Sustainable Fire Protection for Military Vehicle and Aircraft Applications

Similar documents
Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

Fire suppression systems for server rooms and data centres

Fire Extinguishing Agents for Protection of Occupied Spaces in Military Ground Vehicles

ASSEMBLY 37TH SESSION

MINIMAX FIRE PRODUCTS WHITE PAPER THE COST-BENEFIT ADVANTAGES OF REPLACING HALON WITH 725 PSI MX 1230 CLEAN AGENT FIRE SUPPRESSION SYSTEMS

Study of R161 Refrigerant for Residential Airconditioning

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

Hazardous Material Safety Program

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

DFE T ECHNOLOGY. At Conceptronic, the design and management process for reflow soldering systems is called Dynamic Flow Engineering, or DFE.

How can I protect invaluable assets and the environment from the effects of a fire?

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

Full Scale Battery Tests

BOC FS125 The Fire Extinguishing Solution

Optimization of Hybrid Noncondensable Gas Removal System for a Flash Steam Geothermal Power Plant

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Fire Suppression. Water-Mist : A Revolutionary Green Technology in. - by Nimit Sheth TALL, SMART, SAFE BUILDINGS FOR SMART CITIES.

Module 5: Combustion Technology. Lecture 38: Combustion Burners

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Fire Suppression Tests Using a Handheld Water Mist Extinguisher Designed for Spacecraft Applications

CLEAN AGENTS & CLASS C FIRE HAZARDS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

FIRE SUPPRESSION SYSTEM

HALON FLIGHTLINE EXTINGUISHER EVALUATION: DATA SUPPORTING STANDARD DEVELOPMENT [INCLUDES NOVEMBER 2007 ADDENDUM]

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Performance of an Improved Household Refrigerator/Freezer

REVIEW ON WATER MIST FIRE SUPPRESSION SYSTEM

COMMISSION REGULATION (EU)

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

High Performance Diesel Fueled Cabin Heater. Abstract

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

This is a repository copy of Fluorinated halon replacement agents in explosion inerting.

Energy Use in Refrigeration Systems

Performance Measurement of R32 Vapor Injection Heat Pump System

Smoke Layer Height and Heat Flow through a Door

Fire Test Evaluation using the Kerosene and Aviation Fuel

Sprinklers Modeling for Tunnel Road Fire Fighting

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING

XC10 combined fire detection and extinguishing control

European Ethylene Producers Conference (EEPC) October 24-26, 2012 Flame Interaction and Rollover Solutions in Ethylene Cracking Furnaces

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Evaluation of HCFC Alternative Refrigerants

MINIMUM PERFORMANCE REQUIREMENT FOR AIR FORCE FLIGHTLINE FIRE EXTINGUISHERS:

WATER MIST CONVENTION AND EXHIBITION

Examination of Performance of Water Mist Fire Suppression Systems under Ventilation Conditions

XC10 combined fire detection and extinguishing control

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

Performance of CO2 Cycles with a Two-Stage Compressor

Safe, Effective, Environment-friendly

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

HFO-1234yf Performance in a Beverage Cooler

Bombardier Challenger Fire Protection

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

The Condensate Water Systems

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

White Paper. The Victaulic Vortex Fire Suppression System Fire Suppression for Electrical and Electronic Applications

ON-BOARD INERT GAS GENERATING SYSTEMS: A BETTER ALTERNATIVE Justin Bright Advisor: Margaret Browning Hampton University. Abstract

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

Daikin s Policy. and Comprehensive Actions on the Environmental Impact of

Homework Chapter2. Homework Chapter3

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

*Corresponding author;

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

K.F. Fong *, C.K. Lee, T.T. Chow

How can you minimize consequential damages in case of a fire?

Transcritical CO2 Bottle Cooler Development

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

HKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009

Steam: Yesterday, Today and Tomorrow The Use of Steam as an Efficient Heat Source

The Experimental Study and Simplified Model of. Water Mist Absorbing Heat Radiation

Numerical analysis of flow characteristics of fire extinguishing agents in aircraft fire extinguishing systems

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

DELTA-TE III. Nozzle-mix line burner

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

AUTOMATIC FIRE & EXPLOSION SUPPRESSION SYSTEM.

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

A comprehensive systems-level approach in cabin design minimizes fire potential and helps ensure passenger safety. aero quarterly qtr_04 11

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Adequate protection of enclosed facilities

Transcription:

Sustainable Fire Protection for Military Vehicle and Aircraft Applications Aerojet Gary Holland gary.holland@rocket.com Jennifer McCormick jennifer.mccormick@rocket.com +1-425-885-5000 3M Company Paul Rivers perivers2@mmm.com +1-651-733-0029 Abstract Next generation Halon alternative fire protection solutions ideally incorporate sustainable technologies that balance performance needs with safety and environmental concerns when used to address fire threats. The fire extinguishing performance of FK-5-1-12 has been demonstrated in military ground vehicle and aircraft applications. In order for clean agents to be effectively used in these types of environments, they must be applied in a manner that quickly disperses the agent so that explosion fire threats can be mitigated and suppressed. Solid propellants are used for generating large quantities of working gas upon command in applications ranging from automotive airbag inflation to fire extinguishment. The working gas from solid propellant is utilized in Hybrid Fire Extinguisher (HFE) technology to dispense a variety of fire suppression fluids including clean agents. The combination of HFE technology with FK-5-1-12 creates a fire protection system that is highly effective against explosive-like fires, maintains large safety factors for occupied space applications, and is environmentally sustainable. FK-5-1-12 has several positive features when compared to other Halon alternatives including zero ozone depletion potential, five-day atmospheric lifetime, global warming potential of one, and a low toxicity profile. Furthermore, FK-5-1-12 is a liquid agent at room temperature; as such, combined with the HFE, it remains safely unpressurized until deployed. The HFE uses solid propellant to pressurize the system, which enables consistent operation over a wide temperature range. Since the HFE is not pressurized until activated; it can be operated in any orientation; and chemically active additives can be incorporated into the propellant making the effluent gases more effective at extinguishing fires than inert agents, thus allowing overall system weight and size to be reduced. Various different test series have been conducted in order to demonstrate the performance of a Hybrid Fire Extinguisher with FK-5-1-12. This includes static discharge and live fire testing. Initial live fire testing was sponsored through the Next Generation Fire Suppression Technology Program (NGP). The NGP sponsored testing validated the principle in a simulated aircraft environment. Since then, third party testing has successfully demonstrated the required performance of a Hybrid Fire Extinguisher with FK-5-1-12 for vehicle crew compartments. The fire protection system is also under consideration for use in US Army applications. The combination of the two technologies creates a system that further enhances the advantages of the individual technologies and effectively addresses the fire threat scenarios observed in military ground vehicles and aircraft.

Introduction The current challenge in developing long term solutions that replace Halon fire suppression is to strike the right balance of performance and safety while navigating the rapidly changing regulatory landscape. Through critical exemptions, military decision makers and airframe manufacturers have heretofore not been required to make a wholesale conversion from Halon. Many applications have been largely immune to any conversion requirements. But, the accelerated transformation in the environmental regulatory climate in the USA has introduced sustainability as a key factor in deciding what solutions are employed equal to Halon. Weight, space and extinguishment speed are critically important in the uniquely demanding needs in military vehicles and modern aircraft of all types. Now the combination of proven gas generation technology with novel non-kyoto 2 nd generation clean agent chemistry is being recognized for its effectiveness at reducing risk not only from explosion and fire but from uncertain future regulatory action. Hybrid Fire Extinguishers Hybrid Fire Extinguishers (HFEs) consist of two major subsystems: a propellant cartridge (or solid propellant gas generator) and a tank filled with fire suppression fluid. The propellant cartridge is used to pressurize the tank, and thus it is what makes an HFE unique with respect to traditional nitrogen pressurized systems. Figure 1 contains a diagram of a generic HFE. 1 Figure 1 Hybrid Fire Extinguisher Solid Propellant Gas Generators (SPGGs) provide a means for efficiently storing gas that can be released upon demand. They are advantageous for many specialized applications since the discharge rate and temperature of the gas can be tailored. One of the most common uses of SPGGs is for the inflation of automobile airbags; therefore, the reliability and consistent performance has been proven through decades of field experience.

The major components of an SPGG include the following 2 : Initiator (often called a squib) Propellant Housing (or pressure vessel) Control orifice(s) (or discharge ports) Figure 2 contains a diagram of a generic SPGG 1. Figure 2 Solid Propellant Gas Generator The Initiator receives the firing signal and activates a small pyrotechnic charge that ignites the propellant. One of the most common types of initiator designs is the bridgewire initiator. A low resistance material (the bridgewire) is located between two electrical conductors and surrounded by a pyrotechnic charge. The charge is ignited when the proper high-voltage discharge (firing signal) is used to heat and break the bridgewire. 3 The propellant portion of the HFE consists of two components; a booster and a main propellant. The booster propellant typically consists of a fast-burning, easily ignitable propellant that receives the initiator charge and quickly generates a significant quantity of hot gas. This increases the pressure within the housing to a level where the main propellant can be efficiently ignited and burned. The slower-burning main propellant generates the majority of the SPGG working gas. The working pressures of SPGGs range from hundreds to tens of thousands of pounds per square inch depending upon the application. The housing acts as the pressure vessel while the control orifice(s) regulate the gas flow from the SPGG.

The amount and rate of working gas expelled by an SPGG depends upon the properties of the solid propellant and the design of the SPGG components. A number of equations are used to describe the relationships between the various parameters. Two major equations used to describe the mass flow rate of gas generated by burning solid propellant are as follows: ṁ = A b rρ b (1) r = ap 1 n (2) where ṁ is the mass flow rate of gas, A b is the burning area of the propellant, r is the propellant burn rate, ρ b is the propellant density, r is the burn rate in units of length/time (typically inches/second), p 1 is the chamber pressure (typically psia), a is the pressure coefficient, and n is the burn rate exponent. 2,3 Propellant burn rate is affected by temperature, pressure, and the ratio of the burning area-toorifice area. This allows the system performance to be tailored to meet design factors. Namely, the affect of temperature variation can be minimized through the appropriate design of control orifice(s). This allows SPGGs to exhibit consistent performance over wide temperature ranges. In the case of an HFE, the propellant cartridge (or SPGG) is used to pressurize the tank that holds the fire suppression agent. This is in contrast to typical nitrogen pressurized systems where the tank is pre-pressurized with nitrogen gas. That being said, the pressurization profile within the tank of a HFE can be tailored by adjusting the SPGG performance parameters. The unique pressurization profile is not the only benefit from using an SPGG rather than nitrogen to pressurize the HFE tank. In a SPGG, the gas is discharged at an elevated temperature and it flows out of the control orifice(s); therefore it more effectively vaporizes the fire suppression fluid in the tank as it heats and mixes the agent. The ability to vaporize agents makes the use of an HFE especially advantageous in cold temperature situations and when the suppressant is a liquid at typical ambient conditions. The ability of propellant driven discharge devices to improve the effectiveness of fire suppression agents has been previously demonstrated. The FAA conducted a series of tests in the 1960s with several different Halon agents, such as CBrF 3 (Halon 1301) and CBrClF 2 (Halon 1211). Testing was conducted at ambient and simulated 50,000 foot altitude conditions. Side by side comparisons of agent effectiveness when dispensed from either nitrogen pressurized or propellant pressurized (hybrid) systems were conducted. The results showed that propellant pressurized systems were more effective for all of the agents, and the difference in performance was even more pronounced under the cold 50,000 foot altitude simulated conditions. In the latter environment, the effectiveness (on a weight basis) was increased by over 50 percent. Under ambient conditions, the amount of required weight was decreased by 29 to 37 percent depending upon the agent. 4,5 The use of propellant to pressurize and dispense fire suppression agents has been shown to offer many advantages. In addition to the advantages noted previously, the chemistry of propellant can be altered in order to change the make-up of the propellant exhaust. Chemical additives can be used to promote catalytic radical termination of the combustion process. Chemically active

propellants have been tested and shown to increase the effectiveness of fire suppression systems. 1,6,7 FK-5-1-12 Use in Hybrid Fire Extinguishers FK-5-1-12 s initial development centered on commercial fire suppression applications as a Halon replacement in streaming and total flooding. FK-5-1-12 has a boiling point of 49.2 C (120.6 F) and a freezing point of -108.0 C (-162.4 F); therefore, it is a liquid in storage at all anticipated temperatures in end use. The effective use concentration for most applications ranges from 4 6%v/v. Although the FK-5-1-12 s vapor pressure compared with Halon 1301 or other halocarbons is a relatively low 40.4 kpa @ 25 C (5.9 psig @ 77 F), its heat of vaporization is a low 88.0 kj/kg (37.9 BTU/lb) at its boiling point. So, it doesn t require much energy to convert the material to a gas. FK-5-1-12 effectively vaporizes over a wide temperature range, since its typical use concentration is well below its saturation point in air. 8 This ease of vaporization makes FK-5-1- 12 an efficient total flooding agent. The enhanced combination of FK-5-1-12 with the unique Hybrid Fire Extinguisher dispensing technology creates a system that vaporizes the agent more effectively than specialized nozzles alone and enhances the distribution of the agent throughout a protected volume. The HFE using FK-5-1-12 is not pressurized until system actuation. This is a distinct advantage over conventional super-pressurized systems, because the extinguisher tank can be almost completely filled safely with FK-5-1-12. No ullage space is required to expel FK-5-1-12 as in conventionally super-pressurized systems. This allows for potentially less cylinders required with added potential for weight and space savings. The temperature of FK-5-1-12 upon discharge from an HFE can be used as one measure for the efficiency of the vaporization from the unit. Static discharge tests were conducted to measure the temperature. A standard HFE was loaded with 2.5 liters (4 kg) of FK-5-1-12, and thermocouples were placed within the HFE discharge manifold, inside the nozzle, and just beyond the nozzle approximately 10 inches within the agent plume. The HFE was mounted to a wall in an open area and the unit was functioned. Figure 3 contains a diagram of the test setup.

HFE Mounted on Sidewall in Open Area 10 in T_manifold located just below the tank outlet inside the manifold 3 ft T_plume located 10 inches away from nozzle T_nozzle located at one of the nozzle holes Figure 3 Static Discharge Test Setup Static discharge tests were conducted at cold and ambient conditions. The ambient test units were assembled in the test lab under ambient room temperature conditions 21.1± 5.5 C (70± 10 F). Cold temperature test units were conditioned inside of a conditioning chamber that was set to -57.8 C (-72 F). The test chamber is not cold conditioned; therefore, the test unit was removed from the conditioning chamber and functioned within 10 minutes in order to minimize the increase in temperature of the FK-5-1-12 within the tank prior to testing. Figure 4 contains temperature plots from representative cold and ambient tests. Discharge Temperature Test Results of HFE using FK-5-1-12 Temperature (F) 400 350 300 250 200 150 100 T_manifold (Cold) T_nozzle (Cold) T_plume (Cold) T_manifold (Ambient) T_nozzle (Ambient) T_plume (Ambient) 50 0 0 100 200 300 400 500 600 700 800 900 1000-50 Time (msec) Figure 4 - Discharge Temperature Test Results of HFE using FK-5-1-12

The plots in Figure 4 show that the peak temperatures of the agent in the manifold (just after tank exit but before the nozzle) were 139 C (282 F) and 177 C (350 F) for the cold and ambient tests respectively. The temperature of the fluid at the exit of the nozzle were cooler at 88.3 C (191 F) and 150 C (302 F) respectively for the cold and ambient tests. The average plume temperatures over the first 400 milliseconds were 10.6 (51 F) and 15 C (59 F) for the cold and ambient tests respectively. The fluid temperature(s) in the nozzle and manifold are above the boiling point of FK-5-1-12 for both the ambient and cold test conditions. In addition to static discharge testing, live fire testing with HFEs using FK-5-1-12 has been conducted. Multiple demanding test scenarios representative of aircraft dry bays, engine nacelles and vehicle crew compartments have been demonstrating the extinguishing effectiveness of Hybrid Fire Extinguishers using FK-5-1-12. Examples follow of testing conducted in fixtures representative of aircraft dry bays and engine nacelles. In 2006 and 2007, approval and validation testing was conducted to qualify FK-5-1-12 for the protection of engine nacelles with hybrid systems using gas generators similar to that of the HFE. At the request of Airbus France, FAA conducted and completed FK-5-1-12 Halon equivalency testing in the minimum performance standard (MPS) full-scale engine nacelle fire simulator at the FAA Technical Center, Atlantic City, New Jersey, USA. FAA uses a FireEx, a specially arranged delivery system designed to accommodate varying volumes from which a candidate clean agent alternative super-pressurized with nitrogen in solution is discharged into the MPS test fixture. This was done to assure a specified fill density was achieved. For the non-super-pressurized FK-5-1-12, however, the fill procedure was modified in order that testing would more closely resemble the same manner in which a hybrid gas generator-driven system would deliver FK-5-1-12 into an engine. Using a piston flow arrangement, FAA pressurized the FireEx head space with nitrogen immediately prior to the test discharge. FK-5-1-12 was then expelled through nozzles completely volatizing within the MPS test fixture. An example of such a discharge is shown in Figure 5. 9 Figure 5 Typical FK-5-1-12 Nozzle Spray Pattern in the FAA Full-scale Engine Nacelle Fire Simulator

The result of the testing in accordance with the FAA protocol was an FK-5-1-12 Halon 1301 equivalency of 6.1%v/v. In application, this equivalency concentration is required to be held for a minimum of 0.5 seconds in full-scale engine tests. This success led to full testing in July, 2007 at the Airbus test facility in Toulouse France. The Toulouse testing included a gas generator/fk-5-1-12 ECOLOG hybrid system fixed to a fullscale engine assembly; in this case, a Rolls Royce Trent 500 jet engine typically used on the Airbus A340 aircraft. Concentrations in the engine upon system discharge were measured at 24 points, double the number required for Halon, using the Pacific Scientific Halonyzer while simulating in-flight conditions with a functioning engine. Cylinders were conditioned to the low temperature extreme (-55 C) as well as ambient conditions. A schematic of the system is shown in Figure 6. 10 Figure 6 ECOLOG Propellant Driven System using FK-5-1-12 in Airbus Testing The test results exceeded the minimum FAA MPS requirements for both the full engine as well as the APU compartment and indicates the robustness of the technology in demanding applications. System optimization is ongoing with deployment expected on Airbus s new A350. A series of tests were conducted in a Fire Test Fixture that has been developed to conduct comparison testing of a variety of different propellant and fire suppression agents. The Fire Test Fixture houses a baffled JP-8 fire and a blower is used to adjust the airflow. The fire is a spray fire and the fixture s main compartment is a rectangular structure that measures 2 feet wide by 2 feet tall with a length of 6 feet. For the FK-5-1-12 Hybrid Fire Extinguisher testing, the Fire Test Fixture was used to represent a generic aircraft dry bay fire. Figure 7 contains a diagram of the Fire Test Fixture, and Table 1 contains a summary of the Fire Test Fixture s main parameters. 1,6

Figure 7 Fire Test Fixture Table 1 Fire Test Fixture Parameters Airflow Mass flow rate 454 g/s 1.0 lb m /s Volumetric Flow Rate 385 L/s 13.6 ft 3 /s Linear Flow Rate (in pipe) 762 cm/s 25 ft/s Fuel Flow Fuel JP-8 Mass flow Rate 15 g/s 0.033 lb m /s Volumetric flow rate 19 ml/s 0.005 gal/s Stoichiometry Air-fuel ratio (m air /m fuel ) 31 Equivalence Ratio 0.50 Fire Zone Dimensions Flame Temperature 1000 K 1300 F Intensity 700 kw 700 kw Length 122 cm 4 ft Cross-Sectional Area 3700 cm 2 4 ft 2 Volume 450 L 16 ft 3 Residence Time 1.2 s 1.2 s Injection Interval ~100-200 ms ~100-200 ms

A number of standardized measures of agent effectiveness have been used throughout several reports with regards to Fire Test Fixture test results. These measures are as follows: Total Agent Mass o In the case of a Hybrid Fire Extinguisher, this is the total mass of the propellant contained in the SPGG plus the total amount of fire suppression agent contained in the tank Normalized Fire Suppression Number (FSN) o Value that is used to compare the performance of an agent to a baseline agent tested in the Fire Test Fixture. In the case of the Hybrid Fire Extinguisher, the baseline configuration is defined as FS01-40 propellant in the SPGG and HFC- 227ea fire suppression fluid. β or flowrate adjusted mass flow of agent 11 o β = ṁ agent /( ṁ agent + ṁ air ) (3) o where ṁ agent is the mass flow rate of the total agent and ṁ air is the mass flow rate of air Xc or critical mole fraction 11 o Xc = (β/mw agent )/[ (β/mw agent ) + ((1- β)/mw air )] (4) o where MW agent and MW air are the molecular weights of the agent and air respectively The threshold amount of agent is defined as the agent configuration that is able to extinguish the fire in the Fire Test Fixture two out of three times in repeated tests. Table 2 summarizes the threshold results for the Hybrid Fire Extinguisher. 1,6 Table 2 Hybrid Fire Extinguisher Fire Test Fixture Threshold Results Hybrid Fire Extinguisher FS01-40 Propellant in SPGG FK-5-1-12 Fire Suppression Fluid in Tank MW, g/mol 316 HFE Load (g) 358 Discharge mass, g 340 FSN (FS01-40/HFC-227) 1 β 0.789 Xc 0.255 The results indicate that the Hybrid Fire Extinguisher using FK-5-1-12 has equivalent performance to the baseline configuration. A recent test series of Hybrid Fire Extinguishers using FK-5-1-12 has been sponsored and completed at third party facilities against fire threats representative of military vehicle crew compartment fire threats. An independent report containing the results of the third party sponsored testing is expected to be released by the end of first quarter 2008.

Conclusions In testing against a variety of fire scenarios characteristic of threats encountered in military vehicle and aircraft applications, a system comprised of FK-5-1-12 in Hybrid Fire Extinguishers has been demonstrated to be at least as effective (on a total agent mass basis) as a comparable system with a more volatile agent such as HFC-227ea. FK-5-1-12 effectively negates end user risks associated with environmental regulatory activity restricting the use of ozone-depleting and global warming alternatives. The Hybrid Fire Extinguisher efficiently vaporizes the fluid, allowing it to more efficiently fill the open volume upon discharge. These Extinguishers are pressurized by Solid Propellant Gas Generators, whose working gases can be used to mix with and heat the FK-5-1-12 agent prior to discharge from the tank. This system results in a safer Fire Extinguisher that does not require high pressure storage, and also yields uniform discharge rates over a broad temperature range. Furthermore, unlike static-pressurized fire bottles, discharge times in this system can be tailored to meet longer or shorter fire protection requirements.

References 1 Fallis, S.; Reed, R.; McCormick, J.L.; Holland, G.F. Advanced Propellant/Additive Development For Fire Suppressing Gas Generators: Development + Test. Proceedings of the Halon Options Technical Working Conference, Albuquerque, New Mexico, pp. 45.1-45.15, 2002. 2 Society of Automotive Engineers (1968). Gas Generator Design Handbook Vol. 1. McGregor, Texas: Rocketdyne Solid Rocket Division. 3 Sutton, G. & Biblarz, O. (2001). Rocket Propulsion Elements 7 th Edition. New York: John Wiley & Sons Inc. 4 Klueg, E. P. and Demaree, J. E., An Investigation of In-Flight Fire Protection with a Turbofan Powerplant Installation, Final Report, Report No. NA-69-26, Federal Aviation Administration, April 1969. 5 Lu, Y.C., Wierenga, P., Further Advances in the Development of Hybrid Fire Extinguisher Technology. Proceedings of the Halon Options Technical Working Conference, Albuquerque, New Mexico, 2000. 6 Fallis, S.; Reed, R.; McCormick, J. L.; Wilson, K. A.; Holland, G. F. Advanced Propellant/Additive Development for Fire Suppressing Gas Generators. Proceedings of the Halon Options Technical Working Conference, Albuquerque, New Mexico, pp. 364-372, 2001. 7 Hamins, A.; Cleary, T.; and Yang, J. An Analysis of the Wright Paterson Full-Scale Engine Nacelle Fire Suppression Experiments. U.S. Dept. of Commerce, Technology Administration, National Institute of Standards and Technology, Gaithersburg, Maryland, NISTIR 6193, 1997. 8 Schmeer, J. et al. Consideration of Liquid to Gas Phenomena for a Sustainable, High-boiling, Tropodegradeable halocarbon, HOTWC, Albuquerque, May 2003. 9 Personal communication with Mr. Doug Ingerson, FAA Technical Center, Atlantic City NJ, 26 February, 2008. Photograph used with permission. 10 Deletain, R., Fabre, C., Airbus, An Airbus Project addressing the Halon Replacement concern for Engine/APU fire extinguishing application, FAATC 4th Triennial Fire & Cabin Safety Conference, Atlantic City NJ USA, November 1, 2007. 11 Linteris, G.T., Knyazev, V., and Babushok, V., Premixed Flame Inhibition by Manganese and Tin Compounds, Proceedings of the 2001 Halon Options Technical Working Conference, pp. 72-82, Albuquerque, NM, 2001.