PREMIER PLATINUM INFRARED TRIPLE RANGE HYDROCARBON SENSOR Exd Certified versions *** Available in EN50271 / SIL1 Certified versions ***

Similar documents
Technical data sheet TDS0034

LOW POWER VERSION DUAL HYDROCARBONS AND CARBON DIOXIDE SENSOR Exd Certified VERSIONS *** Available in EN50271 / SIL1 Certified versions ***

PREMIER PLATINUM INFRARED GAS SENSOR

Technical data sheet TDS0060

CO2 Carbon Dioxide Sensor

Key Features. General Description

IR1xxx Series 1, IR2xxx Series 1 Miniature Infrared Gas Sensors for Hazardous Areas and Intrinsic Safety in Mining

IR15TT-R Miniature Infrared Gas Sensor for Monitoring Carbon Dioxide and Methane up to 100% Vol.

IR25 Dual Gas Series Datasheet

IR15 Dual Gas Series Datasheet

IR15TT-R Miniature Infrared Gas Sensor for Monitoring Carbon Dioxide and Methane up to 100% Vol.

IR1 Single Gas Series Datasheet

VQ500 Series Combustible Gas Detector Elements

IRceL CH4 Methane (CH 4

MICROpeL 75 Combustible Gas Sensor Part Number: PM

Integrated IR Datasheet

Lamp Supply (Recommended)

4P75 CiTipeL Combustible Gas Sensor Part Number: PM

4P-90 CiTipeL Combustible Gas Sensor Part Number: PM

ALTAIR 5X Multigas Detector Product Specification

Dräger Polytron Pulsar 2 Detection of flammable gases and vapours

P R O D U C T D ATA S H E E T

Dräger Polytron Pulsar 2 Open Path Gas Detector

PrimaX IR Gas Transmitter Designed for Reliable Performance in Extreme Conditions

ULTIMA X5000. MSAX5000.com

Model D12-IR. Digital Gas Transmitter...

Dräger PIR 3000 Detection of flammable gases and vapours

S5000 Gas Monitor. GMS5000.com

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

Dräger X-am 2500 Multi-Gas Detection

Dräger Polytron Pulsar 2 Detection of flammable gases and vapours

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011

Dräger Polytron 8000 Stationary gas detector (EC)

Dräger Polytron SE Ex Fixed Gas Detector

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

VQ600 Datasheet. Pellistor Gas Sensor for Hazardous Areas (Fixed Systems) FEATURES TECHNICAL SPECIFICATION OPERATION

Dräger X-am 5600 Personal Monitor Multi-Gas Detection Device

SIMRAD GD10 IR GAS DETECTOR

Module Features are-configurable, no module jumpers to set

4) Intrinsic Safety Certification

Dräger X-am 5000 Multi-Gas Detection

SIMRAD GD10PE IR GAS DETECTOR

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Dräger Pac Ex 2. Elegant and smart... Explosive hazards and lack or surplus of oxygen under control

PolyGard Single Point Controller SPC-X3-34XX for Combustible Gases

Xgard. Fixed detectors For flammable, toxic or oxygen gases

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

TX6351 TX6352 Sentro 1 Universal Gas Detector Contents

OLCT 700 & 710. Certifications FIXED GAS DETECTION. Better detection. Better protection.

Danfoss gas detection units

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS

INSTRUCTION MANUAL (ATEX / IECEx)

Dräger PIR 7000 Flammable Gas Detection

Dräger X-am 5000 Multi-Gas Detection

Hydrocarbon Gas Detector

SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL

Pac Ex 2. Elegant and smart Explosive hazards and lack or surplus of oxygen under control

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

GAS PLUS ALARM SYSTEM

SEC Signature Process Gas Analyzer

Sensepoint. Fit For Purpose Flammable, toxic and Oxygen versions available High performance, low cost Suitable for new and retro fit applications

Safe Operation Manual. Honeywell IQ Force Gas Detector

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Datasheet: K-22 LO Sensor

THE BELGIAN PIONEER IN GAS DETECTION

REGARD. REGARD 4-20 AND Ex CHANNEL CARDS INSTALLATION AND OPERATING MANUAL (FOR ATEX VERSION CARDS)

Dräger Polytron 8310 Stationary gas detector (DSIR)

IREX Pellistor exchange IR gas detector

GasAlertMicroClip X3 Specifications

P R O D U C T D ATA S H E E T

APPLICATION DATA SHEET

SprintIR -W CO2 Sensor

Dräger PEX 3000 Flammable Gas Detection

Carbon Monoxide Transmitter

Installation Manual Tracker 221

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

Combustible Gas Detection and Control System

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

FIRERAY 5000 range USER GUIDE

Dräger Pulsar 7000 Series Detection of flammable gases and vapours

Sensepoint. Fit For Purpose Flammable, toxic and oxygen versions available High performance, low cost Suitable for new and retro fit applications

Model 144H. Product Data Sheet , Rev DB February Content

3M Oldham OLCT 100. Description. Fixed Gas Detector

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

Gas cylinder scale Model GCS-1

VQ600 Series Combustible Gas Sensing Head

Relays for use in hazardous locations. Class I, Division 2 and ATEX

Danfoss gas detection unit Type GD Heavy Duty

CO warning instruments and gas spillage detectors

INSTRUCTION MANUAL (ATEX / IECEx)

G-TECTA TM. Portable Gas Detection Instruments

IMPORTANT. PLEASE NOTE: The infrared beam path MUST be kept clear of obstructions at all times!

BA374C Intrinsically safe field mounting indicating temperature transmitter

MODEL 9010/9020 LCD CONTROL UNIT

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

APPLICATION DATA SHEET

Transcription:

Technical data sheet TDS0118 PREMIER PLATINUM INFRARED TRIPLE RANGE HYDROCARBON SENSOR Exd Certified versions *** Available in EN50271 / SIL1 Certified versions *** SIL1 Non - SIL MSH-PS/HC MSHia-PS/HC MSH-P/HCP MSHia-P/HCP FEATURES High resolution infrared sensor measures methane from 0 to 100% volume with a resolution of 0.01 % for 0-5% methane and 0.1% for 5-100% volume. Combines all the features of the well-proven range of Premier hydrocarbon sensors, enabling the accurate measurement of 0-100% vol. methane with one sensor. Offers reduced response times when compared with earlier versions. Contains all the necessary optics, electronics and firmware to provide a linearised, temperature-compensated output for both methane and propane. Can be configured for either methane, 0-100% or propane 0-2% volume measurements. Choice of output format digital output (floating point and binary), direct pellistor replacement or industry standard 0.4 to 2 volts. Manual calibration option can be performed without digital commands. User configurable using USB powered Premier Configuration Unit. Analogue output is scaleable in % volume or % LEL. Internal Flash memory allowing sensor firmware updates via configuration equipment. Enhanced EMC protection. Dynament Limited Hermitage Lane Industrial Estate ٠ Kings Mill Way ٠ Mansfield ٠ Nottinghamshire ٠ NG18 5ER ٠ UK. Tel: 44 (0)1623 663636 ٠ Fax: 44 (0)1623 421063 email: sales@dynament.com ٠ www.dynament.com TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 1 of 12

DESCRIPTION Dynament infrared sensors operate by using the NDIR principle to monitor the presence of the target gas. The sensor contains a long life tungsten filament infrared light source, an optical cavity into which gas diffuses, a dual temperature compensated pyroelectric infrared detector, an integral semiconductor temperature sensor and electronics to process the signals from the pyroelectric detector. Two versions are available:- 3 Pin Version - Pellistor Replacement Infrared These sensors provide a pellistor style linearised, temperature-compensated output as shown in Graph 1. They can either be supplied pre-set to customer specification or may be configured by the user by means of a configuration unit available from Dynament Ltd. The output signal can be set to rise or fall with increase in the gas level. 5 Pin Version - Multi-Purpose Range This version of the sensor provides maximum user flexibility by providing the following output options:- Industry Standard 0.4 to 2 volt linearised, temperature-compensated output as shown in Graph 2, or alternative voltages for zero and full-scale outputs. Digital output for direct communications with instrument electronics. Rising or falling output with increasing gas level for the pellistor replacement, bridge output as shown in graph 1. The digital output is a UART format comprising 8 data bits, 1 stop bit and no parity. Refer to specification for available baud rates. Contact Dynament Ltd for protocol details. Voltage Voltage Bridge Supply Voltage Rising 2.5 Volts Maximum 2 Volts Supply Mid-point Falling 0.4 V 0.1 Volts Minimum - full scale Zero + full scale Gas Zero full scale Gas Graph 1 Graph 2 Pellistor Replacement Characteristic 0.4 2 Volt Characteristic TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 2 of 12

Patent Protection The sensor design is protected by the following Patents Great Britain GB 2 401 432 & GB 2 403 291 Europe EP 1544603 & EP 1818667-Pending France EP [ FR ] 1544603 Germany EP [ DE ] 1544603 Italy EP [ I ] I1544603 Switzerland EP [ CH ]1544603 USA 7, 244, 939 Other World Patents Pending TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 3 of 12

Relative Response Characteristics The Premier High Resolution methane sensor is calibrated to provide an output signal linearised for 0-100% volume methane during manufacture. However, the sensor will also respond to a range of other hydrocarbon gases. The following graph shows the relative response to some of the common hydrocarbons. These characteristics can be used as a guide to setting up the associated instrument alarm levels. 5.00 4.50 Premier methane sensor cross sensitivity Reading on methane scale % volume 4.00 3.50 3.00 2.50 2.00 1.50 1.00 0.50 M ethane Ethane Propane Butane Pentane Hexane Ethylene Ethanol Propylene Cyclopentane 0.00 0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 Applied gas % volume Note Refer to data sheet TDS0050 for additional cross reference data TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 4 of 12

Temperature Compensation The Premier sensor is temperature compensated over the range of -20 C to +50 C. The output variation is ± 0.1% volume methane or ± 10% of the reading for the range 0 to 5% volume, whichever is greater. Gas Reading % Volume Methane 5 4.5 4 3.5 3 2.5 2 1.5 1 Premier high Resolution Methane Sensor Temperature Compensation, Gas Range 0 5% Volume, 20⁰C to +50⁰C Min limit Max Limit Ideal reading 0.5 0 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 Applied Gas % Volume Methane For the range 5% to 100% volume the output variation is ± 10% of the reading. Premier high Resolution Methane Sensor Temperature Compensation, Gas Range 5 100% Volume, 20⁰C to +50⁰C 95 Gas Reading % Volume Methane 85 75 65 55 45 35 25 Min limit Max Limit Ideal reading 15 5 5 15 25 35 45 55 65 75 85 95 Applied Gas % Volume Methane TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 5 of 12

Linearity The linearity at ambient temperature is ± 10% of the applied gas, or +/-0.05% volume, whichever is greater. The following graphs show actual test data for linearity over the ranges 0-5% volume and 5-100% volume. 5 Premier high Resolution Methane Sensor Linearity, Gas Range 0 5% Volume, Sample of 7 Sensors Gas Reading % Volume Methane 4.5 4 3.5 3 2.5 2 1.5 1 Min Limit Max Limit Average 0.5 0 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 Applied Gas % Volume Methane Premier high Resolution Methane Sensor Linearity, Gas Range 5 100 % Volume, Sample of 7 Sensors Gas Reading % Volume Methane 95 85 75 65 55 45 35 25 Min Limit Max Limit Average 15 5 5 15 25 35 45 55 65 75 85 95 Applied Gas % Volume Methane TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 6 of 12

Calibration options Dynament recommend a maximum interval of 12 months between calibration checks. A small amount of zero drift can be accomodated by re-zeroing the gas detector against the sensor. The degree of drift that is acceptable should be determined by the user. Note that the subsequent change in gas reading will be greater than the change in zero reading. The Hi-Res Gas sensor has three ranges in all. Range 1 0-5% volume methane Range 2 0-100% volume methane Range 3 0-2% volume propane If the sensor requires either a Zero or Span adjustment, there are two methods that can be used: 1) By using the Premier Configuration Unit When used in conjunction with dedicated PC software, this device uses the data communication pins on the sensor to provide a means of calibration. 2) By using the data communications pins and software written in accordance with the protocol supplied by Dynament. Gas calibration is best carried out at 50% of the range for ranges 1, & 3 and at 100% for range 2. Other calibration levels, between 10% and 100% of the range can be used but may affect the accuracy of the readings. If the calibration gas level is entered incorrectly for any range, there will be an error in the calibration. It is the user s responsibility to ensure that the calibration procedure is correctly applied. Checks on the correct calibration gas level that are used during span operations should be implemented within the calibration routine of the host gas detector s firmware. Note: a zero calibration must always be carried out before a span calibration. Sensor warm-up time When power is first applied to the sensor, the voltage at the output pin is held at a pre-determined level. The default setting for this start-up value is the zero gas value. This condition is maintained for a default warm-up time of 45 seconds, after this time the output voltage represents the calculated gas value. Sensors can take up to 1 minute to indicate the correct gas reading. Note: the sensor can calculate any reading from -100% FSD to +200% FSD in the first minute. The output value that is read using the communications pins is always held at -250% FSD during the warm-up time. Both the voltage at the output pin during the warm-up time, and the duration of the warm-up time can be pre-programmed to alternative values at the time of ordering sensors. Temperature transients and gas flow rates. The Premier sensor employs a pyroelectric detector, the output from which can be disrupted by sudden changes in temperature. If there is an excessive change in the ambient temperature, gas sample temperature or flow rate, then the output signal will be momentarily frozen. Correct operation is restored when the effects of the transient have settled. Rates of change in the ambient temperature should be restricted to 2 C/minute and gas flow rates kept below 600 cc/minute. TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 7 of 12

Power supply considerations The sensor power supply rise time must be less than 50 ms to ensure correct operation. Operation outside the range of 3 5 V dc will result in either fault indication, or the sensor will not function correctly. Sensor over-range condition The sensor will continue to provide an output up to a pre-determined percentage of the full scale value; at this point the reading is clamped, regardless of any further increase in detected gas level. The over-range value should be specified when ordering; choose from the following values 100%, 125%, 150% and 200% The linearity of the output is only guaranteed up to the full scale for the sensor; the over-range condition for the host instrument should therefore be determined by the user. Sensor fault indication The sensor constantly performs checks on the internal memory contents, the incoming supply voltage and the analogue signal values. These checks are used to ensure that the sensor is operating within its correct parameters, and that no internal faults have developed. If a fault condition is detected: 1) the output will be set to 0V. 2) The output value that is read when using the communications pins, instead of the voltage output pin, will be set to -250% full-scale. As mentioned in the Sensor warm-up time section above, the voltage at the output pin during the warm-up time can be specified when ordering sensors. Digital interface The digital communication pins RX and TX operate at a 2.8V logic level. When interfacing to external circuitry that uses a higher voltage level it is necessary to limit the current that can flow. The external voltage level should be 5V maximum and a 3K3 resistor should be used in series with each communication pin. The Rx and Tx voltage limits are as follows: RX - VIH: Input High minimum voltage - 0.8 VDD = 2.24V RX - VIL: Input Low maximum voltage - 0.2 VDD = 0.56V TX - VOH: High minimum voltage - VDD - 0.7 = 2.1 TX - VOL: Low maximum voltage - 0.6V Contact Dynament Ltd for details of the required protocol. TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 8 of 12

SPECIFICATION @ 20 C (68 F) ambient temperature Operating Voltage Range: Operating Current: Programmable Voltage Ranges: Methane measuring range: Propane measuring range: Resolution: 3.0 5.0 V d.c. Constant current operation, current range 75 85mA Voltage Types 0.1V to 2.7V d.c. Bridge Types 0v to Bridge Supply Voltage 0-5%, 0-100% volume, or both 0-2% volume 0.01% for readings up to 5% volume methane 0.1% for readings from 5% up to 100% volume methane 0.01% propane for all readings Linearity: Warm up time: Accuracy: Pressure limits Methane response Time T50: <10s Methane response Time T90: <30s Propane response Time T50: <10s Propane response Time T90: <30s Zero Repeatability: Span Repeatability: Long term zero drift: Operating temperature range: Temperature performance over the range -20 C to +50 C(-4 F to 122 F): * May not be applicable when using gas cross-reference factors voltage resolution 42.7 µv. The output is linear within ± 10% of the applied gas, or +/-0.05%, whichever is greater. To final zero ± 2% full-scale: 1 minute ± 10% of the reading @ 20 C (68 F), 1 bar pressure, applied gas. ± 5% of the calibration pressure to maintain the accuracy ±0.05% volume methane ± 0.1% volume methane at 5% applied gas. ± 2% volume methane at 100% applied gas. ± 0.05% volume methane per month -20 C to +50 C (-4 F to 122 F) ± 0.1% volume or ± 10% of reading up to 50% of full scale, ± 15% of reading from 50% to 100% of full scale, or 2% of full scale whichever is greater over the range - 20 C to +50 C (-4 F to 122 F) Storage temperature range: -20 C to +50 C (-4 F to 122 F) Humidity range: 0 to 95% RH non-condensing. Digital signal format: 8 data bits, 1 stop bit, no parity. 2.8V logic level Standard baud rates: 38,400, 19,200, 9600, 4800 Zero output voltage Full-scale output voltage User configurable parameters and functions: Positive or negative going output Sensor zero function Sensor span function Over-range value MTBF: > 5 years Weight : 15 grams TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 9 of 12

CERTIFICATION DETAILS European ATEX Certification Approval body Sensor types MSH-P, MSH-PS SIRA Sensor types MSHia-P, MSHia-PS Certificate Number SIRA 04ATEX1357U (Ex & EN50271 / SIL1) Test Standards Certification Codes Input parameters Operating temperature EN60079-0:2012+A11:2013, EN60079-1:2014, EN60079-11:2012, EN60079-26:2015 EN 50271:2010 I M2 Ex db I Mb II 2 G Ex db IIC Gb 0.8W max, 30V max. (See footnote) -20 C to +60 C (See footnote) I M1 Ex db+ia I Ma II 2 G Ex db IIC Gb Ui=6V dc, Pi=0.8W (See footnote) International IECEx Certification Sensor types MSH-P, MSH-PS Sensor types MSHia-P, MSHia-PS Approval body SIRA Certificate Number IECEx SIR 05.0053U Test Standards Certification Codes IEC 60079-0:2011 IEC60079-1:2014 IEC 60079-11:2011 EN 60079-26:2014 Ma Ex db+ia I and/or Ex db I and/or Ex db IIC Gb Ex db IIC Input parameters 0.8W max, 30V max. Ui=6V dc, Pi=0.8W Operating temperature -20 C to +60 C (See footnote) North American Certification Sensor type MSH-P Sensor type MSHia-P Approval body Underwriters Laboratory Inc. Underwriters Laboratory Inc. File Reference E336365 E336365 Test Standards Hazardous Locations UL 60079 0, 4 th Edition UL 60079-1, 6 th Edition CAN/CSA-C22.2 No. 60079-0-1-7 CAN/CSA-C22.2 No. 60079-1 part 1, 1 st Edition Class 1, Zone 1, AEx d IIC and Ex d IIC Hazardous Locations UL913 7 th, Edition UL 60079 0, 4 th, Edition UL 60079 11, 2 nd, Edition CAN/CSA-C22.2 No. 157-92 Class I, II, III, Division 1 Class 1, Zone 0, AEx ia IIC, T4 with 60 C ambient Input/Entity parameters 0.8W max, 30V max. Ui=6V dc, Pi=0.8W, Ci=4.105µF, Li=0 mh Input parameters are defined for certification purposes only, refer to the Specification table for the sensor operating voltage and temperature range. TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 10 of 12

+ ve supply, see notes Signal 4.24 7.62 Tx 0.43 Rx MECHANICAL DETAIL - ve supply, see notes 5.08 10.67 4.8 +0.5/-0.0 16.6-0/+0.2 20 Dia. 15mm Dia 20mm NOTES 1. TOLERANCE: +/- 0.15 UNLESS OTHERWISE STATED. 2. RECOMMENDED PCB SOCKET WEARNES CAMBION LTD CODE: 450-3326-01-06-00. 3. USE ANTI-STATIC PRECAUTIONS WHEN HANDLING 4. DO NOT CUT PINS 5. DO NOT SOLDER DIRECTLY TO PINS 6. THE LABELLING ADDS UP TO 0.2 TO THE OUTER DIAMETER, AND UP TO 0.2 TO THE OVERALL HEIGHT All dimensions are in millimetres. Pins viewed from underside Diameter of pins = 1.5 +/- 0.05 Tx & Rx communication connections are available as either pads or pins NOTE The above pin configuration is shown for the POSITIVE version of the sensor. The NEGATIVE version has the +ve and ve supply pin positions exchanged. See ordering details. Warranty information All Dynament Platinum sensors carry a five year warranty against defects in materials and workmanship. The warranty is invalidated if the sensors are used under conditions other than those specified in this data sheet. Particular attention should be paid to the following criteria: Observe the correct supply polarity Do not exceed the maximum rated supply voltage of 5V Do not solder directly to the sensor pins Do not expose the sensor to corrosive gases such as hydrogen sulphide Do not allow condensation to take place within the sensor Dynament reserve the right to alter technical specifications, without prior notice, when it is appropriate to implement a technical enhancement that leads to improved performance. Should any changes be required that could affect the customer s use of the product, Dynament will endeavour to contact customers directly to inform them of the changes. TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 11 of 12

Ordering Details In order to completely specify the type of sensor that is required, the customer needs to provide the following information:- An Order Code (see below) that specifies the sensors basic physical and electrical characteristics. The sensor configuration requirements, including the required gas measurement ranges. EXAMPLE OF ORDER CODES MSH PS / HC / 3 / B / P / F FILTER : BLANK = OMITTED, F = FITTED SUPPLY POLARITY : P = Positive, N = Negative OUTPUT TYPE : B = Bridge, V = Voltage NUMBER OF PINS : 3, 4 or 5 CONFIGURATION OPTIONS (To be stated on customer order in addition to the Order Code) GAS TYPE : HC = Hydrocarbon, SIL1 HCP = Hydrocarbon Platinum, Non-SIL1 PLATINUM SENSOR: P = Non-SIL1 PS = SIL1 MSHia (For Mining M1applications only) 1. voltage for zero. 2. voltage for span. 3. Rising or falling output voltage with increasing gas level (for Bridge outputs) 4. Sensitivity e.g. 100 mv = 100 % volume CH4 for Bridge outputs, 0.4 2.4V = 100% volume methane for Voltage output sensors. 5. Communication speed 38,400 baud (default), specify alternative rate if required. 6. Over-range value: 100%, 125%, 150% and 200% of full-scale value. Pellistor Replacement - Explanation of Positive & Negative Polarity SIG DET COMP RX OUTPUT TX + - POS RX OUTPUT TX + - POS Note On the 3 pin version of the sensor, the RX and TX connections are pads, not pins. Typical Pellistor Pinout Premier Negative Polarity Option Premier Positive Polarity Option Use where the DET pin of the existing pellistor is connected to the Negative of the pellistor bridge supply. Use where DET pin of the existing pellistor is connected to the Positive of the pellistor bridge supply. TDS0118 Issue 2.4 13/07/17 Change Note 571 Page 12 of 12