DESIGN STANDARDS SECTION 15600

Similar documents
RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

SECTION (15530) - REFRIGERANT PIPING

SECTION (15530) - REFRIGERANT PIPING

PROJ. NO SECTION REFRIGERANT PIPING

SECTION REFRIGERANT PIPING

REFRIGERANT PIPING SYSTEM

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

Ratio Architects, Inc. Section Refrigerant Piping

REFRIGERANT PIPING

SECTION REFRIGERANT PIPING SYSTEMS

SECTION REFRIGERANT PIPING

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

Service Step by Step Trouble-Shooting Check-List

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COILS

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

Refrigeration Technology in Building Services Engineering

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

.2 Section Waste Management and Disposal.

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

Sporlan Valve Division Parker Hannifan/CIC Group

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

HVAC Compressor Replacement. Terry Bell, Carmichael Engineering Ltd. Moderator: Daniel Gardiman, Carmichael Engineering Ltd.

PL Series Premier Indoor Plenum Coils

INSTALLATION INSTRUCTIONS

1.1 This section applies to air handling units for HVAC Systems.

The Essentials Of Working With R-410A

General Service Bulletin

Refrigerant Valves/Accessories

Condensing Unit Installation and Operating Instructions

SECTION HYDRONIC PIPING AND SPECIALTIES

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

National Maritime Center

INSTALLATION INSTRUCTIONS

Installation and Operation Manual

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

University of Delaware

REFRIGERATION PRODUCTS

CAUTION. Check Equipment and Job Site. Clearance Requirements. Unpack Unit

Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel:

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

Condensing Unit Installation and Operating Instructions

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

Chapter-8 Capacity Control of Refrigeration Systems

Bulletin , March Electric Hot Gas Bypass Valves

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

Direct Fired Units w/ Packaged Cooling

D-8 OUTLINE SPECIFICATION FOR HTHW HEAT EXCHANGERS

SECTION METERS AND GAGES FOR PLUMBING PIPING

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE

NEW CHILLER SCHEDULE

PACKAGED AIR COOLED Product Data Catalog

Installation Instructions

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

R Series Cooling Modules

Division 23 - HVAC Switzerland Beallsville K-12. Section HYDRONIC PIPING SECTION HYDRONIC PIPING PART 1 - GENERAL

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Eclipse Technical Training CME686 CME810 CP686 CP886 CP1086

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

Condensing Unit and Refrigeration System Installation & Operations Manual R448A/R449A

SECTION HYDRONIC PIPING

Liebert CSU3000 Chiller

Entry Level Assessment Blueprint Heating, Ventilation and Air Conditioning (HVAC)

SECTION ROTARY-SCREW WATER CHILLERS

Air-Cooled Condenser. Installation Instructions. Revision Date: 12/21/98

THE PRODUCTS YOU NEED. THE QUALITY YOU WANT. THE INNOVATION YOU DESERVE.

NATURAL GAS PIPING

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

R E D I C O N T R O L S

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

R.A.S.E.R.S System. Installation Guide

NO: 9-16 DATE: 2/11/16 EMERSON CLIMATE TECHNOLOGIES WHOLESALERS -EXECUTIVES -PRODUCT MANAGERS -EMERSON TM TECHNICAL SPECIALISTS -BRANCH PERSONNEL

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

Installation Manual BCS2000/3000

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

Desiccants & Driers. By Norm Christopherson

REFRIGERANT PIPING INTRODUCTION

INSTALLATION INSTRUCTIONS TXV Coils EDM, EDD, EDA

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

Installation, Start-Up and Service Instructions

Air Cooled Condenser Installation and Operating Instructions

Transcription:

PART 1 - GENERAL 1.1 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.2 General requirements: A. Reciprocating or open drive chillers not allowed for outdoor applications. B. Signed and stamped final refrigeration system drawings must be received for review prior to equipment installation for all custom refrigeration applications. This applies to all systems designed for -20 F and lower other than factory fabricated chest freezers. Drawings must include capacities and sizing of specialty valves. C. All custom Ultra-Low (-20 F and colder) refrigeration systems must be designed as cascading systems. D. In order of desirability, from highest to lowest, (with the understanding that size precludes some styles of compressors/chillers), UAF Facilities Services prefers: 1. Scroll compressors - preferable; these are limited in available size to about 60 tons. 2. Screw compressors - acceptable above 60 tons. 3. Centrifugal chillers - acceptable above 60 tons. 4. Reciprocating compressors - discouraged, but may be considered above 60 tons. 5. Steam absorption chillers acceptable upon requirement by UAF Facilities Service, generally above 300 tons with adequate steam capacity E. Desired voltage for Ultra-Low (-20 F and below) chest freezers is 208V. F. Provide all Ultra-Low freezers with built-in set of Form-C (normally open - normally closed) contacts for remote alarming. 15600-1

G. Coordinate custom refrigeration system control system design with UAF Facilities Services. Control logic will incorporate Siemens Building Technologies PPCL proprietary control language. H. Provide for outdoor air-cooled condensing units: Cold weather, low-temp motors and crank case heaters in compressors. PART 2 - PRODUCTS 2.1 Chillers: A. Manufacturers: 1. Trane. 2. York. 3. McQuay 2.2 Pipe and tubing materials: A. Copper tubing: Type ACR, hard-drawn straight lengths, and soft-annealed coils, seamless copper tubing. Tubing shall be factory cleaned, nitrogen charged, ready for installation, and have sealed end caps to protect interior of pipe until installed. B. Copper tubing: Type L, hard-drawn straight lengths, and soft-annealed coils, seamless copper tubing. 2.3 Fittings: A. Wrought copper fittings: streamlined pattern. 2.4 Joining materials: A. Brazing filler metals: Class B Ag-1 (Silver). 2.5 Valves: A. Solenoid valves: 250 F. temperature rating, 400 psig working pressure; forged brass with Teflon valve seat. B. Evaporator pressure regulating valves: Pilot-operated, forged brass or cast bronze; complete with pilot operator, stainless steel bottom spring, pressure gauge tappings. C. Thermal expansion valves: Thermostatic adjustable, modulating type; size as required for specific evaporator requirements; factory set for proper evaporator superheat requirements. 15600-2

D. Hot gas bypass valve: Adjustable type, sized to provide capacity reduction beyond the last step of compressor unloading; wrought copper fittings for solder-end connections. 2.6 Refrigerant piping specialties: A. Strainers: 500 psig maximum working pressure; forged brass body with Monel 80-mesh screen and screwed cleanout plug. B. Moisture/liquid indicators: 500 psig maximum operating pressure, 200 F. maximum operating temperature. C. Filter-driers: 500 psig maximum operating pressure, steel shell, flange ring and spring. Furnish complete with replaceable filter-drier core kit, including gaskets, as follows: 1. Standard capacity desiccant sieves to provide micronic filtration. 2. High capacity desiccant sieves to provide micronic filtration and extra drying capacity. D. Suction line filter-drier: 350 psig maximum operating pressure, 225 F. maximum operating temperature. E. Suction line filters: 500 psig maximum operating pressure. Furnish complete with replaceable filter core kit including gaskets. F. Flanged unions: 400 psig maximum working pressure, 330 F. maximum operating temperature. Flanges and bolts shall have factory-applied rust-resistant coating. G. Flexible connectors: 500 psig maximum operating pressure, seamless tin bronze or stainless steel core, high tensile bronze braid synthetic covering. Stainless steel for all over 300 PSI. H. Hard braze all non-replaceable FD. 2.7 Refrigerant: A. AC system refrigerant R-22 (Ozone Depletion Potential (ODP) =0.034). B. AC system refrigerant R-410a (Environmentally friendly ODP = 0). PART 3 - EXECUTION 3.1 Installation, general: A. Refrigeration system acid neutralizing agents are not allowed. B. Where refrigeration equipment is shipped in broken down condition on skids and requires 15600-3

field erection of piping joints, contractor must submit manufacturer-approved assembly instruction with names of factory authorized assembly technicians performing the work. C. When equipment is placed at the construction site, the contractor must provide visual confirmation that the factory applied holding charge is still intact. D. Do not exceed or bypass manufacturer-designed and specified safety limits and equipment (pressure switches, oil safe switches, etc.). E. All refrigeration piping joints shall be nitrogen purged during brazing. Designated UAF Facilities Services personnel to witness process. F. No aftermarket alterations of factory fabricated freezer equipment. G. All refrigeration systems requiring field assembly and field charging of refrigerant system shall be pulled down by triple evacuation method and backpurged with dry nitrogen gas. Measure degree of vacuum with calibrated electronic meter. System specific evacuation requirements: 1. Air conditioning systems: a. Follow manufacturer's recommended evacuation and charging procedures. b. Triple pull-down of entire system to 1000, 500, and 200 microns respectively. c. Each pull-down held for 2 hours with no greater than 50 micron rise in any test. 2. Walk-in freezers down to -40 F: a. Triple pull-down of entire system to 600, 300, and 200 microns respectively. b. Each pull-down held for 1 hour with no greater than 50 micron rise in any test. c. Execute procedure using ¼" soft copper tubing, braided hoses not allowed. 3. Walk-in freezers below -40 F and all Ultra-Low chest freezers: 3.2 Piping installation: a. Triple pull-down of entire system to 400, 200, and 50 microns respectively. b. Each pull-down held for 1 hour with no greater than 50 micron rise in any test. c. Execute procedure using ¼" soft copper tubing, braided hoses not allowed. A. Insulate suction lines. 15600-4

B. Slope refrigerant piping: 1. Install horizontal hot gas discharge piping with 1/2" per 10 feet downward slope away from the compressor. 2. Install horizontal suction lines with 1/2" per 10 feet downward slope to the compressor, with no long traps or dead ends which may cause oil to separate from the suction gas and return to the compressor in damaging slugs. 3. Liquid lines may be installed level. 4. Reference manufacturers' standards. C. Install strainers immediately ahead of each expansion valve, solenoid valve, hot gas bypass valve, compressor suction valve, and as required to protect refrigerant piping system components. Install strainer upstream from TXV and in suction line upstream from compressor. D. Install moisture/liquid indicators in liquid lines between filter/driers and thermostatic expansion valves and in liquid line to receiver. 1. Install moisture/liquid indicators in lines larger than 2-1/8" OD, using a bypass line. E. Install unions to allow removal of solenoid valves, pressure regulating valves, expansion valves, and at connections to compressors and evaporators. No unions in main refrigerant piping. F. Install flexible connectors at the inlet and discharge connection of compressors. Purge with nitrogen at.2 CFH while brazing. 3.3 Pipe joint construction: A. Fill the pipe and fittings during brazing with an inert gas (i.e. nitrogen or carbon dioxide) to prevent formation of scale. 3.4 Valve installation: A. Install globe valves on each side of strainers and driers, in liquid and suction lines at evaporators. B. Install a full sized 3-way bypass around each drier. C. Install solenoid valves ahead of each expansion valve and hot-gas bypass valve. Install solenoid valves in horizontal lines with coil at the top. D. Thermostatic expansion valves may be mounted in any position, as close as possible to the evaporator. 15600-5

1. Where refrigerant distributors are used, mount the distributor directly on the expansion valve outlet. 2. Install the valve in such a location so that the diaphragm case is warmer than the bulb. 3. Secure the bulb to a clean, straight, horizontal section of the suction line using two bulb straps. Do not mount bulb in a trap or at the bottom of the line. 4. Where external equalizer lines are required, make the connection where it will clearly reflect the pressure existing in the suction line at the evaporator outlet. END OF SECTION 15600-6