AQUACIAT LD ILD. Use. Range. Water chillers Heat pump. AQUACIAT LD series. AQUACIAT ILD series. Heat recovery. Cooling only. Cooling and heating

Similar documents
DYNACIAT LG. Use. Range. Water chillers Heat pump. DYNACIAT LGN series. DYNACIAT LG series. Hydraulic module

AQUACIAT LD ILD. Use. Range. Water chillers Heat pump. AQUACIAT LD series. AQUACIAT ILD series. Heat recovery. Cooling only.

AQUACIAT LD ILD. Use. Range. Water chillers Heat pump. AQUACIAT LD series. AQUACIAT ILD series. Heat recovery. Cooling only. Cooling and heating

Compact and silent Scroll compressors All-season operation

DYNACIAT LG. Use. Range. Water chillers Heat pump. DYNACIAT LGN series. DYNACIAT LG series. Hydraulic module

HYDROCIAT LW. Use. Range. Water chillers Heat pump. Cooling capacity kw Heating capacity kw. HYDROCIAT LW, ST series

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

DYNACIAT POWER. High energy efficiency Compact and quiet

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

38RBS Air-Cooled Condensing Units. product selection data. commercial and industrial applications. compact design.

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet

30RB /30RQ

30RB /30RQ

AR Ductable Air-Cooled Liquid Chillers Ductable Reversible Air-to-Water Heat Pumps

30RBS /30RQS Air-Cooled Liquid Chillers, Reversible Air-to-Water Heat Pumps. product selection data

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

GeoCIAT Modular. Components. Heat pump Heating only, Glycol/water mix/water. Refrigerant and hydraulic module diagram. HomeConnect control.

38RBS Air-Cooled Condensing Units. Nominal cooling capacity: kw. Features. Easy and fast installation

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

VEXTRA. acoustic comfort Saves up to. 40% floor space. Use. Range. Description. Drycoolers. Slim design and. Capacity up to kw.

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

30RB A /30RQ

30XA Air-Cooled Liquid Chillers. Nominal cooling capacity kw

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

OPERA MORE. Use. Range. Drycoolers Air-cooled condensers. for LESS. Capacity: up to 1100 kw. Water misting. Free cooling

30RBM/30RBP AIR-COOLED SCROLL CHILLERS WITH GREENSPEED INTELLIGENCE PRODUCT SELECTION DATA

30HXC Nominal cooling capacity kw

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw

The refrigerant circuit was studied in detail. Each step is verified, ensuring that each unit is perfectly leak-tight.

30RH B Nominal cooling capacity kw Nominal heating capacity kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

ECOCIAT. Domestic hot water heat recovery unit. Use. Range

AGEO CALEO. Water-to-water high temperature heat pumps USE RANGE DESCRIPTION. Designed to replace a conventional boiler and produce domestic hot water

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module PRODUCT SELECTION DATA. Compact design

FLOWAY. Floway Range. The dual-flow air handling unit with heat recovery guaranteeing an Economical and Durable solution. use.

30RBM/30RBP Air-Cooled Scroll Chillers with Greenspeed Intelligence PRODUCT SELECTION DATA. MAINTENANCE INSTRUCTIONS Low sound level

30XAS Air-Cooled Liquid Chillers PRO-DIALOG + Nominal cooling capacity kw. Features and advantages. Very economical operation

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

61AF High-Temperature Monobloc Air-to-Water Heat Pumps with Integrated Hydronic Module. Nominal heating capacity kw.

DRYPACK. Protecting installations Energy optimisation. Operating principle. Description. Biogas dehumidification system. Improved profitability.

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Unit with optional hydronic module 61WG/30WG. Nominal cooling capacity kw Nominal heating capacity kw

61WG/30WG/30WGA. Water-Cooled and Condenserless Liquid Chillers Water-Sourced Heat Pumps. product selection data. 30WG optimized for cooling

High temperature air-to-water heat pumps

MAGISTER. Compact and attractive design Energy savings with EC motor and self-regulating control. Easy to install. Use. Chilled water operation

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

30XAS A Air-Cooled Liquid Chillers. Nominal cooling capacity kw 50 Hz. Features and advantages. Very economical operation

EXPAIR. Use. Precision air handling cabinets. Reducted footprint Dual-wall construction

30HXC - 50 HZ. Water-Cooled Screw Compressor Liquid Chillers. Nominal cooling capacity kw

30RBY/RQY Ductable Air-Cooled Liquid Chillers/ Ductable Air-to-Water Heat Pumps PRO-DIALOG +

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

30GX - 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw

30GK. Air-Cooled Liquid Chillers. Nominal cooling capacity kw

Neosys Product catalogue

DYNACIAT ILG. Use. Description. Heat pumps

30RBM/30RBP Air-Cooled Scroll Chillers with Greenspeed Intelligence PRODUCT SELECTION DATA. MAINTENANCE INSTRUCTIONS Low sound level

CLIMACIAT AIR COMPACT

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

30RBV/30RQV Inverter Air-Cooled Liquid chillers & Reversible Air to Water Heat Pumps PRODUCT SELECTION DATA INSTALLATION, OPERATION AND

30RB/RQ Air-Cooled Liquid Chillers/Air-to-Water Heat Pumps. product selection data

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

AQUACIAT. Inverter Heat pump USE RANGE GRAND INVERTER

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

Split inverter air-to-water heat pump CERTIFIED BY CERTITA. option 30/35-40/45

AQUASNAP JUNIOR 30RHV

30GX 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

30RB /30RQ

HT V2 HT Split

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

Construction details: Structure and base in hot dip galvanised sheet steel with epoxy pain finish (RAL 9002)

Split-system cooling units and heat pumps SERIES. Outdoor unit. Indoor unit OPERATING LIMITS. Inlet air conditions Cooling Heating.

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

MISSING 30XB / 30XBP AIR-COOLED FIXED-SPEED SCREW CHILLER PRODUCT SELECTION DATA

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AQUACIAT2 HYBRID. Natural GAS condensation boiler Self-adjusting electronic control. Use. Range. Heat pumps and gas boilers

LZA High efficiency air to water heat pumps with HP compressor

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS


GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

kw COOLING kw HEATING

Transcription:

Compact and silent Scroll compressors High efficiency brazed-plate heat exchangers All-aluminium micro-channel condenser Self-adjusting electronic control Cooling capacity: 40 to 56 kw Heating capacity: 4 to 58 kw 40a Cooling only Cooling and heating Hydraulic module Heat recovery Use The latest generation of AQUACIAT heat pumps and water chillers are the perfect solution for all heating and cooling applications in the Office, Healthcare, Industry, Administration, Shopping Centres and Collective Housing markets. These units are designed for outdoor installation and require no special protection against adverse weather conditions. AQUACIAT is optimised to use ozone-friendly HFC R40A refrigerant. This range guarantees compliance with the most demanding requirements for increased seasonal energy efficiency (ESEER and SCOP) and CO reduction to comply with the various applicable European directives and regulations. Range AQUACIAT LD series Cooling only version. AQUACIAT ILD series Reversible heat pump version. These two versions are optimised to meet the most demanding technical and economic requirements HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A

Description Water chillers AQUACIAT units are packaged machines supplied as standard with the following components: - Hermetic SCROLL compressors - Brazed-plate condenser or evaporator water type heat exchanger - Air-cooled exchanger with axial fan motor assembly all-aluminium micro-channel coil, cooling only version copper tube coil with aluminium fins, reversible heat pump version - Electrical power and remote control cabinet: 400V-3ph-50Hz (+/-0%) general power supply + earth transformer fitted as standard on the machine for supplying the remote control circuit with 4V - Connect Touch electronic control module - Casing for outdoor installation The entire AQUACIAT range complies with the following EC directives and standards: - Machinery directive 006/4/EC - Electromagnetic compatibility directive 04/30/EU - EMC immunity and emissions EN 6800-3 C3 - Low voltage directive 04/35/EU - RoHS 0/65/EU - Pressure equipment directive (PED) 04/68/EU - Machinery directive EN 60-04 - - Refrigerating systems and heat pumps EN 378- Description ILD 00 A A > generation of the range 50 > unit size LD > cooling only version ILD > reversible version Configuration LD-ILD LD-ILD, XLN option Standard Standard Xtra Low Noise HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A

Description of the main components Compressors - Hermetic SCROLL type - Electronic motor overheating protection - Crankcase heater - Mounted on anti-vibration mounts Water type heat exchanger - Brazed-plate exchanger - Evaporator or condenser mode exchanger on the reversible heat pump version - Plate patterns optimised for high efficiency - 9 mm armaflex thermal insulation - Frost protection provided by the heater Air-cooled exchanger - Air-cooled exchanger : all-aluminium micro-channel coil, cooling only version copper tube coil with aluminium fins, reversible heat pump version - Condenser or evaporator mode exchanger on the reversible heat pump version - axial fans with composite blades offering an optimised profile, fixed speed as standard or variable speed as an option - motors IP 54, class F Refrigerating accessories - Dehumidifier filters - Hygroscopic sight glasses - Electronic expansion valves - Service valves on the liquid line - 4-way cycle inversion valve in cooling/heating mode on the reversible heat pump version Control and safety instruments - Low and high pressure sensors - Safety valves on refrigerating circuit - Water temperature control sensors - Evaporator antifreeze protection sensor - Factory-fitted evaporator water flow rate controller Electrical cabinet - Electrical cabinet with IP 44 protection rating - A connection point without neutral - Front-mounted main safety switch with handle - Control circuit transformer - 4V control circuit - Fan and compressor motor circuit breaker - Fan and compressor motor contactors - Connect Touch microprocessor-controlled electronic control module - Wire numbering - Marking of the main electrical components Frame Frame made from RAL7035 light grey & RAL 704 graphite grey painted panels. Connect Touch control module - User interface with 4.3 inch touchscreen - Intuitive, user-friendly navigation using icons - Clear text display of information available in 5 languages (F-GB-D-E-I) The electronic control module performs the following main functions: - Regulation of the water temperature (at the return or at the outlet) - Regulation of the water temperature based on the outdoor temperature (water law) - Regulation for low temperature energy storage - Second setpoint management - Complete management of compressors with start-up sequence, timer and runtime balancing - Self-adjusting and proactive functions with adjustment of drift control for parameters - In-series staged power control system on the compressors according to the thermal requirements - Management of compressor short-cycle protection - Frost protection (exchanger heater) - Phase reversal protection - Management of occupied/unoccupied modes (according to the time schedule) - Compressor and pump runtime balancing - Management of the machine operation limit according to the outdoor temperature - Sound level reduction device (night mode according to the user programme) with limitation of compressor capacity and fan speed - Diagnosis of fault and operating statuses - Management of a fault memory allowing a log of the last 50 incidents to be accessed, with operating readings taken when the fault occurs - Master/slave management of the two machines in parallel with runtime balancing and automatic changeover if a fault occurs on one machine - Weekly and hourly time schedule for the machine, including 6 periods of absence - Pump standby based on demand (energy saving) - Calculation of the water flow rate and operating pressure (hydraulic module version) - Electronic adjustment of the water pump speed and water flow rate (variable speed pump option) - Display of all machine parameters (3 access levels, User/ Maintenance/Factory, password-protected): temperature, setpoints, pressures, water flow rate (hydraulic version), runtime. HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A 3

Remote control Connect Touch is equipped as standard with an RS485 port and an ETHERNET (IP) connection, offering a range of options for remote management, monitoring and diagnostics. Using the integrated Webserver, a simple internet connection uses the unit's IP address to access the Connect Touch interface on the PC, facilitating everyday management tasks and maintenance operations. A range of communication protocols are available: MODBUS/ JBUS RTU (RS485) or TC/IP as standard, LONWORKS BACNET IP as an option, enabling most CMS/BMS to be integrated. Several contacts are available as standard, enabling the machine to be controlled remotely by wired link: - Automatic operation control: when this contact is open, the machine stops - Heating/cooling mode selection - Setpoint /setpoint selector: when this contact is closed, a second cooling setpoint is activated (energy storage or unoccupied mode, for example) - Power limitation: closing the contact concerned allows the power or refrigerating consumption of the machine to be limited by stopping one or more compressors (this limit can be set with a parameter) - Fault reporting: this contact indicates the presence of a major fault which has caused one or both refrigerating circuits to stop - Operational status reporting indicates that the unit is in production mode. - Activation control for partial energy recovery using the desuperheater - Switch control for the customer pump, external to the machine (on/off). Contacts available as an option: - Setpoint adjustable via 4-0 ma signal: this input is used to adjust the setpoint in COOLING mode - On/off control for a boiler - 4-stage on/off management for additional heaters. Web server IP address Remote management via web server Connection to RJ port Connection via IP address All the HMI functionalities available on the PC Simplified remote monitoring E-mail alerts Maintenance Connect Touch has two maintenance reminder functions as standard, making users aware of the need to regularly perform maintenance operations and to guarantee the service life and performance of the unit. These two functions can be activated independently. A reminder message appears on the unit's HMI screen, and stays there until it is acknowledged by the maintenance operator. The information and alert relating to these functions are available on the communication bus to be used on the CMS/BMS. - the scheduled maintenance reminder: when activated, this function enables the period between two maintenance inspections to be set. This period may be set by the operator in either days, months or operating hours, depending on the application. - the compulsory F-GAS sealing test maintenance reminder: when activated, this function, which is the default factory setting, enables the period between two sealing tests to be selected, according to the refrigerant charge, in compliance with the FGAS regulations 4 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A

Available options Water chillers Options Description Advantages LD ILD Condenser with anti-corrosion post-treatment Corrosion protection, traditional coils Medium-temperature brine solution Low-temperature brine solution Xtra Fan Copper/aluminium coils supplied with Blygold Polual treatment applied Fins made of pre-treated aluminium (polyurethane and epoxy) Production of chilled water at low temperatures (down to 0 C) with ethylene glycol and propylene glycol. Production of chilled water at low temperatures (down to -5 with ethylene glycol and - C with propylene glycol). Unit equipped with special variable speed fans: Xtra Fan (see dedicated section for the maximum available pressure according to the size), with each fan equipped with a connection flange and sleeves for connection to the duct system. Improved corrosion resistance, recommended for industrial, rural and marine environments Improved corrosion resistance, recommended for moderate marine and urban environments Covers specific applications such as ice storage and industrial processes Covers specific applications such as ice storage and industrial processes Ducted fan discharge, optimised condensing temperature control (or evaporating temperature control on the heat pump version), based on the operating conditions and system characteristics no Xtra Low Noise Sound absorbing enclosure for the compressor and low speed fans Reduces the noise level by reducing the fan speeds Protective grilles Metal protective grilles Protects the coils against any impacts no (*) Soft Starter Electronic starter on each compressor Reduces the start-up current Winter operation (down to -0 C) Antifreeze protection down to -0 C Water heat exchanger and hydraulic module frost protection Partial heat recovery Master/slave operation HP single-pump hydraulic module HP dual-pump hydraulic module LP single-pump hydraulic module LP dual-pump hydraulic module HP single variable-speed pump hydraulic module HP variable speed dual pump hydraulic module Controls the fan speed Electric heater on the hydraulic module Trace heaters on the water heat exchanger, water pipes, hydraulic module, expansion vessel and buffer tank module Unit equipped with a desuperheater on each refrigerating circuit Unit equipped with an additional water outlet temperature sensor, to be installed on site, enabling Master/Slave operation of units connected in parallel Single high-pressure water pump, water filter, electronic water flow control, pressure transducers. For more details, refer to the dedicated section (expansion tank not included. Option with integrated hydraulic safety components available.) Dual high-pressure water pump, water filter, electronic water flow control, pressure sensors. For more details, refer to the dedicated section (expansion tank not included. Option with integrated hydraulic safety components available.) Single low-pressure water pump, water filter, electronic water flow control, pressure sensors. For more details, refer to the dedicated section (expansion tank not included. Option with integrated hydraulic safety components available.) Dual low-pressure water pump, water filter, electronic water flow control, pressure sensors. For more details, refer to the dedicated section (expansion tank not included. Option with integrated hydraulic safety components available.) Single high pressure water pump with variable speed drive, water filter, electronic water flow rate control, pressure sensors. Multiple water flow control options. For more details, refer to the dedicated section (expansion tank not included. Option with integrated hydraulic safety components available.) Dual high pressure water pump with variable speed drive, water filter, electronic water flow rate control, pressure sensors. Multiple water flow control options. For more details, refer to the dedicated section (expansion tank not included. Option with integrated hydraulic safety components available.) Stable operation of the unit when the air temperature is between 0 C and -0 C. Frost protection of the hydraulic module at low outdoor temperatures Frost protection of the water type heat exchanger and hydraulic module down to an outdoor air temperature of -0 C Simultaneous free production of hot water (high temperature) and production of chilled water (or hot water for the heat pump) Optimised operation of two units connected in parallel with run time equalisation Quick, easy installation (plug & play) Quick, easy installation (plug & play) Quick, easy installation (plug & play) Quick, easy installation (plug & play) Quick, easy installation (plug & play), significant reduction in energy consumption for pump use (more than two-thirds), tighter water flow control, improved system reliability Quick, easy installation (plug & play), significant reduction in energy consumption for pump use (more than two-thirds), tighter water flow control, improved system reliability ALL MODELS ALL MODELS with desuperheater or low and very low temperature glycol/water mix option (*) Standard equipment on ILD version Refer to the selection tool to find out which options are not compatible. HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A 5

Options Description Advantages LD ILD HP variable speed dual pump hydraulic module LON communication gateway BACnet/IP External management of the boiler Management of electric heaters Compliance with Russian regulations Protect anti-corrosion protection for micro-channel coils Protect4 anti-corrosion protection for micro-channel coils Water heat exchanger connection sleeves, screw connection Reinforced filtration of the fan frequency inverter Reinforced filtration of the pump frequency inverter Expansion vessel Buffer tank module Anti-vibration mounts Flexible connection couplings for the exchanger Desuperheater flexibles connection (kit) Dual high pressure water pump with variable speed drive, water filter, electronic water flow rate control, pressure sensors. Multiple water flow control options. For more details, refer to the dedicated section (expansion tank not included. Option with integrated hydraulic safety components available.) Two-directional communication board complying with Lon Talk protocol Two-directional high-speed communication using BACnet protocol over Ethernet network (IP) Control board factory installed on the unit for controlling a boiler Control board factory-fitted on the unit with additional inputs/ outputs enabling up to 4 external heating stages to be managed (electric heaters.etc.) Quick, easy installation (plug & play), significant reduction in energy consumption for pump use (more than two-thirds), tighter water flow control, improved system reliability Connects the unit by communication bus to a building management system Easy and high-speed connection by Ethernet line to a building management system. Allows access to multiple unit parameters "Expands the remote control capacities to include a boiler on/off control. Facilitates control of a basic heating system" Expands the remote control capacities to include a maximum of four electric heaters. Facilitates control of a basic heating system EAC certification Compliance with Russian regulations Coating which uses a conversion process to alter the aluminium surface into a coating which forms an integral part of the coil. Complete immersion in a bath to ensure 00% coverage. No thermal transfer variation, tested to withstand more than 4000 hours of salt spray as per ASTM B7 Flexible, durable polyepoxide coating applied using an electroplating process to give micro-channel coils an anti-uv top layer. Minimal variation in the thermal transfer, tested to withstand more than 6000 hours of constant neutral salt spray as per ASTM B7, improved impact resistance as per ASTM D794 Water heat exchanger inlet/outlet connection sleeves, screw connection Fan frequency inverter compliant with IEC 6800-3 class C Pump frequency inverter compliant with IEC 6800-3 class C 6-bar expansion vessel integrated into the hydraulic module (requires option 6) Integrated buffer tank module Elastomer anti-vibration mounts to be fitted underneath the unit Flexible connections for the water type heat exchanger Flexibles connections on the desuperheater water side Protect coating which doubles the corrosion resistance offered by micro-channel coils, recommended for use in moderately corrosive environments Protect4 coating gives a fourfold increase in the corrosion resistance offered by micro-channel coils, recommended for use in corrosive environments no no no no Allows unit connection to a screw connector Allows the unit to be installed in a residential environment, by reducing electromagnetic disturbance Allows the unit to be installed in a residential environment, by reducing electromagnetic disturbance Easy, quick installation (ready to use), and closed circuit protection of hydraulic systems to counter excessive pressure Prevents compressor short cycling and no with variable speed pump option with variable speed fan option with variable speed pump option provides stability of the water in the loop Isolates the unit from the building, preventing vibrations and noise from being transmission to the building. Must be used in conjunction with a flexible connection on the water side Easy to install. Limits the transmission of vibrations to the water network Easy installation. Limit transmission of vibrationson the water network Water filter on the evaporator Water filter Prevents fouling in the water network no pump Setpoint adjustable via 4-0 ma signal Free cooling mode drycooler management MM supervision (accessory) Connections enabling a 4-0 ma signal input Control and connections for an Opera or Vextra drycooler in free cooling mode equipped with the FC optional control unit Monitoring solution which allows customers to track and monitor their equipment remotely in real time Simplified energy management, enabling the setpoint to be set by a 4-0 ma external signal Simplified system management, increased control capacities to enable the drycooler to be used in free cooling mode Real-time expert technical support to improve equipment availability and reports at customer hand to monitor and optimize operating equipment. no pump no ALL MODELS Refer to the selection tool to find out which options are not compatible. 6 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A

Technical characteristics - Cooling only AQUACIAT LD 50A 80A 00A 40A 60A 300A 360A 390A 450A 50A 600A Cooling Standard unit C Nominal capacity kw 40 44 5 58 67 79 87 97 4 35 56 C EER kw/kw.87.76.67.66.7.70.73.73.67.70.65 Full load performances* C Nominal capacity kw 53 59 69 8 85 98 4 6 5 7 94 C EER kw/kw 3.44 3.3 3. 3.3.97 3.06 3.8 3.09 3.0.99 3.0 Seasonal efficiency* C ESEER kw/kw 3.75 3.88 3.95 3.80 3.6 3.67 3.9 3.94 3.83 3.68 3.87 Part Load integrated values IPLV kw/kw 4.54 4.7 4.8 4.58 4.6 4.39 4.55 4.53 4.55 4.9 4.64 Sound levels Standard unit Sound power () db(a) 80 8 8 8 87 87 84 84 84 90 90 Sound pressure at 0 m () db(a) 49 49 49 49 55 55 5 5 5 58 58 Unit + Xtra Low Noise option Sound power () db(a) 79 80 80 80 80 80 83 83 83 83 83 Sound pressure at 0 m () db(a) 48 48 48 48 48 48 5 5 5 5 5 Dimensions Length mm 090 090 090 090 090 090 70 70 70 70 70 Width mm 09 09 09 09 09 09 3 3 3 3 3 Height mm 440 440 440 440 440 440 440 440 440 440 440 Height with Buffer Tank Module mm 040 040 040 040 040 040 040 040 040 040 040 Operating weight with micro-channel coils (3) Standard unit kg 4 430 436 449 445 463 753 76 77 89 854 Unit + High pressure single pump option kg 463 47 478 49 487 505 80 89 84 903 98 Unit + High pressure dual pump option kg 489 498 504 57 53 53 865 874 89 940 965 Unit + High pressure single pump option kg + Buffer tank module 859 868 874 887 883 90 53 6 75 336 36 Unit + High pressure dual pump option + Buffer tank module kg 885 894 900 93 909 97 98 307 34 373 398 Compressors Hermetic Scroll 48.3 r/s Circuit A Qty 3 3 3 Circuit B Qty - - - - - - - - - No. of control stages Qty 3 3 3 4 4 Refrigerant with micro-channel coils (3) R40A Circuit A kg 4.7 5.3 5.9 6.7 6. 7.3 0.7 0.8.4 6.5 7.4 tco eq 9.8..3 4.0.9 5..3.6 3.8 3.6 5.5 Circuit B kg - - - - - - - - - 6.5 7.4 tco eq - - - - - - - - - 3.6 5.5 * In accordance with standard EN45-3:03. For information, calculated from the sound power Lw(A). C Cooling mode conditions: water type heat exchanger inlet/outlet temperature (3) Values are guidelines only. Refer to the unit name plate. C/7 C, outdoor air temperature 35 C, evaporator fouling level 0 m ² K/W. (4) On delivery, the vessels are preinflated to a standard value, which may not be C Cooling mode conditions: water type heat exchanger inlet/outlet temperature 3 C/8 C, outdoor air temperature 35 C, evaporator fouling level 0 m ² K/W. the optimum one for the installation. To enable the water volume to be varied as desired, adapt the inflation pressure to a value close to that which corresponds to IPLV Calculations based on standard performances (in accordance with AHRI 550-590). the static height of the installation. Fill the installation with water (bleeding out any () In db ref=0- W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 487 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with ISO 964-. air) at a pressure more than 0 to 0 kpa higher than the vessel pressure. () In db ref 0µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 487 (with an associated uncertainty of +/-3dB(A)). Eurovent certified values HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A 7

Technical characteristics - Cooling only Oil charge AQUACIAT LD 50A 80A 00A 40A 60A 300A 360A 390A 450A 50A 600A POE SZ60 (EMKARATE RL 3-3MAF). Circuit A l 5.8 7. 7. 7. 7 7 0.8 0.5 0.5 7 7 Circuit B l - - - - - - - - - 7 7 Control Connect Touch Control Minimum output % 50 50 50 50 50 50 33 33 33 5 5 Air heat exchanger Fans - Standard unit All-aluminium micro-channel coil Quantity Maximum total air flow l/s 3885 3883 3687 3908 503 578 6940 6936 7370 006 0556 Maximum rotation speed r/s 6 6 6 6 Water heat exchanger Direct expansion, plate heat exchanger Water content l.6 3 3.3 4 4.8 5.6 8.7 9.9.3.4 4.7 Max water-side operating pressure without hydraulic module kpa 000 000 000 000 000 000 000 000 000 000 000 Hydraulic module (option) Single or dual pump (as required) Pump, Victaulic screen filter, relief valve, water and air bleed valves, pressure sensors Expansion tank volume (option) l 35 35 35 35 35 Expansion vessel pressure (4) bar.5.5.5.5.5 Max. water-side operating pressure with kpa hydraulic module 400 400 400 400 400 400 400 400 400 400 400 Buffer tank module (option) Single or dual pump (as required) Pump, Victaulic screen filter, relief valve, water and air bleed valves, pressure sensors Water volume l 50 50 50 50 50 50 50 50 50 50 50 Expansion tank volume (option) l 8 8 8 8 8 8 35 35 35 35 35 Expansion vessel pressure (4) bar.5.5.5.5.5 Max. water-side operating pressure with kpa hydraulic module 400 400 400 400 400 400 400 400 400 400 400 Water connections with or without hydraulic module Victaulic Connections inch External diameter mm 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 Casing paint Colour code RAL 7035 and RAL704 * In accordance with standard EN45-3:03. C Cooling mode conditions: water type heat exchanger inlet/outlet temperature C/7 C, outdoor air temperature 35 C, evaporator fouling level 0 m ² K/W. C Cooling mode conditions: water type heat exchanger inlet/outlet temperature 3 C/8 C, outdoor air temperature 35 C, evaporator fouling level 0 m ² K/W. IPLV Calculations based on standard performances (in accordance with AHRI 550-590). () In db ref=0- W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 487 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with ISO 964-. () In db ref 0µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 487 (with an associated uncertainty of +/-3dB(A)). For information, calculated from the sound power Lw(A). (3) Values are guidelines only. Refer to the unit name plate. (4) On delivery, the vessels are preinflated to a standard value, which may not be the optimum one for the installation. To enable the water volume to be varied as desired, adapt the inflation pressure to a value close to that which corresponds to the static height of the installation. Fill the installation with water (bleeding out any air) at a pressure more than 0 to 0 kpa higher than the vessel pressure. Eurovent certified values 8 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A

Technical characteristics - Reversible heat pump AQUACIAT ILD 50A 80A 00A 40A 60A 300A 30A 360A 390A 450A 50A 600A Cooling Standard unit C Nominal capacity kw 38 43 50 59 64 74 78 86 96 3 3 49 C EER kw/kw.84.7.65.77.7.58.79.7.7.69.77.58 Full load performances* C Nominal capacity kw 48 54 63 7 79 93 97 08 8 43 63 87 C EER kw/kw 3.8 3.6 3.09 3. 3.08.97 3.9 3.4 3. 3. 3.7.9 Seasonal efficiency* C ESEER kw/kw 3.80 3.77 3.8 3.6 3.6 3.57 3.84 3.77 3.88 4.04 3.75 3.67 Heating Standard unit H Nominal capacity kw 4 47 53 6 70 78 80 93 0 7 38 58 H COP kw/kw 3.08 3.05 3.03 3.03 3.06.87 3.08 3.0 3.09 3.06 3.07.97 Full load performances* H Nominal capacity kw 43 47 55 63 7 80 83 95 03 4 6 H COP kw/kw 3.7 3.7 3.76 3.73 3.7 3.47 3.74 3.74 3.77 3.73 3.73 3.59 H SCOP kw/kw 3.07 3. 3. 3.07 3..96 3.4 3.7 3.3 3.3 3.4 3.3 Seasonal efficiency** H Ƞs heat % 0 5 0 5 3 4 6 6 3 H Prated kw 33.0 37 4 5 57 65 66 76 83 97 3 3 Part Load integrated values IPLV kw/kw 4.57 4.54 4.5 4. 4.8 4.9 4.58 4.40 4.46 4.90 4.33 4.39 Sound levels Standard unit Sound power () db(a) 80 8 8 86 87 87 84 84 84 84 90 90 Sound pressure at 0 m () db(a) 49 49 49 55 55 55 5 5 5 5 58 58 Unit + Xtra Low Noise option Sound power () db(a) 79 80 80 80 80 80 83 83 83 83 83 83 Sound pressure at 0 m () db(a) 48 48 48 48 48 48 5 5 5 5 5 5 Dimensions Length mm 090 090 090 090 090 090 70 70 70 70 70 70 Width mm 09 09 09 09 09 09 3 3 3 3 3 3 Height mm 440 440 440 440 440 440 440 440 440 440 440 440 Height with Buffer Tank Module mm 040 040 040 040 040 040 040 040 040 040 040 040 Operating weight (3) Standard unit kg 497 506 543 549 559 564 777 896 905 979 053 057 Unit + High pressure single pump option kg 539 548 585 59 60 606 844 963 97 050 7 3 Unit + High pressure dual pump option kg 565 574 6 67 67 63 889 008 07 098 64 68 Unit + High pressure single pump option + Buffer tank module kg 935 943 98 986 996 00 76 395 404 48 560 563 Unit + High pressure dual pump option + Buffer tank module kg 96 969 006 0 0 07 3 440 449 53 597 600 Compressors Hermetic Scroll 48.3 r/s Circuit A Qty 3 3 3 Circuit B Qty - - - - - - - - - - No. of control stages Qty 3 3 3 4 4 Refrigerant (3) R-40A Circuit A kg.5 3.5 6.5 7.5 8 6.5.5 7.5 8.5 33 9 8.5 tco eq 6. 8. 34.5 36.5 37.6 34.5 44.9 57.4 59.5 68.9 39.7 38.6 Circuit B kg - - - - - - - - - - 9 8.5 tco eq - - - - - - - - - - 39.7 38.6 Oil charge POE SZ60 (EMKARATE RL 3-3MAF). Circuit A l 5.8 7. 7. 7. 7.0 7.0 7. 7.0 7.0 7.0 7.0 7.0 Circuit B l - - - - - - - - - - 7.0 7.0 * In accordance with standard EN45-3:03. ** In accordance with standard EN485:03, average climate conditions. C Cooling mode conditions: water type heat exchanger inlet/outlet temperature C/7 C, outdoor air temperature 35 C, evaporator fouling level 0 m ² K/W. C Cooling mode conditions: water type heat exchanger inlet/outlet temperature 3 C/8 C, outdoor air temperature 35 C, evaporator fouling level 0 m ² K/W. H Heating mode conditions: water type heat exchanger inlet/outlet temperature 40 C/45 C, db/wb outdoor air temperature 7 C/6 C, evaporator fouling level 0 m ² K/W. H Heating mode conditions: water type heat exchanger inlet/outlet temperature 30 C/35 C, db/wb outdoor air temperature 7 C/6 C, evaporator fouling level 0 m ² K/W. IPLV Calculations based on standard performances (in accordance with AHRI 550-590). () In db ref=0- W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 487 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with ISO 964- and certified by EUROVENT () In db ref 0µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 487 (with an associated uncertainty of +/-3dB(A)). Value calculated from the sound power Lw(A). (3) Weight given as a guide. Refer to the unit name plate. Eurovent certified values HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A 9

Technical characteristics - Reversible heat pump AQUACIAT ILD 50A 80A 00A 40A 60A 300A 30A 360A 390A 450A 50A 600A Power control Connect Touch Control Minimum capacity % 50 50 50 50 50 50 50 33 33 33 5 5 Air heat exchanger Grooved copper tube and aluminium fins Fans Quantity Maximum total air flow l/s 369 3690 390 585 584 58 7770 7380 7376 788 0568 0568 Maximum rotation speed r/s 6 6 6 6 6 Water heat exchanger Direct expansion, plate heat exchanger Water content l.6 3 4 4.8 4.8 5.6 8.7 8.7 9.9.3.4 4.7 Max water-side operating pressure without hydraulic module kpa 000 000 000 000 000 000 000 000 000 000 000 000 Hydraulic module (option) Single or dual pump (as required) Pump, Victaulic screen filter, relief valve, water and air bleed valves, pressure sensors Expansion tank volume (option) l 35 35 35 35 35 Expansion vessel pressure (4) bar.5.5.5.5.5 Max. water-side operating pressure with hydraulic kpa module 400 400 400 400 400 400 400 400 400 400 400 400 Buffer tank module (option) Single or dual pump (as required) Pump, Victaulic screen filter, relief valve, water and air bleed valves, pressure sensors Water volume l 50 50 50 50 50 50 50 50 50 50 50 50 Expansion tank volume (option) l 8 8 8 8 8 8 8 35 35 35 35 35 Expansion vessel pressure (4) bar.5.5.5.5.5 Max. water-side operating pressure with hydraulic kpa module 400 400 400 400 400 400 400 400 400 400 400 400 Water connections with/without hydraulic module Victaulic Diameter inch External diameter mm 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 Casing paint Colour code RAL 7035 and RAL704 (4) On delivery, the vessels are preinflated to a standard value, which may not be the optimum one for the installation. To enable the water volume to be varied as desired, adapt the inflation pressure to a value close to that which corresponds to the static height of the installation. Fill the installation with water (bleeding out any air) at a pressure more than 0 to 0 kpa higher than the vessel pressure. 0 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A

Electrical specifications LD / ILD Standard unit (without hydraulic module) 50A 80A 00A 40A 60A 300A 30A 360A 390A 450A 50A 600A Power circuit Nominal voltage V-ph-Hz 400-3-50 Voltage range V 360-440 Control circuit supply 4 V via internal transformer Nominal unit current draw (3) Circuit A + B A 5.6 9 33 36 4.4 5.8 53.4 55.4 6.7 77.3 84.8 05.6 Maximum unit power input () Circuit A + B kw 9.5.3 4.5 7.9 3. 35.8 35.6 4.3 45.6 5.5 6.4 7.6 Unit Cosine Phi at maximum power () 0.83 0.8 0.8 0.83 0.8 0.78 0.78 0.83 0.8 0.79 0.8 0.78 Maximum unit current draw (Un-0%) (5) Circuit A + B A 38 49. 5.4 58.4 74.8 79.6 80. 89 0.3 7.5 49.6 59. Maximum unit current draw (Un) (4) Circuit A&B - Standard unit A 34.8 44.8 46.8 5.8 67 73 73.6 80.6 98.6 07.6 34 46 Maximum start-up current, standard unit (Un) () Circuit A + B A 3.8 34.8 4.8 45.8 76 3 3.6 73.6 07.6 47.6 43 86 Maximum start-up current, unit with soft start (Un) () Circuit A + B A 74.7 86.5 93.8 96. 4.4 39.8 39.8 30.4 55.4 8.4 86.4 5.4 () Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor). () Power input, at the unit's permanent operating limits (indication given on the unit's name plate). (3) Standardised EUROVENT conditions, water type heat exchanger input/output = C/7 C, outdoor air temperature = 35 C. (4) Maximum unit current at 400V, during non-permanent operation (indication given on the unit's name plate) (5) Maximum unit current at 360V, during non-permanent operation Short circuit current withstand capability (TN system () ) AQUACIAT LD / ILD 50A 80A 00A 40A 60A 300A 30A 360A 390A 450A 50A 600A Value without upstream protection Short time (s) assigned current - Icw - ka eff 3.36 3.36 3.36 3.36 3.36 3.36 3.36 5.6 5.6 5.6 5.6 5.6 Allowable peak assigned current - Ipk - ka pk 0 0 0 0 0 5 5 0 0 5 0 5 Value with upstream protection Conditional short circuit assigned current Icc - ka eff 40 40 40 40 40 40 40 40 40 40 30 30 Associated Schneider circuit breaker Compact type range () NS00H NS00H NS00H NS00H NS00H NS00H NS00H NS00H NS60H NS60H NS50H NS50H () Type of system earthing () If another current limiter protective device is used, its time/current activation and heat thermal restriction I²t limits must be at least equivalent to those of the recommended Schneider circuit breaker. Contact your manufacturer's representative. The short circuit current stability values given above are for the TN system. HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A

Dimensions Water chillers AQUACIAT LD-ILD 50A to 300A Without buffer tank 000 000 440 HT Main hydraulic connection Electrical power connection 090 HT 09 HT Partial heat recovery (option) 000 000 AQUACIAT LD-ILD 50A to 300A With buffer tank 040 HT Main hydraulic connection Partial heat recovery (option) 4 HT 39 HT Electrical power connection 000 000 000 000 Key All dimensions in mm Clearance required for maintenance and air flow Clearance recommended for coil removal Water inlet Water outlet Air outlet, do not obstruct Notes: Non-contractual drawings. When designing a system, refer to the certified dimensional drawings provided with the unit or available on request. Please refer to the certified dimensional drawings for the positioning of the fixing points, weight distribution points and centre of gravity coordinates. Electrical cabinet HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A

Dimensions Water chillers AQUACIAT LD-ILD 30A to 600A Without buffer tank 440 HT Electrical power connection 70 HT 3 HT Main hydraulic connection Partial heat recovery (option) 000 000 000 000 Key All dimensions in mm Clearance required for maintenance and air flow Clearance recommended for coil removal Water inlet Water outlet Air outlet, do not obstruct Notes: Non-contractual drawings. When designing a system, refer to the certified dimensional drawings provided with the unit or available on request. Please refer to the certified dimensional drawings for the positioning of the fixing points, weight distribution points and centre of gravity coordinates. Electrical cabinet HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A 3

Dimensions Water chillers AQUACIAT LD-ILD 30A to 600A With buffer tank 040 HT Electrical power connection Main hydraulic connection 3 HT 30 HT 000 000 Partial heat recovery (option) 000 000 Key All dimensions in mm Clearance required for maintenance and air flow Clearance recommended for coil removal Water inlet Water outlet Air outlet, do not obstruct Notes: Non-contractual drawings. When designing a system, refer to the certified dimensional drawings provided with the unit or available on request. Please refer to the certified dimensional drawings for the positioning of the fixing points, weight distribution points and centre of gravity coordinates. Electrical cabinet 4 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A

This document is non-contractual. As part of its policy of continual product improvement, CIAT reserves the right to make any technical modification it feels appropriate without prior notification. Head office 700 Avenue Jean Falconnier - B.P. 4 0350 - Culoz - France Tel.: +33 (0)4 79 4 4 4 Fax: +33 (0)4 79 4 4 0 info@ciat.fr - www.ciat.com Certified Management System Compagnie Industrielle d Applications Thermiques - S.A. with a registered capital of 6 78 480 - R.C.S. Bourg-en-Bresse B 545 60 4 6 HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 7.749 A