ASENWARE EMERGENCY LIGHT SERIES 1 / 38 EMERGENCY LIGHT SERIES 1 About ASENWARE was set up at 2005 in UK. After over 10 years very fast developing, we keep the high investment for R&D and international certificates, now ASENWARE became a famous brand in Fire system. Our products include Fire Alarm and Fire suppression System, Emergency Light, CCTV cameras and DDC/HVAC system. For more information about us, please email:sales08@asenware.com 2 Emergency Light introduction Emergency Light is a vital and effective life safety tool, providing reassurance and guidance to people at critical times when they need escape quickly and safely from a building. The main reason for installing an emergency lighting system is to enable the building to meet fire safety legislation in a way that is visually acceptable and meets the user s needs for ease of operation and maintenance. Consequently it is important to establish all the relevant legal requirements for emergency lighting and fire alarm systems before commencing the design these should ideally be agreed between the system designer, user, fire authority, building control officer and system installer. 3 ASENWARE Emergency Light Series 3.1 AW-EL101: General Emergency Light,
ASENWARE EMERGENCY LIGHT SERIES 2 / 38 LED Lamp Emergency Light: Fluorescent T5 Emergency Light: The General Emergency Light is used for high profile commercial and industrial building, new design flow lined fire proof plastic shell and High transparent top cover, available with multi bar LED or fluorescent T5/8W tube,,available with 1h,1.5h,2h,3h duration time, available with self-test function, with battery protection,easy installation. 3.2 AW-EL200 Twin Spot Emergency Luminaires
ASENWARE EMERGENCY LIGHT SERIES 3 / 38 Normal Type: With Switch Type: With Switch and Exit Sign Type:
ASENWARE EMERGENCY LIGHT SERIES 4 / 38 The Twin Spot Emergency luminaires are designed for different country, with metal shell, LED light, nickel-cadmium or lead-acid battery, with battery protection, available with self-test function, available with single lamp control, available with exit direction control. 3.3 AW-EL300 Suspended LED Acrylic Exit Signs LED Acrylic Exit Sign on light 3.4 AW-EL400 Suspended Exit Sign Boards Emergency Exit Sign Board
ASENWARE EMERGENCY LIGHT SERIES 5 / 38 4 AW-EL101: General Emergency Light LED Lamp Emergency Light: Fluorescent T5 Emergency Light: 4.1 General technical parameters Item Supply work voltage range Operation mode Lamp Battery Battery protection Charging time Self-test Control mode Material Value 110V-127VAC 50/60Hz; Or 220V-240VAC 50/60Hz Non-maintained LED 16pcs/bar, 1/2/3/5 bar Or Fluorescent T5/8W tube 1/2/3 Nickel-cadmium Or Lead-acid Yes <24 hours Available Emergency only Or On/Off switch +Emergency Fire proof plastic
ASENWARE EMERGENCY LIGHT SERIES 6 / 38 Installation Wall mounted Protection level IP30 Product size 345x110x80mm Packing Carton Carton quantity 10 Carton size 460*380*280mm Carton weight Approx 13kg with 10pcs/carton Work temperature -10~55 Work humidity 95% Customization Light source, Battery, Duration Time, Package, Control mode Standards ISO9000 CE BS5266-7 IEC-60598-2-22 4.2 Pictures 4.2.1 LED Lamp Emergency Light Type Front side view Left side view Top view Back side view 4.2.2 Fluorescent Lamp Emergency Light Type
ASENWARE EMERGENCY LIGHT SERIES 7 / 38 Front side view Left side view Top view Back side view 4.3 Installation guide
ASENWARE EMERGENCY LIGHT SERIES 8 / 38 Step1: Open the emergency light cover Step 2: Follow the instruction to connect the battery and PCB board with wires Step 4: Install the emergency light on the wall Step 3: Tack four plastic studs on the ceiling Step 6: Finished Step 5: Cover the emergency light shell 4.4 Order information
ASENWARE EMERGENCY LIGHT SERIES 9 / 38 Model No. ON Self Duration Lamp Lamp Battery Battery / - Luminance time type qty type capacity OFF Test (min) AW-EL101LA16NC1AE No A Normal LED 16 60 NC 3.6V/0.15Ah AW-EL101LA16NC2AE No A Normal LED 16 90 NC 3.6V/0.2Ah AW-EL101LA16NC3AE No A Normal LED 16 120 NC 3.6V/0.3Ah AW-EL101LA16NC4AE No A Normal LED 16 180 NC 3.6V/0.4Ah AW-EL101LA32NC1AE No A Normal LED 32 60 NC 3.6V/0.2Ah AW-EL101LA32NC2AE No A Normal LED 32 90 NC 3.6V/0.3Ah AW-EL101LA32NC3AE No A Normal LED 32 120 NC 3.6V/0.4Ah AW-EL101LA32NC4AE No A Normal LED 32 180 NC 3.6V/0.6Ah AW-EL101LA48NC1AE No A Normal LED 48 60 NC 3.6V/0.3Ah AW-EL101LA48NC2AE No A Normal LED 48 90 NC 3.6V/0.4Ah AW-EL101LA48NC3AE No A Normal LED 48 120 NC 3.6V/0.6Ah AW-EL101LA48NC4AE No A Normal LED 48 180 NC 3.6V/0.8Ah AW-EL101LA80NC1AE No A Normal LED 80 60 NC 3.6V/0.5Ah AW-EL101LA80NC2AE No A Normal LED 80 90 NC 3.6V/0.7Ah AW-EL101LA80NC3AE No A Normal LED 80 120 NC 3.6V/0.9Ah AW-EL101LA80NC4AE No A Normal LED 80 180 NC 3.6V/1.3Ah AW-EL101LB16NC1AE No A Supper LED 16 60 NC 3.6V/0.3Ah AW-EL101LB16NC2AE No A Supper LED 16 90 NC 3.6V/0.5Ah AW-EL101LB16NC3AE No A Supper LED 16 120 NC 3.6V/0.6Ah AW-EL101LB16NC4AE No A Supper LED 16 180 NC 3.6V/0.7Ah AW-EL101LB32NC1AE No A Supper LED 32 60 NC 3.6V/0.5Ah AW-EL101LB32NC2AE No A Supper LED 32 90 NC 3.6V/0.7Ah AW-EL101LB32NC3AE No A Supper LED 32 120 NC 3.6V/0.9Ah AW-EL101LB32NC4AE No A Supper LED 32 180 NC 3.6V/1.2Ah AW-EL101LB48NC1AE No A Supper LED 48 60 NC 3.6V/0.7Ah AW-EL101LB48NC2AE No A Supper LED 48 90 NC 3.6V/0.9Ah AW-EL101LB48NC3AE No A Supper LED 48 120 NC 3.6V/1.2Ah AW-EL101LB48NC4AE No A Supper LED 48 180 NC 3.6V/1.8Ah AW-EL101LB80NC1AE No A Supper LED 80 60 NC 3.6V/1.0Ah AW-EL101LB80NC2AE No A Supper LED 80 90 NC 3.6V/1.5Ah AW-EL101LB80NC3AE No A Supper LED 80 120 NC 3.6V/1.8Ah AW-EL101LB80LC4AE No A Supper LED 80 180 NC 6.0V/2.8Ah AW-EL101LA16NC1ME No M Normal LED 16 60 NC 3.6V/0.15Ah AW-EL101LA16NC2ME No M Normal LED 16 90 NC 3.6V/0.2Ah AW-EL101LA16NC3ME No M Normal LED 16 120 NC 3.6V/0.3Ah AW-EL101LA16NC4ME No M Normal LED 16 180 NC 3.6V/0.4Ah AW-EL101LA32NC1ME No M Normal LED 32 60 NC 3.6V/0.2Ah AW-EL101LA32NC2ME No M Normal LED 32 90 NC 3.6V/0.3Ah AW-EL101LA32NC3ME No M Normal LED 32 120 NC 3.6V/0.4Ah
ASENWARE EMERGENCY LIGHT SERIES 10 / 38 AW-EL101LA32NC4ME No M Normal LED 32 180 NC 3.6V/0.6Ah AW-EL101LA48NC1ME No M Normal LED 48 60 NC 3.6V/0.3Ah AW-EL101LA48NC2ME No M Normal LED 48 90 NC 3.6V/0.4Ah AW-EL101LA48NC3ME No M Normal LED 48 120 NC 3.6V/0.6Ah AW-EL101LA48NC4ME No M Normal LED 48 180 NC 3.6V/0.8Ah AW-EL101LA80NC1ME No M Normal LED 80 60 NC 3.6V/0.5Ah AW-EL101LA80NC2ME No M Normal LED 80 90 NC 3.6V/0.7Ah AW-EL101LA80NC3ME No M Normal LED 80 120 NC 3.6V/0.9Ah AW-EL101LA80NC4ME No M Normal LED 80 180 NC 3.6V/1.3Ah AW-EL101LB16NC1ME No M Supper LED 16 60 NC 3.6V/0.3Ah AW-EL101LB16NC2ME No M Supper LED 16 90 NC 3.6V/0.5Ah AW-EL101LB16NC3ME No M Supper LED 16 120 NC 3.6V/0.6Ah AW-EL101LB16NC4ME No M Supper LED 16 180 NC 3.6V/0.7Ah AW-EL101LB32NC1ME No M Supper LED 32 60 NC 3.6V/0.5Ah AW-EL101LB32NC2ME No M Supper LED 32 90 NC 3.6V/0.7Ah AW-EL101LB32NC3ME No M Supper LED 32 120 NC 3.6V/0.9Ah AW-EL101LB32NC4ME No M Supper LED 32 180 NC 3.6V/1.2Ah AW-EL101LB48NC1ME No M Supper LED 48 60 NC 3.6V/0.7Ah AW-EL101LB48NC2ME No M Supper LED 48 90 NC 3.6V/0.9Ah AW-EL101LB48NC3ME No M Supper LED 48 120 NC 3.6V/1.2Ah AW-EL101LB48NC4ME No M Supper LED 48 180 NC 3.6V/1.8Ah AW-EL101LB80NC1ME No M Supper LED 80 60 NC 3.6V/1.0Ah AW-EL101LB80NC2ME No M Supper LED 80 90 NC 3.6V/1.5Ah AW-EL101LB80NC3ME No M Supper LED 80 120 NC 3.6V/1.8Ah AW-EL101LB80LC4ME No M Supper LED 80 180 LC 6.0V/2.8Ah AW-EL101TA01NC1AE No A Normal FL T5 1 60 NC 3.6V/0.8Ah AW-EL101TA01NC2AE No A Normal FL T5 1 90 NC 3.6V/1.1Ah AW-EL101TA01NC3AE No A Normal FL T5 1 120 NC 3.6V/1.5Ah AW-EL101TA01NC4AE No A Normal FL T5 1 180 NC 3.6V/2.0Ah AW-EL101TA02NC1AE No A Normal FL T5 2 60 LC 6.0V/1.0Ah AW-EL101TA02LC2AE No A Normal FL T5 2 90 LC 6.0V/1.5Ah AW-EL101TA02LC3AE No A Normal FL T5 2 120 LC 6.0V/2.0Ah AW-EL101TA02LC4AE No A Normal FL T5 2 180 LC 6.0V/3.0Ah AW-EL101TA03LC1AE No A Normal FL T5 3 60 LC 6.0V/1.5Ah AW-EL101TA03LC2AE No A Normal FL T5 3 90 LC 6.0V/2.2Ah AW-EL101TA03LC3AE No A Normal FL T5 3 120 LC 6.0V/3.0Ah AW-EL101TA03LC4AE No A Normal FL T5 3 180 LC 6.0V/4.5Ah AW-EL101LA16NC1AO Yes A Normal LED 16 60 NC 3.6V/0.15Ah AW-EL101LA16NC2AO Yes A Normal LED 16 90 NC 3.6V/0.2Ah AW-EL101LA16NC3AO Yes A Normal LED 16 120 NC 3.6V/0.3Ah AW-EL101LA16NC4AO Yes A Normal LED 16 180 NC 3.6V/0.4Ah
ASENWARE EMERGENCY LIGHT SERIES 11 / 38 AW-EL101LA32NC1AO Yes A Normal LED 32 60 NC 3.6V/0.2Ah AW-EL101LA32NC2AO Yes A Normal LED 32 90 NC 3.6V/0.3Ah AW-EL101LA32NC3AO Yes A Normal LED 32 120 NC 3.6V/0.4Ah AW-EL101LA32NC4AO Yes A Normal LED 32 180 NC 3.6V/0.6Ah AW-EL101LA48NC1AO Yes A Normal LED 48 60 NC 3.6V/0.3Ah AW-EL101LA48NC2AO Yes A Normal LED 48 90 NC 3.6V/0.4Ah AW-EL101LA48NC3AO Yes A Normal LED 48 120 NC 3.6V/0.6Ah AW-EL101LA48NC4AO Yes A Normal LED 48 180 NC 3.6V/0.8Ah AW-EL101LA80NC1AO Yes A Normal LED 80 60 NC 3.6V/0.5Ah AW-EL101LA80NC2AO Yes A Normal LED 80 90 NC 3.6V/0.7Ah AW-EL101LA80NC3AO Yes A Normal LED 80 120 NC 3.6V/0.9Ah AW-EL101LA80NC4AO Yes A Normal LED 80 180 NC 3.6V/1.3Ah AW-EL101LB16NC1AO Yes A Supper LED 16 60 NC 3.6V/0.3Ah AW-EL101LB16NC2AO Yes A Supper LED 16 90 NC 3.6V/0.5Ah AW-EL101LB16NC3AO Yes A Supper LED 16 120 NC 3.6V/0.6Ah AW-EL101LB16NC4AO Yes A Supper LED 16 180 NC 3.6V/0.7Ah AW-EL101LB32NC1AO Yes A Supper LED 32 60 NC 3.6V/0.5Ah AW-EL101LB32NC2AO Yes A Supper LED 32 90 NC 3.6V/0.7Ah AW-EL101LB32NC3AO Yes A Supper LED 32 120 NC 3.6V/0.9Ah AW-EL101LB32NC4AO Yes A Supper LED 32 180 NC 3.6V/1.2Ah AW-EL101LB48NC1AO Yes A Supper LED 48 60 NC 3.6V/0.7Ah AW-EL101LB48NC2AO Yes A Supper LED 48 90 NC 3.6V/0.9Ah AW-EL101LB48NC3AO Yes A Supper LED 48 120 NC 3.6V/1.2Ah AW-EL101LB48NC4AO Yes A Supper LED 48 180 NC 3.6V/1.8Ah AW-EL101LB80NC1AO Yes A Supper LED 80 60 NC 3.6V/1.0Ah AW-EL101LB80NC2AO Yes A Supper LED 80 90 NC 3.6V/1.5Ah AW-EL101LB80NC3AO Yes A Supper LED 80 120 NC 3.6V/1.8Ah AW-EL101LB80LC4AO Yes A Supper LED 80 180 LC 6.0V/2.8Ah AW-EL101LA16NC1MO Yes M Normal LED 16 60 NC 3.6V/0.15Ah AW-EL101LA16NC2MO Yes M Normal LED 16 90 NC 3.6V/0.2Ah AW-EL101LA16NC3MO Yes M Normal LED 16 120 NC 3.6V/0.3Ah AW-EL101LA16NC4MO Yes M Normal LED 16 180 NC 3.6V/0.4Ah AW-EL101LA32NC1MO Yes M Normal LED 32 60 NC 3.6V/0.2Ah AW-EL101LA32NC2MO Yes M Normal LED 32 90 NC 3.6V/0.3Ah AW-EL101LA32NC3MO Yes M Normal LED 32 120 NC 3.6V/0.4Ah AW-EL101LA32NC4MO Yes M Normal LED 32 180 NC 3.6V/0.6Ah AW-EL101LA48NC1MO Yes M Normal LED 48 60 NC 3.6V/0.3Ah AW-EL101LA48NC2MO Yes M Normal LED 48 90 NC 3.6V/0.4Ah AW-EL101LA48NC3MO Yes M Normal LED 48 120 NC 3.6V/0.6Ah AW-EL101LA48NC4MO Yes M Normal LED 48 180 NC 3.6V/0.8Ah AW-EL101LA80NC1MO Yes M Normal LED 80 60 NC 3.6V/0.5Ah AW-EL101LA80NC2MO Yes M Normal LED 80 90 NC 3.6V/0.7Ah
ASENWARE EMERGENCY LIGHT SERIES 12 / 38 AW-EL101LA80NC3MO Yes M Normal LED 80 120 NC 3.6V/0.9Ah AW-EL101LA80NC4MO Yes M Normal LED 80 180 NC 3.6V/1.3Ah AW-EL101LB16NC1MO Yes M Supper LED 16 60 NC 3.6V/0.3Ah AW-EL101LB16NC2MO Yes M Supper LED 16 90 NC 3.6V/0.5Ah AW-EL101LB16NC3MO Yes M Supper LED 16 120 NC 3.6V/0.6Ah AW-EL101LB16NC4MO Yes M Supper LED 16 180 NC 3.6V/0.7Ah AW-EL101LB32NC1MO Yes M Supper LED 32 60 NC 3.6V/0.5Ah AW-EL101LB32NC2MO Yes M Supper LED 32 90 NC 3.6V/0.7Ah AW-EL101LB32NC3MO Yes M Supper LED 32 120 NC 3.6V/0.9Ah AW-EL101LB32NC4MO Yes M Supper LED 32 180 NC 3.6V/1.2Ah AW-EL101LB48NC1MO Yes M Supper LED 48 60 NC 3.6V/0.7Ah AW-EL101LB48NC2MO Yes M Supper LED 48 90 NC 3.6V/0.9Ah AW-EL101LB48NC3MO Yes M Supper LED 48 120 NC 3.6V/1.2Ah AW-EL101LB48NC4MO Yes M Supper LED 48 180 NC 3.6V/1.8Ah AW-EL101LB80NC1MO Yes M Supper LED 80 60 NC 3.6V/1.0Ah AW-EL101LB80NC2MO Yes M Supper LED 80 90 NC 3.6V/1.5Ah AW-EL101LB80NC3MO Yes M Supper LED 80 120 NC 3.6V/1.8Ah AW-EL101LB80LC4MO Yes M Supper LED 80 180 LC 6.0V/2.8Ah AW-EL101TA01NC1AO Yes A Normal FL T5 1 60 NC 3.6V/0.8Ah AW-EL101TA01NC2AO Yes A Normal FL T5 1 90 NC 3.6V/1.1Ah AW-EL101TA01NC3AO Yes A Normal FL T5 1 120 NC 3.6V/1.5Ah AW-EL101TA01NC4AO Yes A Normal FL T5 1 180 NC 3.6V/2.0Ah AW-EL101TA02NC1AO Yes A Normal FL T5 2 60 LC 6.0V/1.0Ah AW-EL101TA02LC2AO Yes A Normal FL T5 2 90 LC 6.0V/1.5Ah AW-EL101TA02LC3AO Yes A Normal FL T5 2 120 LC 6.0V/2.0Ah AW-EL101TA02LC4AO Yes A Normal FL T5 2 180 LC 6.0V/3.0Ah AW-EL101TA03LC1AO Yes A Normal FL T5 3 60 LC 6.0V/1.5Ah AW-EL101TA03LC2AO Yes A Normal FL T5 3 90 LC 6.0V/2.2Ah AW-EL101TA03LC3AO Yes A Normal FL T5 3 120 LC 6.0V/3.0Ah AW-EL101TA03LC4AO Yes A Normal FL T5 3 180 LC 6.0V/4.5Ah 4.5 Note 4.5.1 Self-test: A=Disable, M=Enable 4.5.2 Lamp type: LED=2835LED, FL T5= Fluorescent T5/8W tube 4.5.3 Battery type: NC=Nickel-cadmium, LC=Lead acid 4.5.4 Supply Default Model No. is AW-EL101LA48NC4AE, 48pcs LED, 180min duration time, 220VAC. 4.5.5 Different signs of exit adhesive sticker:
ASENWARE EMERGENCY LIGHT SERIES 13 / 38 The surface exit indicator sticker is optional. 5 AW-EL200 Twin Spot Emergency Luminaires 5.1 AW-EL201
ASENWARE EMERGENCY LIGHT SERIES 14 / 38 AW-EL200 is an economic Twin Spot Emergency Luminaires 5.1.1 General technical parameters Item Value Supply work voltage range 110V-127VAC 50/60Hz; Or 220V-240VAC 50/60Hz Operation mode Non-maintained Lamp LED 1pcs/ spot Twin spot Battery Nickel-cadmium Or Lead-acid Battery protection Yes Charging time <24 hours Self-test Available Control mode Emergency only Or On/Off switch +Emergency Material Metal Installation Wall mounted Protection level IP30 Product size 280mm*65mm*265mm Packing Carton Carton quantity 10 Carton size 575mm*355mm*275mm Carton weight Approx 8.5kg with 10pcs/carton
ASENWARE EMERGENCY LIGHT SERIES 15 / 38 Work temperature -10~55 Work humidity 95% Customization Light source, Battery, Duration Time, Package, Control mode ISO9000 Standards CE BS5266-7 IEC-60598-2-22 5.1.2 Pictures Front side view Left side view Right side view Back side view
ASENWARE EMERGENCY LIGHT SERIES 16 / 38 5.1.3 Installation guide
ASENWARE EMERGENCY LIGHT SERIES 17 / 38 Step1: Prepare 2 sets expansion screw PA3.5*15mm. Step2: Drill 2 holes apart of 211mm on the suitable place of the wall, then insert 2 sets plastic bar of the expansion screws. 211mm A B B Step4: Put the emergency light on the 2 screws, via the 2 slotted holes of the back side. Step3: Install the 2 screws into the plastic bars, but keep the head of the screw over about 3-5mm of the wall. Step5: After the installation, plug into the power socket. Then the emergency light can work normally. 5.1.4 Order information Model No. ON/ OFF Self - Test Luminance Lamp type Lamp qty Duration Time (min) Battery type Battery capacity
ASENWARE EMERGENCY LIGHT SERIES 18 / 38 AW- EL201LA02NC1AE No A Normal LED 2 60 NC 1.2V/0.3Ah AW- EL201LA02NC2AE No A Normal LED 2 90 NC 1.2V/0.45Ah AW- EL201LA02NC3AE No A Normal LED 2 120 NC 1.2V/0.6Ah AW- EL201LA02NC4AE No A Normal LED 2 180 NC 1.2V/0.8Ah AW- EL201LA02NC1ME No M Normal LED 2 60 NC 1.2V/0.6Ah AW- EL201LA02NC2ME No M Normal LED 2 90 NC 1.2V/0.8Ah AW- EL201LA02NC3ME No M Normal LED 2 120 NC 1.2V/1.2Ah AW- EL201LA02NC4ME No M Normal LED 2 180 NC 1.2V/1.6Ah 5.1.5 Note 5.1.5.1 Self-test: A=Disable, M=Enable 5.1.5.2 Lamp type: LED=2835LED, FL T5= Fluorescent T5/8W tube 5.1.5.3 Battery type: NC=Nickel-cadmium, LC=Lead acid 5.1.5.4 Supply Default Model No. is AW-EL201LA02NC4AE, 2pcs LED, 180min duration time,220vac. 5.2 AW-EL202
ASENWARE EMERGENCY LIGHT SERIES 19 / 38 Twin Spot Emergency Luminaires with switch AW-EL202 is a Twin Spot emergency luminaires with 2 switches, each lamp spot can be switched ON/OFF. Each lamp has 6 LEDs to supply high luminance. 5.2.1 General technical parameters Item Supply work voltage range Operation mode Lamp Lamp control Battery Battery protection Charging time Self-test Control mode Material Installation Protection level Product size Value 110V-127VAC 50/60Hz; Or 220V-240VAC 50/60Hz Non-maintained LED 6pcs/ spot Twin spot Left switch+ right switch Nickel-cadmium Or Lead-acid Yes <24 hours Available Emergency only Or On/Off switch +Emergency Metal Wall mounted IP30 295mm*105mm*295mm
ASENWARE EMERGENCY LIGHT SERIES 20 / 38 Packing Carton Carton quantity 10 Carton size 595mm*530mm*300mm Carton weight Approx 16kg with 10pcs/carton Work temperature -10~55 Work humidity 95% Customization Light source, Battery, Duration Time, Package, Control mode ISO9000 Standards CE BS5266-7 IEC-60598-2-22 5.2.2 Pictures Front side view Left side view Right side view Back side view
ASENWARE EMERGENCY LIGHT SERIES 21 / 38 5.2.3 Installation guide Step1: Prepare 2 sets expansion screw PA3.5*15mm. Step2: Drill 2 holes apart of 195mm on the suitable place of the wall, then insert the 2 sets plastic bar of the expansion screws. A B Step4: Put the emergency light on the 2 screws, via the 2 slotted holes of the back side. Step3: Install the 2 screws into the plastic bars, but keep the head of the screw over about 3-5mm of the wall. Step5: After the installation, plug into the power socket. Then the emergency light can work normally.
ASENWARE EMERGENCY LIGHT SERIES 22 / 38 5.2.4 Order information Model No. ON/ OFF Self - Test Luminance Lamp type Lamp qty Duration Time (min) Battery type Battery capacity AW- EL202LA12NC1AE Yes M Normal LED 12 60 LC 6.0V/0.4Ah AW- EL202LA12NC2AE Yes M Normal LED 12 90 LC 6.0V/0.6Ah AW- EL202LA12NC3AE Yes M Normal LED 12 120 LC 6.0V/0.8Ah AW- EL202LA12NC4AE Yes M Normal LED 12 180 LC 6.0V/1.2Ah Note: Self-test: A=Disable, M=Enable Lamp type: LED=2835LED, FL T5= Fluorescent T5/8W tube Battery type: NC=Nickel-cadmium, LC=Lead acid Supply Default Model No. is AW-EL202LA12NC4AE, 12pcs LED, 180min duration time,220vac. Other model No. are customized. 5.3 AW-EL203
ASENWARE EMERGENCY LIGHT SERIES 23 / 38 AW-EL203 is a Twin Spot emergency luminaires with 4 switches, each lamp spot can be switched ON/OFF, Each lamp has 6 LEDs to supply high luminance. And there are 2 EXIT indicators: left side and right side, each indication has a LED and can be switched ON/OFF. 5.3.1 General technical parameters Item Supply work voltage range Operation mode Lamp Lamp control Exit direction indicator control Battery Battery protection Charging time Self-test Control mode Material Installation Protection level Product size Value 110V-127VAC 50/60Hz; Or 220V-240VAC 50/60Hz Non-maintained LED 6pcs/ spot Twin spot Left switch+ right switch Left switch+ right switch Nickel-cadmium Or Lead-acid Yes <24 hours Available Emergency only Or On/Off switch +Emergency Metal Wall mounted IP30 295mm*105mm*295mm
ASENWARE EMERGENCY LIGHT SERIES 24 / 38 Packing Carton Carton quantity 10 Carton size 595mm*530mm*300mm Carton weight Approx 16kg with 10pcs/carton Work temperature -10~55 Work humidity 95% Customization Light source, Battery, Duration Time, Package, Control mode ISO9000 Standards CE BS5266-7 IEC-60598-2-22 5.3.2 Pictures Front side view
ASENWARE EMERGENCY LIGHT SERIES 25 / 38 Left side view Right side view Back side view 5.3.3 Installation guide Step1: Prepare 2 sets expansion screw PA3.5*15mm Step2: Drill 2 holes apart of 195mm on the suitable place of the wall, then insert the 2 sets plastic bar of the expansion screws. Step4: Put the emergency light on the 2 screws, via the 2 slotted holes of the back side. Step3: Install the 2 screws into the plastic bars, but keep the head of the screw over about 3-5mm of the wall.
ASENWARE EMERGENCY LIGHT SERIES 26 / 38 6 AW-EL300 Suspended LED Acrylic Exit Signs AW-EL300 is suspended installation type with 6-8 LED light and transparent acrylic board. It is easy to be carved to different design, to be suitable different country language, different exit direction, even different photo like coffee, toilet, casher and so on. It is nice looking, always used in office building, shopping mall, coffee shop, restaurant, hotel, hospital and so on. 6.1.1 General technical parameters Item Supply work voltage range Operation mode Lamp Value 110V-127VAC 50/60Hz; Or 220V-240VAC 50/60Hz Non-maintained LED 6pcs
ASENWARE EMERGENCY LIGHT SERIES 27 / 38 Sight distance 20m Material Aluminum+Transparent acrylic board Exit direction made Carved Battery Nickel-cadmium Battery protection Yes Charging time <24 hours Duration time 180 minutes Work mode Constant light Installation Suspended Protection level IP30 Product size 340*180*25mm Packing Carton Carton quantity 10 Carton size 380*205*270mm Carton weight Approx 14kg with 10pcs/carton Work temperature -10~55 Work humidity 95% Customization Different design ISO9000 Standards CE BS5266-7 IEC-60598-2-22 6.1.2 Available designs
ASENWARE EMERGENCY LIGHT SERIES 28 / 38 If big quantity, the sign can be customization. 6.2 AW-EL400 Suspended Exit Sign Boards AW-EL400 is an economic and conventional EXIT sign board, can be made different design according to the different country s fire standard. 6.2.1 General technical parameters Item Value Supply work voltage range 110V-127VAC 50/60Hz; Or 220V-240VAC 50/60Hz Operation mode Non-maintained Lamp LED 4pcs Sight distance 20m Material Aluminum + glass Exit direction made Screen print Battery Nickel-cadmium Battery protection Yes Charging time <24 hours Duration time 120 minutes Work mode Constant light Installation Suspended Protection level IP30 Product size 360*145*25mm Packing Carton Carton quantity 10 Carton size 375*160*270mm Carton weight Approx 10kg with 10pcs/carton Work temperature -10~55 Work humidity 95%
ASENWARE EMERGENCY LIGHT SERIES 29 / 38 Customization Standards Different design ISO9000 CE BS5266-7 IEC-60598-2-22 6.2.2 Available designs (If big quantity, the sign can be customization.) 7 Locate luminaires at mandatory points of emphasis Initial design is conducted by situating luminaires to reveal specific hazards and highlight safety equipment and signs, in addition to providing illumination to assist safe travel along the escape route. This should be performed regardless of whether it is an emergency escape route or an open (anti-panic) area.
ASENWARE EMERGENCY LIGHT SERIES 30 / 38
ASENWARE EMERGENCY LIGHT SERIES 31 / 38 Note - the term near means within 2 meters measured horizontally. 8 Ensure that exit signs are of correct format and size Signs which are provided at all exits intended to be used in an emergency and along escape routes shall be illuminated to indicate the route of escape to a point of safety. Where direct sight of an emergency exit is not possible, an illuminated directional sign (or series of signs) shall be provided to assist progression towards the emergency exit. Maximum viewing distances
ASENWARE EMERGENCY LIGHT SERIES 32 / 38 9 Illumination requirements The sign must conform to the colours of ISO 3864, which defines that exit and first aid signs must be white with green as the contrast colour. The ratio of luminance of the white colour to the green colour must be between 5:1 and 15:1. The minimum luminance of any 10mm patch area on the sign must be greater than 2cd/m 2 and the ratio of maximum to minimum luminance shall be less than 10:1 for either colour.
ASENWARE EMERGENCY LIGHT SERIES 33 / 38 10 Locate luminaires at the following essential areas in the buildings a) Lift cars - although only in exceptional circumstances will they be part of the escape route, do present a problem in the public may be trapped in them in the event Of a supply failure. b) Toilets - all toilets for the disabled and facilities exceeding 8m 2 floor area or without borrowed lights. c) Escalators - to enable users to get off them safely.
ASENWARE EMERGENCY LIGHT SERIES 34 / 38 e) Covered car parks - the normal pedestrian routes should be provided with non-maintained luminaires of at least 1 hour duration. d) Motor generator, control or panel room - require battery supplied emergency lighting to assist any maintenance or operating personnel in the event of failure.
ASENWARE EMERGENCY LIGHT SERIES 35 / 38 11 Escape route lighting it is essential to provide any additional luminaires to ensure that minimum illuminance levels are met to enable the routes to be used safely. In addition, every compartment on the escape route must have at least two luminaries, to provide some light in the event of luminaires failure. A uniformity ratio of 40:1 maximum to minimum must not be exceeded. This illuminance must be provided must be provided for the full duration and life of the system. 50% of the illuminance must be available within 5 seconds and the full value within 60 seconds of supply failure. Add additional luminaire to achieve 1 lux minimum. 12 Open (anti-panic) core areas Areas larger than 60m 2, open areas with an escape route passing through them, or hazards identified by the building risk assessment all require emergency lighting. The
ASENWARE EMERGENCY LIGHT SERIES 36 / 38 current standard is easy to design for and to verify, promoting systems that provide good uniformity rather than ones that use a few large output luminaires. 13 High risk task area lighting Areas of high physical risk, or the control rooms of dangerous plant and production lines, need emergency lighting to enable them to be shut down safely. BS5266 Part 1: 1999 defines that emergency lighting should provide 10% of the normal lighting level at the hazard, with a minimum of 15 Lux. (In practice this minimum is unlikely ever to be a problem, as it would only be valid if the risk area had a normal illumination level less than 150 lux).
ASENWARE EMERGENCY LIGHT SERIES 37 / 38 14 Control Non-maintained luminaires must be activated by failure of supply to the normal lighting. They must therefore be connected an unswitched live taken from the local normal lighting final circuit. 15 Testing and log book Discussions with the user or system designer should identify: - The caliber and reliability of staff available to do the testing - The level of difficulty in performing the test - If discharge tests need to be done outside normal working hours, or phased so only alternate luminaires are tested in buildings that are permanently occupied.
ASENWARE EMERGENCY LIGHT SERIES 38 / 38 The testing requirements in the code of practice are: Function test All emergency luminaires should be tested be breaking the supply to them and checking that they operate satisfactorily. The supply must then be restored and the charging indicators must be seen to be operating correctly. This test must be performed at least once once per month and the results logged. Discharge test The luminaires must be tested for their full rated duration period and checked for satisfactory operation. The supply must then be restored and the charging indicators rechecked. This test must be performed at least annually and the results logged. 16 Manual testing If manual testing is utilized, the following points should be considered: - Is a single switch to be used? Unless the whole building is to be switched off, a separate switch should be used for each final circuit. As the feed to non-maintained circuits must be taken from the switch this will probably mean that the building will have to be walked around twice, once to check the luminaires and once to check that they are recharging. - Are luminaires to be individually switched? In practice, only a single walk around the building will be needed. However, the test switches could spoil the decor of the building and they must be of a type that is tamper proof. After the tests, the performance of the luminaires must be logged. ************************************************************************************************ Thanks for reading ASENWAER Emergency Light Series Catalog and User Manual, we supply the perfect quality products and lower price, and we supply 7*24 online technology support for before and after sales, each product has 2 years warranty, and if the problem is because of our product quality, we supply free replacement. Hope to cooperate with you!.