Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350

Similar documents
Owner s Manual Refrigerated Compressed Air Dryers Model F-100

Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532

Owner s Manual Refrigerated Compressed Air Dryer Model F-50

Owners Manual Refrigerated Air Dryer MHT SERIES

OWNER/OPERATOR MANUAL COMPONENTS, INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

Rev. A AUGUST 2012 RNP SERIES REFRIGERATED COMPRESSED AIR DRYERS OPERATOR MANUAL RNP25 RNP35 RNP50

Owners Manual UA75 TO UA1200 SERIES Refrigerated Air Dryer

PROdry. High Inlet. Temperature. refrigerated. compressed air. dryers. Contents. For Sales & Service please contact:

DRYMAX DRYMAX DRYMAX DRYMAX

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

NEWGATE TECHNOLOGIES, INC.

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

InstructIon Manual KrEs EQuIPMEnt stands

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Horizontal Bottle Cooler Installation and Operation Manual

GRF-SERIES REFRIGERATION TYPE NON CYCLING STANDARD

RNP SERIES 33 F 39 F 1 C 4 C OFF OPERATOR MANUAL

Rev. None AUGUST 2012 MDM SERIES MODULAR MEMBRANE AIR DRYERS OPERATOR MANUAL MDM1 MDM4 MDM9 MDM13 MDM24 MDM49 MDM66 MDM106 MDM138

MANUAL 8/12/05. Model BKP TM 100 INSTALLATION, OPERATION & MAINTENANCE. Commercial High Efficiency Heat Pipe Dehumidifier

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

DHW Series INSTRUCTION MANUAL. Pressure Swing Desiccant Compressed Air Dryer Models 7 through 50 scfm

3800 North Mill Road Vineland, NJ USA Tel: Fax: Web: Rev. A

REFRIGERATED DROP-INS (2-6)FT-DI Installation and Operating Manual

Parts and Service Manual BURNISHER MODEL: MR , MR , MR , MR

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL

Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC iers.com

SANI-VAC MODEL #750 WARNING! FOR YOUR SAFETY PLEASE READ INSTRUCTIONS BEFORE OPERATING TOOL. & WEAR EYE PROTECTION

EBAC MODEL BD-150 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Blue Air. Commercial Refrigeration Inc. Installation & Operation Manual Ice Cream Freezers

FAN-FORCED UTILITY HEATER

Operating Instructions Manual. Condensate Separators. Models 4GNL3 thru 4GNL9 and 53RG84 thru 53RG95

CHILLER. Model CH3000. Operator s & Installation Manual

Installation & Operation Manual Ice Cream Freezers

EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System

DRY-PAK INDUSTRIAL AIR DRYER Installation and Instruction Manual

Milk Coolers Installation and Operation Manual Please read this manual completely before attempting to install or operate this equipment!

MODEL MW200 MODEL MW600 AIR DRYER

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

OPERATING INSTRUCTIONS

RecoverX-CAR Contaminated Automotive Refrigerant Recovery System Operation and Maintenance Manual

WCPT-3 and WCPT-4. Effective Date: 2017 IMPORTANT INFORMATION READ BEFORE USE. Drop-in Display Cases

PDF Created with deskpdf PDF Writer - Trial ::

EBAC MODEL NEPTUNE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

MIGHTY PRO 1/4 HP CHILLER

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

T-Series Air Conditioner T15 Model

Superdryer Dehumidifiers

RPI Industries, Inc.

VSA Series Air Dryer. User s Guide

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

CH250 AND CH251 CHILLERS

R Series Cooling Modules

HYBRID DRYER. PDH1 - PDH2 Series. Save These Instructions

OWNER S MANUAL FINLEY FIREPLACE. Product code: UPC code: Date of purchase: / /

CH750, CH751 & CH951 CHILLERS

Refrigerated Air Dryers

RPI Industries, Inc.

Henny Penny Island Warmer Model HMI-103 Model HMI-105 TECHNICAL MANUAL

DR Series. Installation & Operations Manual. Model: DR-10 HIGH OUTPUT SHOCK TREATMENT OZONE GENERATOR

BLOCK ICE MAKERS BY DELTA ICE, AIR AND HEAT INC.

INGERSOLLrAND AIR COMPRESSORS CAUTION: HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS

Compressed Air Dryer

Refrigerator Freezer Installation and Operation Manual

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS

PORTABLE AFTERCOOLER MODEL CA-350 PORTABLE AFTERCOOLER/FILTER AFTERCOOLER OPERATION MANUAL

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER

Noncycling Refrigerated Air Dryers Range AD 10 to AD 4000

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

XC Portable Air Conditioning

Turbo Air Speed up the Pace of Innovation TBB-4SB CAUTION! PLEASE KEEP POWER SWITCH ON BEFORE OPERATING THIS EQUIPMENT

A2Z Ozone, Inc. PRODUCT MANUAL

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model ABM - 700

MDH Series Air Dryer. User s Guide

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

INSTALLATION AND OPERATING MANUAL

ProAir CR23 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

CD30 / CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

2001 Smith Eastern Corporation

HYBRID DRYER. PDH1 - PDH2 Series WARNING: OPERATOR MUST READ AND UNDERSTAND THIS MANUAL COMPLETELY BEFORE OPERATING THIS EQUIPMENT.

Humidistat-Thermostat

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

Instruction Manual Refrigerated Counter Top Displays

INSTALLATION AND OPERATING MANUAL

COMMERCIAL REFRIGERATOR INSTRUCTION MANUAL

COMMERCIAL REFRIGERATOR INSTRUCTION MANUAL

ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER

INSTALLATION & OPERATING INSTRUCTIONS MODEL #17900 KEGERATOR MANUAL

TG-10 Wall Mount Installation and Operation Manual. High Output Ozone Generator

INSTALLATION AND OPERATING MANUAL

Transcription:

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage. Retain instructions for future reference. WARNING: Air treated by this equipment is not suitable for breathing without further purifi cation. Refer to O.S.H.A. standards for the requirements for breathing quality air. Figure 1 - F-200, 250, 300 & F-350 ARROW DRYERS 745 CLARK AVE. BRISTOL, CT 06010 TOLL FREE: (877) 640-8300 Form F-0042A Revised 11/04

3 6 2 9 10 8 7 1 4 5 11 1) Heat Exchanger/Separator 2) Compressor 3) Expansion/Control Valve 4) Refrigerant Filter 5) Hot Gas Valve 6) Fan Motor 7) Power On Light/Switch 8) Dew Point Indicator 9) Drain Alarm Light 10) Drain Override 11) Drain 1

Receiving and inspection Arrow Dryers are carefully prepared for shipment at the factory to protect them from damage in transit. Dryers are shipped F.O.B. factory. Immediately upon arrival, check the dryer for possible damage. If damage is found, report it to the carrier and file a damage claim. Check the dew point indicator gauge. If the dew point indicator gauge reads zero, it indicates a possible refrigerant leak. Notify your dealer immediately. Be sure you have the right dryer. Check the nameplate for voltage and amperage How the Air Dryer Works Compressed air enters the inlet and passes through the air-to-air heat exchanger where the air is partially cooled by the exiting cold air. Next, the air passes through a refrigerant-to-air heat exchanger where it is cooled to near the freezing point of water. As the air is cooled, it loses the capacity to hold water vapor. The water vapor condenses into water droplets and drains to the separator. Passing through the separator, air flow slows down and causes more water to condense and collect in the bottom of the separator bowl. The water is exhausted by the automatic drain. The compressed air, now at a pressure dew point of 35ºF, leaves the dryer through the air-to-air heat exchanger where it is heated by the incoming air. Location and Installation Locate the dryer indoors in a protected area where ambient temperature will range between 45ºF and 100ºF. Dryers are usually located near the compressor. Do not cycle the dryer with the compressor. If an aftercooler is used after the compressor, install the dryer downstream of the aftercooler and receiver (see figure 2). Install the dryer so that there is sufficient room around it to permit circulation of air through the refrigeration condensing unit. Allow for easy access into the dryer through the cover panel. Check the nameplate for voltage and amperage. The dryer is furnished with a 6 foot electrical cord for connection to a grounded outlet. Be sure that the compressor air passes through the dryer in the proper direction. Connect the compressed air lines to the inlet and outlet connection as marked on the cabinet. Connect the air lines with standard pipe fittings. The mechanical separator has an automatic zero loss drain with a 1/2 drain line connection located on the outside of the dryer cabinet. It is recommended that a bypass line is piped around the dryer. Shutoff valves should be installed at both inlet and outlet, with another valve in the bypass line. This complies with O.S.H.A. lockout regulations and permits the dryer to be removed from the system or serviced without turning off the air supply. Typical Compressed Air Systems Figure 2 2

Dimensions F-200, 250, 300 & F-350 Air Dryer ARROW F-200, 250, 300 & F-350 Wiring Diagram 230/1/60 F-200, 250, 300 & F-350 Wiring Diagram 230/3/60-460/3/60 Specifications Model Power Capacity Dimensions Air Line Drain Net Max. Full L.R. No. Supply SCFM (Inches) Conn. Line H.P. Refrig Wt. Press. Load AMP @ 100 PSIG Length Height Width FPT Conn. Charge* Lbs. PSI AMP F-200-2 230/1/60 200 34 33 27 1 1/2 1/2 1 7 lbs. 275 175 11.75 56.0 F-200-3 230/3/60 200 34 33 27 1 1/2 1/2 1 7 lbs. 275 175 10.4 65.5 F-200-4 460/3/60 200 34 33 27 1 1/2 1/2 1 7 lbs. 275 175 3.59 25.0 F-250-2 230/1/60 250 34 33 27 1 1/2 1/2 1 1/4 9 Lbs. 295 175 12.4 61 F-250-3 230/3/60 250 34 33 27 1 1/2 1/2 1 1/4 9 Lbs. 295 175 9.1 55 F-250-4 460/3/60 250 34 33 27 1 1/2 1/2 1 1/4 9 Lbs. 295 175 10.2 51 F-300-2 230/1/60 300 34 33 27 1 1/2 1/2 1 1/4 9 1/2 Lbs. 295 175 12.4 61 F-300-3 230/3/60 300 34 33 27 1 1/2 1/2 1 1/4 9 1/2 Lbs. 295 175 9.1 55 F-300-4 460/3/60 300 34 33 27 1 1/2 1/2 1 1/4 9 1/2 Lbs. 295 175 10.2 51 F-350-2 230/1/60 350 34 33 27 2 1/2 1 1/2 9 1/2 Lbs. 315 175 16 82 F-350-3 230/3/60 350 34 33 27 2 1/2 1 1/2 9 1/2 Lbs. 315 175 9.4 66 F-350-4 460/3/60 350 34 33 27 2 1/2 1 1/2 9 1/2 Lbs. 315 175 4.7 33 CFC-Free R-134A NOTE: The air leaving the dryer is reheated to 25 F below the inlet air temperature 3

Design Conditions The Dryer must not be cycled with the air compressor. The dryer is non-cycle and is designed to run continuously (even under light loads). If the compressed air system remains pressurized and the air compressor cycles off and on to maintain line pressure, the dryer should remain in operation to keep the air lines dry. Air Flow SCFM: The rated air flow (SCFM) of the dryer is designed for 100 PSIG. Above the rated air flow, the dew point will rise and moist air may reappear downstream. The dryer may cycle off and on under excessive load and cause compressor damage. Inlet Air Temperature: The dryer will function normally up to 100ºF. Above this temperature, the dryer capacity will fall off. Inlet air temperature should be controlled so that it does not exceed 100ºF. How to Make Minor Refrigerant Suction Pressure Adjustments 1) Keep the dryer running under no load and turn off or bypass the compressed air. 2) Remove the dryer cover and locate the control valve (See Figure 3). 3) Remove cap. With 5/16 allen wrench a turn clockwise to increase or counterclockwise to decrease the suction pressure (1/4 turn will normally be enough). Wait 3 to 4 minutes for the suction pressure to settle. Repeat if needed. Replace cap when adjustments are completed. Figure 3 Line Pressure: The maximum design pressure is 175 PSIG. Ambient Air Temperature: Locate the dryer indoors in a protected area where the ambient temperature will range between 45ºF and 100ºF. Note: Above an ambient temperature of 100ºF the refrigerant will rise until the dryer shuts down. Several off and on cycles under these conditions will damage the compressor. Automatic Expansion Valve: The automatic expansion valve regulates the refrigerant suction pressure. The expansion valve is factory set between 33 and 36 PSIG. Start UP 1) On initial start-up of system check electrical connections to the dryer, as well as the air piping, so inlet and outlet piping are connected to correct ports. 2) Check panel mounted Dew Point Indicator gauge before starting. The indicator must read above the green area and into the high red section. 3) When ready to operate the compressed air system, the dryer should be started before air compressor is started. 4) When closing the start switch the indicator light on the front panel of dryer will show there is power to the refrigeration compressor. The dew point indicator will slowly drop and hold within the green area the gauge. 5) When pressure has dropped to this level the air compressor can be started and air flow can begin. NOTE: All dryer models are designed to operate without compressed air load in order to pre-cool the heat exchanger surface. Maintenance and Care NOTE: Refrigerant air dryers require relatively little maintenance if they are used accordance with the installation and operating instructions. Cleaning Fin Surface NOTE: These are air cooled refrigeration systems and depend upon cooling air drawn from the area around the dryer for efficient operation. 1. Inspect the fin surface of the condenser regularly and keep it free of dust, lint or paper. NOTE: A vacuum cleaner or low pressure air hose can be used for regular and normal maintenance of the fin surface. 2. Machine shop applications with oil vapor in the room air may require cleaning with fin surface cleaners available from refrigerant supply houses. Automatic Drain Operation This air dryer is equipped with an automatic zero loss drain. The condensate which has been collected from the wet compressed air is stored in a separator and controlled with a float level device that will automatically trigger the opening of a drain solenoid valve discharging the stored condensate. On the front control panel there is a manual override button that will activate the drain manually when pressed. A drain alarm light has been installed on the control panel and will remain on when a malfunction occurs preventing the discharge of the condensate. NOTE: Operation of dryer is automatic and continuous. Refrigerant compressor does not cycle off and on. Discharge of condensate through drain is automatic. To Stop To stop the unit turn start-stop switch to off position. IMPORTANT: IF IT IS NECESSARY TO PROTECT THE AIR SYSTEM DURING NORMAL SHUT-DOWN THE IN- LET SHUT-OFF VALVE TO THE DRYER SHOULD BE CLOSED TO PREVENT WET AIR FROM ENTERING AIR SYSTEM. 4

TROUBLESHOOTING CHART Symptom Possible Causes(s) Corrective Action Unit will not run. 1. No Power. 1. Correct power supply, fuses, circuit breaker. 2. Internal compressor overload. 2. Feel the temperature of the compressor and allow to cool off if hot. Observe the fan motor. Have the motor checked if it does not run. Clean the condenser. Dew Point Indicator Red Area High 1. Internal compressor overload. 1. Check for air overload. Check inlet air temperature. Check operation of fan motor. 2. High ambient temperature. 2. Check room temperature and hold between 45 F and 100 F. Indicator light off No power to the dryer. Check power supply, fuses, circuit breaker. Dew Point Indicator Red Area Low 1. Low refrigerant charge. 1. Have qualified refrigeration service technician check out dryer or call factory. 2. Low ambient temperature. 2. Relocate dryer to heated area between 45 F and 100 F 3. Low hot gas valve setting. 3. Re-adjust hot gas valve to the green area on the dew point indicator gauge. (See minor pressure adjustments) High pressure drop 1. High air flow. 1. Air flow above rated flow of dryer. 2. Drain valve not discharging. 2. Manually blow down drain until water flow stops. Clean drain. 3. Freezing moisture in evaporator. 3. Re-adjust hot gas valve to the green area on the dew point indicator gauge. (See minor pressure adjustments) 4. Plugged separator element or drain. 4. Clean or replace. Water downstream of dryer 1. Compressed air is flowing through 1. Dryer must be operating 5-10 dryer before it is turned on. minutes before compressed air load. 2. Dirty separator element or drain. 2. Disassemble and clean. 3. Overload dryer above air flow 3. Reduce air load to dryer capacity. specifications.* 4. High suction pressure. 4. Inlet air temperature too hot. 5. Low outlet air pressure. 5. Freezing of water, adjust suction pressure.* 6. Low refrigerant charge. 6. Contact service technician to leak check. NOTE: Check or repairs of the refrigeration system must be done by a qualified refrigeration service technician with the required gauges and other equipment. *All adjustments must be made under no compressed air load. 5

If Trouble Starts If the dryer cycles off and on for any reason TURN OFF THE DRYER. Call the factory for instructions, Check or repairs of the refrigeration systems must be made by a qualified refrigeration service technician. Before calling the factory for instructions, have the following data to report. Model No. Serial No. Refrigeration Suction Pressure. REPLACEMENT PARTS Model F-200-2 F-200-3 F-200-4 Voltage 230/1/60 230/3/60 460/360 Compressor Make Copeland R-134A Copeland R-134A Copeland R-134A Refrigeration System *Condensing Unit 14673 14672 14602 *Compressor 14785 14786 14787 Expansion Valve 14546 14546 14546 Hot Gas Bypass Valve 91233 91233 91233 Refrigerant Filter 14517 14517 14517 Electrical Fan Motor 98945 98945 98949 Fan Blade 94941 94941 94941 Fan Switch 91639 91639 91639 Power On Light/Switch 97846 97846 97846 Low Pressure Switch 91287 91287 91287 Crankcase Heater 91616 91490 91616 Gauges *Dew Point Indicator 14765 14765 14765 Cabinet Panels Base Panel 14666 14666 14666 Cover Panel 14663 14663 14663 Back Panel 14667 14667 14667 End Panel Right Side Vented 14664 14664 14664 End Panel Left Side Vented 14665 14665 14665 Support Bracket Right 14661 14661 14661 Support Bracket Left 14662 14662 14662 *Replacement part for refrigeration service only 6

If Trouble Starts If the dryer cycles off and on for any reason TURN OFF THE DRYER. Call the factory for instructions, Check or repairs of the refrigeration systems must be made by a qualified refrigeration service technician. Before calling the factory for instructions, have the following data to report. Model No. Serial No. Refrigeration Suction Pressure. REPLACEMENT PARTS Model F-250-2 F-250-3 F-250-4 F-300-2 F-300-3 F-300-4 Voltage 230/1/60 230/3/60 460/360 230/1/60 230/3/60 460/360 Compressor Make Copeland R-134A Copeland R-134A Copeland R-134A Copeland R-134A Copeland R-134A Copeland R-134A Refrigeration System *Condensing Unit 14624 14626 14625 14624 14626 14625 *Compressor 14779 14780 14781 14779 14780 14781 Expansion Valve 14515 14515 14515 14515 14515 14515 Hot Gas Bypass Valve 91233 91233 91233 91233 91233 91233 Refrigerant Filter 14517 14517 14517 14517 14517 14517 Electrical Fan Motor 94935 94935 101934 94935 94935 101934 Fan Blade 98946 98946 98946 98946 98946 98946 Fan Switch 91639 91639 91639 91639 91639 91639 Power On Light/Switch 97846 87846 97846 97846 97846 97846 Dual Pressure Switch 91645 91645 91645 91645 91645 91645 Gauges *Dew Point Indicator 14765 14765 14765 14765 14765 14765 Cabinet Panels Base Panel 14666 14666 14666 14666 14666 14666 Cover Panel 14663 14663 14663 14663 14663 14663 Back Panel 14667 14667 14667 14667 14667 14667 End Panel Right Side Vented 14664 14664 14664 14664 14664 14664 End Panel Left Side Vented 14665 14665 14665 14665 14665 14665 Support Bracket Right 14661 14661 14661 14661 14661 14661 Support Bracket Left 14662 14662 14662 14662 14662 14662 *Replacement part for refrigeration service only 7

If Trouble Starts If the dryer cycles off and on for any reason TURN OFF THE DRYER. Call the factory for instructions, Check or repairs of the refrigeration systems must be made by a qualified refrigeration service technician. Before calling the factory for instructions, have the following data to report. Model No. Serial No. Refrigeration Suction Pressure. REPLACEMENT PARTS Model F-350-2 F-350-3 F-350-4 Voltage 230/1/60 230/3/60 460/360 Compressor Make Copeland R-134A Copeland R-134A Copeland R-134A Refrigeration System *Condensing Unit 14627 14628 14594 *Compressor 14782 14783 14784 Expansion Valve 14515 14515 14515 Hot Gas Bypass Valve 91233 91233 91233 Refrigerant Filter 14517 14517 14517 Electrical Fan Motor 94935 94935 101934 Fan Blade 98946 98946 98946 Fan Switch 91639 91639 91639 Power On Light/Switch 97846 87846 97846 Control Transformer ---------- 91390 91390 Dual Pressure Switch 91645 91645 91645 Gauges *Dew Point Indicator 14765 14765 14765 Cabinet Panels Base Panel 14666 14666 14666 Cover Panel 14663 14663 14663 Back Panel 14667 14667 14667 End Panel Right Side Vented 14664 14664 14664 End Panel Left Side Vented 14665 14665 14665 Support Bracket Right 14661 14661 14661 Support Bracket Left 14662 14662 14662 *Replacement part for refrigeration service only 8

NOTES:

NOTES:

ORDER REPLACEMENT PARTS BY CALLING (877) 640-8300 Please provide following information: Model Number Serial Number (if any) Part Description and Number Address parts correspondence to: ARROW DRYERS 745 Clark Ave. Bristol, CT 06010 WARRANTY POLICY When used under the conditions recommended by the manufacturer, Arrow Dryers, this model is warranted to be free from defects in material and workmanship for a period of twenty-four (24) months from date of receipt, not to exceed thirty (30) months from the factory ship date, provided Arrow is furnished the customer s name, address, and date of shipment information These units will utilize either a braze plate or modular type heat exchanger which will be warranted for five (5) years. This warranty is limited to the replacement of the heat exchangers, F.O.B. Factory, and subject to the same restrictions as outlined below concerning misuse, abuse or accident. The automatic drain carries a 90-day warranty. This warranty will apply to equipment installed, operated and maintained in accordance with the procedures and recommendations as outlined in the owner s manual published by Arrow Dryers. During the life of this warranty, Arrow Dryers will repair or replace (at Arrow Dryers option) any defective part or assembly, free of charge, F.O.B. its plant if such defect occurred in normal service and was not due to apparent misuse, abuse or accident. Any warranty service performed in the field must be authorized by Arrow Dryers, Unauthorized service voids the warranty and any resulting charge will not be paid by Arrow Dryers. Arrow Dryers makes no other warranties or guarantees, expressed or implied. The merchantability of the components is expressly excluded. The manufacturer assumes no liability for indirect or consequential damages. 9