Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Similar documents
Purdue e-pubs. Purdue University

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Study of R161 Refrigerant for Residential Airconditioning

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Air-Cooled Heat Exchanger Performance for R410A

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Sub-Critical Operation of the CO2 Expander/ Compressor

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Low GWP Refrigerants for Air Conditioning Applications

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

R32 Compressor for Air conditioning and Refrigeration applications in China

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Performance of CO2 Cycles with a Two-Stage Compressor

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

System Using Exhaust Heat from Residential GHPs

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

High Efficiency R-134a Compressor for Domestic Refrigerator

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Thermal Modelling for the Motor in Semi-hermetic Screw Refrigeration Compressor under Part-load Conditions

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Efficiency of Non-Azeotropic Refrigerant Cycle

Performance Testing of Unitary Split-System Heat Pump with an Energy Recovery Expansion Device

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Investigation, Analysis and Solution of Higher Noise of Heat Pump Water Heater

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Higher Efficiency, Lower Sound, and Lower Cost Air Conditioning Compressors: Part 1 Efficiency

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Purdue e-pubs. Purdue University. T. Hamada Mitsubishi Heavy Industries Ltd. N. Nishiura Mitsubishi Heavy Industries Ltd.

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Heat Transfer Characteristics and Heat Exchanger Performances for R407C Using Herringbone Heat Transfer Tube

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

The Effect of Inner Grooved Tubes on the Heat Transfer Performace of Air-Cooled Heat Exchangers of Co2 Heat Pump System

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

System Modeling of Gas Engine Driven Heat Pump

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Performance Measurement of R32 Vapor Injection Heat Pump System

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Manufacturing & Testing of Air-to-Refrigerant Heat Exchangers Based on 0.8mm Diameter Tubes

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Development and Application of Micro Channel Heat Exchanger for Heat Pump

Investigation of Evaporator Performance with and without Liquid Overfeeding

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Compressor Capacity Control

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Compressor Capacity Control: A New Direction

Real Time Upright Freezer Evaporator Performance Under Frosted Conditions

Experimental Investigation of Purification Function of Air Conditioner

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger Xiangfei Liang Shumin Xing Rong Zhuang Bo Zheng Follow this and additional works at: http://docs.lib.purdue.edu/iracc Liang, Xiangfei; Xing, Shumin; Zhuang, Rong; and Zheng, Bo, "Experimental Investigation on Condensation Performance of Fin-and- Flat-Tube Heat Exchanger" (2010). International Refrigeration and Air Conditioning Conference. Paper 1027. http://docs.lib.purdue.edu/iracc/1027 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2150, Page 1 Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger Xiangfei LIANG*, Shumin XING, Rong ZHUANG, Bo ZHENG Refrigeration Institute of, Inc. of Zhuhai, Jinji West Rd., Zhuhai City, 519070, P. R. China Phone: +86-756-8668924, Fax: +86-756-8668982, E-mail: liangxf@gree.com.cn * Corresponding Author ABSTRACT Condensation heat transfer performance of louvered fin-and-flat-tube heat exchanger () in single slab and in residential air-conditioning system were experimentally investigated, and were compared with fin-and-circular-tube heat exchangers (CTHX) under the same testing conditions. The test results showed that: had the characteristics of low pressure drop of air side, high pressure drop of refrigerant side and less refrigerant charge; the overall heat transfer performance of copper was higher than that of 7mm CTHX but a little lower than that of 9.52mm CTHX; the cooling capacity and EER of the residential air-conditioning system with were a little lower than those of the system with 9.52mm CTHX. 1. INTRODUCTION The rising price of the original material and the upgrading EER of the AC are accelerating the R&D on high efficient heat exchangers. The tube outer diameter of the fin-and-tube heat exchanger tends to decreasing with the good effects such as lower air-side pressure drop and less refrigerant charge, and the other trend which has the same effects is to flatten the circular tube. Wilson et al (2001) reported that when the 9.52mm 0.3mm circular tube was flattened to 2.57mm height, the condensation heat transfer enhancement factor of smooth tube reached 1.7~2.3 and that of internal grooved tube reached 3.5-4.5. When a circular tube was flattened, the flat cross section sketched in fig. 1 will be formed. The ratio of cross section area of the flattened tube to that of the circular tube with equal inner perimeter will decrease sharply with the height of the flat tube decreasing, as showed in fig. 2. Therefore, the refrigerant charge related to internal volume will decrease sharply, too. The internal volume of the flattened tube will be 28.9% the volume of 9.52mm 0.3mm circular tube and 39% the volume of 7mm 0.3mm circular tube when they were flattened to 2mm height. A s,f /A s,c 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 Figure 1: Sketch of circular tube and flattened tube in cross section view 0.2 0.1 0.0 Original Tube 9.52 0.3 Original Tube 7 0.3 0 1 2 3 4 5 6 7 8 9 10 Height/mm Figure 2: Cross section area ratio varies with the flattened tube height

2150, Page 2 The air-side friction drag of the fin-and-flat-tube heat exchanger will decrease due to the smaller form drag of the flat tube. The wake region of flat tube shrinks greatly and the fin efficiency increases due to smaller longitudinal tube pitch and longer fin-to-tube contact line in the air flow direction, compared to circular tube with equal outer perimeter, which will contribute to improve the heat transfer performance. However, the application feasibility of the new type heat exchanger to residential air-conditioning should be estimated through experiment and comparison to the traditional heat exchanger. The condensation heat transfer performance and air-side pressure drop of a new type heat exchanger with louvered fin and flat smooth copper tube were tested and compared with 9.52mm and 7mm traditional heat exchangers with louvered fin and internal grooved copper tube under the same working conditions in the paper. The cooling capacity and EER were tested and compared in a split type residential air conditioner just with the condenser altered among the three heat exchangers under the rated operating condition. 2. EXPERIMENT SETUP AND PROCEDURE 2.1 Test facility The experiments of heat exchanger condensation heat transfer performance were carried out in Air-conditioning and Heat Exchangers Laboratory which described by Liang et al (2006). The lab had an air enthalpy method calorimeter, so the split type residential air conditioner with three different condensers to be compared can be tested in the lab. 2.2 Test section The parameters of the three different condensers are listed in table 1. The picture and the refrigerant circuit of the fin-and-flat-tube heat exchanger () were showed in fig. 3 and fig. 4, respectively. There were thirty flat tubes flattened from 7mm 0.3mm circular tube in the, but only twenty-nine tubes were actually used into the refrigerant circuit. The longitudinal tube pitch of the which is 17mm was the shortest among the three HXs. Each HX in table 1 has the same length of frontal area and the closely equal height. Table 1: The geometric parameters of the condensers HX Symbol Tube Material Rows Fin Type Fin Longitudinal Transversal Pitch Tube Pitch Tube Pitch 7S (Flattened) Copper Single Louvered 1.63mm 17mm 21.65mm 7G Copper Single Louvered 1.6mm 19.05mm 12.7mm 9.52G Copper Single Louvered 1.6mm 25.4mm 22mm (Note: S-Smooth, G-Grooved) Figure 3: Picture of Figure 4: Refrigerant circuit of 2.3 Test procedure

2150, Page 3 The three single-slab condensers were tested firstly to gain the condensation capacity, air side and refrigerant side pressure drops, then tested to get the cooling capacity and power consumed after they were bended and installed in a split type residential air conditioner. The single-slab condensers were tested under the following working conditions controlled for comparison purpose: dry bulb temperature, wet bulb temperature and frontal velocity of inlet air, refrigerant pressure and superheat at inlet and refrigerant subcooling at outlet of the condenser. When air side pressure drop was tested, only the foregoing three parameters of the inlet air were controlled, the refrigerant loop shut down and there was no refrigerant in the condenser. The operating condition specified for condensers as follows, Refrigerant: R-22 Inlet refrigerant absolute pressure: 1.729-2.033MPa Inlet air dry bulb temperature: 35 Inlet refrigerant superheat: 20 Inlet air wet bulb temperature: 24 Outlet refrigerant subcooling: 2-8 Inlet air frontal velocity: 0.5-2.8m/s The cooling capacity and EER were tested and compared in a split type residential air conditioner under the rated operating condition just with the condenser altered among the three heat exchangers. The refrigerant charge and the opening of the same electronic expansion valve (EEV) were adjusted to optimize the cooling capacity and EER of the residential air conditioner. The operating condition specified for residential air conditioner as follows, Inside room dry bulb temperature: 27 Outside room dry bulb temperature: 35 Inside room wet bulb temperature: 19 Outside room dry bulb temperature: 24 3. RESULTS AND DISCUSSION 3.1 Test results of single-slab heat exchangers The air side pressure drop of the three heat exchangers tested is showed in fig. 5 and that of the is the lowest under the same frontal velocity. The air side pressure drop of is 14.3Pa, and is 29% and 46% lower than that of and, respectively, at the frontal velocity 2m/s. The main reason is in that the flat tube has lower form drag than the original circular tube. The condensation capacity of the three condensers tested was reduced for better comparison with each other. Relative condensation capacity per unit frontal area (Q c /A y )/(Q c /A y ) R defined as ratio of the target condenser s condensation capacity per unit frontal area to a constant. The s condensation capacity per unit frontal area was modified by multiplying the factor 1.0345 (=30/29) to take into account the unused 30 th tube. The relative condensation capacity per unit frontal area of the three condensers were showed in fig. 6, that of is a little lower than or equivalent to that of, but about 10% lower than that of, when the inlet air frontal velocity v y is in the range of 1.5~2.0m/s. The relative trend showed in fig. 6 usually is not the trend in actual use since the condenser blower can not provide constant air volume flow rate when the condensers have different airside friction drag. To take the airside pressure drop into consideration, physical parameter for the abscissa in fig.6 was changed into fan power theoretically consumed per unit frontal area, thus fig. 7 formed. The theoretical fan power per unit frontal area is the product of outlet air velocity v a and the total pressure p a,t which produced by the condenser blower. From fig. 7 we can see that, the relative condensation per unit frontal area of is obviously higher than that of, but a little lower than that of. The refrigerant side pressure drop of the three condensers under different test conditions were showed in fig. 8, the abscissa of the figure is the ratio of the total mass flow rate to a constant. Obviously, the pressure drop of is greatly higher than that of and. The smaller cross section area of flat tube caused higher refrigerant mass flow velocity, and the normal velocity gradient adjacent to the internal wall of the flat tube is much higher, the refrigerant circuit of has a very longer circuit, which are the main factors leading to higher pressure drop. The has the characteristic of high pressure drop in refrigerant side, which greatly limits this type of heat exchanger s application to condenser just for cooling unit. It can not be used as evaporator or condenser for air source heat pump.

2150, Page 4 p a //Pa 50 45 40 35 30 25 20 15 1.1 1 0.9 10 5 0 0.5 1.0 1.5 2.0 2.5 3.0 v y /m/s (35/24 ) Figure 5: Air side pressure drop 0.8 1.4 1.6 1.8 2.0 v y /m/s (35/24, R22, 1.856MPa, SH20,SC8 ) Figure 6: Relative condensation capacity per unit frontal area 1.4 1.3 1.2 1.1 1.0 p r /kpa 140 120 100 80 60 40 0.9 0.8 10 30 50 70 90 110 130 p a,t v a /W/m 2 (35/24, R22, 1.73MPa, SH20,SC8 ) Figure 7: Relative condensation capacity per unit frontal area 20 0 0.7 1 1.3 1.6 1.9 (R22) Figure 8: Refrigerant side pressure drop 3.2 Test results of the residential air conditioner installed with heat exchanger as condenser The split type residential air conditioner was charged with R22, the compressor displacement of which is 19.5cc/rev (motor rotate speed about 2880rev/min). EEV opening and refrigerant charge were adjusted to optimize the cooling system after target condenser was installed in the residential air conditioner. Test results were listed in table 2, from this table we can see that, the cooling capacity and EER of the system with is higher than those of the system with but lower than those of the system with. The refrigerant charge of the system with is 18.7% and 27.8% lower than that of the system with and, respectively.

2150, Page 5 If the 30 th flat tube was in the refrigerant circuit of, the cooling capacity and EER would be more close to those of the system with. The comparison results in the cooling system obviously agree with the foregoing results in single-slab heat exchanger. Table 2: Test results of the residential air conditioner HX Symbol R22 Charge/g Cooling Capacity/W Power/W EER 650 3167 1055 3.00 800 3119 1064 2.93 900 3182 1041 3.06 4. CONCLUSIONS Condensation heat transfer performance of a new type louvered fin-and-flat-tube heat exchanger () in single slab and in residential air-conditioning system were experimentally investigated, and were compared with fin-andcircular-tube heat exchangers (CTHX) under the same testing conditions. The test results showed that: 1) had the characteristics of low pressure drop of air side, high pressure drop of refrigerant side and less amount of refrigerant charged. The pressure drop of is 29% and 46% lower than that of 7mm and 9.52mm CTHX, respectively, at the frontal velocity 2m/s. 2) The overall heat transfer performance of was higher than that of 7mm CTHX but a little lower than that of 9.52mm CTHX. 3) The cooling capacity and EER of the residential air-conditioning system with were a little lower than those of the system with 9.52mm CTHX, and the refrigerant charge is 27.8% lower than the system with 9.52mm CTHX. 4) The application of the new type was limited to condenser for cooling unit in practice due to its refrigerant side high pressure drop. The heat transfer performance of the new type will be improved by using internal grooved flat tube or grooved elliptical tube. The grooved elliptical tube will be helpful to reduce the refrigerant side pressure drop, thus the application arrange will probably extend to evaporator or condenser for air source heat pump. REFERENCES Liang, X., Zhai, L., Huang, H. and Zhuang R., 2006, Investigation of Inserts to Enhance Flow Boiling Heat Transfer in Tubes. Proceedings of International Refrigeration and Air Conditioning Conference at Purdue. Wilson, J. W., Chato, J. C. and Newell, T. A., 2001, CDA Flattened Copper Tube Project Final Report. ARTI Final Report. CDA- Report2.