DELUGE SYSTEMS FALSE OPERATIONS

Similar documents
FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

LEARNING SPECIAL HAZARD DETECTION TYPES

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617)

Fire protection in hazardous locations:

Fire Detection System: An Overview

BERMAD Fire Protection

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

rpsa FIRE PROTECTION ENGINEERS

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

Meeting NFPA standards for

EXTINGUISHING SYSTEM DETECTION AND CONTROL

I am Rick Jeffress and I handle sales for Fike Video Image Detection. We thank the AFAA for coordinating the venue for this presentation, and we

El Reno Fire Department Fire Alarm Plan Review Worksheet

Detection, and Suppression Systems

OPEN SPRINKLER SYSTEM

Chapter 17, Initiating Devices

Releasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

Electromagnetic Compatibility of Alarm Systems

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

FIRE PROTECTION SYSTEMS

Open-area Smoke Imaging Detection (OSID)

Florida Building Code 2010

Deluge & Preac tion Systems

Course FP100 BACKFLOW PREVENTERS (BFPs) 101 FOR AUTOMATIC FIRE SPRINKLER SYSTEM M. Nabeel Waseem, M.Eng, PE, CFPS 2018

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

NEBOSH International Technical Certificate in Oil and Gas Operational Safety

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

DEALING WITH FIRE SAFETY

Flame Detection Jon Sarfas

CERTIFICATION BULLETIN

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

Fire Alarm System Fundamentals

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

TotalPac X Single interlock SUREFIRE system

Radar technology in surveillance

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials

GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard

A P P L I C A T I O N S G U I D E. Single-Ended Reflected Beam Smoke Detector

Schools and the Fire Code A Partnership for Safety

Multi-Point Peripherals

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

Tampa, FL Fire Cause Classification Task Group Tue, 14 April 2011

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

InstrumentationTools.com

Enhanced MRO Hangar Fire Protection

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

Self Inspection Program

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

Fire Safety Compliance

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS


ICC CODE CORNER 2012 IFC Code & Commentary

Report on First Revisions with Statement June 2014 NFPA 101

Symbols for Control Panels

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

Crime Central Station Burglary Alarm Systems

Prevention of Fires and Explosions in Wood Pellet Facilities. Allen Wagoner, FLAMEX, Inc.

UL 94 Flammability Ratings: Introduction

CHAPTER 7 ALTERATIONS LEVEL

Objective 1: Describe fire alarm systems.

TECHNICAL AND USER REQUIREMENTS FOR PERSONAL ALERT SAFETY SYSTEMS

E-16 Main Engine Remote Control System

Advanced Fire Alarm Systems Training Program Outline (5 Day)

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

TECHNICAL DATA OBSOLETE

CCTV, HOW DOES IT WORK?

Operator: Save these instructions for future use!

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

Model DRD-AS Conventional Infrared Flame Detector User Manual Ver. 1.0

TrueAlarm Analog Sensing

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Smoke detection in hazardous areas:

Smoke Alarms. Rev. A Copyright 2011 James D Peisker

Case Study. Selecting fire and gas detectors for harsh and remote locations. INSTRUMENTATION

E-17 Flammable Gas Detection and Alarm System

Touchpad Exit Controller Administration Guide

PERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D40 FIRE PROTECTION 02/18

CONSTRUCTION REQUIREMENTS

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

THE FIXED AEROSOL EXTINGUISHING SYSTEM - FIRE JACK

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

Fire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours

Report on First Revision June 2014 NFPA 5000

Maintaining Building and Fire Safety During Active Assailant Events and Other Terrorist Events

TotalPac X Firecycle III Preaction Double interlock system

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

NFPA 96, 2017 REVIEW SUMMARY

Public Safety DAS Annunciator Panel

(h) Pesticide Application.

System Test Report CLEAN AGENT

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

Explosion Protection Engineering Principles

Apollo Intelligent Auto Aligning Beam Detector. User Guide

Transcription:

DELUGE SYSTEMS FALSE OPERATIONS

Deluge Water/Foam Systems: False operations result in significant water/foam damages and might also cause destruction by fire!

Deluge Foam Systems: In case of Fire, the Main Valve might be close (Management Decision wary about false operations). I witnessed several cases, when following an annunciation, the employees fearing false deluge, rushed to close the main valve before making sure it was not a fire!!

Deluge Foam Systems: Obviously, False Operation might defeat the Whole Fire Protection notion, yet there is very little in the Standards to cope with this problem

MAIN CAUSES OF DELUGE SYSTEM FALSE ACTIVATION Deluge Valve Related Causes False Detection Initiation Manual Activation

DELUGE VALVE RELATED CAUSES, Cont.d., Surge Pressure in the Supply Line. While the normal max. pressure in a system is 12 bars, the actual surge pressure may exceed 25 bars, causing opening of the valve.

DELUGE VALVE RELATED CAUSES, Cont.d., The Source of a Surge Pressure: In case of several deluge system fed from the same Mains and Pump room, a surge pressure might be created by the initiation of one of these system.

DELUGE VALVE RELATED CAUSES, Cont.d., The Source of a Surge Pressure, Cont,d.,: 4x8 Deluge Valves open simultaneously Causing pressure drop to ZERO. Then 6000 GPM Pumps Start Imaging Pumps falling down from a Cliff

DELUGE VALVE RELATED CAUSES, Cont.d., It is not only causing FALSE activation of the second system, but it might deplete the water supply necessary for the first activated system resulting in FAILED EXTINGUISHMENT of this system!!

Disintegration of 2x10, 8 and 4 Pipes due to 8 deluge valve opening. About 300m long piping collapsed.

DELUGE VALVE RELATED CAUSES Most of the False Deluge initiations are caused by Unwanted Alarm. Investing heavily in the Water Based System creates a tendency to compromise on the detection system.

NFPA 11- False operations Aircraft Hangars: US Millions $ Potential Losses. There are several reports from the USA about false activation of foam systems.

NFPA 11- False operations A case we investigated: HiEX system caused $2.5 Million loss in a Storage Hall.

NFPA 11- False operations Ten (10) other false operations resulted each in several $ 100K loss.

NFPA 15- Water Deluge System Water Deluge system protects 60MW Transformer. There was a False Operation, the Transformer was tripped. The consequential losses: Several Millions US $

We Shall see later several cases of False operation

FALSE OPERATION AND DETECTION RELATED REFERENCE IN STANDARDS

REFERENCE STANDARDS NFPA 11: Foam Systems- No reference. NFPA 12: CO 2 Gas extinguishing. Some remarks about FACP causes of false operation in the Appendix. NFPA 15: Instructions regarding Smoke Detection and some reference for false alarm.

REFERENCE STANDARDS NFPA 409: Some Remarks about detection system. Almost nothing about false operation. NFPA 2001: Gas Extinguishing Systems- No much reference. NFPA 2010: Aerosol Extinguishing- Some Reference.

NFPA 11- Deluge Foam Systems: None, except for reference to environment. NFPA 15 is much better! See next slide

NFPA 11-2016 Edition Standard for Low-, Medium-, and High- Expansion Foam 4.9.2 Automatically Actuated Systems. 4.9.2.1 An automatic system shall be activated by automatic detection equipment. 4.9.2.2 Operation shall be controlled by listed or approved mechanical, electrical, hydraulic, or pneumatic means.

NFPA 11, Cont.d., 4.9.2.5* Automatic Detection Equipment. A.4.9.2.5 See applicable sections of NFPA 72. 4.9.2.5.1 Automatic detection equipment whether pneumatic, hydraulic, or electric shall be provided with supervision arranged so that failure of equipment or loss of supervising air pressure or loss of electric energy results in positive notification of the abnormal condition. 4.9.2.5.2 Where approved by the AHJ, small systems for localized hazards shall be permitted to be unsupervised.

NFPA 11. C-6: HIGH AND MEDIUM EXPANSION FOAM 6.7 Operation and Control of Systems 6.7.1* Detection of Fires. 6.7.1.1 Automatic detection shall be used for fixed systems. 6.7.1.1.1* Removal of automatic detection shall be permitted when approved by the AHJ. 6.7.1.2* Automatic detection shall be by listed or approved methods or devices capable of detection and indicating heat, smoke, or flame. Automatic detection devices shall be installed in accordance with NFPA 72.

NFPA 12-CO 2 Extinguishing A.4.5.2 Modern solid-state circuits, including microprocessors, are capable of responding to extremely short electrical impulses. While response to such transient signals is a desirable characteristic for some types of devices, it is an extremely undesirable characteristic for control units used to discharge carbon dioxide. Control units for releasing carbon dioxide systems must be designed to prevent unwanted discharges due to transient electrical impulses and to actuate pre-discharge alarms and time delays before discharging carbon dioxide.

NFPA 12-CO 2 Extinguishing A.4.5.2 Modern solid-state circuits, Cont.d, Undesired transient impulses can be introduced into the control panel from sources external to the panel, or unwanted transients can be generated within the control panel itself. For example, a microprocessor could produce undesired transient impulses for various reasons. Designs must incorporate technology to prevent discharge of carbon dioxide in the event that a microprocessor in the control unit emits spurious signals. If circuits that initiate carbon dioxide discharge are not designed to ignore such transients, an unwanted discharge could result.

NFPA 15- Std. for Fixed Spray System: Addresses the detection system in some details for the purpose of operation with some reference for false alarm. See Chapter 6 Installation Requirements

NFPA 15- Chapter 6, Cont.d., 6.5.2.1 The selection, location, and spacing of automatic fire detectors for the actuation of fixed water spray systems shall meet or exceed the applicable requirements of NFPA 72, National Fire Alarm and Signaling Code, and be consistent with the following: (1) Data obtained from field experience (2) Tests (3) Engineering surveys (4) Manufacturer s recommendations (5) Detectors listing criteria

NFPA 15-6.5.2.1 Cont.d., (6) Nature of the hazard being protected (7) Both normal and abnormal air velocities (8) Range of anticipated temperatures (9) Maximum expected rates of temperature change under non-fire conditions (10) Number and height of structural levels (11) Effects of precipitation (rain and snow) (12) Presence and magnitude of electromagnetic interference (13) Presence of obstructions that might retard or mitigate timely detection (14) Other conditions that might affect the efficacy of the fire detection employed

NFPA 15-6.5.2.1 Cont.d., 6.5.2.2 Detectors shall be located so as to promptly respond to a fire, flammable gas release, or other design condition. 6.5.2.2.1 The detection system shall be capable of detecting a fire up to the elevation of the highest level of protected equipment surface. 6.5.2.2.2 Detectors shall be located so that no portion of the hazard being protected extends beyond the perimeter line detectors.

See NAPA 15, Chapter 7- Design Objectives 7.7 Automatic Detection Equipment. 7.7.1* General. Detection systems providing an actuation signal to fixed water spray systems shall be designed in accordance with NFPA 72, National Fire Alarm and Signaling Code. 7.7.2 The spacing, location, and position of detectors shall be in accordance with 6.5.2.

See NFPA 15, Chapter 7- Design Objectives 7.7.3* The following shall be evaluated when selecting and adjusting detection equipment: (1) Normally changing conditions (2) Non-fire temperature changes 7.7.4* Response Time. 7.7.4.1 The detection system shall be designed to cause actuation of the system actuation valve to operate without delay. 7.7.4.2 Where ambient conditions exist that cause false system operations, detection systems shall be permitted to include delays that would override these conditions.

See NAPA 15, Chapter 12 Ultra-High-Speed Water Spray Systems 12.3.14 Detection. 12.3.14.1 General. The detection systems shall be in accordance with NFPA 72, National Fire Alarm Code.

See NAPA 15, Chapter 12 Ultra-High-Speed Water Spray Systems 12.3.14.2 Sensing devices shall be as follows: (1) Response characteristics: (a) Radiant energy-sensing devices capable of sensing the expected wavelength emissions of the materials in combustion. (b) Other types of sensing devices having equivalent response characteristics to radiant energy-sensing devices shall be permitted to be used. (2) Protected from physical damage (3) Suitable for the electrical area classification where they are installed (4) Accessible for testing, cleaning, and maintenance (5) Aimed and adjusted to minimize false actuation

See NAPA 15, Chapter 12 Ultra-High-Speed Water Spray Systems 12.3.15 Control Panel. 12.3.15.1 The control panel shall conform to the requirements of NFPA 72, National Fire Alarm and Signaling Code. 12.3.15.2 The control panel shall be located in an area protected from physical injury and from electromagnetic energy emitted from other electrical devices that could induce false actuation. 12.3.15.3 Control panel enclosures shall be rated for the ambient environment where they are located.

NFPA 409- Aircraft Hangars, Cont.d.,; 6.2.8 Detection and Actuation System Design. 6.2.8.1 General. 6.2.8.1.1 Actuation systems shall be provided with complete circuit supervision and shall be arranged in accordance with Section 6.4. 6.2.8.1.2 These detectors shall be installed in accordance with NFPA 72. 6.2.8.1.3 Detection systems shall be provided with supervision as required by NFPA 72.

NFPA 409- Aircraft Hangars, Cont.d.,; Chapter 7: High Expansion System & Pre-Action 7.7 Detection and Actuation Systems. 7.7.1 Detectors for actuating pre-action sprinkler systems shall be Rate-of-rise, Fixedtemperature, or Rate-compensation type. Note: These type have very slow response!!

NFPA 409- Aircraft Hangars, Cont.d.,; Chapter 7: High Expansion System 7.7.2 Detectors for actuating high- or lowexpansion foam systems shall be rate-of-rise, fixed-temperature, or rate compensation type or water flow of a wet pipe sprinkler system. Note: These type have very slow response!!

NFPA 409- Aircraft Hangars, Cont.d.,; Chapter 7: High Expansion System & Pre-Action 7.7.3 These detectors shall be installed in accordance with NFPA 72. 7.7.4 Detection systems shall be provided with supervision as required by NFPA 72.

NFPA 2001-Gas Extinguishing; Abort Switch is necessary. No guidelines for prevention.

NFPA 2010-Aerosol Extinguishing 6.4.6* Unwanted System Operation. Care shall be taken to thoroughly evaluate and correct any factors that could result in unwanted discharges.

NFPA 72- Detection; The term used is: Unwanted Alarm. But there is no reference for extinguishing systems except for Abort Switch if exist.

NFPA 72- National Fire Alarm and Signaling Code 3.3.304* Unwanted Alarm. Any alarm that occurs that is not the result of a potentially hazardous condition. 3.3.304.1 Malicious Alarm. An unwanted activation of an alarm initiating device caused by a person acting with malice.

NFPA 72- National Fire Alarm and Signaling Code 3.3.304.2* Nuisance Alarm. An unwanted activation of a signaling system or an alarm initiating device in response to a stimulus or condition that is not the result of a potentially hazardous condition. 3.3.304.3 Unintentional Alarm. An unwanted activation of an alarm initiating device caused by a person acting without malice. 3.3.304.4 Unknown Alarm. An unwanted activation of an alarm initiating device or system output function where the cause has not been identified.

NFPA 72- Cont.d., Unwanted alarms might be intentional, unintentional, or unknown. If they were caused intentionally, they might have been done by someone with the intent to cause disruption and should be classified as malicious. However, an unintentional alarm might occur when, for example, a child activated a manual fire alarm box not knowing the consequences. Similarly, someone accidentally causing mechanical damage to an initiating device that results in an alarm is causing an unintentional alarm.

NFPA 72- Cont.d., A.3.3.304 Unwanted Alarm. Unwanted alarms are any alarms that occur when there is no hazard condition present. These are sometimes also called false alarms. Because the term false has been used by many people to mean many different things, this Code is instead using the terms unwanted, fault, nuisance, unintentional, unknown, and malicious to categorize the different types of alarms.

THE FIRE DETECTION SYSTEM, What do we get? The Foam Designer System, being a Water Engineer has no Idea. The Fire Detection Designer being an Electrical / Electronic Engineer, has no idea about the Foam /Deluge system requirements.

Detection Approved System, what is this: There is UL approval Standard, UL 864 Standard for Control Units and Accessories for Fire Alarm Systems Edition 9 Edition 10 is dated Dec 1, 2014 to be effective Dec 1, 2018

UL 864 Standard, Cont.d., More Stringent Testing to reduce False Alarm. In Israel Systems are Approved based on older UL edition. Probable adoption of Edition 9 in 2017, 10 years after the official adoption in the US

UL 864 Standard, Cont.d., For the approval Detection Lab., the Detection is of importance. For the Deluge System s designer, the mere detection is less important than the releasing role both in terms of operation and reliability.

Detection Reliability One Addressable Loop to which many detectors are connected, many none water proof connection boxes are unreliable. After one test the detection system circuity is wet. The system is approved but the damage remains.

Releasing Reliability To achieve better reliability use a Dedicated Releasing Module or Panel rather than an Output Module for the job.

CODES REFERENCE SUMMARY The only respectable reference to false operation is by NFPA 15, NFPA 2010 and Some Explanation in NFPA-12.

CAUSES OF FALSE OPERATION: Unwanted Activation of the FACP: Detectors responding to none-fire elements such as Dust, Steam, Water Fog, Exposure to moisture, corrosion. Human Error Intentional Activation.

CAUSES OF FALSE OPERATION: Detectors In the case of Linear Beam Detectors: Any Obscuration, Misalignment, Partial Obstruction, Lighting Fixtures as well as wrong positioning.

CAUSES OF FALSE OPERATION: Detectors The New OSID Detectors are supposed to respond only to smoke particles via UV and IR radiation. WE had 3 unexplainable initiations in one system. The detectors also responded to FOAM!

CAUSES OF FALSE OPERATION: FACPs FACP may activate operation due to voltage disturbances, lightning, effect of nearby power system (See also NFPA 12 reference) It may also activate system due to initiation of unrelated detector.

CAUSES OF FALSE OPERATION: FACPs We had recently a case of a point type detector that responded to dust. The FACP activated a foam deluge system although this detector was not configured by the software to activated the foam system!

CAUSES OF FALSE OPERATION: DELUGE VALVES The Diaphragm was damaged by previous pressure surges. Stones or Debris caught between the diaphragm and the seat. Pressure Surges overcoming the diaphragm.

CAUSES OF FALSE OPERATION: DELUGE VALVES, Cont.d., The Pressure Surge is prevalent on Pump Starts when the pressure in the Main was low, mainly due to line maintenance.

CAUSES OF FALSE OPERATION, THE DELUGE VALVES In particular when the pressure on the diaphragm drops whist the main pressure is minimal or zero.

DEPENDANCE ON THE RELIABILITY FIRE DETECTION SYSTEMS.

The Deluge system requires a detection system. NFPA 11 that addresses Foam Systems send us to NFPA 72 which is Detection System Code. The Time Response of the Foam system which is a function of the performance of the detection system is critical to its success. Yet, no guidelines are provided (Unlike NFPA 15). NFPA 72 addresses Detection but has no guidelines about the applications initiated by detection system except for the notification arrangements. Water Based Engineers using NFPA 11 have no communication with the Electronic Engineers dealing with the detection system.

CASE #1 False Alarm operating a Low Expansion Foam system in a storage space. The system was configured to discharge foam upon initiation of any of four (4) Flame Detectors. The detection system consisted of a FACP with 4 flame detectors. An additional point type smoke detector was added to protect the FACP. This detector was configured to operate only a notifying device. The FACP and the detector where positioned about 30 m from the protected space.

CASE #1, Cont.d., The point type detector was installed just next to the FACP, a poor position. While drilling a concrete floor for installation of a new rack, about 4 m from the FACP, the dust cloud generated initiated the detector installed 1.5 m above the floor. The detector initiated through the FACP the foam system. The detector initiated through the FACP the foam system.

CASE #2 False Discharge of Hi-Ex Foam. Linear Beam Detectors responded to windy dust activated the system.

Header feeding 4x8 deluge Valves.

False CASE #3 Discharge of Hi-Ex Foam due to False operation of two linear beam detectors

CASE #3 & 4 Two Foam Deluge Valves, for two storage halls. Two False Foam Discharge: #1: False Initiation of two Linear Beam Detectors. #2: Shutoff of Main Line for several hours, Pump Restart when the pressure on the Diaphragm was low.

CASE #4, Pressure loss over the diaphragm During Mains shutoff for repairs Cutoff of Main Supply for repairs.

CASE #4, Cont.d., One of two deluge valves. The Easy Lock internal balls playing the roll of Non-Return Valve. Dripping

CASE #4, Cont.d., We disconnected the Supply System.

CASE #4, Cont.d., Within 4 hours the pressure on the diaphragm drops from 140 to CASE #4, Cont.d., 56PSI. When a pump starts the deluge valve opens.

CASE #4, Cont.d., There is no filter in the system, thus stones propelled by the rushing water might cause the damage seen on the photo below.

CASE #4, Cont.d., After two false operations and a couple of testing the diaphragm of the valve failed due to Surge Pressures (Water Hammer).

CASE #5 & 6 Due to maintenance, the fire pumps were tripped. After a day the Pumps were restarted. The pressure in the mains overcome the diaphragm.

CASE #7 Storage Hall,, no detector initiation. Seems to be FACP false initation.

Recommendations: 1. Make sure there is a suitable filter upstream to prevent debris ingress. 2. Prevent pressure drop from the Diaphragm. 3. If the Mains is shut off, instructs closing the system Valve.

Recommendations, Cont.d., 4. Install a pressostat warning against Low Pressure over the Diaphragm.. 5. Regarding the Manual operation, don t make it trivial for a curious person to play with it. 6. It is very important to provide maintenance instructions with the valve.

Recommendations, Cont.d, 7. For close air pressurized system, make sure the air compressor is provided with a dryer.. 8. Detection System plays a major part in the successful operation of the whole system as well as i.r.o. False Operation : See Item 10 below

Recommendations, Cont.d, 9. The Detection System Designer should study the importance of prompt operation of the whole system. NFPA-15 has reasonable guidelines 10. Make sure that the FACP together with the releasing station are approved by UL Edition 9 or EN54 and EN 12094

Recommendations, Cont.d, 11. Use dedicated Releasing Module or Panel 12. False operations might have severe consequences. It is up the designer to take it under consideration

Recommendations, Cont.d, 11. False operations might have severe consequences. It is up the designer to take it under consideration