Infrared Ceiling Mount Sensor LOS-CI Series LOS-CI- 0.0.06 The LOS-CI Series ceiling-mount passive infrared sensors can integrate into Lutron systems or function as standalone controls using a Lutron power pack. The sensor uses a small semiconductor heat detector that resides behind a multi-zone optical lens. The sensor s detector is sensitive to the heat emitted by the human body. In order to trigger the sensor, the source of heat must move from one range of detection to another. Non-moving hot objects will not cause the lights to turn on. Features Intelligent, continually adapting passive infrared (PI) sensor Passive infrared sensing eliable motion detection with high error immunity Snap-locks to ceiling-mounted cover plate Non-Volatile Memory: settings saved in protected memory are not lost during power outages 50 to,500 sq.ft. coverage mounted on 8 ft. ceiling Affords choice of turning lights off or dimming to a preset level in the unoccupied state when integrated with a Lutron system. Models Available Cat. No. Color Coverage (sq.ft.) Field of View LOS-CI-50-WH White 50 60 LOS-CI-500-WH White,500 60 Self-Adaptive Feature The LOS-CI Series ceiling-mount occupant sensors provides reliable detection with high error immunity. The internal microprocessor analyzes the information from the PI technology and determines the optimum setting to use in order to properly cover the space.
Specifications LOS-CI Series LOS-CI- 0.0.06 Timer Adjustment Automatic mode: Continually adapting sensor automatically adjusts settings to the space Manual mode: 8 to minutes Test mode: 8 seconds LED Lamp ed: infrared motion detected Housing ugged, high-impact, injection-molded plastic Color-coded leads 6 (6.cm) Operating voltage: 0- V, Class (PELV) low-voltage Operating current: ma nominal Control output: 0- V active high logic control signal with short-circuit protection, open collector when unoccupied UL and CUL listed Operating Environment Temperature: F to 0 F (0 C to 0 C) elative humidity: less than 95%, non-condensing For indoor use only Dimensions. (8).5 () Measurements are in inches (mm) Front View Side View
Wiring Single Sensor to System LOS-CI Series or More Sensors to System LOS-CI- 0.0.06 control system ed (+0- V ) (common) control system ed (+0- V ) (common) To additional sensors, maximum determined by lighting controller to Sensors with Pack 0/77/7 V 60 Hz; 0 V 50/60 Hz Hot Neutral ed (+0- V ) (common) Pack White ed ed Manual switch off (optional) Load Note: Maximum occupant sensors. Switching Multiple Loads with Auxiliary Packs Hot 0/77/ 7 V 60 Hz; Neutral 0 V 50/60 Hz Manual switch off (optional) Load ed ed Auxiliary Pack Note: Maximum of devices total (occupant sensors and auxiliary power packs) can be connected to a power pack. ed (+0- V ) (common) Pack White ed ed Load
LOS-CI Series LOS-CI- 0.0.06 Installation Sensor Placement The occupant sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets, shelves, indirect hanging fixtures, etc. Keep the occupant sensor away from air flow from ventilation outlets, windows, fans, etc. Closely follow the diagrams shown concerning major and minor motion coverage. The sensor can detect major motion (such as a person taking a half-step) at a greater distance than it can detect minor motion (such as writing or typing at a desk). May not detect occupancy with no significant difference between ambient and body temperatures. ange Diagrams 6.5 (.9) (.7) (.7) LOS-CI-50 (6.7) LOS-CI-500 Major motion detection Minor motion detection Dimensions are in feet (m).
Installation LOS-CI Series LOS-CI-5 0.0.06 Mounting Normal Mounting Twist and lock threaded mounting post onto cover plate. Drill through ceiling tile with assembly, using cutter end of the threaded mounting post. Secure with washer and nut. Mounting to Non-Standard Ceiling or Fixture Mount twist-lock cover plate using mounting screws, nuts, and washers (included). Drill/punch wire routing hole through ceiling tile at center of cover plate. /6 () Cutter end Wire Lengths (feet) # Sensors # Aux. PPs 0 0 0 AWG 750 75 50 75 50 50 0 AWG 00 600 00 600 00 00 8 AWG 00 00 800 00 800 800.5 (.).5 (6) Mounting Plate Dimensions. (06.6) Measurements are in inches (mm) Using the Infrared Mask Typical Mask Patterns Conference oom Mask 80 Mask Full Mask Center Ceiling Mount (Mask blocks sensor seeing out doorway into hall) Corner Ceiling Mount (No mask needed) ectangular Areas Over the Door Specific Areas You Wish to Mask
LOS-CI Series LOS-CI-6 0.0.06 Sensor Adjustments Override Settings Auto/Manual Threshold LED Motion Indicator eset Learned Settings A Off (Default) Automatic (Normal) Auto Threshold Adjustment Lights indicate motion etain Settings (Normal) On Manual on/off (Override) High Sensitivity (Low turn-on threshold) Disable LED Indicator Erase all learned settings, estart Learning (Toggle On) Strong Airflow Compensation Over Doorway Installation Timer Adjust Auto Sensitivity B Off On Disable Compensation (Normal) Enable Compensation No (Normal) Yes (Use increased turn-on threshold) Adjust Timer Automatically Use Manual Setting (No adjustment) Adjust Sensitivity Automatically Adjust Sensitivity Manually Timer Test Mode Factory Settings. emove the retainer cover.. otate the black timer adjustment knob to about midway ( o clock).. eturn setting to minimum setting (full CCW). ed: Infrared sensitivity 75% default : Timer 8 min. A B Factory Settings o clock Full CCW Note: The timer will remain in the 8-second test mode for hour, then automatically reset to 8 minutes.. To manually take the timer out of the 8-second test mode, turn the timer adjustment approximately /6 clockwise to make the setting slightly above minimum (just above the 8-minute setting).