AllStyle Coil Company, LP 7037 Brittmore Houston, TX Phone Fax

Similar documents
maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH

Your safety and the safety of others are very important.

INSTALLATION INSTRUCTION

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

AHG**-0B Series Hydronic Air Handling Units

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

CWA4 Chilled & Hot Water Fan Coil

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

INSTALLATION MANUAL WARNING WARNING MODULAR NON-VARIABLE SPEED AIR HANDLERS MODELS: MA LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES

Installer s Guide 4FWCA, 4FWCF 18-GF01D1-2. Air Handlers Upflow / Horizontal Left or Right 2 5 Ton

MODELS B1PA024, 030 AND 036

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

MERIT SERIES Up Flow / Horizontal

INSTALLATION INSTRUCTIONS

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

Installation Instructions

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2

MERIT Series R-410A - Upflow / Horizontal

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

F, P Series Multi-Position Air Handler Electric or No Heat, with available 5-Speed High Efficiency ECM Motor

INSTALLATION INSTRUCTIONS

MERIT Series R-410A - Upflow / Horizontal

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

BCE4 PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER WITH VARIABLE SPEED APPLICATION INSTALLATION CABINET COMPONENTS CONTROLS WARRANTY

Installation Instructions

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

Installation Instructions

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER

TECHNICAL SPECIFICATIONS

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

TECHNICAL SPECIFICATIONS

Installation Instructions

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHP SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

AUXILIARY ELECTRIC HEATER KITS FOR 7.5 AND 10 TON COMMERCIAL AIR HANDLERS

Product Data. FH4A Fan Unit. Sizes 001 thru 004

DEDICATED VERTICAL/WALL MOUNT

wiring diagrams AIR-COOLED CONDENSING UNITS SPLIT-SYTEM HEAT PUMP UNIT UNITS PRODUCED AFTER SEPTEMBER 1996 DIAGRAM INDEX

B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor

Installation Instructions

INSTALLATION AND OWNERS MANUAL

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

MX Series Indoor Modular Blowers Electric Heat, Hot Water Heat, or No Heat

VERTICAL MOUNT AIR HANDLERS

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.

HEATING & COOLING SPLIT SYSTEM HEAT PUMP & AIR CONDITIONER 14 SEER INTERTHERM SERIES

Product Data. Features/Benefits. 40QKB024,036 40QKE024,036,048 Cooling Only and Heat Pump In-Ceiling Cassettes. 2to4NominalTons

Wiring Diagrams. 38ARZ ARS ARD Air-Cooled Condensing Units 50/60 Hz

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

AIR HANDLERS RBHA- SERIES HEAT PUMP AIR HANDLERS AND FAN COIL UNIT

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

Installation Instructions

INSTALLATION INSTRUCTION

1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series

FF1DNA, FF1DNE FAN COIL UNITS. Sizes 018, 024, 030. Form No. PDS FF1D.18.3 FEATURES FF1D

DVPEC. Multi-Position, Variable-Speed air handler. Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

Product Data. FH4A Fan Unit. Sizes 001 thru 004

INSTALLATION GUIDE. AAN & AEN Series - Manufactured Housing Electric Furnace. 1. Safety Instruction. 2. Inspection ! CAUTION CAUTION `!

HIGH EFFICIENCY AIR HANDLER

MODELS K2EU060A, K4EU090A, & K3EU120A

INSTALLATION AND MAINTENANCE INSTRUCTIONS. MCE4 Series. Electric Cooling Package Unit. Save these instructions for future reference

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

ARPT Series. Multi-Position. 2 to 5 Tons. Internal TXV, Multi-Speed PSC Motor

Rheem Air Handler. RF1T- Series X-13 (ECM) Motor Efficiencies up to 16 SEER. RF1P- Series PSC Motor Efficiencies up to 14.5 SEER

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

INSTALLATION INSTRUCTIONS

Product Data. FF1DNA, FF1DNE Fan Coil Units. Sizes 018 thru 030 FEATURES/BENEFITS

INSTALLATION INSTRUCTIONS HIGH EFFICIENCY PACKAGED AIR CONDITIONER

COMFORT PACK INSTALLATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION AND MAINTENANCE INSTRUCTIONS EF Electric Furnace

MBR. Multi-Position, Multi-Speed Modular Blower With PSC Motor 1½ to 5 TONS. Contents. Product Features

Wiring Diagrams DIAGRAM INDEX

HIGH EFFICIENCY AIR HANDLER

SPLIT SYSTEM HEAT PUMP 1½ 5 TON HERITAGE 13 MODELS 2A6H A American Standard Heating & Air Conditioning

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

Ruud Standard Efficiency Air Handler

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Product Data. FH4C Base Series Fan Coil Sizes 001 thru 004 AIR HANDLER TECHNOLOGY AT ITS FINEST

The Premium Quality Fan Coil Units for Vertical, Horizontal (Left or Right) Application with Direct Expansion, Hydronic or Electric Heat

Heatrix Electric Duct Heater HXOB Installation Instructions

INSTALLATION INSTRUCTIONS

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

Ruud Standard Efficiency Air Handler

Rheem Air Handlers. RHML- Series X-13 (ECM) Motor

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

Concealed Ducted Split Series R-407C MBH

PAC SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (GEN 3, STYLE A)

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

Thru-The-Wall THDC Series R-410A Condensing Units Ton Series

Ruud Air Handler. RF1T- Series X-13 (ECM) Motor Efficiencies up to 16 SEER. RF1P- Series PSC Motor Efficiencies up to 14.5 SEER

AIR HANDLERS AIR HANDLERS

Transcription:

AllStyle Coil Company, LP 7037 Brittmore Houston, TX 77041 Phone 713-466-6333 Fax 713-466-6363 April 2005 VL / VLX Series Air Handler VL / VLX Series Air Handlers Installation Operation Maintenance The VL / VLX series is designed for permanent vertical installations in a closet or recessed mounted in a wall. Units of three tons and less can be installed with front return through the option return air filter grill. An optional wall hanging kit is available. Air conditioning and heat pump coils are available to match specific manufacturer s outdoor units. Various models are available for applications up to four tons of nominal cooling capacity. The VL model is 18 3/8 W x 18 ¼ D x 36 ¾ H with up to 2.5 tons nominal capacity, up to 10 KW electric resistance heat. The VLX model is 20 5/8 W x 22 D x 40 1/8 H inches, up to four tons of nominal capacity, up to 20 KW electric resistance heat. Cabinets are fully insulated, constructed from embossed galvanized steel. Front panels are painted for an attractive appearance. Time delay fan relays are standard on all models. All models are prewired for heat pump application. Flowrator refrigerant metering devices are standard. Thermal expansion valves or check and expansion valves are available factory or field installed. All models are 208/230 single phase 60 hertz and are provided with a 24 volt control transformer. Installation of this unit shall be made in accordance with the National Electric Code, NFPA No. 90A and 90B, and any other local codes or utilities requirements. WARNING: Due to possible damage to equipment or personal injury, installation, service and maintenance should be performed by a trained, qualified person. Consumer service is recommended only for filter replacement. WARNING: Insure all power is disconnected before installing or servicing this unit. More than one disconnect device may be required to de-energize the equipment. Hazardous voltage can cause sever personal injury. Make certain all panels are in place before operating the unit. Installation Operation Maintenance Page 1 of 4

VL / VLX Series Air Handler Carefully unpack the unit and inspect the contents for damage. If any damage is found at the time of delivery, proper notification and claims should be made with the carrier who delivered the unit. Check the rating plate to assure model number and voltage, plus any kits agree with what you ordered. The manufacturer should be notified within 5 days of any discrepancy or parts shortage. Location The blower coil unit should be centrally located and may be installed in a closet or recessed mounted in a wall with 0 clearance from any side, front, rear or duct work. The unit must be installed in a level position to ensure proper condensation drainage. Make sure the unit is level in both directions within 1/8 on either side. When the unit is installed in a closet or utility room, the room should be large enough, and have an opening to allow replacement of the unit. All servicing is done from the front and a clearance of 24 is needed for service unless the closet door aligns with the front of the furnace. The unit is designed to sit on a platform or hang on the wall with an optional wall hanging kit. If the unit is going to be installed with the return air through the base, remove the lower access door and remove the fiberboard insulation panel from the bottom channel. This channel may be used as a filter rack. A standard 18x18x1 in filter will fit the channel on the VL, a 20x20x1 inch filter is required on the VLX model. Be sure to replace the lower access door prior to operating the unit. If the unit is to hang on the wall, an optional wall mounting kit is required. Carefully follow the instructions in the kit. When the unit is mounted flush in the wall between studs, the optional return air filter grille panel is required. The unit should be position approximate 10 to 12 inches above the finished floor elevation between the studs of the wall. This will allow proper spacing to trap the primary auxiliary condensate drains. (see fig. A) Any modifications to existing framing should be accomplished by the general contractor to ensure structural strength is maintained in the structure. The structural opening in the framing should be 36 7/8 high and 18 ½ wide for the VL model. Rought opening for the VLX model should be 20 ¾ wide and 40 ½ high. The unit should be positioned where the front edge of the cabinet is flush with the finished face of the wall. All service connection openings are recessed away from the front to allow clearance for 3 ½ wall framing. Three installation tabs are provided on each side of the unit to facilitate mounting. Bend the tabs out 90 degrees and the tabs will position the unit to allow for ½ sheet rock finished walls. Duct Work The duct work should be installed in accordance with the NFPA No. 90A Installation of Air Conditioning and Ventilating systems and No. 90B Residential Type Warm Air Heating and Air Conditioning Installation. The duct work should be insulated in accordance with the applicable requirements for the particular type installation as required by HUD, FHA, VA the applicable building code, local utility or other governing body. Condensate Drain Figure A The unit is supplied with 3/4 inch primary and auxiliary condensate drains. Both drains must be Page 2 of 4

VL / VLX Series Air Handler trapped outside the unit and piped in accordance with applicable building codes. Do not reduce the drain line size less the connection size on the drain pan. Condensate should be piped to an open drain or to the outside. All drains must pitch downward away from the unit a minimum of 1/8 per foot of line to ensure proper drainage. Refrigerant Piping Refrigerant pipe connections are located on the top of the unit. Refrigerant piping external to the unit shall be sized in accordance with the instructions of the manufacturer of the outdoor equipment. When units are recessed mounted in the wall, make certain that piping connections are pressure tested prior to the wall being closed. Metering Device All units are shipped with a checkflow piston installed which is designed for air conditioning or heat pump operation. If your application requires a thermal expansion valve or check expansion valve then it is necessary to remove the piston from the distributor assembly and install the proper metering device. Be sure to follow the instruction in the kit to ensure proper installation. Blower This unit is supplied with a multi-speed motor with a direct drive blower wheel which can obtain various air flows. The unit is shipped with the blower connected for high speed. If a lower blower speed is required, disconnect all power to the unit, remove the black indoor fan motor lead from the fan relay, place an insulated cap on the black lead, remove the insulated cap from the red indoor fan motor lead, place a spade connector on the lead and connect it to the fan relay where the black lead was originally connected. Be sure to check the air flow and the temperature drop across the evaporator coil to ensure that you have sufficient air flow. Wiring Consult all schematic and pictorial wiring diagrams of this unit and the outdoor equipment to determine compatibility of the wiring connections and to determine specific requirements. All field wiring to the blower coil should be installed in accordance with the latest edition of the National Electric Code NFPA No. 70 and any local codes. Check rating plates on unit for rated volts, minimum circuit ampacity and maximum over current protection. Supply circuit power wiring must be 75 degree C. (167 degree F) minimum copper conductors only. Copper supply wires shall be sized to the National Electric Code or local code requirements, whichever is more stringent. The unit is shipped wired for 230/240 Volt AC 60 HZ 1 Phase Operation. If the unit is to operated at 208 VAC 60HZ, then follow the instruction on the indoor unit wiring diagram to change the low voltage transformer to 208 VAC operation. Be sure the unit is properly grounded. Class 2 low voltage control wiring should not be run in conduit with power wiring and must be separated from power wiring, unless class 1 wire of proper voltage rating is used. Low voltage control wiring should be 18 Awg, color coded (105 degree C minimum). For lengths longer than 100ft., 16 Awg wire should be used. Make certain that separation of control wiring and power wiring has been maintained. Air Filter An air filter must be installed prior to the air entering the evaporator coil to protect the coil, blower and other internal parts from excessive dirt and dust. If the unit is installed for the return air through the unit base, then the internal filter rack may be utilized. If you decide to use a remote filter, then it should be sized for a maximum of 300 feet/minute air velocity. If the unit is recess mounted in a wall utilizing the optional wall mount return filter grille, be sure to install a filter in the panel. The door must be fastened in place securely to ensure proper filtration of return air. Thermostat Select a thermostat that is commonly referred to as a single stage cooling with electric heat subbase. This stat will energize the fan on a demand for heat or cool. Install the thermostat on an inside wall, away from drafts, lights or other heat sources in a location that has good air circulation from the other rooms being controlled by the thermostat. The thermostat should be mounted 4 to 5 feet above the floor. Sequence of Operation Page 3 of 4

VL / VLX Series Air Handler Cooling (cooling only or heat pump with reversing valve energized in heat mode). When the thermostat calls for cooling, the blower relay is energized. The N.O. contacts will close, after a time delay, the indoor blower will operate. The circuit between R and Y is completed: causing the contactor on the outdoor equipment to close and start the compressor and the outdoor fan motor. Cooling (heat pump with reversing valve energized in cooling mode). When the thermostat calls for cooling, the circuit between R and G and R and O is completed. Circuit R and O energizes the reversing valve to the cooling position, Circuit R and G energizes blower relay. The N.O. contacts will close, after a time delay, the indoor blower will operate. The circuit between R and Y is completed: causing the contactor on the outdoor equipment to close and start the compressor and the outdoor fan motor. Heating (electric heat only). When the thermostat calls for heat, the circuit between R and W is completed, the heat sequencer is energized. A time delay will occur: Then the heating element(s) and the indoor blower motor will come on. Heating (heat pump reversing valve energized in heat mode). When the thermostat calls for heat, the circuits between R and B, R and Y and R and G are completed. Circuit R and B energize the reversing valve switching it to the heat position. Circuit R and Y energized the outdoor unit contactor starting the compressor and outdoor fan. Circuit R and G energizes the blower relay starting the blower motor. If the indoor room temperature should continue to fall, circuit R and W2 is by the second-stage heat bulb on the thermostat. Circuit R-W2 energizes the heat sequencer. The completed circuit will energize the supplemental electric heat. The system air filter(s) should be inspected, cleaned or replaced at least monthly. If the filter is mounted internal to unit, make sure that electrical power is disconnected before removing the access panels. Make certain that the access panels are replaced and secured properly before placing the unit back in operation. This product is designed for dependable service; however, periodic maintenance should be scheduled to be conducted by trained professional service personnel. This service should be conducted at least annually, and should include testing and inspection of electrical and refrigerant components. The heat transfer surface should be cleaned. The blower motor is permanently lubricated for normal operating conditions. Warnings Do not store or use any corrosives or combustibles in the vicinity of this unit. All panels must be in place and properly secured before operating this equipment. All electrical power servicing this unit must be disconnected prior to removal of any panels. Service of this unit must be accomplished by qualified trained professional personnel only Conforms to UL STD 1995 THIS UNIT IS MANUFACTURED IN THE USA BY: AllStyle Coil Co., LP 7037 Brittmore Houston, TX 77041 Blower Time Delay. This unit is equipped with timed on and a timed off relay. This relay delays the start and delays the stopping of the indoor fan motor to maximize the efficiency of the unit. Defrost. Supplemental heat during defrost can be provided by connecting B on the blower coil to the defrost relay on the oudoor heat pump. This will complete the circuit between R and B (in the blower coil) through a set of contacts in the defrost relay in the outdoor unit when the unit starts the defrost cycle. This circuit, when it is connected, will help prevent cold air from being discharged from the indoor unit during the defrost Maintenance Page 4 of 4

L2 G TB-1 USE COPPER CONNECTORS ONLY. Use Conductors Suitable for 167 Deg F. MAXIMUM CIRCUIT BREAKER 60 AMP 208/230 VOLTS 21.6/28.8 KW 104/120 TOTAL HEATER AMPS MINIMUM CIRCUIT AMPACITY 137/157 M3 M4 M1 M2 HEAT RELAY 2 CIRCUIT NO.2 CIRCUIT NO.1 L2 Field Wiring Factory Wiring GND ABBREVIATIONS Consult National Code for Wire Size DIAGRAM REPRESENTS THE MAXIMUM NUMBER OF CONTROLS, HEATERS/ CONTROLS WHICH MAY BE INSTALLED. FEWER COMBINATIONS WILL RESULT IN LESS WIRING THAN SHOWN. TRANSFORMER INDOOR FAN MOTOR BRN BRN CAPACITOR TIME DELAY RELAY AllStyle Air Handlers ALLSTYLE COIL COMPANY, L.P. 7037 BRITTMORE HOUSTON,TX 77041 (713) 466-6333 Wiring change required to convert transformer to 208 Volts. Disconnect power. Disconnect orange high voltage lead from transformer and cap with an insulated terminal. Connect yellow transformer lead where orange lead was originally connected. 230 VOLTS AC 60 HZ SINGLE PHASE FORM W01-10 Oct 01

L2 G TB-1 USE COPPER CONNECTORS ONLY. Use Conductors Suitable for 167 Deg F. MAXIMUM CIRCUIT BREAKER 60 AMP 208/230 VOLTS 21.6/28.8 KW 104/120 TOTAL HEATER AMPS MINIMUM CIRCUIT AMPACITY 137/157 M7 M8 HEAT RELAY 2 M5 M6 M3 M4 M1 M2 HEAT RELAY 2 CIRCUIT NO.2 L2 CIRCUIT NO.1 L2 Field Wiring Factory Wiring GND GND Consult National Code for Wire Size TRANSFORMER INDOOR FAN MOTOR DIAGRAM REPRESENTS THE MAXIMUM NUMBER OF CONTROLS, HEATERS/ CONTROLS WHICH MAY BE INSTALLED. FEWER COMBINATIONS WILL RESULT IN LESS WIRING THAN SHOWN. Wiring change required to convert transformer to 208 Volts. Disconnect power. Disconnect orange high voltage lead from transformer and cap with an insulated terminal. Connect yellow transformer lead where orange lead was originally connected. BRN BRN CAPACITOR 230 VOLTS AC 60 HZ SINGLE PHASE AllStyle Air Handlers ALLSTYLE COIL COMPANY, L.P. 7037 BRITTMORE HOUSTON,TX 77041 (713) 466-6333 FORM W02-10 SEP02