Outside Humidity and Temperature Sensor

Similar documents
HT/O Outside Humidity and Temperature Sensor

DMFPM-2R MULTIFUNCTIONAL

RH & T Sensors & Humidistats. RH-DT Duct Mount RH & T Sensors. Description

Interface Modules for SENTRI

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT FLR TYPE FLAMEPROOF RADIATORS

Installation Instruction Venturi-Air Duct Kit. (Part No. S )

IMR 5000 IMR 400. CEMS Operating Manual IMR USA S/N: Sample IMR Sensors Inside IMR 400. Gas Dryer Inside. IMR Environmental Equipment Inc.

DESIGN MANUAL. The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0)

Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air

RSMFM-2R MULTIFUNCTIONAL

Installation and user manual for the BiWire / Conventional Repeater Panel

4100U City and Relay Cards Installation Instructions

Operating Instructions

HEATFAST HF9101-V1 AMBIENT SENSING TRACE HEATING THERMOSTAT

MODEL A5-2 SOLVENT & WATER RECOVERY SYSTEMS (EXPLOSION PROOF UNITS)

Frost Protection Thermostat

Analog Room Pressure Monitor RPC Series

Installation, Operation and Maintenance Manual

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EXHEAT INDUSTRIAL FLR & FLRA TYPE FLAMEPROOF RADIATORS

EW447-EW452 Series Mechanical Heat Meters FOR HEATING AND COOLING APPLICATIONS

IMR 5000 Operating Manual S/N: SAMPLE For information only! IMR Environmental Equipment Inc.

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI

Flush-mounted room thermostat

Thermal Reset Limit Thermostats Electromechanical TW according to DIN EN 14597

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

HYGROMER - MP 400 A Meteorology probe

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

CM921 - User Guide 1 day Wireless Programmable Room Thermostat with LoT technology

OPERATING AND MAINTENANCE MANUAL

INSTALLATION USE AND MAINTENANCE MANUAL. ATC Evolution ATC EVOLUTION. Class I - IP55 INFRARED HEATER ATC ELECTRICAL & MECHANICAL

Air Sampling Smoke Detection

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FAW, FAW-C & FAW-C-T TYPE AIR WARMERS FCR & FCR-A TYPE CONVECTORS

SEL-3422 Motor Relay HMI Quick-Start Guide

CO2 transmitters TRANSMITTERS TO DETECT CARBON DIOXIDE (CO 2 )

Inta City Concealed Shower Mixing Valve CT80010CP

CERAMIC HEATER MODEL NO: DEVIL 350B 230V/110V OPERATING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS GC ISS 1

Dual Input ph/orp Analyzer

VACUUM EXTRACTOR MODEL NO: CWVE1 OPERATING & MAINTENANCE INSTRUCTIONS PART NO: GC0916

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Digital Heat Block User Manual

AUTO CM CM USER GUIDE

Combi C30 & C35. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

2-ZONE EASYFIT INTRUDER ALARM

Induction Fryer. Instruction manual. Model Modèle Modell Modello Modelo Malli: CP793

Document No Issue 02 operation & installation manual. ZXr-A ZXr-P

ECO AND DATE /06 ARTWORK DESCRIPTION. 22 page A6 : Saddle stitch (2-wire) 6 page : 4 colour : 170gsm Silk 18 page : 1 colour : 100gsm Silk

2-Channel Smoke Detector SD - 110

Instruction manual. Remote control electric IR HEATER

Duct and Rough Service Carbon Monoxide Sensor

MIX Boiler & Font Range Service Manual

SLIM-LINE RC FAN CONVECTOR.

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

MODEL: O ELECTROCHEMICAL O2 DETECTOR (Used with ST1400 O2 Sensor) Part Number: MAN Rev. 0

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

DUST EXTRACTOR MODEL No: CDE1000

Endura AZ40 Oxygen and carbon monoxide equivalent (COe) analyzer

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

illuminated filter kettle

RFM Series RFM-ISR Barrier. Installation Manual

FTK+ Application. Types Available. Duct sensor for humidity and temperature. Datasheet

Complete packages with Software and Controller

It offers easy installation and the possibility for fast exchange of the sensor unit for service purposes.

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards.

10yr O2NE & Safe-Ox. User Manual

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy.

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

PCR-300 PCR-300 RC. Installation and Operating Instructions

HyBo - Hydraulic Interface Unit AMBIENT HEATING AND DOMESTIC HOT WATER PRODUCTION FOR CENTRAL HEATING SYSTEM UNIT CODE EHIU1

1228s Multidrop INSTRUCTIONS. Installation and Operation of the AMC-1228s Electrochemical Sensor Module For Use With Multidrop AMC Monitors

Dual Input Toroidal Analyzer

Dual Input ph/conductivity Analyzer

GETTING STARTED GUIDE NI Channel, 0 ma to 20 ma, 16-Bit Analog Output Module. This document explains how to connect to the NI 9265.

RH and Air Temperature Sensors

for relative humidity and temperature with calibration certificates

Semi flush-mount room thermostat

Model No: Little Devil II (inc ss)

Mitocell: Instructions for Use

Mix Boiler & Font Range ( #, #, #, , )

HI-LINE SUPER RC FAN CONVECTOR MODELS: 25-18,

Hygro/hygrothermal transducers (hygrometric)

Drying Cabinet Installation and Operating Manual

Pasto Sous vide water bath

Miniature Infrared Temperature Sensors with Optional Touch Screen Display. PSC-SSS-PM with touch screen display (-CRT version)

SECURITY LIGHT MODEL NO: CL6PIR OPERATION INSTRUCTIONS PART NO: GC0215

Installation, Operating and Servicing Instructions. Silverlink 600 Electric Pasta Boilers PB33, PB66

AU MX Digital Loop Card Installation Instructions

USERS, INSTALLATION AND SERVICING INSTRUCTIONS

DRY:SOON TOWEL WARMER

SAFETY INFORMATION AND WARNINGS

30KW ELECTRIC FAN HEATER

product safety Please read these instructions before operating the appliance and retain them for future use.

Commissioning Methodologies (CM) MUBS-09 Duct Mounted Temperature & Humidity Sensor Testing Method Statement

Hygro/hygrothermal transducers (hygrometric)

OPERATING & MAINTENANCE INSTRUCTIONS FOR EXHEAT RFA-OS TYPE FLAMEPROOF OVERSINK WATER HEATER

Transcription:

Installation Instructions HT/O Outside Humidity and Temperature Sensor Important: Retain these instructions CONTENTS 1 Unpacking... 1 2 Installation... 1 Fault Finding... 4 4 Maintenance... 5 5 Disposal... 8 1 Unpacking HT/O Installation Instructions TG200992 2 Installation 1 Dimensions 2 a Requirements 10 mm, 0.9 22 mm 0.87 Ø 5 mm 0.2 196 mm, 7.72 69.5 mm, 2.74 b 112 mm, 4.4 c d e f g ambient limit -40 C (-40 F) +60 C (+140 F) measurement -0 C (-22 F) +50 C (+122 F) HO 2 0 %RH 100 %RH Protection: IP65 HT/O Installation Instructions TG200992 Issue 1/A 0/01/08 1

HT/O Installation Instructions 2 Installation (continued) 2 B1 < L1 Requirements (continued) h i j k L1 > 1 m, 1 yd L2 B2 < L2 a Remove Cover b Caution: This unit contains static sensitive devices. Suitable anti-static precautions should be taken throughtout the operation to prevent damage to the units. BS EN100015/1 Basic Specification: protection of electrostatic sensitive devices. a 4 Fit Bracket, Shield and Sensor b c 44 mm (1.7 ) Ø 6 mm (0.24 ) 2 wallplugs and screws supplied 2 HT/O Installation Instructions TG200992 Issue 1/A 0/01/08

Installation Instructions HT/O 2 Installation (continued) 5 Insert Cable through gland 6 Wire to Controller 2 analog input channels IQ1 & IQ2 V+ RH T Tp C (+24V) IN C IN } humidity } temperature linked for current (I) linked for thermistor (T) earth (ground) screens at IQ end M16 gland V+ RH T Tp 0 (0V) N (in) + (+24V) 0 (0V) N+1 (in) + (+24V) N N+1 IQ humidity temperature linked for current (I) linked for thermistor (T) earth (ground) screens at IQ end Fit Cover Configure IQ 7 8 1 1 or IQ Configuration Manual 90-15 HT/O Installation Instructions TG200992 Issue 1/A 0/01/08

HT/O Installation Instructions 2 Installation (continued) 9 Set up IQ Sensor types It is recommended to use SET (Software Tool) for the setting of the sensor type module. For all IQ2 series controllers with firmware version 2.1 or greater, or IQ series controllers, the following SET Unique Sensor References should be used: Humidity :Humidity I Temperature :Thermistor HTOT ( C) Thermistor HTOT F ( F) Alternatively enter scaling manually as defined in tables below. For all other IQ contriollers see Sensor Scaling Reference Card TB100521A Temperature (thermistor) (-0 to +50 C, -22 t0 122 F) Units: C F Y I nput type 1 (therm V ) E Exponent U Upper 55 11 L Lower -5-1 P Points 11 x Ix Ox 1 2.641 50 122 2.470 40 104 4.460 0 86 4 6.66 10 50 5 7.668 0 2 6 8.102-5 2 7 8.482-10 14 8 8.807-15 5 9 9.078-20 -4 10 9.299-25 -1 11 9.476-0 -22 Humidity (current) (0 to 100 %RH) Y I nput type 2 (curr ma ) E Exponent U Upper 100 L Lower 0 P Points 2 x Ix Ox 1 4 0 2 20 100 10 Test System IQ Δ T Δ H Fault Finding Faults Long response time Complete failure Humidity reading too high Possible Causes Filter pollute d No power supply Condensation on sensor probe Remedies Replace filter Check power supply and cable Dry probe and replace filter if necessary 4 HT/O Installation Instructions TG200992 Issue 1/A 0/01/08

Installation Instructions HT/O 4 Maintenance Over time, the sensing element may become covered in dust. The dust can be removed using compressed air. Under no circumstances should water or cleansing agents be used on the sensing elements. It is recommended that the accuracy of the sensor is verified every 12 months. If the sensor falls outside the quoted accuracy, replace the filter and recalibrate as shown below: 1 Remove Cover Caution: This unit contains static sensitive devices. Suitable anti-static precautions should be taken throughtout the operation to prevent damage to the units. BS EN100015/1 Basic Specification: protection of electrostatic sensitive devices. 2 Detach Sensor Remove from Radiation Shield 4 Replace filter a unscrew b See Section 5, Disposal 7 2, 9 d c ACC/HTO/FILTER Caution: Do not touch humidity sensing element 5 Preparation Keep sensor and humidity chamber in same room for 4 hours before. Place probe in humidity chamber 0 mins before. Keep temperature constant during calibration. 6 push buttons Locate buttons 7 2, 9 calibration LED HT/O Installation Instructions TG200992 Issue 1/A 0/01/08 5

HT/O Installation Instructions 4 Maintenance (continued) 7 Two point calibration For calibration over whole working range Start calibration at lower humidity point. Difference between the two points should be >0%RH Low Humidity Calibration 1 Remove lid from the calibration chamber (ACC/CAL/HT) and clean chamber thoroughly. 2 Insert one of the cloths provided with the calibrating liquid. Pour calibrating liquid (ACC/CAL/HT/5%) onto the fabric. Refit lid and screw tightly. Insert probe into sensor aperture of chamber and tighten collar to provide air tight seal around the probe. Wait 0 min. 4 Press Down pushbutton for s to start. LED will illuminate. 5 Press Up or Down pushbutton to adjust measured value in 0.1% steps. 6 Either: Press Up pushbutton for s to stop. Calibrated value is stored. LED is extinguished. Or: Press Down pushbutton for s to exit calibration without storing value. LED is extinguished. High Humidity calibration 7 Remove lid from the calibration chamber (ACC/CAL/HT) and clean chamber thoroughly. 8 Insert one of the cloths provided with the calibrating liquid. Pour calibrating liquid (ACC/CAL/HT/80%) onto the fabric. Refit lid and screw tightly. 9 Insert probe into sensor aperture of chamber and tighten collar to provide air tight seal around the probe. Wait 0 min. 10 Press Up pushbutton for s to start. LED will illuminate. 11 Press Up or Down pushbutton to adjust measured value in 0.1% steps 12 Either: Press Up pushbutton for s to stop. Calibrated value is stored. LED is extinguished. Or: Press Down pushbutton for s to exit calibration without storing value. LED is extinguished. 8 One point calibration For calibration over limited range about single point This calibration decreases accuracy over remainder of working range Single Point Humidity Calibration 1 Remove lid from the calibration chamber (ACC/CAL/HT) and clean chamber thoroughly. 2 Insert one of the cloths provided with the calibrating liquid. Pour calibrating liquid (ACC/CAL/HT/5% or / 80%) onto the fabric. Refit lid and screw tightly. Insert probe into sensor aperture of chamber and tighten collar to provide air tight seal around the probe. Wait 0 min. 4 Either: (If chamber humidity >50%RH.) Press Up pushbutton for s to start. LED will illuminate. Or: (If chamber humidity <50%RH.) Press Down pushbutton for s to start. LED will illuminate. 5 Press Up or Down pushbutton to adjust measured value in 0.1% steps 6 Either: Press Up pushbutton for s to stop. Calibrated value is stored. LED is extinguished. Or: Press Down pushbutton for s to exit calibration without storing value. LED is extinguished. 9 Replace Radiation Shield 10 Re-attach Sensor 11 Replace Cover 6 HT/O Installation Instructions TG200992 Issue 1/A 0/01/08

Installation Instructions HT/O 4 Maintenance (continued) 12 Test System IQ Δ T Δ H HT/O Installation Instructions TG200992 Issue 1/A 0/01/08 7

HT/O Installation Instructions 5 Disposal WEEE Directive : At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre. Do not dispose of with normal household waste. Do not burn. Please send any comments on this or any other Trend technical publication to techpubs@trendcontrols.com Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 7,Switzerland by its Authorized Representative, Trend Control Systems Limited. Trend Control Systems Limited 2007. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes. Trend Control Systems Limited P.O. Box 4, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)140 211888 Fax:+44 (0)140 241608 www.trend-controls.com Trend Control Systems USA 6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-900, Fax: (425)869-8445 www.trend-controls.com 8 HT/O Installation Instructions TG200992 Issue 1/A 0/01/08