors. If water enters at the intermediate connection point, it may cause insufficient insulation to ground or a poor electrical contact. (If an intermediate connection is necessary, be sure to take measures to prevent water from entering the cables.) 4. Install an earth longer than other cables. Power supply Isolator 3 poles isolator S A-Control S2 Outdoor Unit S3 S Interface unit/ S2 Flow temp. controller S3 Warning: In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S, S2, S3 terminals when the power is energized. If isolator should be used between Interface unit/ Flow temp. controller and outdoor unit, please use 3-pole type.

7 REFRIGERANT SYSTEM DIAGRAM PUHZ-W2VHA PUHZ-W2VHA-BS P-Sensor TH7 STOP VALVE REV/V TH3 Water OUT Plate HEX TH32 Water IN TH6 Strainer (#00) LEV-B CHECK/V Power Receiver Strainer (#00) L/P SW TH33 Strainer (#00) CHECK/V H/P SW MUFFLER TH4 TH34 COMP TH8 P/B Distributor Strainer(#00) LEV-A Strainer(#00) Refrigerant flow in heating Refrigerant flow in cooling Symbol Part name Detail COMP H/P SW L/P SW Plate HEX REV/V STOP VALVE CHECK/V P-Sensor P/B LEV-A LEV-B TH33 TH32 TH3 TH4 TH6 TH7 TH8 TH34 Power Receiver Compressor High pressure switch (63H) Low pressure switch (63L) Plate Heat Exchanger Reversing (4-way) valve (2S4) Stop valve Check valve Pressure sensor (63HS) Power board Linear expansion valve -A Linear expansion valve -B Suction temperature thermistor Inlet water temperature thermistor Liquid temperature thermistor Discharge temperature thermistor Plate HEX liquid temperature thermistor Ambient temperature thermistor Heatsink temperature thermistor Comp. surface temperature thermistor Power Receiver DC inverter scroll compressor (Mitsubishi Electric Corporation) For protection (OFF:4.5MPa) For protection (OFF:-0.03MPa) MWA2-46LM (MITSUBISHI) Change the refrigerant circuit (Heating / Cooling) and for Defrosting For refrigerant charge High pressure / Low pressure / For production test use For calculation of the condensing temperature from high pressure Inverter power board Heating:Secondary LEV Cooling:Primary LEV Heating:Primary LEV Cooling:Secondary LEV For LEV control For freeze protection and for compressor frequency control Heating:Evaporating temperature Cooling:Sub cool liquid temperature For LEV control and for compressor protection Heating:Sub cool liquid temperature Cooling:Evaporating temperature For fan control and for compressor frequency control For power board protection For compressor protection For accumulation of refrigerant 2

8 TROUBLESHOOTING 8-. TROUBLESHOOTING <Check code display by self-diagnosis and actions to be taken for service (summary)> Present and past check codes are logged and displayed on the control board of outdoor unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring at service, are summarized in the table below. Check the contents below before investigating details. Unit conditions at service Check code Actions to be taken for service (summary) The trouble is reoccurring. The trouble is not reoccurring. Displayed Not displayed Logged Not logged Judge what is wrong and take a corrective action according to 8-3. SELF-DIAGNOSIS ACTI TABLE. Conduct troubleshooting and ascertain the cause of the trouble. Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise, etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, matters related to wiring, etc. 2 Reset check code logs and restart the unit after finishing service. There is no abnormality in electrical component, controller board, etc. Re-check the abnormal symptom. 2 Conduct troubleshooting and ascertain the cause of the trouble. 3 Continue to operate unit for the time being if the cause is not ascertained. 4 There is no abnormality concerning of parts such as electrical component, controller board, etc. 8-2. CHECK POINT UNDER TEST RUN Before test run After installation of outdoor units, piping work and electric wiring work, re-check that there is no water leakage, loosened connections and incorrect polarity. Measure impedance between the ground and the power supply terminal block (L, N) on the outdoor unit by 500 V Megger and check that it is.0 M or over. Turn on power supply 2 hours before test run in order to protect compressor. Make sure to read operation manual before test run. (Especially items to secure safety.) 3

8-3. SELF-DIAGNOSIS ACTI TABLE <Abnormalities detected when the power is turned on> Check code Abnormal point and detection method Case Judgment and action No voltage is supplied to terminal block (TB) of outdoor unit. a) Power supply breaker is turned off. b) Contact failure or disconnection of power supply terminal c) Open phase (L or N phase) Check following items. a) Power supply breaker b) Connection of power supply terminal block. (TB) c) Connection of power supply terminal block. (TB) None 2 Electric power is not charged to power supply terminal of outdoor power circuit board. a) Contact failure of power supply terminal b) Open phase on the outdoor power circuit board Disconnection of connector LI, NI 3 Electric power is not supplied to outdoor controller circuit board. a) Disconnection of connector (CNDC) 4 Disconnection of reactor (DCL) 5 Defective outdoor power circuit board 6 Defective outdoor controller circuit board 2 Check following items. a) Connection of power supply terminal block. (TB) b) Connection of terminal on outdoor power circuit board. Check connection of the connector LI or NI. Refer to "8-6. TEST POINT DIAGRAM". 3 Check connection of the connector CNDC on the outdoor controller circuit board. Check connection of the connector CNDC on the outdoor power circuit board. Refer to "8-6. TEST POINT DIAGRAM". 4 Check connection of reactor. (DCL) Check connection of "DCL" and "DCL2" on the outdoor power circuit board. 5 Replace outdoor power circuit board. 6 Replace outdoor controller circuit board (When items above are checked but the units can not be repaired.) F3 F5 63L connector open Abnormal if 63L connector circuit is open for 3 minutes continuously from being switched on. 63L: Low-pressure switch 63H connector open Abnormal if 63H connector circuit is open for 3 minutes continuously from being switched on. 63H: High-pressure switch Disconnection or contact failure of 63L connector on outdoor controller circuit board 2 Disconnection or contact failure of 63L 3 63L is working due to refrigerant leakage or defective parts. 4 Defective outdoor controller circuit board Disconnection or contact failure of 63H connector on outdoor controller circuit board 2 Disconnection or contact failure of 63H 3 63H is working due to defective parts. 4 Defective outdoor controller circuit board Check connection of 63L connector on outdoor controller circuit board. Refer to "8-6. TEST POINT DIAGRAM". 2 Check the 63L side of connecting wire. 3 Check refrigerant pressure. Charge additional refrigerant. Check continuity of 63L. Replace low pressure switch if it is defective. 4 Replace outdoor controller circuit board. Check connection of 63H connector on outdoor controller circuit board. Refer to "8-6. TEST POINT DIAGRAM". 2 Check the 63H side of connecting wire. 3 Check for continuity of 63H. Replace high pressure switch if it is defective. 4 Replace outdoor controller circuit board. F9 2 connector open Abnormal if both 63H and 63L connector circuits are open for 3 minutes continuously from being switched on. 63H: High-pressure switch 63L: Low-pressure switch Disconnection or contact failure of connector (63H,63L) on outdoor controller circuit board. 2 Disconnection or contact failure of 63H, 63L 3 63H and 63L are working due to defective parts. 4 Defective outdoor controller board. Check connection of connector (63H,63L) on outdoor controller circuit board. Refer to "8-6. TEST POINT DIAGRAM". 2 Check the 63H and 63L side of connecting wire. 3 Check continuity of 63H and 63L. Replace the pressure switch if it is defective. 4 Replace outdoor controller circuit board. 4

Check code Abnormal point and detection method Case Judgment and action EA Eb EC Miswiring of Interface unit/flow temp. controller-outdoor unit connecting wire. Outdoor controller circuit board can automatically check the number of connected Interface unit/flow temp. controller. Abnormal if the number cannot be checked automatically due to miswiring of Interface unit/flow temp. controlleroutdoor unit connecting wire and etc. after power is turned on for 4 minutes. 2. Abnormal if outdoor controller circuit board recognizes excessive number of Interface unit/flow temp. controller. Miswiring of Interface unit/flow temp. controller-outdoor unit connecting wire (converse wiring or disconnection) Outdoor controller circuit board can automatically set the unit number of Interface unit/flow temp. controller. Abnormal if the Interface unit/flow temp. controller number cannot be set within 4 minutes after power on because of miswiring (converse wiring or disconnection) of Interface unit/flow temp. controller-outdoor unit connecting wire. Start-up time over The unit cannot finish start-up process within 4 minutes after power on. Contact failure or miswiring of Interface unit/flow temp. controller-outdoor unit connecting wire Diameter or length of Interface unit/flow temp. controlleroutdoor unit connecting wire is out of specified capacity. Excessive number of Interface unit/flow temp. controller is connected to outdoor unit. (2 units or more) Defective transmitting receiving circuit of outdoor controller circuit board Defective transmitting receiving circuit of Interface/Flow temp. controller board Noise has entered into power supply or Interface/Flow temp. controller-outdoor unit connecting wire. Contact failure or miswiring of Interface unit/flow temp. controller-outdoor unit connecting wire Diameter or length of Interface unit/flow temp. controlleroutdoor unit connecting wire is out of specified capacity. Defective transmitting receiving circuit of outdoor controller circuit board Defective transmitting receiving circuit of Interface/Flow temp. controller board Noise has entered into power supply or Interface unit/flow temp. controller-outdoor unit connecting wire. Contact failure of Interface unit /Flow temp. controller-outdoor unit connecting wire Diameter or length of Interface unit/flow temp. controlleroutdoor unit connecting wire is out of specified capacity. Noise has entered into power supply or Interface unit/flow temp. controller-outdoor unit connecting wire. Check disconnection or looseness or polarity of Interface unit/flow temp. controller-outdoor unit connecting wire of Interface unit/flow temp. controller and outdoor units. Check diameter and length of Interface unit/ Flow temp. controller-outdoor unit connecting wire. Total wiring length: 80 m (Including wiring connecting each Interface unit/flow temp. controller unit and between Interface unit/flow temp. controller and outdoor unit) Also check if the connection order of flat cable is S, S2, S3. Check the number of Interface unit/flow temp. controller that is connected to outdoor unit. (If EA is detected.) ~ Turn the power off once, and on again to check. Replace outdoor controller circuit board or Interface/Flow temp. controller board if abnormality occurs again. Check transmission path, and remove the cause. Note: The descriptions above, -, are for EA, Eb and EC. 5

<Abnormalities detected while unit is operating> Check code Abnormal point and detection method Case Judgment and action High pressure (High-pressure switch 63H operated) Abnormal if high-pressure switch 63H operated ( * ) during compressor operation. *4.5 MPa ~5 Check water circuit and repair the defect. U 63H: High-pressure switch Decreased water flow 2 Clogged filter of water pipe 3 Dirt of plate heat exchanger 4 Locked water pump 5 Malfunction of water pump 6 Clogged or broken pipe 7 Locked outdoor fan motor 8 Malfunction of outdoor fan motor 9 Short cycle of outdoor unit 0 Dirt of outdoor heat exchanger Decreased airflow caused by defective inspection of outside temperature thermistor (It detects lower temperature than actual temperature.) 2 Disconnection or contact failure of connector (63H) on outdoor controller board 3 Disconnection or contact failure of 63H connection 4 Defective outdoor controller board 5 Defective operation of linear expansion valve 6 Malfunction of fan driving circuit 6 Check piping and repair the defect. 7~0 Check outdoor unit and repair the defect. Check the detected temperature of outside temperature thermistor on LED display. (SW2: Refer to "8-7.OUTDOOR UNIT OPERATI MITOR FUNCTI".) 2~4 Turn the power off and check F5 is displayed when the power is turned on again. When F5 is displayed, refer to Judgment and action for F5. 5 Check linear expansion valve. Refer to "8-5.HOW TO CHECK THE COMPENTS". 6 Replace outdoor controller board. U2 High discharging temperature Abnormal if discharge temperature thermistor (TH4) exceeds 25: or 0: continuously for 5 minutes. Abnormal if during defrosting discharge temperature thermistor (TH4) exceeds 0: continuously for 30 minutes. High comp. surface temperature Abnormal if comp. surface temperature (TH34) exceeds 70:. In the case of high comp. surface temperature error, compressor does not restart unless the thermistor (TH34) becomes less than 95:. Overheated compressor operation caused by insufficient refrigerant 2 Defective thermistor 3 Defective outdoor controller board 4 Defective operation of linear expansion valve 5 In the case of the unit does not restart : Detection temp. of thermistor (TH34) ] 95: Check intake super heat. Check leakage of refrigerant. Charge additional refrigerant. 23 Turn the power off and check if U3 is displayed when the power is turned again. When U3 is displayed, refer to Judgement and action for U3. 4 Check linear expansion valve. Refer to "8-5.HOW TO CHECK THE COMPENTS". U3 Open/short circuit of discharge temperature thermistor (TH4)/comp. surface thermistor (TH34) Abnormal if open (3: or less) or short (27: or more) is detected during compressor operation. (Open (3: or less) detection is inoperative for 0 minutes of compressor starting process and for 0 minutes after or during defrosting.) Disconnection or contact failure of connector (TH4/TH34) on the outdoor controller circuit board. 2 Defective thermistor 3 Defective outdoor controller circuit board Check connection of connector (TH4/TH34) on the outdoor controller circuit board. Check the lead wire for thermistor (TH4/TH34). Refer to "8-6. TEST POINT DIAGRAM". 2 Check resistance value of thermistor (TH4/ TH34) or temperature on LED display. (Thermistor/TH4/TH34: Refer to "8-5.HOW TO CHECK THE COMPENTS".) (SW2: Refer to"8-7.outdoor UNIT OPERATI MITOR FUNCTI".) 3 Replace outdoor controller board. 6

Check code Abnormal point and detection method Case Judgment and action U4 Open/short of outdoor unit thermistors (TH3, TH32, TH33, TH6, TH7, and TH8) Abnormal if open or short is detected during compressor operation. Open detection of thermistors TH3, TH32 and TH6 is not detected for 0 seconds to 0 minutes after compressor starting and 0 minutes after and during defrosting. Note: Check which unit has abnormality in its thermistor by switching the mode of SW2. (Refer to "8-7.OUTDOOR UNIT OPERATI MITOR FUNCTI".) Heatsink thermistor (TH8) is in the power module. Disconnection or contact failure of connectors Outdoor controller circuit board: TH3, TH32, TH33, TH6/TH7 Outdoor power circuit board: ( ) CN3 2 Defective thermistor 3 Defective outdoor controller circuit board Check connection of connector (TH3, TH32, TH33, TH6/TH7) on the outdoor controller circuit board. Check connection of connector (CN3) on the outdoor power circuit board. Check the lead wire for thermistor (TH3, TH32, TH33, TH6, TH7, TH8). Refer to "8-6. TEST POINT DIAGRAM". 2 Check resistance value of thermistor (TH3, TH32, TH33, TH6, TH7, TH8) or check temperature on LED display. (Thermistor/TH3, TH32, TH33, TH6, TH7, TH8: Refer to "8-5.HOW TO CHECK THE COMPENTS.") (SW2: Refer to "8-7.OUTDOOR UNIT OPERATI MITOR FUNCTI".) 3 Replace outdoor controller circuit board. Thermistors Symbol Name Open detection Short detection TH3 Thermistor <Liquid temperature> - 40 C or below 90 C or above TH32 Thermistor <Inlet water temperature> - 40 C or below 02 C or above TH33 Thermistor <Suction pipe temperature> - 40 C or below 90 C or above TH6 Thermistor <Plate HEX liquid temperature> - 40 C or below 90 C or above TH7 Thermistor <Ambient temperature> - 40 C or below 90 C or above TH8 Internal thermistor - 35 C or below 70 C or above U5 Temperature of heatsink Abnormal if heatsink thermistor (TH8) detects 94 C. The outdoor fan motor is locked. 2 Failure of outdoor fan motor 3 Air flow path is clogged. 4 Ambient temperature is high. 5 Defective thermistor 6 Defective input circuit of outdoor power circuit board 7 Failure of outdoor fan drive circuit 2 Check outdoor fan. 3 Check air flow path for cooling. 4 Check if there is something which causes temperature rise around outdoor unit. (Upper limit of ambient temperature is 46:.) Turn off power, and on again to check if U5 is displayed within 30 minutes. If U4 is displayed instead of U5, refer to check code U4. 5 Check resistance value of thermistor (TH8) or temperature by microcomputer. (Thermistor/TH8: Refer to "8-5.HOW TO CHECK THE COMPENTS".) (SW2: Refer to "8-7. OUTDOOR UNIT OPERATI MITOR FUNCTI".) 6 Replace outdoor power circuit board. 7 Replace outdoor controller circuit board. U6 Power module Check abnormality by driving power module in case overcurrent is detected. (UF or UP error condition) Defective outdoor power circuit board 2 Decrease of power supply voltage 3 Loosens, disconnection or reverse of compressor wiring connection 4 Defective compressor Replace outdoor power circuit board. 2 Check facility of power supply. 3 Correct the wiring (U V W phase) to compressor. Refer to "8-6. TEST POINT DIAGRAM (Outdoor power circuit board)". 4 Check compressor referring to "8-4.HOW TO CHECK THE PARTS". U7 U8 Too low superheat due to low discharge temperature Abnormal if discharge superheat is continuously detected -5: or less for 3 minutes even though linear expansion valve has minimum open pulse after compressor starts operating for 0 minutes. Outdoor fan motor Abnormal if rotational frequency of the fan motor is not detected during DC fan motor operation. Fan motor rotational frequency is abnormal if; 00 rpm or below detected continuously for 5 seconds at 20: or more outside air temperature 50 rpm or below or 500 rpm or more detected continuously for minute. Disconnection or loose connection of discharge temperature thermistor (TH4) 2 Defective holder of discharge temperature thermistor 3 Disconnection or loose connection of linear expansion valve s coil 4 Disconnection or loose connection of linear expansion valve s connector 5 Defective linear expansion valve Failure in the operation of the DC fan motor 2 Failure in the outdoor circuit controller board 7 2 Check the installation conditions of discharge temperature thermistor (TH4). 3 Check the coil of linear expansion valve. Refer to "8-5.HOW TO CHECK THE COMPENTS". 4 Check the connection or contact of LEV-A and LEV-B on outdoor controller circuit board. 5 Check linear expansion valve. Refer to "8-4.HOW TO CHECK THE PARTS". Check or replace the DC fan motor. 2 Check the voltage of the outdoor circuit controller board during operation. 3 Replace the outdoor circuit controller board. (when the failure is still indicated even after performing the remedy above.)

Check code Abnormal point and detection method Case Judgment and action Detailed codes 0 To find out the details about U9 error, turn SW2-, 2-2, 2-3, 2-4, 2-5 and 2-6 when U9 error occurs. To find out the detail history (latest) about U9 error, turn SW2-, 2-2 and 2-6. Refer to "8-7.OUTDOOR UNIT OPERATI MITOR FUNCTI". Overvoltage error Increase in DC bus voltage to 400 V Abnormal increase in power source voltage 2 Disconnection of compressor wiring 3 Defective outdoor power circuit board 4 Compressor has a ground fault. Check the field facility for the power supply. 2 Correct the wiring (U. V. W phase) to compressor. Refer to "8-6. TEST POINT DIAGRAM (Outdoor power circuit board)". 3 Replace outdoor power circuit board. 4 Check compressor for electrical insulation. Replace compressor. U9 (4220) 02 04 Undervoltage error Instantaneous decrease in DC bus voltage to 200 V Input current sensor error/ L-phase open error Decrease in input current through outdoor unit to 0.A only if operation frequency is more than or equal to 40Hz or compressor current is more than or equal to 6A. Decrease in power source voltage, instantaneous stop. 2 Disconnection or loose connection of CN52C on the outdoor power circuit board/controller circuit board 3 Defective converter drive circuit in outdoor power circuit board 4 Defective 52C drive circuit in outdoor power circuit board 5 Disconnection or loose connection of main smoothing capacitor CB 6 Disconnection or loose connection of CN2 on the outdoor power circuit board /controller circuit board 7 Power circuit failure on DC supply for 8V DC output on outdoor controller circuit board Defective input current detection circuit in outdoor power circuit board 2 Defective outdoor controller circuit board Check the field facility for the power supply. 2 Check CN52C wiring. 3 Replace outdoor power circuit board. 4 Replace outdoor power circuit board. 5 Check CB wiring. 6 Check CN2 wiring. 7 Replace outdoor controller circuit board. Replace outdoor power circuit board. 2 Replace outdoor controller circuit board. 08 0 20 Abnormal power synchronous signal No input of power synchronous signal to power circuit board Power synchronous signal of 44 Hz or less, or 65 Hz or more is detected on power circuit board. PFC error (Overvoltage/ Undervoltage/Overcurrent) PFC detected any of the followings a) Increase of DC bus voltage to 420V. b) Decrease in PFC control voltage to 2V DC or lower c) Increase in input current to 50A peak (For models equipped with single-phase PFC only) PFC/IGBT error (Undervoltage) When Compressor is running, DC bus voltage stays at 30V or lower for consecutive 0 seconds Distortion of power source voltage, noise superimposition. 2 Disconnection or loose connection of earth wiring 3 Disconnection or loose connection of CN2 on the outdoor power circuit board /controller circuit board 4 Defective power synchronous signal circuit in outdoor controller circuit board 5 Defective power synchronous signal circuit in outdoor power circuit board Not applicable for W2VHA models. Incorrect switch settings on the outdoor controller circuit board for model select 2 Defective outdoor power circuit board 3 Defective outdoor controller circuit board Check the field facility for the power supply. 2 Check earth wiring. 3 Check CN2 wiring. 4 Replace outdoor controller circuit board. 5 Replace outdoor power circuit board. Check for the switch settings for Model Select on the outdoor controller circuit board. Correction of a model select 2 Replace outdoor power circuit board. 3 Replace outdoor controller circuit board. 8 Continue to the next page.

Check code Abnormal point and detection method Case Judgment and action Overheat protection Check outdoor unit air passage. Abnormal if outdoor pipe thermistor (TH3) detects 70: or more or condensing Ud temperature of pressure sensor (63HS) detects 70: or more during compressor operation. Defective outdoor fan (fan motor) or short cycle of outdoor unit during cooling operation 2 Defective outdoor pipe thermistor (TH3) 3 Defective outdoor controller board 4 Defective pressure sensor 23 Turn the power off and on again to check the check code. If U4 is displayed, follow the U4 processing direction. 4 Check pressure by microcomputer. (Pressure sensor/ 63HS) (SW2: Refer to "8-7.OUTDOOR UNIT OPERATI MITOR FUNCTI".) UF Compressor overcurrent interruption (When compressor locked) Abnormal if overcurrent of DC bus or compressor is detected within 30 seconds after compressor starts operating. Decrease of power supply voltage 2 Looseness, disconnection or converse of compressor wiring connection 3 Defective compressor 4 Defective outdoor power board 5 Decreased water flow 6 Clogged filter of water pipe 7 Clogged plate heat exchanger 8 Locked water pump 9 Malfunction of water pump Check facility of power supply. 2 Correct the wiring (U V W phase) to compressor. Refer to "8-6. TEST POINT DIAGRAM (Outdoor power circuit board)". 3 Check compressor. Refer to "8-4.HOW TO CHECK THE PARTS". 4 Replace outdoor power circuit board. 5~9 Check water circuit and repair the defect. UH UL Current sensor error or input current error Abnormal if current sensor detects.0 A to.0 A during compressor operation. (This error is ignored during test run.) Abnormal if 38 A of input current is detected or 34 A or more of input current is detected for 0 seconds continuously. Low pressure (63L operated) Abnormal if 63L is operated (under -0.03 MPa) during compressor operation. 63L: Low-pressure switch Disconnection of compressor wiring 2 Defective circuit of current sensor on outdoor power circuit board 3 Decrease of power supply voltage Stop valve of outdoor unit is closed during operation. 2 Disconnection or loose connection of connector (63L) on outdoor controller board 3 Disconnection or loose connection of 63L 4 Defective outdoor controller board 5 Leakage or shortage of refrigerant 6 Malfunction of linear expansion valve Correct the wiring (U V W phase) to compressor. Refer to "8-6. TEST POINT DIAGRAM (Outdoor power circuit board)". 2 Replace outdoor power circuit board. 3 Check the facility of power supply. Check stop valve. 2~4 Turn the power off and on again to check if F3 is displayed on restarting. If F3 is displayed, follow the F3 processing direction. 5 Correct to proper amount of refrigerant. 6 Check linear expansion valve. Refer to "8-5.HOW TO CHECK THE COMPENTS". UP Compressor overcurrent interruption Abnormal if overcurrent DC bus or compressor is detected after compressor starts operating for 30 seconds. Decrease of power supply voltage 2 Looseness, disconnection or converse of compressor wiring connection 3 Defective fan of outdoor units 4 Short cycle of indoor/outdoor units 5 Defective input circuit of outdoor controller board 6 Defective compressor 7 Decreased water flow 8 Clogged filter of water pipe 9 Clogged plate heat exchanger 0 Locked water pump Malfunction of water pump Check facility of power supply. 2 Correct the wiring (U V W phase) to compressor. Refer to "8-6. TEST POINT DIAGRAM (Outdoor power circuit board)". 3 Check outdoor fan. 4 Solve short cycle. 5 Replace outdoor controller circuit board. 6 Check compressor. Refer to "8-4.HOW TO CHECK THE PARTS". Note: Before the replacement of the outdoor controller circuit board, disconnect the wiring to compressor from the outdoor power circuit board and check the output voltage among phases, U, V, W, during test run. No defect on board if voltage among phases (U-V, V-W and W-U) is same. Make sure to perform the voltage check with same performing frequency. 7~ Check water circuit and repair the defect. 9

Check code Abnormal point and detection method Judgment and action Case E0 or E4 E or E2 E3 or E5 Remote controller transmission error (E0)/signal receiving error (E4) Abnormal if main or sub remote controller cannot receive any transmission normally from Interface unit/flow temp. controller of refrigerant address 0 for 3 minutes. (Check code: E0) Abnormal if sub-remote controller could not receive any signal for 2 minutes. (Check code: E0) Abnormal if Interface/Flow temp. controller board can not receive any data normally from remote controller board or from other Interface/Flow temp. controller board for 3 minutes. (Check code: E4) Interface/Flow temp. controller board cannot receive any signal from remote controller for 2 minutes. (Check code: E4) Remote controller control board Abnormal if data cannot be read normally from the nonvolatile memory of the remote controller control board. (Check code: E) Abnormal if the clock function of remote controller cannot be operated normally. (Check code: E2) Remote controller transmission error (E3)/signal receiving error (E5) Abnormal if remote controller could not find blank of transmission path for 6 seconds and could not transmit. (Check code: E3) 2 When remote controller receives the transmitted data same time and compares these data. Abnormal if the data is judged to be different for 30 continuous times. (Check code: E3) Abnormal if Interface/Flow temp. controller board could not find blank of transmission path. (Check code: E5) 2 When Interface/Flow temp. controller receives the transmitted data same time and compares these data. Abnormal if the data is judged to be different for 30 continuous times. (Check code: E5) Contact failure at transmission wire of remote controller All remote controllers are set as sub remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED, LED2) on the outdoor controller circuit board. Miswiring of remote controller Defective transmitting receiving circuit of remote controller Noise has entered into the transmission wire of remote controller. Check disconnection or looseness of Interface unit/flow temp. controller unit or transmission wire of remote controller. Set one of the remote controllers main, If there is no problem with the action above. Check wiring of remote controller. Total wiring length: max. 500 m (Do not use cable 3 or more.) The number of connecting remote controller: Refer to the indoor units service manual. When it is not the above-mentioned problem of ~ Diagnose remote controllers. a) When RC OK is displayed, remote controllers have no problem. Turn the power off, and on again to check. If abnormality generates again, replace Interface/Flow temp. controller board. b) When RC NG is displayed, replace remote controller. c) When RC E3 or ERC 00-66 is displayed, noise may be causing abnormality. Defective remote controller Replace remote controller. 2 remote controllers are set as main. (In case of 2 remote controllers) Note that some models can only connect remote controller. For more detail, refer to the indoor unit's service manual. 2 Defective transmitting receiving circuit of remote controller 3 Defective transmitting receiving circuit of Interface/Flow temp. controller board 4 Noise has entered into transmission wire of remote controller. Set a remote controller to main, and the other to sub. 2~4 Diagnose remote controller. a) When RC OK is displayed, remote controllers have no problem. Turn the power off, and on again to check. When becoming abnormal again, replace indoor controller board. b) When RC NG is displayed, replace remote controller. c) When RC E3 or ERC 00-66 is displayed, noise may be causing abnormality. E6 E8 Interface unit/flow temp. controller-outdoor unit communication error (Signal receiving error) Abnormal if Interface/Flow temp. controller board cannot receive any signal normally for 6 minutes after turning the power on. 2 Abnormal if Interface/Flow temp. controller board cannot receive any signal normally for 3 minutes. Interface unit/flow temp. controlleroutdoor unit communication error (Signal receiving error) (Outdoor unit) () Abnormal if outdoor controller circuit board could not receive anything normally for 3 minutes. Contact failure, short circuit or, miswiring (converse wiring) of Interface unit/flow temp. controller-outdoor unit connecting wire 2 Defective transmitting receiving circuit of Interface/Flow temp. controller board 3 Defective transmitting receiving circuit of Interface/Flow temp. controller board 4 Noise has entered into Interface unit/flow temp. controlleroutdoor unit connecting wire. Contact failure of Interface unit/ Flow temp. controller-outdoor unit connecting wire 2 Defective communication circuit of outdoor controller circuit board 3 Defective communication circuit of Interface/Flow temp. controller board 4 Noise has entered into Interface unit/flow temp. controlleroutdoor unit connecting wire. * Check LED display on the outdoor control circuit board. (Connect A-control service tool, PAC- SK52ST.) Check disconnection or looseness of Interface unit/flow temp. controller-outdoor unit connecting wire of Interface unit/flow temp. controller or outdoor unit. 2~4 Turn the power off, and on again to check. If abnormality generates again, replace Interface/Flow temp. controller board or outdoor controller circuit board. Check disconnection or looseness of Interface unit/flow temp. controller-outdoor unit connecting wire of Interface unit/flow temp. controller or outdoor unit. 2~4 Turn the power off, and on again to check. Replace Interface/Flow temp. controller board or outdoor controller circuit board if abnormality is displayed again. 20

Check code Abnormal point and detection method Judgment and action Case E9 EF Ed P6 Interface unit/flow temp. controlleroutdoor unit communication error (Transmitting error) (Outdoor unit) () Abnormal if 0 receiving is detected 30 times continuously though outdoor controller circuit board has transmitted. (2) Abnormal if outdoor controller circuit board could not find blank of transmission path for 3 minutes. Non defined check code This code is displayed when non defined check code is received. Serial communication error Abnormal if serial communication between outdoor controller circuit board and outdoor power circuit board is defective. Freezing/overheating protection is working () Freezing protection <Cooling mode> Abnormal if plate heat exchanger pipe temperature (TH6) stays at -5: or lower for 0 seconds or abnormal if plate heat exchanger pipe thermistor (TH6) stays at -2: or lower and compressor operation frequency is minimum for 5 minutes after compressor starts operating for 6 minutes. <Heating mode> Abnormal if inlet water temperature thermistor (TH32) is 5: or lower, and the following condition ( or 2) are detected.. minute has passed since defrosting operation started and plate heat exchanger pipe temperature thermistor (TH6) stays at -6: or lower for continuously 30 seconds. 2. During defrosting operation and plate heat exchanger pipe temperature thermistor (TH6) stays at -6: or lower for continuously 0 seconds. (2) Overheating protection <Heating mode> Abnormal if condensing temperature of pressure sensor (63HS) detects Tcond. : or more and compressor operation frequency is less than or equal to 30 Hz. Detection is inoperative during defrosting. Interface unit/flow temp. controller-outdoor unit connecting wire has contact failure. 2 Defective communication circuit of outdoor controller circuit board 3 Noise has entered power supply. 4 Noise has entered Interface unit/flow temp. controlleroutdoor unit connecting wire. Noise has entered transmission wire of remote controller. 2 Noise has entered Interface unit/flow temp. controlleroutdoor unit connecting wire. Wire disconnection or contact failure of connector CN2 between the outdoor controller circuit board and the outdoor power circuit board 2 Wire disconnection or contact failure of connector CN4 between the outdoor controller circuit board and the outdoor power circuit board 3 Defective communication circuit of outdoor power circuit board 4 Defective communication circuit of outdoor controller circuit board for outdoor power circuit board () Freezing protection <Cooling mode> Reduced water flow Clogged filter Leakage of water 2 Low temperature Low-load Inlet water is too cold. 3 Defective water pump 4 Defective outdoor fan control 5 Overcharge of refrigerant 6 Defective refrigerant circuit (clogs) 7 Malfunction of linear expansion valve <Heating mode> Reduced water flow Clogged filter Leakage of water 2 Low temperature Low-load Inlet water is cold. 3 Defective water pump 4 Leakage or shortage of refrigerant 5 Malfunction of linear expansion valve (2) Overheating protection <Heating mode> Reduced water flow Clogged filter Leakage of water 2 High temperature Over-load Inlet water is too warm. 3 Defective water pump 4 Overcharge of refrigerant 5 Defective refrigerant circuit (clogs) 6 Malfunction of linear expansion valve Check disconnection or looseness of Interface unit/flow temp. controller-outdoor unit connecting wire. 2~4 Turn the power off, and on again to check. Replace outdoor controller circuit board if abnormality is displayed again. 2 Turn the power off, and on again to check. Replace Interface/Flow temp. controller board or outdoor controller circuit board if abnormality is displayed again. 2 Check connection of each connector CN2 and CN4 between the outdoor controller circuit board and the outdoor power circuit board. 3 Replace outdoor power circuit board. 4 Replace outdoor controller circuit board. () Freezing protection <Cooling mode> 2 Check water piping. 3 Check water pump. 4 Check outdoor fan motor. 5~7 Check operating condition of refrigerant circuit. 7 Check linear expansion valve. <Heating mode> 2 Check water piping. 3 Check water pump. 4 Correct to proper amount of refrigerant. 5 Check linear expansion valve. Refer to "8-5. HOW TO CHECK THE COMPENTS". (2) Overheating protection <Heating mode> 2 Check water piping. 3 Check water pump. 45 Check operating condition of refrigerant circuit. 6 Check linear expansion valve. Tcond stage-g stage-f stage-e stage-d stage-c stage-b stage-a stage-x stage-y -8-7 -5-4 -2 - -9-8 -6-5 -3-2 34 35 39 40 Tcond Model W2 Ambient temperature (TH7) [ :] stage-a stage-b stage-c stage-d stage-e stage-f stage-g 63 60 57 53 48 48 48 stage-x stage-y 6 59 2

Check code Abnormal point and detection method Judgment and action Case P8 UE Pipe temperature Abnormal if the following conditions are detected for continuously 3 minutes after compressor starts operating for 0 minutes.. Cooling mode T63HS-TH7 [ 2: and TH3-TH7 [ 4: or T63HS-TH3 < 0: and TH32-TH6 [ 0: and Compressor operation frequency is 6Hz or more. 2. Heating mode T63HS-TH32 [ 2: and TH6-TH32 [ : and TH7-TH3 [ : and Compressor operation frequency is 6Hz or more. T63HS: Condensing temperature of pressure sensor (63HS) Thermistor TH3: Liquid temperature TH32: Inlet water temperature TH6: Plate HEX Liquid temperature TH7: Ambient temperature Abnormal pressure of pressure sensor (63HS) Abnormal if pressure sensor (63HS) detects 0. MPa or less. Detection is inoperative for 3 minutes after compressor starting and 3 minutes after and during defrosting. Leakage or shortage of refrigerant 2 Malfunction of linear expansion valve 3 Refrigerant circuit is clogged with foreign objects. Note: Clogging occurs in the parts which become below freezing point when water enters in refrigerant circuit. 4 Disconnection of thermistor holder. Disconnection or contact failure of connector (63HS) on the outdoor controller circuit board 2 Defective pressure sensor 3 Defective outdoor controller circuit board Check intake superheat. Check leakage of refrigerant. 2 Check linear expansion valve. 3 After recovering refrigerant, remove water from entire refrigerant circuit under vacuum more than hour. 4 Check temperature display on outdoor controller circuit board. Temperature display is indicated by setting SW2 of outdoor controller circuit board. Check the holder of thermistor. Check connection of connector (63HS) on the outdoor controller circuit board. Check breaking of the lead wire for thermistor (63HS). 2 Check pressure by microcomputer. (Pressure sensor/ 63HS) (SW2: Refer to "8-7. OUTDOOR UNIT OPERATI MITOR".) FUNCTI". 3 Replace outdoor controller board. PE Inlet water temperature Abnormal if the following conditions are detected for continuously 0 seconds.. Cooling mode During compressor operation TH32 < 3: 2. Heating mode (exclude defrosting) During compressor operation TH32 < -0: 3. Defrosting mode During compressor operation TH32 < 0: Thermistor TH32: Inlet water temperature Reduced water flow Clogged filter Leak of water 2 Low temperature Low-load Low temperature inlet water 3 Defective water pump 4 Leakage or shortage of refrigerant 2 Check water piping. 3 Check water pump. 4 Check intake superheat. Check leakage of refrigerant. 22

8-4. HOW TO CHECK THE PARTS PUHZ-W2VHA PUHZ-W2VHA-BS Parts name TH3: Liquid pipe temp. TH4: Discharge temp. TH6: Plate Hex liquid pipe temp. TH7: Ambient temp. TH8: Heatsink temp. TH32: Inlet water temp. TH33: Suction pipe temp. TH34: Comp. surface thermistor Check points Disconnect the connector then measure the resistance with a tester. (At the ambient temperature of 0 to 30:) TH4 TH34 TH3 TH6 TH7 TH33 TH32 TH8 Normal 60 to 40 k" 4.3 to 9.6 k" 4.4 to 9.8 k" 39 to 05 k" Abnormal Open or short Fan motor (MF) Solenoid valve coil <Four-way valve> (2S4) Refer to the next page. Measure the resistance between the terminals with a tester. (At the ambient temperature of 20:) Normal Abnormal 435 ± 50 " Open or short Compressor (MC) U Measure the resistance between the terminals with a tester. (Winding temperature 20:) V W Normal 0.88 " Abnormal Open or short Linear expansion valve (LEV-A) (LEV-B) Disconnect the connector then measure the resistance with a tester. (Winding temperature 20 C) M Gray Orange Red Yellow Black 2 3 4 5 Normal Gray - Black Gray - Red Gray - Yellow Gray - Orange 46±3Ω Abnormal Open or short 23

Check method of DC fan motor (fan motor / outdoor controller circuit board) Notes High voltage is applied to the connector (CNF, 2) for the fan motor. Pay attention to the service. Do not pull out the connector (CNF, 2) of the motor with the power supply on. (It may damage the outdoor controller circuit board and fan motor.) 2 Self check Symptom: The outdoor fan does not run. Check fuse (F5) on outdoor controller circuit board. Is the fuse normal? Yes No Replace fan motor. Replace outdoor controller circuit board. Wiring contact check Check contact of fan motor connector (CNF) (CNF2) Is there contact failure? Yes Recover wiring. No Power supply check Measure the voltage on the outdoor controller circuit. TEST POINT VDC DC 280-380 V (between (+) and 4 (-) of CNF,2) 2 VCC DC 5 V (between 5 (+) and 4 (-) of CNF,2) Is the voltage normal? Yes Replace fan motor. No Check fan motor rotation. OK END Replace outdoor controller circuit board. NG Replace outdoor controller circuit board. Check fan motor rotation. OK END NG Replace fan motor. 24

8-5. HOW TO CHECK THE COMPENTS <Thermistor feature chart> Low temperature thermistors Thermistor <Liquid pipe> (TH3) Thermistor <Plate Hex liquid pipe> (TH6) Thermistor <Ambient> (TH7) Thermistor <Suction pipe> (TH33) Thermistor R0 = 5 kω ± 3% B constant = 3480 ± 2% Rt =5exp{3480( 273+t 273 )} 0: 5 kω 0: 9.6 kω 20: 6.3 kω 25: 5.2 kω 30: 4.3 kω 40: 3.0 kω Resistance (k") 50 40 30 20 0 0-20 -0 0 0 20 30 40 50 Temperature (:) Medium temperature thermistor Thermistor <Heatsink> (TH8) Thermistor R50 = 7 kω ± 2% B constant = 450 ± 3% Rt =7exp{450( 273+t 323 )} 0: 80 kω 25: 50 kω 50: 7 kω 70: 8 kω 90: 4 kω Resistance (k") 200 50 00 50 0 25 50 75 00 25 Temperature (:) High temperature thermistors Thermistor <Discharge pipe> (TH4) Thermistor <Comp. surface> (TH34) Thermistor R20 = 7.465k' ± 2% B constant = 4057 ± 2% Rt =7.465exp{4057( 273+t 393 )} 20: 250 kω 30: 60 kω 40: 04 kω 50: 70 kω 60: 48 kω 70: 34 kω 80: 24 kω 90: 7.5 kω 00: 3.0 kω 0: 9.8 kω Resistance (k") 500 400 300 200 00 0 25 50 75 00 20 Temperature (:) 25

Low temperature thermistor Thermistor <Inlet water> (TH32) Thermistor R0 = 5 kω ± 2.5% B constant = 3450 ± 2% Rt =5exp{3450( 273+t 273 )} 0: 5 kω 0: 9.6 kω 20: 6.3 kω 25: 5.2 kω 30: 4.3 kω 40: 3.0 kω Resistance (k") 50 40 30 20 0 0-20 -0 0 0 20 30 40 50 Temperature(:) <HIGH PRESSURE SENSOR> Vout (V) 4.5 2.5 SENSOR Vout WHT BLU BLK MULTI CTROLLER BOARD 5V DC 3 2 MICRO PROCESSOR 0.5 63HS GND 2.5 5 PRESSURE (MPa) 3- : 5V (DC) 2- : Output Vout (DC) 26

Linear expansion valve () Operation summary of the linear expansion valve Linear expansion valve opens/closes through stepping motor after receiving the pulse signal from the outdoor controller board. Valve position can be changed in proportion to the number of pulse signal. <Connection between the outdoor controller board and the linear expansion valve> Outdoor controller board DC2V LEV 6 M 3 2 5 4 Gray Orange 2 Red 3 Yellow 4 Drive circuit Black 5 Connector LEV-A LEV-B <Output pulse signal and the valve operation> Output (Phase) 2 OFF Output 2 3 4 5 6 7 8 OFF OFF OFF OFF OFF OFF OFF OFF OFF Opening a valve : 8 7 6 5 4 3 2 8 Closing a valve : 7 8 The output pulse shifts in above order. When linear expansion valve operation stops, all output phase become OFF. 3 OFF OFF OFF OFF OFF 4 OFF OFF OFF OFF OFF (2) Linear expansion valve operation Valve position (capacity) Close Open When the switch is turned on, 700 pulse closing valve signal will be sent till it goes to point in order to define the valve position. (The pulse signal is being sent for about 20 seconds.) When the valve moves smoothly, there is no sound or vibration occurring from the linear expansion valve: however, when the pulse number moves from to or when the valve is locked, sound can be heard. No sound is heard when the pulse number moves from to in case coil is burnt out or motor is locked by open-phase. Sound can be detected by placing the ear against the screw driver handle while putting the screw driver to the linear expansion valve. 500 pulse Opening a valve all the way Extra tightening (about 32 pulse) Pulse number 27

(3) How to attach and detach the coil of linear expansion valve <Composition> Linear expansion valve is separable into the main body and the coil as shown in the diagram below. Coil Stopper Main body Lead wire <How to detach the coil> Hold the lower part of the main body (shown as A) firmly so that the main body does not move and detach the coil by pulling it upward. Be sure to detach the coil holding main body firmly. Otherwise pipes can bend due to pressure. A <How to attach the coil> Hold the lower part of the main body (shown as A) firmly so that the main body does not move and attach the coil by inserting it downward into the main body. Then securely attach the coil stopper to main body. (At this time, be careful that stress is not added to lead wire and main body is not wound by lead wire.) If the stopper is not firmly attached to main body, coil may be detached from the main body and that can cause defective operation of linear expansion valve. To prevent piping stress, be sure to attach the coil holding the main body of linear expansion valve firmly. Otherwise pipe may break. Be sure to attach the stopper. A 28

<CAUTI> TEST POINT is high voltage. 8-6. TEST POINT DIAGRAM Outdoor controller circuit board PUHZ-W2VHA PUHZ-W2VHA-BS SW Forced defrost, detect history record reset SW9 Function switch SW2 Operation monitor function SW7 Function switch CNDM to 2: Input of low-level sound priority mode SW6 CN52C Model select Connect to the power circuit board (CN52C) (HW40V) SW5 Function switch SW8 Function switch CN4 Transmission to outdoor power circuit board (CN4) SV Connection for option (Drain hose heater output) 2S4 4-way valve LEV-A,B 63H Linear expansion valve High pressure switch TH34 Thermistor <Comp. surface> CN2 Connect to the outdoor power circuit board (CN2) -5: Reception from power circuit board 2-5: Zero cross signal (0-5 V DC) 3-4: 8V DC 6-5: 6V DC 7-5: 6V DC 63L Low pressure switch TH4 Thermistor <Discharge> TH3 Thermistor <Liquid pipe> TH7/6 Thermistor <Outdoor/ Plate Hex liquid> CNAC TH32 2 to 4: Power supply for outdoor controller circuit board (230 V AC) to 3: Power supply for indoor and outdoor unit connection wire (230 V AC) Thermistor <Inlet water temperature> TH33 Thermistor <Suction pipe temperature> VFG (Voltage between right pins of PC5C and PC5D, pin 3 and pin 4) (Same as (CNF7(+)-4(-)) VSP (Voltage between pins of C5A, C5B): DC 0 V (when stopped), DC 6.5 V CNF, CNF2 (when operated) Connect to the fan motor -4: 280-380 V DC 5-4: 5 V DC 6-4: 0-6.5 V DC 7-4: 5 V DC (When stopped) 7.5 V DC (When operated) (0 V-5 V pulse) CNS S-S2: 230 V AC CNDC 280-380 V DC (+, 3-) (Outdoor power circuit board for) 29

Outdoor power circuit board PUHZ-W2VHA PUHZ-W2VHA-BS Brief Check of POWER MODULE Usually, they are in a state of being short-circuited if they are broken. Measure the resistance in the following points (connectors, etc.). If they are short-circuited, it means that they are broken.. Check of POWER MODULE Check of DIODE circuit R - L, S - L, R - N, S - N 2 Check of IGBT circuit L2 - N 3 Check of INVERTER circuit P - U, P - V, P - W, N - U, N - V, N - W Note: The marks R, S, L, L2, P, N, U, V and W shown in the diagram are not actually printed on the board. CN4 Connect to the outdoor controller circuit board (CN4) N2 Power module Connect to the smoothing capacitor CB - CN2 Connect to the outdoor controller circuit board (CN2) -5: Transmitting signal to outdoor controller circuit board (0-5 V DC) 2-5: Zero cross signal (0-5 V DC) 3-4: 8 V DC 6-5: 6 V DC 7-5: 6 V DC CN52C CNDC 52C driving signal Connect to the outdoor controller circuit board (CN52C) S W U/V/W Connect to the compressor (MC) Voltage among phases: 0 V-80 V AC V U P2 L2 P N 280-380 V DC (+, 3-) Connect to the outdoor controller circuit board (CNDC) E2, E3 Connect to the earth R L DCL, DCL2 EI, E4 Connect to the smooth- Connect to DCL Connect to the ing capacitor CB + earth 30 CNAC, CNAC2 230 V AC Connect to the outdoor controller circuit board (CNAC) NI, LI Voltage of 230 V AC is input (Connect to the terminal block (TB))

8-7. Outdoor unit operation monitor function Operation indicator SW2: Indicator change of self diagnosis The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit <Digital indicator LED3 working details> (Be sure that the to 6 in the SW2 are set to OFF.) () Display when the power supply is. When the power supply is, blinking displays by turns. Wait for 0 seconds at the longest. (2) When the display lights (Normal operation) Operation mode display LED3 (Lighting) second interval SW2 (Initial setting) The tens digit : Operation mode Display Operation Model O C H d OFF COOLING HEATING DEFROSTING 2 Display during error postponement Postponement code is displayed when compressor stops due to the work of protection device. Postponement code is displayed while error is being postponed. The ones digit : Relay output Display Warming-up Compressor Compressor 4-way valve Solenoid valve (3) When the display blinks Inspection code is displayed when compressor stops due to the work of protection devices. Display Inspection unit 0 Outdoor unit Display U U2 U3 U4 U5 U6 U7 U8 U9 Ud UF UH UP P6 P8 UE PE Ed 0 2 3 4 5 6 7 8 A Contents to be inspected (During operation) Abnormal high pressure (63H operated) Abnormal high discharging temperature, shortage of refrigerant Open/short circuit of discharging thermistor (TH4, TH34) Open/short of outdoor unit thermistors (TH3, TH32, TH6, TH7, TH8 and TH33) Abnormal temperature of heatsink Abnormality of power module Abnormality of superheat due to low discharge temperature Abnormality in outdoor fan motor Voltage fault, Input current sensor error Overheat protection Compressor overcurrent interruption (When Comp. locked) Current sensor error Compressor overcurrent interruption Abnormality of Interface or FTC units Abnormality of pipe temperature Abnormality pressure of pressure sensor Abnormality of inlet water temperature Serial communication error Display Contents to be inspected (When power is turned on) F5 63H connector(yellow) is open. E8 Interface unit/flow temp. controller-outdoor communication error (Signal receiving error) (Outdoor unit) E9 Interface unit/flow temp. controller-outdoor communication error (Transmitting error) (Outdoor unit) EA Miswiring of Interface unit/flow temp. controller-outdoor unit connecting wire, excessive number of indoor units (2 units or more) Eb Miswiring of Interface unit/flow temp. controller-outdoor unit connecting wire (converse wiring or disconnection) EC Startup time over E0~E7 Communication error except for outdoor unit 3

SW2 setting The black square ( ) indicates a switch position. Display detail Explanation for display Unit Pipe temperature / Liquid (TH3) - 40 to 90-40 to 90 (When the coil thermistor detects 0: or below, and temperature are displayed by turns.) (Example) When -0:; 0 : Discharge temperature (TH4) 3 to 27 3 to 27 (When the discharge thermistor detects 00: or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 05:; 05 : Fan steps 0 to 0 0 to 0 Step 2 3 4 5 6 Compressor /OFF 0 to 9999 0 to 9999 (When the number of times is 00 or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 42500 times (425 00 times); 4 25 00 times Compressor accumulated operation hours 0 to 9999 0 to 9999 (When it is 00 hours or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 2450 hours (245 0 hours); 2 45 0 hours Compressor running current 0 to 50 0 to 50 (Value after the decimal point will be truncated.) A Compressor running frequency 0 to 255 0 to 255 (When it is 00 Hz or more, hundreds digit, tens digit and ones digit are displayed by turns. (Example) When 05 Hz; 05 Hz LEV-A opening pulse 0 to 500 0 to 500 (When it is 00 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns. (Example) When 50 pulse; 50 Pulse Deferred error history () Deferred error Blinking: being deferred Lighting: deferment is cancelled 00 is displayed in case of no deferment Code display Operation mode when the error occurred Operation mode when the unit is stopped due to an error is displayed. The displayed code is when the SW2 is set as below. (SW2) Code display 2 3 4 5 6 32

SW2 setting The black square ( ) indicates a switch position. Display detail Explanation for display Unit Pipe temperature/liquid (TH3) when error occurred - 40 to 90-40 to 90 (When the coil thermistor detects 0: or below, and temperature are displayed by turns.) (Example) When - 5:; 5 : Discharge temperature (TH4) when error occurred 3 to 27 3 to 27 (When the temperature is 00: or more, the hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 30:; 30 : Compressor current when error occurred 0 to 50 0 to 50 A 2 3 4 5 6 Error history () (latest) Alternate display of faulty unit number and check code When no error history, 0 and are displayed by turns. Code display Error history (2) Alternate display of faulty unit number and check code When no error history, 0 and are displayed by turns. Code display Compressor operation duration 0 to 999 0 to 999 (When it is 00 minutes or more, the hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 245 minutes; 2 45 Minute LEV-B opening when error occurred 0 to 500 (When it is 00 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns. (Example) When 50 pulse; 50 Pulse Capacity settings The outdoor capacity code is shown as below Model Code PUHZ-W2 20 Code display 33

The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Outdoor unit setting information The tens digit (Total display for applied setting) Setting details Display details H P / Cooling only Single phase / 3 phase The ones digit Setting details Defrosting switch 0 : H P : Cooling only 0 : Single phase 2 : 3 phase Display details 0 : Normal : For high humidity (Example) When heat pump, 3 phase and defrosting (normal) are set up, 20 is displayed. Code display Plate HEX liquid pipe temperature (TH6) - 39 to 88-39 to 88 (When the temperature is 0: or less, and temperature are displayed by turns.) : 2 3 4 5 6 Condensing temperature (T63HS) - 39 to 88-39 to 88 (When the temperature is 0: or less, and temperature are displayed by turns.) : Calculated maximum frequency 0 to 50 0 to 50 (When it is 00 Hz or more, hundreds digit, tens digit and ones digit are displayed by turns. 2 3 4 5 6 (Example) When 05 Hz; 05 Hz Water inlet temperature (TH32) 0 to 00 0 to 00 : 2 3 4 5 6 Ambient temperature (TH7) - 39 to 88-39 to 88 (When the temperature is 0: or less, and temperature are displayed by turns.) : 2 3 4 5 6 Outdoor heatsink temperature (TH8) - 40 to 200-40 to 200 (When the temperature is 0: or less, and temperature are displayed by turns.) (When the thermistor detects 00: or more, hundreds digit, tens digit and ones digit are displayed by turns.) : Discharge superheat (SHd) 0 to 255 Cooling and Heating: SHd = TH4-T63HS 0 to 255 (When the SHd is 00 C or more, hundreds digit, tens digit and ones digit are displayed by turns.) C 34

The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Number of defrost cycles 0 to FFFE 0 to FFFE (in hexadecimal notation) (When more than FF in hex (255 in decimal), the number is displayed in order of 6 3 's and 6 2 's, and 6 's and 6 0 's places. (Example) When 5000 cycles; 2 cycles 9 C4 Input current of outdoor unit 0 to 500 0 to 500 (When it is 00 or more, hundreds digit, tens digit and ones digit are displayed by turns.) 0. A LEV-B opening pulse 0 to 500 0 to 500 (When it is 00 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns.) Pulse U9 error detail history (latest) 2 3 4 5 6 Description Normal Overvoltage error Undervoltage error Input current sensor error L-phase open error Abnormal power synchronous signal PFC/IGBT error Undervoltage Display 00 0 02 * Display examples for multiple errors: Overvoltage (0) + Undervoltage (02) = 03 Undervoltage (02) + Power-sync signal error (08) = 0A L phase open error (04) + PFC/IGBT error (20) = 24 04 08 20 Code display Direct current bus voltage 50 to 400 50 to 400 (When it is 00V or more, hundreds digit, tens digit and ones digit are displayed by turns.) V Capacity save 0 to 00 When there is no setting of capacity save, 00 is displayed. 0 to 00 (When the capacity is 00%, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 00%; 00 % Deferred error history (2) of outdoor unit Deferred check code display Blinking: being deferred Lighting: deferment is cancelled 00 is displayed in case of no deferment. Code display Deferred error history (3) of outdoor unit Deferred check code display Blinking: being deferred Lighting: deferment is cancelled 00 is displayed in case of no deferment. Code display 35

The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Error history (3) (Oldest) Faulty unit number and check code are displayed alternately. When no error history, 0 and are displayed by turns. Code display Error thermistor display When there is no error thermistor, is displayed. 3: Liquid pipe thermistor (TH3) 3: Water inlet temp. thermistor (TH32) 6: Plate HEX liquid pipe thermistor (TH6) 7: Ambient temp. thermistor (TH7) 8: Heatsink thermistor (TH8) 4: Discharge thermistor (TH4) 3: Suction pipe thermistor (TH33) 34: Comp. surface thermistor (TH34) Code display Operation frequency when error occurred. 0 to 225 0 to 225 (When it is 00 Hz or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 05 Hz; 05 Hz Fan step when error occurred. 0 to 0 0 to 0 Step 2 3 4 5 6 LEV-A opening pulse when error occurred. 0 to 500 0 to 500 (When it is 00 pulse or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 30 pulse; 30 Pulse Plate HEX liquid pipe temperature (TH6) when error occurred. - 39 to 88-39 to 88 (When the temperature is 0 C or less, and temperature are displayed by turns.) (Example) When 5 C; 5 : Condensing temperature when error occurred. - 39 to 88-39 to 88 (When the temperature is 0 C or less, and temperature are displayed by turns.) (Example) When 5 C; 5 : Water inlet temperature (TH32) when error occurred. 0 to 00 0 to 00 : Ambient temperature (TH7) when error occurred. - 39 to 88-39 to 88 (When the temperature is 0 C or less, and temperature are displayed by turns.) (Example) When - 5 C; 5 : 36

The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Outdoor heatsink temperature (TH8) when error occurred. - 40 to 200-40 to 200 (When the temperature is 0 C or less, and temperature are displayed by turns.) (When the temperature is 00 C or more, hundreds digit, tens digit and ones digit are displayed by turns.) : Discharge superheat (SHd) when error occurred. 0 to 255 Cooling and Heating: SHd=TH4-T63HS 0 to 255 (When the temperature is 00 C or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 50 C; 50 : Sub cool (SC) when error occurred. 0 to 30 Cooling: SC = T63HS-TH3 Heating: SC = T63HS-TH6 0 to 30 (When the temperature is 00 C or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 5 C; 5 : Compressor operation duration before the unit stops with error 0 to 999 0 to 999 (When it is 00 minutes or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 45 minutes; 4 5 Minute Maximum frequency when error occurred 0 to 50 0 to 50 (When it is 00 Hz or more, hundreds digit, tens digit and ones digit are displayed by turns. (Example) When 05 Hz; 05 Hz Requested capacity step when error occurred 0 to 7 0 to 7 Step Compressor frequency control status The following code will be a help to know the operating status of unit. Ten place (left side): Display Compressor frequency control Input current restriction control 2 Compressor current restriction control First digit (Total figure of the corresponding relays are displayed.) Display Compressor frequency control Discharge temp.control(not to over rise). 2 Condensing temp.control(not to over rise). 4 Freezing protection control 8 Heatsink temp.control(not to over rise). When the following 3 points are under control; LED () Input current restriction control. (2) Condensing temp. control (not to over rise). a (3) Heatsink temp. control (not to over rise). Code display 37

The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Comp. surface temperature (TH34) 3 to 27 3 to 27 (When the temperature is 00: or more, the hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 30:; 30 : Outdoor suction pipe temperature (TH33) - 39 to 88-39 to 88 (When the temperature is 0 C or less, and temperature are displayed by turns.) (Example) When 5 C; 5 : Requested capacity step (Q STEP) 0 to 7 0 to 7 Step 2 3 4 5 6 U9 Error details (To be shown while error call is deferred.) Description Normal Overvoltage error Undervoltage error Input current sensor error L-phase open error Abnormal power synchronous signal PFC/IGBT error Undervoltage Display 00 0 02 * Display examples for multiple errors: Overvoltage (0) + Undervoltage (02) = 03 Undervoltage (02) + Power-sync signal error (08) = 0A L phase open error (04) + PFC/IGBT error (20) = 24 04 08 20 Code display 38

Data Sheet for Air to Water Compact type Applicable model PUHZ-W2VHA(-BS) Model name: [Serial No. : ] Date : SW2 setting : / 0:OFF SW2 setting : / 0:OFF Operation Data Recorded operation status 23456 23456 I nlet/outlet water temperature / Operation mode when the error occurred (Mode) 0000 O utdoor Inlet/Outlet Air temperature / Error history () [Latest] (Code) 000 D ischarge/suction temperature / Error history (2) (Code) 00 D ischarge/suction pressure / Error history (3) [Oldest] (Code) 0000 P ower supply Voltage/Frequency ( V / Hz ) / Deferred error history () (Code) 0000 W ater flow Volume ( L/min ) Deferred error history (2) (Code) 000 Inlet water temp. [TH32] 0 0 0 Deferred error history (3) (Code) 0 0 Plate HEX liquid pipe temp. [TH6] 0000 Condensing temp. [T 63HS ] 0 Condensing temp. [T 63HS ] 000 Plate HEX liquid pipe temp. [TH6] 00 Ambient temp. [TH7] 0 0 Compressor running frequency (Hz) 0 0 0 Compressor running frequency (Hz) 0 0 0 Fan steps (Step) 0 0 Fan steps (Step) 0 0 0 0 Liquid pipe temp. [TH3] 0 0 0 Liquid pipe temp. [TH3] 0 0 0 0 0 Discharge temp. [TH4] 0 0 0 0 Discharge temp. [TH4] 0 0 0 0 0 LEV-A opening pulse [LEV-A] 0 0 0 LEV-A opening pulse [LEV-A] 0 0 0 0 0 LEV-B opening pulse [LEV-B] 0 0 0 0 LEV-B opening pulse [LEV-B] 0 0 0 0 Ambient temp. [TH7] 0 0 0 Requested capacity step [Q STEP ] 0 Water inlet temp. [TH32] 0 0 0 0 Comp. surface temp. [TH34] 0 Heat sink temp. [TH8] 0 0 0 Suction temp. [TH33] 0 0 Calculated max. frequency (Hz) 0 0 when error occurred Heat sink temp. [TH8] 0 0 Discharge Super Heat [SHd] 0 Calculated max. frequency (Hz) 0 0 Compressor operation duration (Min) 0 0 0 0 0 Number of defrost cycle [SC] 0 0 0 0 0 Demand capacity (%) 0 0 0 Direct current bus line voltage (V) 0 0 0 0 Compressor running current (A) 0 0 0 0 Input current (0.A) 0 0 0 0 Compressor frequency control status * 0 0 * Temperature differential code [ΔTj] 0 0 0 Sub Cool [ SC ] 000 Compressor operation duration (Min) 0 0 Requested capacity step [Q STEP ] 0 Discharge Super Heat [SHd] 0 0 Compressor running current (A) 0 0 0 Capacity setting (Code) 0 0 0 0 Compressor /OFF ( 00) 0 0 0 0 0 Compressor accumulated operation hours ( 0hours) 0 0 0 0 U9 error detail history (latest) (Code) 0 0 0 Check sum (Code) 0 0ths digit :Input current restriction control st digit :Discharge temp. control 4:Freeze protection control 2:Compressor current restriction control 2:Condensing temp. control 8:Heat sink temp. control 39

8-8. FUNCTI OF SWITCHES PUHZ-W2VHA PUHZ-W2VHA-BS Switch Selection Function Mark No. (with) OFF (without) SW SW5 Initial setting* Function details Effective timing Forced defrosting to start usual setting OFF Switch to force defrosting Always 2 To clear error history to clear usual setting OFF Switch to clear (erase) the followings: ()Check codes and Suspension flags in RAM (2)Check codes and Suspension flags in EEPROM Always 3 No function Do NOT use PUHZ-W2VHA OFF 4 Abnormal disregard Disregard Normal OFF Check code (P8,UH): Always Abnormal detection disregard 5 No function Do NOT use PUHZ-W2VHA OFF 6 No function Do NOT use PUHZ-W2VHA OFF Silent setting (FAN) Silent setting (FAN) usual setting OFF Fan speed setting in silent mode 2 Silent setting (Hz) Silent setting (Hz) usual setting OFF Hz setting in silent mode 3 No function Do NOT use PUHZ-W2VHA OFF 4 No function Do NOT use PUHZ-W2VHA OFF 5 Defrost control selection For high humidity Standard OFF Switches to optimal defrosting operation for low-temperature and high-humidity regions. 6 No function Do NOT use PUHZ-W2VHA OFF Always SW6-3 Model Setting 4 Single phase / 3 phase Model SW6 2 3 W 0 0 =, 0=OFF As shown in the left table Do NOT use Single phase 5-8 Model Setting 2 Model SW6 5 6 7 8 W2 0 0 =, 0=OFF As shown in the left table Make sure to set SW6-5 to 8 correctly SW7-6 No function Do NOT use PUHZ-W2VHA OFF Mode selection Energy saving mode Powerful mode OFF Always SW8 2 Max. current setting Max. current Model OFF W2 29.5A 23.0A OFF When power supply 3 Separate Interface/Flow temp.controller - outdoor unit power supplies Separate power supply Outdoor unit power supply OFF Power supply connection method selection When power supply SW9-4 No function Do NOT use <Important Note> All these dip switches on PUHZ-W2VHA are set as shown above. Spare PCBs, however, will be supplied without any settings, which means that all dip switches are switched OFF. When servicing, please make sure to set all switches correctly, referring to the previous PCB which is removed from the unit. *. Forced defrosting should be done as follows. Change the DIP SW- on the outdoor controller board from OFF to. 2 Forced defrosting will start by the above operation if these conditions written below are satisfied. Heat mode setting 0 minutes have passed since compressor starts operating or previous forced defrosting is finished. Pipe temperature is less than or equal to 8:. Forced defrosting will finish if certain conditions are satisfied. Forced defrosting can be done if above conditions are satisfied when DIP SW- is changed from OFF to. After DIP SW- is changed from OFF to, there is no problem if DIP SW- is left or changed to OFF again. This depends on the service conditions. 40

9 DISASSEMBLY PROCEDURE PUHZ-W2VHA PUHZ-W2VHA-BS OPERATING PROCEDURE PHOTOS & ILLUSTRATI. Removing the service panel and top panel () Remove 3 service panel fixing screws (5 2) and slide the hook on the right downward to remove the service panel. (2) Remove screws (3 for front, 3 for rear/5 2) of the top panel and remove it. Photo Grille fixing screws Top panel fixing screws Slide Top panel Service panel Fan grille Grille fixing screws Service panel fixing screws Cover panel (front) 2. Removing the fan motor (MF, MF2) () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) (3) Remove 5 fan grille fixing screws (5 2) to detach the fan grille. (See Photo ) (4) Remove a nut (for right handed screw of M6) to detach the propeller. (See Photo 2) (5) Disconnect the connectors, CNF and CNF2 on controller circuit board in electrical parts box. (6) Remove 4 fan motor fixing screws (5 20) to detach the fan motor. (See Photo 3) Photo 2 Nut Front panel Propeller Photo 3 Fan motor fixing screws Fan motor 3. Removing the electrical parts box () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) (3) Disconnect the indoor/outdoor connecting wire and power supply wire from terminal block. (4) Disconnect the connectors on the controller circuit board. (5) Remove the terminal cover and disconnect the compressor lead wire. (6) Remove 2 electrical parts box fixing screw (4 0) and detach the electrical parts box by pulling it upward. The electrical parts box is fixed with 2 hooks on the left and hook on the right. Photo 4 Controller circuit board Fan motor fixing screws Hook (right) Terminal block (TB) Electrical parts box fixing screw 4

PHOTOS OPERATING PROCEDURE 4. Removing the thermistor <Plate HEX liquid> (TH6) and thermistor <Ambient> (TH7) () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) (3) Disconnect the connectors, TH7/6 (red) on the controller circuit board in the electrical parts box. (4) Loosen the 2 wire clamps on top of the electrical parts box. (5) Loosen the fastener for the lead wire on the controller circuit board in the electrical parts box. (6) Loosen the cable strap for the lead wire on the bottom of electrical parts box. (7) Pull out the thermistor <Plate HEX liquid> (TH6) and thermistor <Ambient> (TH7) from the sensor holder. Note: In case of replacing thermistor <Plate HEX liquid> (TH6) or thermistor <Ambient> (TH7), replace it together. Photo 5 Thermistor <Plate HEX liquid> (TH6) Photo 6 Lead wire of thermistor <Ambient> (TH7) Low pressure switch (63L) 4-way value Sensor holder 5. Removing the thermistor <Discharge> (TH4) and thermistor <Comp. surface> (TH34) () Remove the service panel. (See Photo ) (2) Disconnect the connector TH4 (white) on the controller circuit board in the electrical parts box. (4) Loosen the wire clamp on separator. (5) Loosen the cable strap for the lead wire on the bottom of electrical parts box. (6) Pull out the thermistor <Discharge> (TH4) from the sensor holder. Photo 7 Thermistor <Comp. surface> (TH34) High pressure sensor (63HS) Thermistor <Discharge> (TH4) [Removing the thermistor <Comp. surface> (TH34)] (7) Remove the top damper, then pull out the thermistor <Comp. surface> (TH34) from the holder of the compressor shell. Top damper 6. Removing the thermistor <Liquid> (TH3) and thermistor <suction> (TH33) () Remove the service panel. (See Photo ) (2) Disconnect the connectors TH3 (white) and TH33 (yellow) on the controller circuit board in the electrical parts box. (3) Loosen the fastener for the lead wire on the controller circuit board in the electrical parts box. (4) Loosen the wire clamp and wire clip on separator. (5) Pull out the thermistor <Liquid> (TH3), <Suction> (TH33) from the sensor holder. Photo 8 Compressor (MC) High pressure sensor (63HS) Compressor (MC) 42 Stay Thermistor <Suction> (TH33) Thermistor <Liquid> (TH3)

OPERATING PROCEDURE PHOTOS 7. Removing the 4-way valve coil (2S4), and linear expansion valve coil (LEV-A, LEV-B) () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) Photo 9 High pressure switch (63H) [Removing the 4-way valve coil] (See Photo 9) (3) Remove 4-way valve solenoid coil fixing screw (M4 6). (4) Remove the 4-way valve coil by sliding the coil toward you. (5) Disconnect the connector 2S4 (green) on the controller circuit board in the electrical parts box. (6) Loosen the fastener for the lead wire on the controller circuit board in the electrical parts box. [Removing the LEV coil] (See Photo 0) 4-way valve coil fixing screw (3) Loosen the lead wires fixed to the pipes with bands. (4) Remove the linear expansion valve coil by sliding the coil upward. Photo 0 (5) Disconnect the connectors, LEV-A (white) and LEV-B (red) on the controller circuit board in the electrical parts box. 8. Removing the 4-way valve () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) (3) Remove the electrical parts box. (See Photo 4) (4) Remove the cover panel (front).(see Photo ) (5) Remove the stay. (6) Remove 5 right side panel fixing screws (5 2) (4: rear of the unit/: right side base) and remove the right side panel. (7) Remove the 4-way valve coil. (See Photo 9) (8) Recover refrigerant. (9) Remove the welded part of 4-way valve. LEV (LEV-A) 4-way valve LEV (LEV-B) Refer to the notes below. 4-way valve Heat exchanger Photo 9. Removing LEV () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) (3) Remove the electrical parts box. (See Photo 4) (4) Remove the cover panel (front). (See Photo ) (5) Remove 3 stay fixing screws (4 0) and remove the stay. (6) Remove 5 right side panel fixing screws (5 2) (4: rear of the unit/: right side base) and remove the right side panel. (7) Remove the LEV coil. (8) Recover refrigerant. (9) Remove the welded part of LEV. Low pressure switch (63L) Refer to the notes below. 0. Removing the high pressure switch (63H) (See Photo 9) and the low pressure switch (63L) () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) (3) Remove the electrical parts box. (4) Remove the cover panel (front). (See Photo ) (5) Remove the stay. (6) Remove 5 right side panel fixing screws (5 2) (4: rear of the unit/: right side base) and remove the right side panel. (7) Pull out the lead wire of high pressure switch and low pressure switch. (8) Recover refrigerant. (9) Remove the welded part of high pressure switch and low pressure switch. Refer to the notes on the right. 43 High pressure sensor (63HS) Notes:. Recover refrigerant without spreading it in the air. 2. The welded part can be removed easily by removing the right side panel. 3. When installing the follwing parts, cover it with a wet cloth to prevent it from heating, then braze the pipes so that the inside of pipes are not oxidized; 4-way valve (procedure 8), 20 C or more LEV (procedure 9), 20 C or more High pressure switch and low pressure switch (procedure 0), 00 C or more

OPERATING PROCEDURE. Removing high pressure sensor (63HS) () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) (3) Pull out the lead wire of high pressure sensor. (4) Remove the 4-way valve coil. (See Photo 9) (5) Recover refrigerant. (6) Remove the welded part of high pressure sensor. Note : Recover refrigerant without spreading it in the air. Note 2: The welded part can be removed easily by removing the right side panel. Note 3: When installing the high pressure sensor, make sure to cover it with a wet cloth to prevent it from heating (00 C or more), then braze the pipes so that the inside of pipes are not oxidized. Photo 2 PHOTOS Low pressure switch (63L) High pressure sensor (63HS) 2. Removing the plate heat exchanger () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) (3) Remove 2 screws (5 2) and remove the front cover panel. (4) Remove the electrical parts box. (See Photo 4) (5) Remove 3 screws (4 0) and remove the stay. (6) Remove 5 screws (5 2) (4: rear of the unit/: right side base) and remove the right side panel. (7) Recover the refrigerant (8) Remove 2 welded pipes of plate heat exchanger inlet and outlet. (9) Remove 3 plate heat exchanger fixing screws (4 0), then remove the plate heat exchanger. Photo 3 Plate heat exchanger Heat exchanger Note : Recover refrigerant without letting it out in the air. Note 2: Before removing the thermistor <Inlet water> (TH32), recover water in the plate heat exchanger. Plate heat exchanger fixing screw Plate heat exchanger fixing screw 44

OPERATING PROCEDURE 3. Removing the compressor (MC) () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) (3) Remove 2 front cover panel fixing screws (5 2) and remove the front cover panel. (4) Remove the electrical parts box. (See Photo 4) (5) Remove 3 stay fixing screws (4 0) and remove the stay. (6) Remove 5 right side panel fixing screws (5 2) (4: rear of the unit/: right side base) and remove the right side panel. (7) Remove 3 separator fixing screws (4 0) and remove the separator. (8) Remove the soundproof cover for compressor. (9) Remove the terminal cover and remove the compressor lead wire. (0) Recover refrigerant. () Remove the 3 points of the compressor fixing nut using a spanner or a adjustable wrench. (2) Remove the welded pipe of compressor inlet and outlet then remove the compressor. Note: Recover refrigerant without spreading it in the air. Photo 4 Terminal cover PHOTOS Compressor (MC) Pipes of power receiver Power receiver 4. Removing the power receiver () Remove the service panel. (See Photo ) (2) Remove the top panel. (See Photo ) (3) Remove 2 front cover panel fixing screws (5 2) and remove the front cover panel. (4) Remove the electrical parts box. (See Photo 4) (5) Remove 3 stay fixing screws (4 0) and remove the stay. (6) Remove 5 right side panel fixing screws (5 2) (4: rear of the unit/: right side base) and remove the right side panel. (7) Recover refrigerant. (8) Remove 4 welded pipes of power receiver inlet and outlet. (9) Remove 2 receiver leg fixing screws (4 0). Compressor fixing nut Plate heat exchanger fixing screw Receiver leg fixing screw Note: Recover refrigerant without spreading it in the air. 45