Model DDX Deluge Valve

Similar documents
Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance

Sprinkler Guards Model C Model D

Model F3 Dry Sprinklers

Model F1 LO K 8.0 (115 metric) Standard Response Sprinklers

Model G5-56 Dry (SIN RA5114) K5.6 (80 metric) Concealed Dry Pendent Sprinkler

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Model F1 Residential Sprinklers for Design Density of.10 gpm/ft 2

TECHNICAL DATA. model c-2

TECHNICAL DATA OBSOLETE

Model F1FR Series Quick Response Standard Spray

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Additional Bulletins applicable to all F1RES LL Sprinklers Wall Wetting - Bulletin 007 Design and Installation - Bulletin 140

Model F3-80 Dry K8.0 (115 metric) Standard-Response, Standard Spray Sprinklers

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

TotalPac X Single interlock SUREFIRE system

TOTALPAC2 Integrated Fire Protection System

TotalPac 3 Firecyle III Deluge Remote controlled system

TECHNICAL DATA OBSOLETE

Sprinkler Guards and Water Shields Model C Model D Model E

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

TotalPac X Firecycle III Preaction Double interlock system

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA. 319a. January 27, 2012

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

Residential Sprinkler For Sloped Ceilings

BERMAD Fire Protection

Deluge & Preac tion Systems

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

quick response Sprinkler 105a October 25, 2010

TECHNICAL DATA. Wet 26a. February 22, 2009

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

standard response elo upright sprinkler

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

standard response dry horizontal sidewall sprinklers

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

Standard response. elo sprinklers

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

(Alarm Valve) & ' ( ()& * +,, & +-,. /0-

standard response Fusible Link Upright sprinkler VK204 (K8.0)

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

TECHNICAL DATA. Viking Technical Data may be found on. The Viking Corporation s Web site at.

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

STANDARD RESPONSE DRY PENDENT ELO SPRINKLERS TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

OPEN SPRINKLER SYSTEM

Standard Spray concealed horizontal sidewall sprinkler VK481

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

Discontinued Product

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

micromatic standard response Upright sprinkler VK100 (K5.6)

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

Page 1 of 7. Form No. F_ Rev Replaces Form No. F_ Rev 17.1 (added 205deg version)

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

Nitin Ventures FZE. (A Division of Nitin Fire Protection Industries Ltd.)

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

Worldwide Contacts.

standard response large orifice dry

micromatic standard response stainless steel sprinklers

standard response/ quick response extended coverage

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

Microfast quick response Fusible element hsw sprinkler

TECHNICAL DATA OBSOLETE

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

Series 759 FireLock Alarm Check Valve

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

mirage standard response concealed pendent sprinkler vk492 (K5.6)

freedom residential flush pendent sprinkler vk476 (K4.9)

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

FREEDOM RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER VK480 TECHNICAL DATA

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

TECHNICAL DATA OBSOLETE

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

TECHNICAL DATA. Page 1 of 6

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

TECHNICAL DATA. Page 1 of 5

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

Transcription:

Model DDX Deluge Valve Bulletin 510 Bulletin 510 Features 1. Differential type, simple, lightweight, dependable construction. 2. Simply and easily trimmed for releasing by: Manual pull stations Wet pilot sprinklers Dry pilot actuators Solenoid valves 3. Drop in seat & clapper assembly simplifies maintenance. 4. Bronze seat with O ring seals resists corrosion and leakage. 5. Pressure actuated clapper facing provides dependable seal. 6. Reset externally. Cover removal not required. 7. Grooved inlet by grooved outlet connections. 8. Water column drain valve to drain standing water column. 9. Upon operation valve latches in open position. No pressure operated relief valve required. The Reliable Model DDX Deluge Valve is a hydraulically operated differential type deluge valve used to control the water supply to a deluge or preaction system. Deluge systems use open sprinklers or nozzles as discharge outlets in the fire area while preaction systems use closed sprinklers or nozzles. Both systems use separate detection devices to control the operation of the deluge valve. Three simple trim arrangements allow for actuation of the Reliable Model DDX Deluge Valve by manual, hydraulic, pneumatic or electric devices such as break glass stations, wet pilot or dry pilot sprinklers and thermal or smoke detectors. The Reliable Model DDX Deluge Valve can be reset externally, without cover removal, by pushing in and turning a resetting knob. Listings & Approvals 1. Listed by Underwriters Laboratories, Inc. and UL certified for Canada. (culus) 2. Certified by Factory Mutual Approvals (FM) Model DDX Deluge Valve, External Reset Feature The Reliable Automatic Sprinkler Co.,Inc., 525 North MacQuesten Parkway, Mount Vernon, New York10552

Operation The Reliable Model DDX Deluge Valve is shown in both closed and open positions in Figure 1. In the closed position, the supply pressure acts on the underside of the clapper and on the push rod through the push rod chamber restriction. The pressure force acting on the push rod is multiplied by the lever and is sufficient to hold the clapper closed against normal supply pressure surges. When a fire is detected, a releasing device vents the push rod chamber to atmosphere through the chamber outlet. Since the pressure cannot be replenished through the restriction as rapidly as it is vented, the push rod chamber pressure falls instantaneously. When the push rod chamber pressure reaches about 1 3 the supply pressure, the upward force of the supply pressure acting on the clapper overcomes the downward force of the lever and the clapper opens. Once the clapper has opened, the lever acts as a latch, preventing the clapper from returning to the closed position. Water from the supply flows through the deluge valve into the system piping. Water also flows through the deluge valve alarm outlet to the alarm devices. After system shutdown, resetting the Model DDX Deluge Valve is even easier and only requires pushing in and turning the reset knob. The external reset feature of the Model DDX Deluge Valve provides a means for simple, economical system testing, which is one essential facet of a good maintenance program. The external reset feature does not, however, eliminate a second facet of good maintenance, namely, periodic cleaning and inspection of the internal valve parts. In the event that water builds up inside the valve due to condensate from the air supply system or water left inside from valve system testing, a drain is available to vent the water from the valve system. After closing the main supply valves, a small valve over the drain cup is simply opened slightly until the water inside the valve body and the main column has drained. Whenever ambient temperature conditions can substantially raise the temperature of the water in the release line and pushrod chamber, the pressure in the pushrod chamber and release line can exceed 175 psi. In an indoor installation where standard room temperature is exceeded, a relief kit may be needed. Pressure relief kit, P/N 6503050000, can be installed in the release line to limit the pressure to 175 psi. Detection and Actuation In general, the Reliable Model DDX Deluge Valve can be released by any listed or approved device which opens sufficiently to vent the push rod chamber in response to a fire. The releasing device is simply connected to the push rod chamber outlet. When the releasing device operates and vents the push rod chamber, the deluge valve opens. Typical releasing devices include Hydraulic Manual Emergency Stations, Model F1-FTR fixed temperature detectors on wet pilot lines, dry pilot actuators and solenoid valves. Model F1-FTR detectors perform both deluge valve releasing and fire detection functions with wet pilot lines. Model F1-FTR detectors are detectors only when dry pilot actuator releasing devices are used. The use of a solenoid valve for deluge valve releasing enables various types of electrical fire detection devices to be used. Typical detection devices include electrical emergency pull stations, thermal detectors and ionization or photoelectric smoke detectors. Electrical detection and releasing equipment used in Supertrol Electrical Systems is described in Bulletins 707 and 708, for both deluge and preaction systems. Models DDX Deluge Valves Figure 1 Clapper Closed and Open Positions 2.

Valve Description 1. Rated working pressure 250 psi (17.2 bar) 2. Factory hydrostatic test pressure 500 psi (34.5 bar) 3. End and trim connection. ANSI/AWWA C606 groove inlet and outlet Valve Size 4 6 Threaded openings Per ANSI B 2.1 4. Face to face dimension: 4 and 100 mm 14 (355 mm) 6 and 150 mm 16 (406 mm) 5. Shipping weight 6. Friction loss Expressed in equivalent length of Sch. 40 pipe, based on Hazen & Williams formula with C = 120. At 15ft/sec. Valve Size 4 6 Valve Size 4 6 Groove Dimensions in Inches (mm) Outlet Diameter 4.500 (114) 6.625 (168) Groove Diameter 4.334 (110) 6.455 (164) 7. Installation position: Vertical Groove Width 3 8 (10) 3 8 (10) Grooved Inlet and Grooved Outlet 64 lb. (29 kg) 95 lb. (43 kg) Equivalent Length 14 (4.27 m) 29.4 (9 m) Outlet Face to Groove 5 8 (16) 5 8 (16) Trim Description The trims for the Reliable Models DDX Deluge Valves are arranged for rapid, easy and compact attachment and serve as connection points to Reliable Model C Mechanical Alarms and other devices. The Model DDX Deluge Valve trim sets are: a. Wet Pilot Trim, 250 psi rated b. Dry Pilot Trim, 175 psi rated c. Electric Actuation Trim, 175 or 250 psi rated The Wet Pilot Trim (Fig. 2) is used when wet pilot sprinklers or hydraulic manual emergency pull boxes are used for detection and releasing. This trim set provides 2 main drain, alarm test, supply pressure gauge and push rod chamber supply connections. Also included in the trim are a push rod chamber pressure gauge, Model B Hydraulic Manual Emergency Station and a connection for releasing devices. The Dry Pilot Trim (Fig. 3) is used when dry pilot sprinklers are used as the fire detection means. This trim set includes the dry pilot actuator, air and water pressure gauges, low air pressure warning switch, air pressure relief valve and connections for the air supply and pilot sprinkler lines. The trim provides 2 main drain, alarm test and push rod chamber connections. Also included are a push rod chamber pressure gauge and the Model B Hydraulic Manual Emergency Station. The dry pilot actuator is fully described in Bulletin 504. Figure 2 Deluge Valve with Wet Pilot Line Trim 3.

Figure 3 Deluge Valve with Dry Pilot Line Trim 4.

Figure 4 Deluge Valve with Electric Actuation Trim 5.

Table 2 provides the recommended air pressure when the dry pilot trim set is used as the actuation means. Table 2 Water Pressure Air Pressure to be Pumped into Dry Pilot Line Maximum Not Less Than Not More Than 20 10 20 50 15 25 75 20 30 100 25 35 125 30 40 150 35 45 175 40 50 The electric Actuation Trim (Fig. 4) is used when electric detection and releasing are desired. This trim set includes a solenoid valve, 2 main drain, alarm test supply pressure gauge and push rod chamber supply connections. A push rod chamber pressure gauge and the Model B Hydraulic Manual Emergency Station are also included. Detailed description of electrical operation can be found in Bulletins 707 and 708. The Model B Hydraulic Manual Emergency Station is a standard item in all trim sets. However, the Model A Hydraulic Manual Emergency Station, described in Bulletin 506, is available as an option. All valves are listed by Underwriters Laboratories, Inc, and certified by UL for Canada (culus) and certified by Factory Mutual Approvals, only when used with the valve manufacturer s trim sets. Ordering Information Specify Valve Model Model DDX Valve Size 4, 6, 100mm or 150mm. When size is specified in mm, a metric valve per Valve Description Section 3.c will be supplied. Trim Wet Pilot Trim, Dry Pilot Trim or Electric Actuation Trim. Each trim set is also available in time saving preassembled kit forms. Specify either individual part trim or preassembled kit trim. Additional equipment Air compressors, electric detection and actuation equipment and mechanical sprinkler alarms must be ordered separately. These devices are described in Bulletin 707. Installation Dimensions in Inches Valve A B C D E F G H J K L M N P Q R 4 5 1 4 6 3 4 9 1 2 14 29 22 3 4 30 3 4 8 1 2 13 3 4 5 1 2 7 3 4 10 1 4 2 1 2 6 1 4 7 1 2 11 1 4 (133) (171) (241) (356) (737) (578) (781) (216) (349) (140) (197) (260) (64) (159) (191) (286) 6 6 1 4 7 3 4 10 1 2 16 30 23 3 4 31 3 4 8 1 2 13 3 4 5 1 2 7 3 4 10 1 4 3 1 4 8 3 4 8 1 2 12 1 4 (159) (197) (267) (406) (762) (603) (806) (216) (349) (140) (197) (260) (83) (222) (216) (311) The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. (800) 431 1588 Sales Offices (800) 848 6051 Sales Fax (914) 668 3470 Corporate Offices www.reliablesprinkler.com Internet Address Revisions indicate updated or new data. EG. Printed in U.S.A. 5/04 P/N9999970269