Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building

Similar documents
Development of Seismic-induced Fire Risk Assessment Method for a Building

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Fire Dynamics Simulation and Evacuation for a Large Shopping Center (Mall), Part II, Evacuation Scenarios

EVACUATION AND SMOKE MOVEMENT INTERACTIVE SIMULATION MODEL

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

A SURVEY OF OCCUPANT RESPONSE TOWARDS AN AUDIBLE FIRE ALARM

Review of A Real Multi-story Store Fire by Applying Evacuation and Smoke Movement Interactive Simulation Model

Performance Requirement for Building Fire Safety from the Viewpoint of Firefighting and Rescue Activity

Simulation study of evacuation in high-rise buildings

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

Case study about initial action by disaster prevention staffs at a fire

Evaluation of Fire Safety Measures in Care Facilities for the Elderly by Simulating Evacuation Behavior

BR-BO Adopted June 1, Evacuation Safety Performance Evaluation Manual

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES

Unit 2 Fire Safety (Zone 1)

Case Study of Underground Car Park. Team Japan

Leakage of Mildly Flammable Refrigerants into a Room

A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM

EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS

Evaluation of a Support System for Large Area Tourist Evacuation Guidance: Kyoto Simulation Results

Experimental Study on Effect of Escape Guidance in Fire Smoke by Travelling Flashing of Light Sources

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Evacuation Hazards in Crowded Subway Stations

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

Final Report - Volume III - Technical Manual for Planning of Fire Prevention System

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Upward Evacuation Experiment for Estimating Evacuation Speed in Water Disaster

Considerations in the Design of Smoke Management Systems for Atriums

S. Motoyui 1 and Y. Sato 2

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

SEPTEMBER-NEWSLETTER-ELEVATOR DANGERS

TRANSMISSIVITY BEHAVIOR OF SHREDDED SCRAP TIRE DRAINAGE LAYER IN LANDFILL COVER SYSTEM *

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel

A Support System for Developing Tourist Evacuation Guidance

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Effects of Smoke on Evacuation Martin Lopušniak 1, a

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

2012 International Symposium on Safety Science and Technology Factor analysis of high-rise building fires reasons and fire protection measures

NEW CD WARP CONTROL SYSTEM FOR THE CORRUGATING INDUSTRY

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

Available online at ScienceDirect. Procedia Engineering 135 (2016 )

Numerical analysis of flow characteristics of fire extinguishing agents in aircraft fire extinguishing systems

Integrated Earthquake Fire Risk Evaluation Based on Single Building Fire Probability Applicable to All Map Scales

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

Lifting of evacuation orders and subsequent efforts in Japan

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

EXECUTIVE SUMMARY FOR OCCUPANT BEHAVIOR, EGRESS, AND EMERGENCY COMMUNICATIONS

CLASSIFICATION AND EXPERIMENTATION FOR THE DEVELOPMENT OF DAYLIGHTING SYSTEMS IN COLD AND SNOWY REGIONS

AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

Simulation of Emergency Evacuation in the Arrival Hall of a Crowded Airport

An experimental study of the impact of tunnel suppression on tunnel ventilation

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

Keywords: slope stability, numerical analysis, rainfall, infiltration. Yu. Ando 1, Kentaro. Suda 2, Shinji. Konishi 3 and Hirokazu.

Hot Issues in Fire Engineering July 2014

A Study on the Effects of Urban Landscape on Citizen s

HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% 23rd World Gas Conference, Amsterdam Main Author. Atsuya Tajima Japan

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG

Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building

A Study on Hierarchy of Spatial Configuration in Outpatient Department of General Hospital

Variable far infrared radiation (VFIR) technique for cubic carrot drying

Health Monitoring System Using FBG-Based Sensors for a 12-Story Building with Column Dampers.

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Simulation of Evacuation Process in a Supermarket with Cellular Automata

Fire evacuation drill

IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

PERFORMANCE ANALYSIS OF GROUND SOURCE HEAT PUMPS FOR DOMESTIC HOT WATER SUPPLY IN THE LOW ENERGY HOUSE AND ITS APPLICATION

Tunnel Fire Dynamics and Evacuation Simulations

Emergency Evacuation Team Training James Zour Life Safety Specialist Transwestern

Japanese Case Study: How to maintain the fire safety in subway station and tunnel

The Study of Evacuation Times from the Multiplex Theatres

People s Subjective Estimation of Fire Growth: An Experimental Study of Young Adults

EVACUATION SIMULATION FOR BUILDING DAMAGE CAUSED. Shiori KUBO Rei FUJITA Hidenori YOSHIDA Lalith WIJERATHNE Muneo HORI

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

EMERGENCY PREPAREDNESS: EVACUATIONS

Impact of quick incident detection on safety in terms of ventilation response

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

Sprinklers Modeling for Tunnel Road Fire Fighting

Design and Construction of South Asia s Tallest Tower Lotus Tower

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

Transcription:

5A-4 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea Feasibility Study of Use of Elevators in Fire Evacuation in a High-rise Building A. Sekizawa 1, S. Nakahama 2, H. Notake 3, M. Ebihara 1, and Y. Ikehata 2 1 Fire and Disaster Management Engineering Laboratory, Graduate School of Engineering, The University of Tokyo, Tokyo, Japan 2 Technology Center, Taisei Corporation, Totsuka-ku, Yokohama, Kanagawa, Japan 3 Institute of Technology, Shimizu Corporation, Etchujima, Koto-ku, Tokyo, Japan Abact In many past fires, not a few people used elevators for their evacuation, although they are told to escape by stairs in emergency. Also, it is expected that the number of people who have difficulty to use stairs in evacuation would become larger, since the proportion of aged people in the total population has been rapidly increasing recently and also accessibility of disabled people has been improved in Japan. To consider this situation, we made a simplified model to evaluate evacuation time by elevators, and conducted some case studies in order to examine the feasibility and issues of elevator use for evacuation. As the result of case studies, if the elevator use group can be designated only for a small part of occupants such as disabled people, it would be effective to use elevator in evacuation for those people. However, for other general people, it would be better to use stairs for their evacuation in most cases as well as to let the evacuation of disabled people by elevator more effective. 1. Introduction * At the situation of a building fire, occupants are told that they should escape to the ground level or a floor of refuge by stairs, but not by elevators. However, in fact in many past fires, not a few people used elevators for their evacuation. For example, Corresponding Author- Tel.: +81-3-5841-725; Fax: +81-3-5841-7327 E-mail address: sekizawa@chemsys.t.u-tokyo,ac,jp in the fire of 20-story Hiroshima Motomachi High-rise Apartments that occurred in October 28, 1996 in Japan, more than a half of the total evacuees used elevators from the results of our questionnaire survey 1). On the other hand, the number of people who have difficulty to use stairs becomes larger year by year in high-rise buildings, since the proportion of aged people in the total population has been rapidly increasing and also accessibility of disabled people has 235 Copyright International Association for Fire Safety Science

been improved recently in Japan. Therefore, the potential demand of elevator use in evacuation has been growing recently especially after the WTC collapse on September 11th, 2001, while evacuation using elevators in case of a fire is still a controversial issue because the safe operation of regular elevators is not always secured during evacuation in a fire. In the context of this situation, we developed a simplified model to simulate the elevator operation for calculating evacuation time by elevators and we conducted some case studies with this elevator service model to examine the feasibility and issues of elevator use for evacuation mainly from the viewpoint of its efficiency of transportation of occupants rather than fire safety aspect during the operation. movement to calculate travel time of elevators. The first pattern is that an elevator movement has a stage of the constant velocity like the case in Figure 1. The second pattern is that an elevator decreases its velocity immediately after reaching the constant velocity, and the third pattern is that an elevator decreases its velocity before reaching the constant velocity as shown in Figure 2. The process of how to calculate the travel time in each pattern is described below in (1), (2), and (3). Velocity(m/second) V 2. Models for Evacuation by Elevator and by Stairs 2.1 Models of elevator service operation for evacuation For the case study of elevator use in evacuation in a high-rise office building, we revised the former model 2),3) in order to handle the operation of multiple elevators. In this section, the outline of the new model of elevator operation is described hereafter. Using this model, we can change the performance of each elevator such as its speed and/or capacity as well as the priority of floors that each elevator goes to independently in order to examine quantitatively both the performacne and the applicable ategy of elevator use in evacuation. By the way, to calculate the elevator travel time, we should consider the stages of elevator movement such as stop, acceleration, constant velocity, deceleration, and stop again. Figure 1 shows the schematic diagram for describing the relationship of these stages. Also, we should consider three patterns of elevator 0 α T 1 T 2 T 3 β Time(second) Figure 1 Schematic diagram for calculating elevator travel time for the pattern that an elevator movement has a stage of the constant velocity (V ). Velocity(m/second) V 0 α T 1 T 3 β Time(second) Figure 2 Schematic diagram for calculating elevator travel time for the pattern that an elevator decreases its velocity before reaching the constant velocity. (1) The pattern that an elevator movement has a stage of the constant velocity. 236

The vertical distance for the elevator movement is calculated by the following equations. 1 2 1 2 L= αt1 + VT2 + βt3 -------------- [1] 2 2 V = αt = βt ---------------------------- [2] 1 3 Where, L : vertical distance for the elevator movement (m) α : elevator acceleration (m/s 2 ) β : elevator deceleration (m/s 2 ) V : imum elevator velocity (m/s) T 1 : acceleration time (s) T 2 : constant velocity time (s) T : deceleration time (s) 3 From equation [1] and [2], we can lead the following equations. V T α V T3 = ------------------------------------ [4] β 2 2 V V L α β T2 = --------------- [5] V 1 = ------------------------------------- [3] Then, we can calculate the total elevator travel time ( T total ) by the following equation. Ttotal = T1+ T2 + T3 2 2 V V L V α β V = + + -- [6] α V β (2) The pattern that an elevator decreases its velocity just after reaching the constant velocity. In this case, T 2 = 0, which means the equation [5] is zero. So, substituting T 2 = 0 in equation [6], the total elevator travel time is represented by the following equation. T V α V β = + ---------------------- [7] total (3) The pattern that an elevator is decreasing its velocity before reaching the constant velocity. The relation between the velocity (V) at the time of changing from acceleration stage to deceleration stage and the acceleration stage as well as the deceleration stage is represented by the following equation. V = αt = βt --------------------------- [8] 1 3 And, substituting T 2 = 0 in the equation [1] and using the equation [8], we can lead the following equation. 2 1 V 1 V L = α + β 2 α 2 β 2 1 1 = V + ------------------ [9] 2α 2β Using equation [8] and equation [9], we can calculate the total elevator travel time by the following equation. Ttotal = T1+ T3 1 1 L = + ---------- [10] α β 1 1 + 2α 2β 2.2 Model of evacuation by stairs In this paper, based on the assumption that evacuees use two egress stairs evenly and they start evacuation simultaneously on every floor, the evacuation time by egress stairs T is calculated as the total sum of 2 237

horizontal walking time, vertical walking time, and either of larger one between passage time through the stairs and passage time through the exit door from the stairs to the first floor. T is represented by the equation [11]. The specifications and results of calculation of evacuation by egress stairs are described in Table 1. T Lh L s P P = + +, Vh V s ( N W) ( Nxit Wxit) -------------- [11] Where, T : evacuation time by stairs (s ) L h : imum horizontal walking distance ( m ) V : horizontal walking speed ( m/ s) h L s : imum vertical walking distance ( m ) V : vertical walking speed ( m/ s) s P : number of evacuees by stairs ( persons ) N : average flow factor in stairs ( persons / m s ) W : available stairs width ( m ) N xit : flow factor of the door on the first floor ( persons / m s ) W xit : available door width on the first floor ( m ) the model for evacuation by stairs, which are described in the former section in this paper. In the case studies, mainly focusing upon the efficiency of transportation of occupants rather than fire safety aspects of elevators during the operation, the following subjects are investigated. (1) First, as the bank, where a fire occurs, changes, how does the evacuation completion time by elevators change? And, which is shorter and preferable to use emergency elevators or to use egress stairs for evacuation in the bank where a fire occurs? (2) Second, from the viewpoint of transportation efficiency, which is preferable between two emergency operational modes of elevators such as the mode(a) that priority is given to the floors just above a fire floor first or the mode(b) that priority is given to the highest floor first? (3) Lastly, as the ratio of elevator use in evacuation at the bank, where a fire occurs, is changing, how the evacuation time of both by emergency-use elevators and by egress stairs are affected by the ratios? 3.2 Floor configuration and the elevation of a building for case study For doing case studies, we used a 53-story model building that has a center core system with reference to the actual high-rise office building in Japan. The floor configuration and the elevation of the building are shown in Figure 3. 3. Case Study 3.1 Purpose of case study In order to examine the feasibility of elevator evacuation using a typical high-rise building, we conducted case studies with our simulation model of elevator operation and 238

Table 1 Specifications and results of calculation of evacuation by egress stairs. Note: The specifications and evacuation time are obtained from the data in section 3.2. Whole Build. A-Bank B-Bank C-Bank D-Bank Ratio of stair use in evacuation (% ) 100% 100% 100% 100% 100% Total number of occupants (persons ) 10920 2730 2730 2730 2730 Number of egress stairs 2 2 2 2 2 Number of occupants for each stairs (persons ) [P ] 5460 1365 1365 1365 1365 Maximum horizontal walking distance (m ) [Lh ] 50 50 50 50 50 Horizontal walking speed (m/s ) [Vh ] 1 1 1 1 1 Maximum vertical walking distance (m ) [Ls ] 193.15 50.8 98.25 145.7 193.15 Vertical walking speed (m/s ) [Vs ] 0.25 0.25 0.25 0.25 0.25 Width of each stairs (m ) [W ] 1.2 1.2 1.2 1.2 1.2 Available width of exit door (m ) [Wxit ] 1.08 1.08 1.08 1.08 1.08 Flow factor of stairs (persons/s m ) [N ] 1.3 1.3 1.3 1.3 1.3 Flow factor of exit door (Persons/s m ) [Nxit ] 1.5 1.5 1.5 1.5 1.5 Evacuation time by stairs (s ) [T ] 4323 1128 1318 1508 1698 Table 2 Occupant load and elevators condition in the building for case studies. Unit A-Bank B-Bank C-Bank D-Bank Emergency EV Service floor floor 1-14 1, 15-27 1, 28-40 1, 41-53 1-53 Number of elevators 8 8 8 8 2 Capacity persons 22 22 22 22 32 Constant travel speed m/s 4 5 6 7 3 Acceleration m/s 2 0.7 0.7 0.7 0.7 0.7 Deceleration m/s 2-0.7-0.7-0.7-0.7-0.7 Door width m 1.1 1.1 1.1 1.1 1.9 Occupant load on each bank persons 2,520 2,520 2,520 2,520 ----- 41-53F D-Bank 41F Emergrncy EV Stair Office Area C-Bank A-Bank Office Area Stair 28-40F 15-27F C-Bank 28F B-Bank Service Floor of EV Fire Floor D-Bank B-Bank Emergency EV Office Area Emergency EV 1-14F 15F A-Bank 2F 1F: Lobby G.L. Figure 3 Floor plan and elevation of a model high-rise building for case study. 239

Although some stories are used as restaurants and medical clinics other than offices in the actual building, but in the case studies it is assumed that every floor is used for office space. A standard floor area is 2,629m 2 and the story height is 3.65m (only the height of the first floor is 7.0m). The floor of refuge is the first (ground) floor, which is a lobby. In the center core, there are four elevator banks for services to the corresponding four parts of floors such as a bottom part (A-Bank :1F-14F), a mid-lower part (B-Bank :15F-27F), a mid-upper part (C-Bank :28F-40F), and a top part (D-Bank: 41F-53F). Hereafter, for shortening purpose, we call each block of floors for elevator services in each bank just as A-bank, B-bank, C-bank, and D-bank respectively. In each bank, there are eight regular elevators and so the total number of regular elevators is 32. By the way, two fire/smoke proof emergency-use elevators are installed at both east and west sides of the building. The emergency-use elevators are usually operated by building staffs as well as firefighters and they can stop at every floor. Also, for emergency evacuation such as in a fire, two fire/smoke proof egress stairs, which has a vestibule shared by the emergency-use elevators, are provided near the emergency-use elevators as seen in Figure 3. For the calculation of evacuation by elevator, we assumed a fire floor on the bottom floor as a most unfavorable condition within floors of each bank. And, total occupant load in each bank and number of elevators as well as their capacity and travel speed are specified in Table 2 according to the actual conditions in the building that is modeled. The occupant load is calculated by the equation [15]. P floor = ρ A officearea ------------------- [15] Where, P floor : number of occupants on one floor ρ : crowd density (office:0.125 persons/m 2 ) A office area : office area of one floor (m 2 ) 3.3 Premises for case study In case studies, we conducted the calculation of evacuation time by elevators on the following premises in consideration of the realistic and/or worst conditions in a fire situation. 1) A fire floor is assumed to be the bottom floor in each part of floors for B-Bank, C- Bank, and D-Bank. Only in A-Bank, a fire floor is assumed to be the second floor, since the first (ground) floor is the floor of refuge. (See Figure 3) 2) A fire in one case is assumed to occur on the bottom floor within one of four parts of a building, but not to occur in two or more parts simultaneously. 3) As the service bank is higher, the constant velocity of elevators in each bank is naturally faster according to actual conditions in the building that is simulated. Specifically, the constant velocity of elevators is 4m/s, 5m/s, 6m/s, and 7m/s for A-Bank, B-Bank, C-Bank, and D- Bank respectively. The constant velocity of emergency-use elevators is set to be 3m/s. 4) In the bank where a fire occurs, only emergency-use elevators that are fire/smoke proof are available for elevator evacuation. In other banks, occupants can use regular elevators for their evacuation, but they cannot use emergency-use elevators because of the priority use by the occupants in the fire bank. 5) Emergency operational modes of elevator service are assumed to be two patterns such as; Mode(a) : For the bank where a fire occurs, elevators start from the first floor and 240

go up directly to the floor just above a fire floor and next go to the second floor above a fire floor, and then go up directly to the highest floor within the bank. After then, elevators descend from the highest floor to lower floors gradually until they reach the third floor above the fire floor and then they directly descend to the first floor. Mode(b) : For banks other than a fire bank, elevators start from the first floor and go up directly to the highest floor within the bank and then elevators descend from the highest floor to lower floors gradually until they reach the bottom floor within the bank. After then, they directly descend to the first floor. During the above operation process, once an elevator is filled up to its capacity, it does not receive further passengers and descends directly to the first floor. After it drops passengers off on the first floor, then it moves up again directly to the higher priority floor where there is any evacuee waiting for an elevator. The elevator service for evacuation continues until no evacuee waits. 6) The occupants on a fire floor are assumed to move down by stairs to the floor just below the fire floor. Therefore, this occupant load is added to that of the floor just below the fire floor in the evacuation calculation. 7) No influence by fire and smoke is considered during the evacuation. In this paper, the transportation efficiency is the main target of concerns. 4. Results and Discussion 4.1 Evacuation time by elevators in each bank and evacuation time by egress stairs. Figure 4 shows the evacuation time by elevators by each bank and evacuation time by egress stairs for a whole building as well as for occupants in D-Bank, when a fire occurs on the bottom floor in the D-Bank. Here, the evacuation time by elevator in A- Bank, B-Bank, and C-Bank is calculated based on the premise that the occupants in the floors in these banks can use regular elevators (8 in each bank) for their evacuation. And, the regular elevators are operated by the emergency operation mode(b) that is stated earlier in section 3.3. In the D-Bank, the occupants can use only emergency-use two elevators that are operated by the emergency operation mode(a). The evacuation time by egress stairs here is calculated for the two patterns such as; (i) All occupants in a whole building use two fire/smoke proof egress stairs, and (ii) Only occupants on the floors in a fire bank use two fire/smoke proof egress stairs. As seen in Figure 4, the dominant evacuation time by elevators is the evacuation time of D-Bank (6,122 seconds), because the occupants can use only two emergency-use elevators. By the way, the time of evacuation by two egress stairs for a whole building (Pattern(i): 4,323 seconds) is smaller than the evacuation time by emergency-use elevators only for D-Bank (6122 seconds), but is much larger than the evacuation time by regular elevators for each of A-Bank, B-Bank, and C-Bank. However, if we see the evacuation time by egress stairs for occupants only on the floors in D-Bank (Pattern(ii): 1,725 seconds), it is far smaller than evacuation time by two emergency-use elevators and moreover it is not so much different from even the evacuation time by eight regular elevators in each bank. This tells that evacuation by elevators is not always faster than evacuation by stairs, and it rather could be less favorable than evacuation by stairs according to conditions. 241

Then, in Figure 5, evacuation times by two emergency-use elevators, by eight regular elevators, and by two egress stairs are shown for each bank of A-Bank, B-Bank, C-Bank, and D-Bank respectively, assuming a fire floor in each corresponding bank. And also, evacuation time by egress stairs for a whole building is put for reference in the bottom. Fire/smoke proof emergency-use elevators are naturally much safer in a fire than regular elevators because they have an attached vestibule and emergency electricity supply, but the number (hence capacity) of emergency-use elevators is limited and their speed is slower than regular elevators. Therefore, if all occupants in each bank try to use emergency-use elevators for their evacuation, it takes much longer time than the cases of evacuation by regular elevators and also by egress stairs in each bank as shown in Figure 5. By the way, evacuation time by egress stairs is quite similar to that by regular elevators in each bank and further the evacuation by egress stairs must be much safer than the evacuation by regular elevators. Therefore, it is recommended that most of general people on the floors in a fire bank should better use two fire/smoke proof egress stairs except the people who have difficulty to use stairs in their evacuation, while the occupants other than in a fire bank may use regular elevators if their safety operation is secured. (T wait =Σ(waiting time * number of people)). Here, two operational modes are the mode(a) that priority is given to the floors above a fire floor first and the mode(b) that priority is given to the highest floor first, both of which are described in more detail in the section 3.3 Premises for case study in this paper. From Figure 6, the evacuation completion times (T evac ) of the two operation modes are just same. And, the elevator operation mode(a) is only a little more preferable than the operation mode(b) in terms of the total sum of products of waiting time and number of people (T wait ), which is introduced for the consideration of potential exposure of occupants to smoke. However, by these simple indices, we cannot distinguish the preference between these two operational modes. Therefore, for this purpose, we should take into account the influence of smoke spread in conjunction with floor height and/or time lapse after ignition in further studies in the future. 4.3 Comparison of efficiency between evacuation by emergency elevators and evacuation by egress stairs as a function of the ratio of elevator use on the floors in D-Bank. To see the change of efficiency of evacuation by elevators along with the population of elevator use, we compared evacuation completion time between the 4.2 Comparison of transportation efficiency between two operational modes of emergency-use elevators. In this section, assuming that a fire occurs on the bottom floor in D-Bank, transportation efficiency of the two operational modes of emergency-use elevators are compared in terms of the total evacuation time (T evac ) and the total sum of products of certain waiting time and number of people that have such waiting time 242

Evacuation Time (s) 0 1000 2000 3000 4000 5000 6000 7000 A-Bank 967 Evacuation by elevators B-Bank C-Bank 1268 1483 Evacuation by 8 regular elevators Evacuation by 2 emergency-use elevators D-Bank 6122 Evacuation by stairs for a whole building Evacuation by stairs for D-bank only 1698 4323 Figure 4 Evacuation time by regular elevators in A-Bank, B-Bank, C-Bank, and, and by emergency-use elevators in D-Bank and evacuation time by egress stairs for a whole building as well as only for D-Bank when a fire occurs on the bottom floor in the D-Bank. Evacuation Time (s) 0 1000 2000 3000 4000 5000 6000 7000 A-Bank 967 1128 2559 B-Bank 1268 1318 3920 C-Bank 1483 1508 5280 D-Bank 1530 1698 6122 Evacuation by Stairs for a whole building 4323 Evacuation by Emergency EV Evacuation by Regular EV Evacuation by Egress Stairs Figure 5 Evacuation time by elevators and by egress stairs in each bank and evacuation time by egress stairs for a whole building. Evacuation Time (s) Total Waiting Time (Σ(wating time * number of people)/1000) 0 1500 3000 4500 6000 7500 9000 EV operation pattern (a) 6122 7660 EV operation pattern (b) 6122 7861 EV operation pattern (a): Priority is given to the two floors above a fire floor. EV operation pattern (b): Priority is given to the highest floor first then to lower floors. Figure 6 Comparison of transportation efficiency between two operation modes of emergency-use elevators for D-Bank assuming a fire in on the Bottom Floor in the D-Bank. 243

Evacuation by Emergency EV Evacuation by Egress Stairs 7000 Evacuation Time (s) 6000 5000 4000 3000 2000 1000 0 0 10 20 30 40 50 60 70 80 90 100 EV Use-Ratio (%) Figure 7 Comparison of evacuation completion time between the evacuation by emergency elevators and the evacuation by egress stairs as a function of the ratio of elevator use in D-Bank. evacuation by emergency elevators and the evacuation by egress stairs as a function of the ratio of elevator use among the occupants in D-Bank, assuming that a fire occurs in D-Bank. Figure 7 shows the evacuation completion time by emergency elevators and by egress stairs respectively for the cases, in which the ratio of elevator use of occupants is changing from 0% to 100% by 10% on the floors in D-Bank. The evacuation completion time by egress stairs is ranging from 1,698 seconds to 910 seconds from 0% to 90% in elevator-use ratio. This is because the evacuation completion time by stairs is determined by the sum of travel time from the highest (53 story) to the first floor (ground floor) without congestion and the time of passage in stairs in the congestion dominated by the flow rate within the stairs, which is in proportion to the number of occupants who use the stairs for their evacuation. On the other hand, the evacuation completion time by emergency-use elevators is increasing steeply in proportion to the ratio of elevator use, which is ranging from 0 second to 6,122 seconds. From this figure, it is seen that the lines of evacuation times by emergency-use elevators and by egress stairs are crossing around 25% in elevator-use ratio and therefore it is suggested that the evacuation by elevators is preferable only if a small part of occupants such as 25% or less of the occupants on the floors in D-Bank use emergency elevators that are available even in a fire. 5. Concluding Remarks In order to examine the feasibility of elevator evacuation using a typical high-rise building, we conducted case studies with our simulation model of elevator operation and the model for evacuation by stairs, mainly focusing upon the efficiency of transportation of occupants. Although within the compass of the conditions of elevator service operation described in this paper, the results of case studies are 244

summarized as follows. 1) If all occupants in each bank try to use emergency-use elevators for their evacuation, it takes much longer time than the cases of evacuation by regular elevators as well as the cases by egress stairs in every bank. On the other hand, evacuation time by egress stairs is quite similar to that by regular elevators in each bank. As evacuation by egress stairs is much safer than the evacuation by regular elevators, so it is recommended that most of general people on the floors in a fire bank should better use fire/smoke proof egress stairs except the people who have difficulty to use stairs in their evacuation. 2) We could not distinguish a clear difference in terms of transportation efficiency between the two operational modes of emergency-use elevators such as the mode(a) that priority is given to the floors above a fire floor first and the mode(b) that priority is given to the highest floor first. However, for this purpose, we should take into account the influence of smoke spread in conjunction with floor height and/or time lapse after ignition in further studies. 3) The evacuation completion time by emergency-use elevators is increasing at a great rate in proportion to the elevator use ratio among the occupants on floors in D- Bank, when assuming that a fire occurs in D-Bank. Also, to compare with evacuation by egress stairs, the advantage of elevators use in terms of transportation efficiency appears in certain limited conditions such as 25% or less of elevator use ratio among the occupants on floors in D-Bank. In conclusion, if the elevator-use group can be designated only for a small part of occupants such as disabled people, it would be effective for those people to use fire/smoke proof elevators in evacuation. However, for other general people, it would be better to use egress stairs for their evacuation in most cases as well as to let the evacuation of disabled people by elevator more effective. In the future, the model improvement and further analyses are needed, considering variety of number and attributes of occupants, operational modes of elevators, hazard potential of smoke exposure to occupants, and so forth. 6. Acknowledgements The authors gratefully acknowledge the courtesy of Mr. Kimio Tanabe, Mitsubishi Electric Corporation who provided advices on elevator operations and the collaboration of Dr. M. Nakano, Dr. K. Kubota, and Dr. Y. Ohmiya in making the data of evacuation behavior of the occupants in the Hiroshima Motomachi high-rise apartments fire. References 1. A. Sekizawa, M. Ebihara, H. Notake, K. Kubota, M. Nakano, Y. Ohmiya, and H. Kaneko, "Occupants Behavior in response to the High-rise Apartments Fire in Hiroshima City", Proceedings of the First International Symposium on Human Behaviour in Fire, pp.147-156, Belfast, Northern Ireland, 1998. 2. S. Nakahama, Y. Ikehata, and H. Hayashi, "Study on Availability of Evacuation by an Elevator in Consideration of the Aged People - Example of the Hiroshima Motomachi High-rise Apartment Fire", Journal of Japan Association for Fire Science and Engineering (KASAI), Vol.48 No.3, pp. 44-49, in Japanese, June 1998. 3. A. Sekizawa, S. Nakahama, M. Ebihara, H. Notake, and Y. Ikehata, Study on Feasibility of Evacuation by Elevators in a High-rise Building Case Study for 245

the Evacuation in the Hiroshima Motomachi High-rise Apartments--, Proceedings of the Second International Symposium on Human Behaviour in Fire, pp.65-76, Boston, USA, 2001. 246