INSTALLATION & OPERATING MANUAL CWA2 Chilled Water Air Handler with Electric Heat 18,000 60,000 BTUH

Similar documents
CWA4-HW (4-Pipe) Rev. 1.2

CWA4 Chilled & Hot Water Fan Coil

CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

1-WAY CEILING CASSETTE FAN COIL UNIT

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER

CAUTION WARNING INSTALLATION INSTRUCTIONS FOR HEALTHY CLIMATE WHOLE HOME DEHUMIDIFIER MODEL HCWH-065 (Y3013) DEHUMIDIFIERS

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Model 1750A/ 1770A Dehumidifier Installation Instructions

Model 1820 Dehumidifier

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

AllStyle Coil Company, LP 7037 Brittmore Houston, TX Phone Fax

B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

Safety and Installation Instructions Model 1700

Installation Instructions

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2

R-410A. Installer s Guide WARNING: 18-GE04D2-5

Installation, Operating & Maintenance Instructions. Horizontal Models: LH & HL

Installer s Guide Convertible Air Handlers 1-1/2 5 Ton

Ceiling Concealed Fan-Coil Unit

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

Installation Instructions

AHG**-0B Series Hydronic Air Handling Units

VERTICAL MOUNT AIR HANDLERS

INSTALLATION INSTRUCTIONS Apartment Fan Coil

AQUASTYLUS Chilled Water Fan Coil Convertible Type CFEA Series 50/60 Hz

REFRIGERATED PREP TABLES Installation, Operation and Maintenance Instructions

B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor

CFFWA4P-12-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 36,000 BTUH

Installation Instructions

CFFWA4P-16-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 48,000 BTUH

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

CFFWA4P-08-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 24,000 BTUH

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

BARD MANUFACTURING COMPANY, INC. W24G-W60G Gas Heat/Electric Cooling Engineering Specification Guide

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation.

WineZone Ceiling Mount Ductless Split 15

CB18/CBS18 Bulletin # September 1994 Supersedes August 1986

Installation Instructions

BARD MANUFACTURING COMPANY, INC. WG3S-WG5S 2-Stage Cooling with Gas Heat Engineering Specification Guide

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier

INSTALLATION INSTRUCTIONS

UPFLOW/DOWNFLOW COILS

MODELS B1PA024, 030 AND 036

T-Series Air Conditioner T20 Model

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES

T-Series Air Conditioner T15 Model

MERIT Series R-410A - Upflow / Horizontal

Installation Instructions

F, P Series Multi-Position Air Handler Electric or No Heat, with available 5-Speed High Efficiency ECM Motor

Installation in Standard & Variable Speed Indoor Air Handlers IMPORTANT

Installation Instructions

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

INSTALLER S GUIDE WARNING: TWE-IN-2A 18-GE02D1-3. Convertible 1 ½ - 5 Ton Air Handlers WARNING HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

INSTALLATION INSTRUCTIONS

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

Installation Instructions

Installation Instructions

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS FOR RCQD COILS

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

ELECTRIC COUNTERTOP DECK OVEN INSTALLATION & OPERATING MANUAL

Model DEHXXCDA1070 & DEHXXCDA1095 Dehumidifier Installation Instructions

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

AHP SERIES INSTALLATION INSTRUCTIONS ELECTRIC FURNACES / AIR HANDLERS

Installation & Operation Manual

OWNER/OPERATOR MANUAL COMPONENTS, INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS

Installation Instructions

MH1WC4W-06-1-B Chilled/Hot Water 1-Way Cassette Fan Coil

90 HIGH EFFICIENCY DOWNFLOW/ HORIZONTAL GAS FURNACES

MERIT SERIES Up Flow / Horizontal

Product Data. FH4A Fan Unit. Sizes 001 thru 004

INSTALLATION INSTRUCTIONS

MERIT Series R-410A - Upflow / Horizontal

INSTALLATION INSTRUCTIONS GPM SERIES LOOP PUMP MODULES

SEISCO - MOUNTING CLEARANCES

T-Series Air Conditioner T53 Model

INSTALLATION INSTRUCTIONS APARTMENT FAN COIL UNIT FMA4X, FMA4P

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

90 HIGH EFFICIENCY DOWNFLOW/ HORIZONTAL GAS FURNACES

M3RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

OIL FIRED WARM AIR FURNACE. Homeowner Instructions

RECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS

INSTALLATION INSTRUCTIONS

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Installation Instructions

UNDERCOUNTER REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

Model 1870F Dehumidifier Installation and Operating Manual

Installation, Safety & Maintenance Manual Model 1750A/1770A

Transcription:

Rev. 1.2

-------------------------------------- CAUTION -------------------------------------- Care must be taken when handling sheet metal. Sheet metal parts have sharp edges and could cause injury. GENERAL Read the entire contents of this manual before beginning installation. Multiaqua assumes no responsibility for equipment installed contradictory to any code requirement or installation instructions. The components of this fan coil have been inspected at the factory and readied for shipment. Upon receiving the shipment a visual inspection of the packaging must be performed. If any damage to the packaging is discovered, an inspection of the components must be performed and noted on the delivery documents. If component damage is found a damage claim must be filed by the receiving party against the delivery party immediately. This product is designed and manufactured to permit installation in accordance with national codes. It is the installer s responsibility to install the product in accordance with national codes and/or prevailing local codes and regulations. Care must be taken to ensure the structural integrity of the supporting members, clearances and provisions for servicing, power supply, coil connections and/or condensate removal. Before the installation ensure the structural strength of the supporting members is sufficient. See Figure 1 for hanging weights of the fan coils. This unit is designed to be installed in a vertical or horizontal configuration. See Figure 2 for fan coil only dimensions. The coil hand of connection is field reversible. FAN COIL MODEL NUMBER Figure 1 APPROXIMATED WEIGHTS (lbs.) 18CWA2-00 118 24CWA2-00 118 36CWA2-00 145 48CWA2-00 170 60CWA2-00 180 2

Physical Dimensions (inches) Model Number A B C D E 18CWA2-00 17.50 21.00 39.75 12.50 16.00 24CWA2-00 17.50 21.00 39.75 12.50 16.00 36CWA2-00 17.50 21.00 39.75 12.50 16.00 48CWA2-00 21.50 25.00 49.75 17.25 19.50 60CWA2-00 21.50 25.00 49.75 17.25 19.50 Figure 2 E D C B A 3

-------- CAUTION ------- Care must be taken when handling sheet metal. Sheet metal parts have sharp edges and could cause injury. INSTRUCTIONS FOR INSTALLING FAN COIL The CWA2 is a chilled water fan coil with optional electric heat is designed for multi-position applications in closets, attics or basements or crawl spaces. They are field convertible to horizontal applications without the need for additional parts. Unit is not suitable for down flow applications. Figure 3 Figure 3 & 4 CONVERTING FAN COIL TO RIGHT HAND DISCHARGE The CWA2 fan coil comes shipped from the factory assembled with a left hand air discharge configuration. Figure 4 Figure 4 1. To convert the fan coil to right hand discharge remove the three front panels. 2. Remove the three screws from the coil mounting brackets and pull entire A-coil assembly out of the fan coil. Figure 5 Figure 5 4

3. Remove the horizontal drain pan from the coil and re-install it on the other side. Figure 6 & 7 4. Ensure the coil mounting brackets are secure in order to avoid coil misplacement inside the cabinet. Check coil slope to make sure that the drain pan slopes toward the drain outlet. An incorrectly installed coil could result in damages to the fan coil and property. Figure 6 5. Re-install the three front panels previously removed in step 1. 6. The unit shall be suitable for 0 clearance to combustible materials. Sufficient clearance must be provided at the front of the fan coil to allow access for maintenance and servicing. 7. The fan coil comes with one primary and one secondary condensate drain connection per configuration. Ensure when connecting the field installed condensate drain lines, the lower of the two fan coil drain connections is piped into the buildings condensate removal method. Figure 8 & 9 SECONDARY DRAIN PRIMARY DRAIN Figure 7 UP FLOW DISCHARGE Figure 8 5

8. The A coil includes an L-shaped piece of sheet metal with one leg of the L covering the top length of one coil slab; the other leg is between/inside the two slabs. Figure 10 When converting the unit to righthand horizontal discharge, the L- shaped piece of sheet metal should be removed, re-positioned and installed so that it covers the length of the top coil slab. This will force any condensate on the end of the top coil slab to run down the inside leg before dripping onto the lower slab. This will also help to prevent any possible condensate water blow off. Figure 11 SECONDARY DRAIN PRIMARY DRAIN HORIZONTAL DISCHARGE Figure 9 Figure 10 Figure 11 6

ELECTRICAL 9. All duct work must be installed per local and national codes. The return air duct and the return air opening provided in the fan coil must have the same area. Figure 12 & 13 All wiring must comply with local and national codes. High and low voltage terminal blocks are provided. An electrical plug is provided for the field installation of electric heat packages. Knockouts are provided in the cabinet for field wiring of the electrical. See page 8 for electric heat package installation instructions. A = High Voltage terminal block. B = Electric Heat Package Connection Plug. C = Low Voltage Terminal Block. CONTROLS Figure 14 B Figure 12 CWA2 Inlet Air Dimensions A B 18CWA2-00 15 17.5 24CWA2-00 15 17.5 36CWA2-00 15 17.5 48CWA2-00 19.25 22.25 60CWA2-00 19.25 22.25 Dimensions are in inches Figure 13 A A 24 VAC transformer, fan relay and electric heat sequencer are provided inside cabinet. All supplied controls are wired onto the low voltage terminal block. B A C Figure 14 7

8

PIPING 10. This fan coil is supplied with one water coil that can be used for chilled and/or hot water. The coil has one dedicated water inlet and outlet. Ensure that both lines are insulated according to local and national building codes. Figure 15 11. Condensate drains must be installed with at least.25 of slope per foot away from the fan coil. Since the drain pan is located on the suction side of the blower, a minimum trap of 1.5 must be installed in the drain line for proper drainage. ROUTINE CHECK UP AND SERVICE This product is designed to provide many years of dependable, trouble free comfort when properly maintained. Proper maintenance will consist of routine filter cleanings/changes, biannual check-ups that include but not limited to filter inspections, electric heater inspections /cleaning of the internal electrical and heat transfer components by a qualified service technician. Failure to provide periodic check-ups and cleaning can result in excessive operating cost and/or equipment failure. INLET OUTLET Figure 15 9