V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

Similar documents
T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

T-Series Air Conditioner T15 Model

T-Series Air Conditioner T20 Model

T-Series Air Conditioner T53 Model

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

T-SERIES Air Conditioner. T53 Model INSTRUCTION MANUAL nvent Rev. G P/N

M52 3-Phase INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

SPECTRACOOL Air Conditioner. N17 Model INSTRUCTION MANUAL. Rev. G 2015 Pentair Equipment Protection P/N

SPECTRACOOL Air Conditioner

T-SERIES Air Conditioner. T62 Model INSTRUCTION MANUAL nvent Rev. F P/N

GENESIS Air Conditioner. M52 3-Phase Model INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Equipment Protection P/N

T-Series Air Conditioner

ProAir CR43 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

INSTRUCTION MANUAL. T-SERIES Air Conditioner. T29 Model Pentair Equipment Protection P/N McLean Parts 5736 N. Michigan Rd.

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL. Rev. D 2015 Pentair Equipment Protection P/N

ProAir CR29 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

ProAir CR23 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

T-Series Air Conditioner

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL. Rev. F 2015 Pentair Equipment Protection P/N

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. I 2017 Pentair Equipment Protection P/N

PROAIR Air Conditioner

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL. Rev. B 2016 Pentair Equipment Protection P/N

ClimaGuard Outdoor Heat Exchanger All Models

PROAIR Air Conditioner

SPECTRACOOL Air Conditioner. N16 Model INSTRUCTION MANUAL. Rev. A 2016 Pentair Equipment Protection P/N

SPECTRACOOL Air Conditioner. N28 Model INSTRUCTION MANUAL nvent Rev. D P/N

GENESIS AIR CONDITIONERS

SPECTRACOOL Air Conditioner. N36 Model INSTRUCTION MANUAL. Rev. N 2014 Pentair Equipment Protection P/N

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

SPECTRACOOL Air Conditioner. N36 Model INSTRUCTION MANUAL nvent Rev. P P/N

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

SPECTRACOOL Air Conditioner. G28 Model INSTRUCTION MANUAL nvent Rev. D P/N

SPECTRACOOL Air Conditioner

Rev. F 2014 Pentair Equipment Protection P/N Distributed by: McLean Parts. fax

GENESIS Top-Mount Air Conditioner. HB16 Model INSTRUCTION MANUAL. Rev. J 2013 Pentair Equipment Protection P/N

SPECTRACOOL Air Conditioner

SPECTRACOOL Air Conditioner. G57 Model INSTRUCTION MANUAL. Rev. E 2014 Pentair Equipment Protection P/N

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner ADVANTAGE RP55 SERIES

AIR CONDITIONER OPERATOR'S MANUAL

Manual For Panel Air Conditioner. Table of Contents

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

ADVANTAGE SERIES KXRP33 AIR-TO-AIR HEAT EXCHANGER

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES K2NA6C14DP50L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRADITIONAL SERIES P47 P52 P59

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner NPT SERIES K_A6C_NPT47L

KNHX32 SERIES NEMA 4/4X AIR-TO-AIR HEAT EXCHANGERS

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner TRIMLINE WNP28 SERIES

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

ADVANTAGE SERIES KXRP28 AIR-TO-AIR HEAT EXCHANGER

KNHE48 SERIES WATER-TO-AIR HEAT EXCHANGER

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner DP SERIES K2A3C14DP50L

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

INSTRUCTION MANUAL. SPECTRACOOL Slim Fit Air Conditioners. All Models

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner INTEGRITY SERIES K_NA4C4P32L KNA6C4P32L

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

ADVANTAGE SERIES KXRP47 AIR-TO-AIR HEAT EXCHANGER

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner

1 Specifications. 2 Operation. PHOENIX 300 Operation & Service Instructions. 2.1 Transporting the Phoenix. 2.2 Location

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner K2A3C8P36LFHN-1

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner DP SERIES K_A4C5DP33L

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner WATER-COOLED RACK MOUNTED

VA G 052 S

RPI Industries, Inc.

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

AIR CONDITIONER OPERATOR'S MANUAL. Keep This Manual With Air Conditioner GUARDIAN SERIES KNA4C9DP47L-1

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

Installation, Operation, and Maintenance Information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL BD-150 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

SPECTRACOOL Slim Fit Air Conditioners. All Models INSTRUCTION MANUAL. Rev. J 2015 Pentair Equipment Protection P/N

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

VA G 052 S VA08 Indoor Model 1200, 1500 and 2000 Watts. Sealed Enclosure Cooling Air Conditioners

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

Installation, Operation, and Maintenance Information

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

VA G 052 S VA08 Indoor Model 1200, 1500 and 2000 Watts. Sealed Enclosure Cooling Air Conditioners

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL

Transcription:

V-SERIES Air Conditioner VA08 Model INSTRUCTION MANUAL Rev. F P/N 90164959

TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3 HOW TO READ MODEL NUMBERS...3 INSTALLATION INSTRUCTIONS...4 Dimensional Drawing...4 MOUNTING CUTOUT DIMENSIONS...5 TECHNICAL INFORMATION...6 SEQUENCE OF OPERATION...6 HEATING (OPTIONAL)...6 COOLING...6 STANDARD AND OPTIONAL COMPONENT OPERATION...6 THERMOSTAT...6 HEAD PRESSURE CONTROL (OPTIONAL)...6 FOR COOLING (35 C RANGE):...6 FOR HEATING (13 C RANGE):...6 UNIT CHARACTERISTICS...7 WIRE DIAGRAMS...8 VA08 GENERIC WIRE DIAGRAM (ACTUAL UNIT OPTIONS MAY VARY)...8 Schematics...9 SERVICE DATA...9 COMPONENTS LIST...9 MAINTENANCE... 10 COMPRESSOR...10 INLET AIR FILTER...10 HOW TO REMOVE, CLEAN OR INSTALL A NEW INLET AIR FILTER...10 CONDENSER AND EVAPORATOR AIR MOVERS...11 REFRIGERANT LOSS...11 TROUBLE SHOOTING... 12 BASIC AIR CONDITIONING TROUBLE SHOOTING CHECK LIST...12 SYMPTOMS AND POSSIBLE CAUSES:...13 WARRANTY AND RETURN POLICY https://hoffman.nvent.com/en/hoffman/warranty-information - 2 -

RECEIVING THE AIR CONDITIONER Inspect the air conditioner. Check for concealed damage that may have occurred during shipment. Look for dents,scratches, loose assemblies, evidence of oil, etc. Damage evident upon receipt should be noted on the freight bill. Damage should be brought to the attention of the delivering carrier -- NOT to nvent Electronics & Electronical Protection China -- within 15 days of delivery. Save the carton and packing material and request an inspection. Then file a claim with the delivering carrier. nvent Electronics & Electronical Protection China cannot accept responsibility for freight damages; however, we will assist you in any way possible. HANDLING AND TESTING THE AIR CONDITIONER If the air conditioner has been in a horizontal position, be certain it is placed in an upright, vertical or mounting position for a minimum of five (5) minutes before operating. CAUTION Do not attempt to operate the air conditioner while it is horizontal or on its side, back or front. The refrigeration compressor is filled with lubricating oil. This will cause permanent damage to the air conditioner and also voids the warranty. TEST FOR FUNCTIONALITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE. Refer to the nameplate for proper electrical current requirements, and then connect the power cord to a properly grounded power supply. Minimum circuit ampacity should be at least 125% of the amperage shown in the design data section for the appropriate model. No other equipment should be connected to this circuit to prevent overloading. Immediately after applying power the evaporator blower (enclosure air) should start running. Operate the air conditioner with the compressor running for five (5) to ten (10) minutes. No excessive noise or vibration should be evident during this run period. You will need to set the cooling thermostat below the ambient temperature to operate the compressor. Condenser air temperatures should be warmer than normal room temperatures within a few minutes after the condenser impeller starts. See sequence of operation for specifics on how the unit operates when powered up. HOW TO READ MODEL NUMBERS VA08 12 25 G 052 A 1 2 3 4 5 6 1. Identifies the type/family of air conditioner and the approximate height (i.e.va08 = Value family about 701mm to 800mm high). 2. This is the air conditioner s listed capacity in Watt at rated conditions. (i.e. 12 = 1200 Watt at 35 C ENCLOSURE 35 C ambient.) 3. 2 = 220/230 Volt,5=50Hz. 4. Identifies the construction material and refrigerant of air conditioner.(i.e.g=galvanized Sheet Metal and R134a). 5. Unique set of numbers for each air conditioner which identifies the accessories on a model. 6. A=The updated version 2018 nvent 90164959-3 -

INSTALLATION INSTRUCTIONS 1. Inspect the air conditioner and verify correct functionality before mounting the air conditioner. See HANDLING AND TESTING THE AIR CONDITIONER on page 3. 2. Using the mounting gasket kit provided with the unit, install gaskets to the air conditioner, Figure 2. 3. Mount air conditioner on enclosure taking care not to damage the mounting gasket. The mounting gasket is the seal between the air conditioner and the enclosure. Avoid dragging the air conditioner on the enclosure with the mounting gasket attached as this could cause rips or tears in the gasket and risk losing the water tight seal. 4. Allow unit to remain upright for a minimum of five (5) minutes before starting. CAUTION! Air conditioner must be in upright position during operation. 5. Refer to the nameplate for electrical requirements. Wire the unit to a properly grounded power supply. Electrical circuit should be fused with slow blow or HACR circuit breaker. 6. Set thermostat for required cabinet temperature. Refer to Sequence of Operation on page 6 for thermostat adjustment and operation. DIMENSIONAL DRAWING 431 403 ACCESS HOLE TO 9.6mm O.D. DRAIN STUB 330 330 32 9 POWER INPUT COOL STAT HEAT STAT (OPTIONAL) ACCESS PANEL FOR OPTIONAL HEATER MOUNTING HOLES (7) AMBIENT AIR IN AMBIENT AIR OUT ENCLOSURE AIR IN REMOVABLE HANGING TABS ENCLOSURE AIR OUT 725 CLEANABLE, REUSABLE ALUMINUM INLET FILTER BEHIND REMOVABLE PANEL 382 Note: 1. Mounting gasket supplied (not shown) 2.*272 is the depth for 2000W model. 3. Units: mm 237(*272) 17 Figure 1-4 -

MOUNTING CUTOUT DIMENSIONS 463 431 403 9 420 140 26 273 725 330 65 16 9 32 388 8(7x ) 152 13(4x ) 152 75 738 445 268 388 330 152 152 704 756 External Mounting Partial Recess Mounting Figure 2 CUTOUT INSTRUCTIONS (As viewed from outside of enclosure) NOTE: Dashed lines represent air conditioner. 2018 nvent 90164959-5 -

TECHNICAL INFORMATION SEQUENCE OF OPERATION The air conditioner comes standard with one internally mounted thermostat. There is one mode of operation; only cooling. During cooling mode the evaporator fan will be running. HEATING (OPTIONAL) When the enclosure temperature is below the heating thermostat setpoint, power is applied to the heater. When the enclosure temperature is 5 C degrees above the setpoint the heater is powered off. COOLING When the enclosure temperature is above the cooling thermostat setpoint, power is applied through the thermostat. The compressor is then energized either directly. The condenser impeller will start immediately if the unit is not equipped with an optional head pressure control switch. If the unit is equipped with an optional head pressure control switch, the condenser impeller will start once the refrigerant pressure reaches the setting of the switch. Component specific information is listed below. Operating the air conditioner below the minimum ambient temperature or above the maximum ambient temperatures indicated on the nameplate voids all warranties. DO NOT set the enclosure thermostat to a temperature lower than 21 C. Doing so can increase the likelihood of frost buildup on the evaporator coil. The moisture that the enclosure air can contain is limited. If moisture flows from the drain tube continuously, this can only mean that ambient air is entering the enclosure. Be aware that frequent opening of the enclosure s door admits humid air that the air conditioner must then dehumidify. STANDARD AND OPTIONAL COMPONENT OPERATION THERMOSTAT The VA08 air conditioner uses our standard 3204580 thermostat. The thermostat setpoint equals the temperature that the air conditioner turns off. The thermostat has a 5 C differential from setpoint until it calls for cooling or heating. An example of operation is shown below. FOR COOLING (35 C RANGE): Tstat setpoint = 35 C Cooling turns on at 40 C Cooling turns off at 35 C FOR HEATING (13 C RANGE): Tstat setpoint = 13 C Heating turns on at 13 C Heating turns off at 18 C NOTE: For testing purposes only, the thermostat stop screw may be removed (on units so equipped) to allow settings below 21 C. After testing, replace the stop screw and verify that the thermostat can not be set below 21 C. Extended operation below 21 C can cause coil freeze ups resulting in reduced load and/or unit damage. HEAD PRESSURE CONTROL (OPTIONAL) Unit is set at the factory, no adjustment necessary. At a saturated condenser temperature of 48 C (1.14 MPa), the condenser fan will power on. At a saturated condenser temperature of 29 C (0.66 MPa), the condenser fan will power off. - 6 -

Dimensional Data UNIT CHARACTERISTICS Model VA081225GXXXA VA081525GXXXA VA082025GXXXA Height(MM) 725 725 725 Width(MM) 431 431 431 Depth(MM) 237 237 272 Unit Weight(kg) 34 35 44 IP Code Cooling Data IP56 internal loop IP34 external loop IP56 internal loop IP34 external loop IP56 internal loop IP34 external loop Refrigerant R134a R134a R134a Refrigerant Charge (g) 550 605 660 Cooling Capacity (W),L35 L35 1200 1500 2000 Cooling Capacity (W),L35 L50 960 1170 1540 Maximum Ambient Temp ( C) 55 55 55 Minimum Ambient Temp ( C) 20 20 20 Enclosure Airflow (m3/h) 388 571 571 External Airflow (m3/h) 524 571 688 Condensate Management Heating Data Hose discharge / Optional powered C/E Hose discharge / Optional powered C/E Hose discharge / Optional powered C/E Capacity (W) 2000 2000 2000 Electrical Data Rated Voltage (V) 230 230 230 Rated Frequency (Hz) 50 50 50 Voltage Range (V) 207-253 207-253 207-253 Cooling Amps at Max Conditions (A) 3.5 3.96 5.7 Heating Amps (A) 8.8 8.8 8.8 Compressor RLA / LRA (A) 1.92/13.5 1.92/ 13.5 3.1 / 22 Evaporator Fan RLA (A) 0.35 0.53 0.53 Condenser Fan RLA (A) 0.39 0.53 0.8 2018 nvent 90164959-7 -

WIRE DIAGRAMS VA08 GENERIC WIRE DIAGRAM (ACTUAL UNIT OPTIONS MAY VARY) - 8 -

SCHEMATICS SERVICE DATA COMPONENTS LIST Part Description Part Number VA081225GXXXA VA081525GXXXA VA082025GXXXA Capacitor, Compressor, Run 3218247 3218247 3218269 Capacitor, Condenser Impeller 3218246 90198027 3218288 Capacitor, Evaporator Impeller 3218246 90198027 90198027 Coil, Condenser 3218244 3218244 3218265 Coil, Evaporator 3218243 3218261 3218261 Compressor 90237688 90237688 89107887 Filter, Air, Reusable 3218252 3218252 3218252 Filter/Dryer 3208853 3208853 3208853 Head Pressure Control Switch (option) 90206992 90206992 90206992 Impeller, Condenser 3206049 90198025 3218286 Impeller, Evaporator 3218245 90198025 90198025 Capillary tube 90232012 90242554 90239288 Thermostat, SPDT, 55-100F 3204580 3204580 3204580 Display(option) 90164848 90164848 90164848 T-Black 769-603/004/000 90164849 90164849 90164849 T-Black 769-103 90164850 90164850 90164850 2018 nvent 90164959-9 -

MAINTENANCE COMPRESSOR The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and should provide years of satisfactory operating service. INLET AIR FILTER Proper maintenance of the inlet air filter, located behind the front cover, will assure normal operation of the air conditioner. If filter maintenance is delayed or ignored, the maximum ambient temperatures under which the unit is designed to operate will be decreased. If the compressor s operating temperature increases above designed conditions due to a dirty or clogged filter (or plugged condenser coil), the air conditioner s compressor will stop operating due to actuation of the thermal overload cut-out switch located on the compressor housing. As soon as the compressor temperature has dropped to within the switch s cut-in setting, the compressor will restart automatically. However the above condition will continue to take place until the filter or coil has been cleaned. It is recommended that power to the air conditioner be interrupted intentionally when abnormally high compressor operating temperature causes automatic shut-down of the unit. The above described shut-down is symptomatic of a clogged or dirty filter, thus causing a reduction in cooling air flow across the surface of the compressor and condenser coil. Do not run the air conditioner for extended periods of time with the filter removed. Particles of dust, lint, etc., can plug the fins of the condenser coil which will give the same reaction as a plugged filter. The condenser coil is not visible through the filter opening, so protect it with a filter. Continued operation under the above conditions can and will damage and shorten compressor life. The air conditioner is available with an easily removable inlet filter to facilitate necessary cleaning. There should be no reason to neglect this necessary maintenance. HOW TO REMOVE, CLEAN OR INSTALL A NEW INLET AIR FILTER RP aluminum washable air filters are designed to provide excellent filtering efficiency with a high dust holding capacity and a minimum amount of resistance to air flow. Because they are constructed entirely of aluminum they are lightweight and easy to service. To achieve maximum performance from your air handling equipment, air filters should be cleaned on a regular basis. The inlet air filter is located behind the front cover. To access filter,pull ring protruding from slot in bottom of front cover. The filter may now be cleaned or new filter installed. Cleaning Instructions: 1. Flush the filter with warm water from the exhaust side to the intake side. DO NOT USE CAUSTICS. 2. After flushing, allow filter to drain. Placing it with a corner down will assure complete drainage. - 10 -

CONDENSER AND EVAPORATOR AIR MOVERS Impeller motors require no maintenance. All bearings, shafts, etc. are lubricated during manufacturing for the life of the motor. If the condenser impeller motor (ambient impeller) should fail, it is not necessary to remove the air conditioner from the cabinet or enclosure to replace the impeller. The condenser impeller is mounted on its own bulkhead and is easily accessible by removing the front cover. CAUTION Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly deteriorate filters, condenser coils, blowers and motors, etc. Contact nvent Electronics & Electronical Protection China for special recommendations. REFRIGERANT LOSS Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks. Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during manufacture may require repair or recharging of the system. This work should only be performed by qualified professionals, generally available through a local, reputable air conditioning repair or service company. If the unit requires recharging, replace the charging tube with a new one, recommended size of charging copper tube is 6.35mm O.D. X 100mm L. Refer to the data on the nameplate which specifies the type of refrigerant and the charge size in ounces. Before recharging, make sure there are no leaks and that the system has been properly evacuated into a deep vacuum. 2018 nvent 90164959-11 -

TROUBLE SHOOTING BASIC AIR CONDITIONING TROUBLE SHOOTING CHECK LIST 1. Check manufacturer s nameplate located on the unit for correct power supply. 2. Turn on power to the unit. The evaporator (Enclosure or COLD air) fan should come on. Is there airflow? YES, proceed to step 3. NO, possible problem: Open motor winding Stuck impeller motor Obstructed wheel Repair or Replace defective part 3. Check thermostat setting and adjust thermostat to the lowest setting. This should turn the condenser fan and the compressor on. Did condenser fan and compressor come on when the thermostat was turned on? YES, proceed to step 4. NO, possible problem: Defective thermostat Replace Part 4. Are all impellers and the compressor running? If not the unit will not cool properly. 5. Check condenser (Ambient or HOT air) impellers for airflow. Is there airflow? YES, proceed to step 6. NO, possible problem: Defective thermostat Open motor winding Stuck impeller motor Obstructed wheel Repair or Replace defective part 6. Carefully check the compressor for operation - motor should cause slight vibration, and the outer case of the compressor should be warm. Is the compressor showing signs of this? YES, wait 5 minutes, then proceed to step 7. NO, possible problem: Defective thermostat Open motor winding Stuck impeller motor Obstructed wheel Repair or Replace defective part 7. Make sure the coils are clean. Then check evaporator air in and air out temperatures. If the temperatures are the same: Possible loss of refrigerant Possible bad valves in the compressor Repair or Replace defective part 8. To check for a bad thermostat, turn power to the unit off. Remove the upper access panel and place both thermostat wires onto one terminal (replace upper access panel for safety). This will activate the switch in the thermostat. Turn the power on and if all impellers and the compressor come on,the thermostat needs to be replaced. - 12 -

SYMPTOMS AND POSSIBLE CAUSES: Unit won t cool SYMPTOM POSSIBLE CAUSE Clogged fins on coil(s) Dirty filter Impellers not running Compressor not running Compressor runs, but has bad valves Loss of refrigerant Compressor tries to start but won t run Low line voltage at start. Should be +/-10% rated voltage. Compressor motor stuck Bad contactor Bad overload switch Unit blows breakers Undersized breaker/fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed (allowing humidity in) Mounting gasket damaged For additional technical support, contact nvent Electronics & Electronical Protection China at 400-820-1133. 2018 nvent 90164959-13 -

NOTES - 14 -

NOTES 2018 nvent 90164959-15 -

Rev. F P/N 90164959