Refrigeration air dryer

Similar documents
Thermoelectric Bath. Series HEB

CKD refrigerating type dryer

HEB Series. Peltier-Type Thermoelectric Bath

Thermoelectric Bath. Series HEB

VRA2000 Series Port size: Rc1/4, Rc3/8, G1/4, G3/4, 1/4NPT, 3/8NPT

% by up ctoond re-heater and

MEMBRANE AIR DRYERS CONTENTS ACCESSORIES GENERAL CATALOG AIR TREATMENT, AUXILIARY, VACUUM, AND FLUORORESIN PRODUCTS. Caution MEMBRANE AIR DRYERS

Refrigerated Air Dryers

Membrane Dryer. Air inflow rate KMM Series to m 3 /min

HEB Series. Thermoelectric Bath

DOUBLE EFFECT ABSORPTION CHILLERS

Refrigerated Compressed Air Dryer

Refrigerated Air Dryers

Owners Manual Refrigerated Air Dryer MHT SERIES

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER

FUTURE AIR SOLUTIONS OIL FREE SCROLL COMPRESSORS

Refrigerated Air Dryers

TUBE DRYERS CONTENTS ACCESSORIES GENERAL CATALOG AIR TREATMENT, AUXILIARY, VACUUM, AND FLUORORESIN PRODUCTS. Caution TUBE DRYERS

Refrigerant air dryers. FD series ( l/s, cfm)

Refrigerated Air Dryers VF Series. DHT Series. Non-Cycling 10-2,000 scfm scfm

GTX Series Thermal Xchange Cycling Refrigeration Dryers GREAT LAKES AIR ANDARD ELECTRONIC DRAIN 5 -YEAR WARRANTY F PRESSURE DEWPOINT

BOGE AIR. THE AIR TO WORK. Refrigerant Dryers RA Series

White paper Compressed air drying

Chapter 9: The basics of air preparation

Cold Energy Saver. Thermal Mass Cycling Refrigerated Air Dryers ( scfm)

INDUSTRIALS GROUP. Refrigerant Dryers. Innovative Compressed Air Treatment Solutions GDD Series

Owners Manual UA75 TO UA1200 SERIES Refrigerated Air Dryer

Refrigerated Air Dryer

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Refrigeration dryers for energy efficient compressed air quality

Membrane Dryers KMM Series

Compressed air preparation Compressed air storage Moisture management. Catalog #1

CRV Variable Operation Refrigeration Dryers scfm

Easy dry line REFRIGERATION AIR DRYERS. With VSCC exclusive patented variable speed system

How to deal with ...R410A MITSUBISHI ELECTRIC R32 R125 R410A AIRCONDITIO NING

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

Scroll Water Cooled Chiller

120D, 150D, 190D, 240D, 370B. How to Order 220V 240V 400V 440V. Note 1) Select one applicable voltage. Voltage. Voltage. Symbol. Model 370B 220V 240V

Refrigerated Air Dryer

Screw Water Cooled Chiller SCW210

REFRIGERATED AIR DRYERS

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250

Refrigerated Air Dryers

High Inlet Temperature Air Dryer. Desiccant Air Dryer. Membrane Air Dryer After-Clooler. Air Filter. Oil-Water Separator Automatic Drain Value

HX Series. Compressed Air Dryers 10 to 2400 scfm. Setting a new standard in Quality and Reliability DRYMAX DRYMAX DRYMAX

DRYAIRE MEMBRANE AIR DRYING SYSTEM MODEL 6770

Membrane Dryers KMM Series

Refrigerated Air Dryer

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

next generation R 1 cycling refrigerated compressed air dryers flow capacity: scfm ( Nm 3 /hr)

GRF Series Non-Cycling Refrigeration Dryers ANDARD ELECTRONIC DRAIN STANDARD ELEC SS EXPANSION VALVE F PRESSURE DEWPOINT

F Series - Refrigeration dryers

Refrigeration Dryers TG TI Series

BURAN BURAN. Refrigeration Compressed Air Dryers for volume flows from 20 to 850 m³/h

Part IV: Flow Side Components Flow Diagram

Vacuum unit ideal for controlling large flow rates Vacuum unit VSQ/VSQP series

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Refrigerated Air Dryer

WAEC Sample Questions and Schemes - Uploaded online by AIR-CONDITIONING AND REFRIGERATION

Aquair BCP. Pool air handling units. Electronic Control Optimized energy consumption DESCRIPTION PRINCIPLE SCHEMES RANGE OPERATING LIMITS

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Introduction of Panasonic CO2 refrigeration system. Panasonic Corporation Refrigeration and Air-Conditioning Devices Business Division

.2 Section Waste Management and Disposal.

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e.

AIR COOLED MINI CHILLER

Reliable technology ensures maximum customer satisfaction. M Correction of SERVICE MANUAL HDSE08-1

Mountable in a 19-inch rack

LG HVAC SOLUTION AIR COOLED SCROLL CHILLER

Refrigeration System with a Capillary Tube and a Thermostat

Module 7: Air Supply System

CHAPTER 4. HVAC DELIVERY SYSTEMS

Climate Control System

Rotary type Oil-free Air Compressor General Catalogue. Oil-free Scroll Air Compressor Oil-free Claw Air Compressor

The Highest Quality Compressed air treatment Refrigerant dryers CFM 0.33 to 91.1 M/min

HEATLESS REGENERATED ADSORPTION DRYER ULTRAPAC SMART

Product Data Sheet Refrigeration Dryer DFLO 66 (-W) bis DFLO 2400 (-W)

Heat pump and energy recovery systems

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A10

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

(2) 325 tpd York Chlorine Liquefier Systems

Product Data Sheet Refrigerant Dryer DFLO-ES 66 (-W) to DFLO-ES 660 (-W) with energy saving management

INSTRUCTION AND MAINTENANCE MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Energy-Saving Refrigeration Dryers SECOTEC

Refrigerated Air Dryers

DAIKIN Huizhou Factory Profile

SCFM REFRIGERATED COMPRESSED AIR DRYERS. CRN Series

AKIMist E Dry Fog Humidifier General Installation Manual

Membrane Air Dryer. Dew point indicator. Fitting to exhaust purge air for dew point checker. Purge air discharge fitting for dehumidification

MDX. Non-Cycling Refrigerated Compressed Air Dryers with Intellidrain Condensate Drain Trap. Operation & Maintenance Manual

REFRIGERATED AIR DRYERS

SECTION AIR COMPRESSORS AND ACCESSORIES

NON-CYCLING REFRIGERATED AIR DRYERS. RNC Series

OACS Outdoor Air-Cooled Central Chillers

Moisture can be very disruptive to a dust. Preventing moisture problems in your dust collector

Transcription:

Principle of refrigeration air dryer Pneumatic circuit (System diagram) Warm wet water is precooled by compressed air chilled and dehumidified by air balancer (A) (precooler). Precooled compressed air is led to cooling chamber (B) (evaporator) and cooled to a pressured dew point of 10 C (min. 3 C) by cold Freon gas vapor. Water vapor in cooled compressed air condenses and changes into water drops (drainage). This drainage is automatically drained by automatic drain (C). Compressed air cooled in cooling chamber (B) is led to air balancer (A) (reheater) again, and is heated again by warm compressed air from the inlet. This becomes warm dry air and is discharged from the air outlet. A B Air inlet Air outlet Pressurized Approx. 10 C dew point Refrigerating circuit C Hot, high-pressure Freon gas discharged from refrigeration compressor (D) is led to condenser (K), and is cooled from ambient temperature to condensed warm high-pressure liquid by condenser cooling fan (E). Warm high-pressure Freon liquid is led to filter dryer (H) where dirt and water in the refrigerant are caught. It is then compressed and expanded into specified low-pressure, low-temperature liquid (mist) by temperature automatic expansion valve (G) (or capillary tube), and led to cooling chamber (B) (evaporator). Low-pressure, low-temperature liquid (mist) led to the cooling chamber is thermally converted into warm wet compressed air, and is sucked into the cooling compressor as evaporated gas. (Capacity control valve (F) bypasses refrigerant gas when thermal load in the cooling chamber is lowered, and returns gas to the refrigeration compressor inlet. This suppresses the amount of refrigerant that flows into the cooling chamber, and prevents freezing from overcooling. When refrigeration compressor suction pressure drops below the set pressure, the valve opens automatically, and hot, high-pressure gas is bypassed. Thus, the refrigeration compressor can be continually run even in a no-load state. Fan control switch (J) is used to turn condenser cooling fan (D) ON and OFF and maintain high pressure (condensed pressure) at a constant range. This pressure switch activates when high pressure is detected. L D E F K G H I PS HP J M Functions of service parts No. A B C D E F G H I J K L M Name Heat Precooler/reheater exchanger Evaporator Automatic drain Refrigeration compressor Condenser cooling fan Capacity control valve Automatic expansion valve Filter dryer Receiver Fan control switch Condenser Accumulator High-pressure switch Operation Exchanges heat between hot, high-moisture compressed air and low-temperature compressed air. Cools compressed air with liquid refrigerant evaporative latent heat, and condenses water vapors to remove moisture. Automatically drains drainage. Compresses low-pressure refrigerant vapors and creates high-pressure refrigerant vapor. Sends cold air to condenser. When air flow drops, flows hot refrigerant gas to prevent overcooling. Depressurizes high-pressure liquid refrigerant to create low-pressure, low-temperature liquid. Filters out foreign matter from the refrigerant circuit. (Water, dirt) Collects refrigerant liquefied by the condenser, separates it into air and liquid, and feeds only liquid refrigerant to the automatic expansion valve. When high-pressure refrigerant pressure rises to the specified pressure, the cooling fan operates, and stops when pressure drops to the specified level. This controls refrigerant temperature. Cools hot, high-pressure refrigerant vapor to create high-pressure liquid refrigerant. Separates liquid refrigerant from vapor so liquid refrigerant cannot be sucked into the refrigerant compressor. Stops refrigerant compressor operation when high-pressure side refrigerant pressure rises to a specified pressure. 16

Features of CKD Refrigeration Air dryer 1 Highly efficient (excluding models such as RD-PRT) 2 New environmentally friendly refrigerant R407C integrated in all sizes (capacities) from small to extra-large units. 3 Energy saving (1) Low pressure loss - highest in the industry (2) Lower power consumption compared to conventional product even while using new refrigerant R407C 4 Stainless steel heat exchanger vessel (container) incorporated as standard from small to extra-large units. Small stainless steel plate heat exchanger incorporated 5 Forced discharge for accurately discharging drainage integrated as a standard from small to extra-large units Refrigerating Desiccant High polymer membrane dryer Air filter Automatic drain other (Module) (Separate) Small F. Precise Electro pneumatic 6 Dew point monitor allowing operation state to be confirmed quickly integrated as a standard from small to extra-large units Auxiliary Flow control valve 7 Dust filter provided as a standard on air-cooled condensers R22 refrigerant commonly used currently has a very low ozone depletion potential of 0.055, but is not zero. An international agreement has agreed to reduce the rate by 35% from 2004, and to completely abolish use by 2020. In some European countries, use has already been completely abolished. (Table 1) Table 1 Refrigerant (Freon) Sweden Germany Norway Netherlands Denmark Belgium Italy USA (new devices) Entire EU Worldwide Completely abolished by end of 1997 Completely abolished by end of 2001 Completely abolished by end of 2004 Completely abolished by end of 2008 Completely abolished by end of 2010 Completely abolished by end of 2015 Completely abolished by end of 2020 As of Sept. 1999 Table 2 New refrigerant to be used as replacement Application Car air-conditioner Electric refrigerator Room air-conditioner Package air-conditioner Low-temperature freezer Regulated refrigerant New refrigerant R12 R134a R12 R134a R22 R410A R22 R407C R502 R404A, R507A Silencer Check valve / others Joint / tube F. generator auxiliary / pad Mechanical dif. pres. Seating / close contact conf. Pressure for coolant for air Total air system Water cooling refrigerator for water Main line unit 17

Air-cooled type and water-cooled Refrigeration air dryers are generally categorized into air-cooled and water-cooled. Refer to the following explanation and select the model according to required applications and performance: The refrigeration air dryer uses evaporative latent heat of the refrigerant to cool compressed air and condense and remove moisture content. The refrigerant repeatedly changes from hot high-pressure gas to hot high-pressure liquid, low-temperature low-pressure liquid, low-temperature low-pressure gas, and to hot high-pressure gas while circulating within a set closed circuit. When evaporating and changing from a low-temperature low-pressure liquid to a low-temperature low-pressure gas, surrounding heat is lost, i.e., compressed air loses heat and cools. This is called the evaporator in the refrigerating cycle. Conversely, the cooling section is called the condenser. High-temperature high-pressure gas discharged from the compressor must be changed to hot high-pressure liquid. The refrigerant is forced-cooled to do so. Either air-cooled or water-cooledis used for forced cooling. Air-cooled (small to extra-large capacities) Air (outer air) is fed by a fan to refrigerant piping, to which fins are installed to improve conductivity, and is cooled. Air is cooled with air around the dryer, so efficiency is generally affected by air temperature. During summer, the place where the dryer is installed (compressor room) becomes very hot, so this method is not effective for cooling. The fan runs continually, but is still insufficient for cooling. In winter, air temperature is low, so the fan starts and stops to adjust the state so that air is not overcooled. Merits: (1) Maintenance is easy. The condenser's dust filter must be cleaned once every several months, but this only involves blowing with compressed air and does not require expertise. If the filter is heavily contaminated, it must be washed or replaced. (2) Only space required for taking in and exhausting air must be secured. Other installation work is not affected. Disadvantages: (1) The refrigerant's high pressure is adjusted by turning the fan ON and OFF, so it is hard to stabilize the high pressure side. It is also harder to stabilize the dew point compared to the water-cooled method. (2) Cooling performance is often insufficient in summer, and overloads easily occur. (3) A large amount of air is fed by the fan, so noise is high and dust often prsent. Heat exhaust (ventilation) may be required. * With the GT Series, the above disadvantages are improved by stabilizing the dew point using the variable control of the cooling fan. In addition, the refrigerating circuit has been strengthened to secure a maximum ambient temperature of 43 C. Water-cooled (medium to extra-large capacities) This cools refrigeration pipes with water, often using a plate or double pipe condenser. All CKD dryers have a stainless steel plated condenser having outstanding heat efficiency and durability. The cooling water rate is adjusted by the check valve on top of the cooling water pipe. The high pressure value of the refrigerant is detected, and valve opening is automatically adjusted by the pressure balance mechanical mechanism. Merits: (1) Cooling water is adjusted variably so high pressure stability is high, and it is easy to stabilize the dew point. (2) Cooling may be stabilized in summer so the system does not fail easily. Stable dew point performance is achieved through the year. (3) The installation environment is not affected. Dust does occur. The fan does not make noise. Heat is not discharged with discharged wind, so room temperature does not rise. Disadvantages: (1) Ancillary facilities, such as water piping, are required. (2) The condenser must be back-washed by qualified personnel once every 6 to 12 months. 18

Cooling water for water-cooled air dryer The following precautions must be observed for cooling water used for the water-cooled condenser in the refrigeration compressor. If the following water quality standards are not satisfied, performance may drop and condenser life could be reduced significantly. Refrigerating Desiccant High polymer membrane dryer 1 Cooling water quality must comply with Refrigerating and Air Conditioning Device Water Quality Guidelines set forth by the Japan Society of Refrigerating and Air Conditioning Engineers. Japan Society of Refrigerating and Air Conditioning Engineers Item ph Electric conductivity Chloride ion Sulfate ion Acid consumption (ph4.8) Total hardness Calcium hardness Ionic silica Iron Copper Sulfide ion Ammonium ion Residual chloride Free carbon Stability index Matson rate Hydrogen carbonate ion Oxygen rate Aluminum Manganese Nitrate ion Sodium ion Evaporation residue Turbidity Fe Cu S-- NH4+ Cl CO2 Chemical formula Cl- SO4-- SiO2 HCO3-/SO4-- HCO3- Al Mn NO3- Na+ PO4--- NH3 Mn++ H2S Cooling water containing many elements that could accumulate or sediment in the condenser or cooling water piping, or containing many corrosive elements must not be used. Soften hard water before using. 2 Install a strainer on the cooling water inlet. 3 Wash the condenser once or twice a year. Unit Water quality standards Water quality standards ph (25 C) ms/m (25 C) { S/cm (25 C)} 6.5 to 8.2 0.2 to 80 {2 to 800} 1 6.5 to 8.2 80 or less (800 or less) 1 CKD water-cooled dryer cooling water 0.5 or less No detection 4.0 or less 6.0 to 7.0 1.0 or more 0.1 or less 0.2 or less 0.1 or less 20 or less 2.0 or less 0.5 or less 10 or less 0.05 or less 2 or less Japan Society of Refrigerating and Air Conditioning Engineers Refrigerating and Air Conditioning Device Water Quality Guidelines Cooling water system - circulation - circulation water (JRA-GL-02-1994) No detection 4.0 or less 6.0 to 7.0 Air filter Automatic drain other (Module) (Separate) Small F. Precise Electro pneumatic Auxiliary Flow control valve Silencer Check valve / others Joint / tube F. generator auxiliary / pad Mechanical dif. pres. Seating / close contact conf. Pressure for coolant for air Total air system Water cooling refrigerator for water Main line unit 19

Refrigerating type air dryer Periodic inspection descriptions Please conduct following inspections periodically. Inspection descriptions Inspection term Every day Every week Every month Every 6 months Inspection points Inspection method Judgment standard Operation Operation light To be lighting at operation. confirmation Operating sound of compressor for refrigeration To be no abnormal noise Fan rotation To be no abnormal noise, and smoothly rotated. To be ON - OFF operation, or turned ON. Dew point (cooling) Dew point monitor To be in the green zone. temperature Inlet air pressure Air pressure gauge To be within product specifications. Drainage Cleaning Automatic drain Press the manual button. Fizz drain discharge noise (For forcible discharge type) or air blow noise must be heard during pushing manual button (GX, GT series) Ambient temperature Near capacitor intake Measure by a thermometer To be within specifications range. Capacitor Cleaning Air cooling Foreign matter or dirt must Clogging Capacitor fin section not be accumulated. Capacitor intake section must not be plugged. Capacitor intake section is not to be exposed to hot air. Water cooling To be 1.6 MPa or less Refrigerant high pressure (Washing is required for 1.8 gauge MPa and over.) Power voltage Power supply Measure by a tester To be within ±10% of specified rated voltage. Operating current Power supply Measure by a tester To be within ±20% of specified rated current. 22