Container Refrigeration

Similar documents
Gas Cooler. Advanced Controller. Flash Tank. Variable Frequency Drive. Multi-stage Compressor

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Condensing Unit Installation and Operating Instructions

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Installation and Operation Manual

Model 76 Dehumidifier Control Installation Instructions

CAREL CONTROLLER. Programming Instructions HOW TO CHANGE LEVEL 1 CONTROL SETTINGS HOW TO CHANGE LEVEL 2 CONTROL SETTINGS

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Installation and Operation Manual

Galaxy Pulsar Plus Controller Family Troubleshooting Table with SMNP Traps

Hoshizaki America, Inc.

TWLC - Tempered Water Logic Controller. The Intelligent Control

CAREL IR33+ CONTROLLER

Installation and Operation Manual

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA

THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH.

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Heat Pump Water Heater (Generation 4) Troubleshooting (Effective 1 Nov 2016)

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12

KM-61BAH KM-101BAH KM-151BAH

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

Condensing Unit Installation and Operating Instructions

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

HP50HA ABG Heat Pump

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

UNIT CONTROLLER 8 (UC8) Troubleshooting guide

FOR SERVICE TECHNICIAN S USE ONLY

Bottom Mount Refrigerator Technical Information

INSTALLATION INSTRUCTIONS

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

Trouble Shooting Guide PWA, 3-phase (D10571)

Warm Case Troubleshooting Guide 9/18/2014

TROUBLESHOOTING GENERAL TROUBLESHOOTING PROBLEM PROBABLE CAUSE CORRECTIVE ACTION

Open Protocol Data Communications

Scotsman Technical Training. CU50 Cube Ice Machine

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

Hoshizaki America, Inc.

Model 1820 Dehumidifier

Operating Instructions XWA11V. XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

Installation and Operation Manual

XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

Operation & Maintenance

The breaker trips at once when it is set to ON. The breaker trips in few minutes when it is set to ON.

IMPORTANT. HOSHIZAKI provides this manual primarily to assist qualified service technicians in the service and maintenance of the icemaker.

Hoshizaki America, Inc.

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

Service Manual Moffat

Liebert Xtreme Density Chiller (XDC) Unit Warranty Inspection Check Sheet

INSTRUCTION MANUAL PORTABLE FRIDGE/FREEZER. Models: RVX-35 / RVX-45 / RVX-50 RVX-55 / RVX-65 / RVX-75

MR3CCUHV Temperature/Defrost Control

REF5-BB Undercounter Blood Bank Refrigerator

MICROPROCESSOR RAPPER CONTROL MODEL MRC-NT

Operating Functions Temperature Parameters

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

Q&A 2016 Practical Guide

OPERATING MANUAL Enertronic Control System 2

Beverage Air IMPORTANT

Dixell Installing and Operating Instructions release 7.0

Service Manual. Chiller unit MQH R 410A. Release Date Rev Review Date november

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408

INSTALLATION INSTRUCTIONS

FOR SERVICE TECHNICIAN S USE ONLY

Heat Pump Defrost Board Replacement Kit

3.2 E1 Outdoor Unit PCB Abnormality E4 Actuation of Low Pressure Sensor E5 Compressor Motor Lock 3 52

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to dryer before servicing, unless testing requires power.

WCAD-Series Vended Washers Troubleshooting And Fault Codes

NO. F ISSUED: JUN. 18, 2008 REVISED: JUN. 17, 2011 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER KM-100A KM-125A MODEL SERVICE MANUAL

TECHNICAL MANUAL CVM 3000 C 5030 CV/04-99 GB

Some alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible.

Installation Manual BCS 1000/1500

Rev B, 9/2/2009. Kodiak Chiller Overview

PARAGON Commercial Refrigeration Controls

Check that connection to main board is clean and sound at J8

Bulletin (Jan 2011) And User s Guide

TEMPERATURE & PRESSURE CONTROLS

HT-2 / 9600 Series Control Contents

Container Refrigeration

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort

WC Series Vended Washers Troubleshooting, and Fault Codes

347002K/177002K/34900

READ AND SAVE THESE INSTRUCTIONS

Hoshizaki America, Inc.

Wired controller KJR-08B/BE. Run. Fault. TB Tot. Out. Query. Heat. Net-On. Turn-On Mode

Hoshizaki America, Inc.

Model 1870F Dehumidifier Installation and Operating Manual

Unit Controller (UC8) Quick Reference Operation and Fault Diagnosis

Hoshizaki America, Inc.

SERVICE MANUAL FOR 6537 & 6538 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

XWA11V. Walk-In Temp / Door /Alarm / Light Module

Hoshizaki America, Inc.

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

NOTICE . SAFE SERVICING PRACTICES. Electric Wall Oven with Electronic Oven Control

Ductless Split Air Conditioner

KM-630MAH KM-630MWH KM-630MRH

NO. F ISSUED: JUN. 15, 2009 REVISED: HOSHIZAKI MODULAR CRESCENT CUBER KMD-201AA KMD-201AWA MODEL SERVICE MANUAL

AXIAL HEATER TROUBLE SHOOTING GUIDE. Models: AX24 N/PV, AX24 N/PV LT, AX24 LP AX26 N/PV, AX26 N/PV LT, AX26 LP AX28 N/PV, AX28 N/PV NT, AX28 LP

FOR SERVICE TECHNICIAN S USE ONLY

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

Transcription:

Container Refrigeration OPERATION AND SERVICE for 69NT40-561-019 Evergreen Container Refrigeration Units

Table 3 6 Controller Alarm Indications (Sheet 1 of 8) AL03 Loss of Superheat Control AL05 Manual Defrost Switch AL06 Keypad or Keypad Harness Fail AL07 Fresh Air Vent Open with Frozen Set Point AL08 High Ratio AL10 CO 2 Sensor AL14 Phase Sequence Detect Fault Superheat has remained below 1.66 C (3 F) degrees for five minutes continuously while compressor running. drawing more than 2.0 amps, compressor pressure ratio is greater than 1.8, and Electronic Expansion Valve (EEV) is at 0% open. Controller has detected continuous Manual Defrost Switch activity for five minutes or more. Controller has detected one of the keypad keys is continuously activity. The VPS is reading greater than 0 CMH while unit is in frozen mode. Controller detects discharge pressure to suction pressure ratio is too high. The controller will attempt to correct the situation by restarting the compressor. Alarm 10 is triggered when the CO 2 sensor voltage is operating outside of the 0.9 v to 4.7 v range, or if the sensor is out of range. Controller is unable to determine the correct phase relationship. Electronic Expansion Valve (EEV) Evaporator Sensor(s) ETS & ETS1. Evaporator Fans Check the operation of the EEV using Cd41. Verify accuracy of temperature sensors, refer to Sensor Checkout Procedure Confirm fans operating properly. Replace EEV if Replace ETS or ETS1 if Replace fan(s) if EVAPORATOR FAN MOTOR ASSEMBLY Section 6.10. Keypad Power cycle the unit. Resetting the unit may correct problem, monitor the unit. If the alarm reappears after 5 minutes replace the keypad. Keypad or Harness Vent Position Sensor (VPS) This is a display alarm and has no associated failure action. Power cycle the unit. Manually reposition vent and confirm using Cd45. Refer to VENT POSITION SENSOR SERVICE Section 6.18. Refer to eautofresh manual. Resetting the unit may correct problem, monitor the unit. If the alarm reappears replace the keypad and harness. If unable to obtain zero reading, replace defective VPS. The alarm is triggered off when voltage is within operating range. N/A Power cycle the unit. Resetting the unit may correct problem, monitor the unit. Wiring Check unit wiring. Confirm pressure readings during start up; suction pressure should decrease and discharge pressure should increase. Correct wiring. Current Sensor Check Cd41, right most digit: If display is 3 or 4 check compressor / sensor wiring. If display is 5 the current sensor is Replace current sensor if 3 24

Table 3 6 Controller Alarm Indications (Sheet 2 of 8) AL16 current Current Sensor Compare Cd3 to actual Replace current sensor draw is over the measured current at wire if Current High calculated maximum T1 T2 or T3 going to the for 10 minutes. compressor contactor. If there is a difference, determine whether this is caused by current sensor or amp clamp tool. Amperage is indeed too high. Confirm supply voltage/frequency is within specification and balanced according to Electrical Data Section 2.3. Correct power supply. AL17 Delta Fault has attempted to start in both directions and fails to generate sufficient pressure differential between SPT and DPT. Operating Conditions Monitor Unit Make sure system pressures are relevant to operating conditions. Alarm is display only the alarm may clear itself during operation N/A Controller will attempt restart every 20 minutes and deactivate the alarm if successful. Suction Transducer (SPT) Monitor unit Confirm accurate SPT Alarm is display only the alarm may clear itself during operation. Check air flow of condenser. Check Refrigerant charge, refer to REFRIGERATION SYSTEM SERVICE Section 6.3 If alarm remains active or is repetitive replace compressor at next available opportunity, refer to COMPRESSOR Service Section 6.4. Resume normal operation. Replace SPT if If alarm remains active or is repetitive replace compressor at next available opportunity. 3 25

Table 3 6 Controller Alarm Indications (Sheet 3 of 8) AL18 High AL19 High AL20 Control Contactor Fuse (F3) pressure is over the maximum for 10 minutes within the last hour. temperature exceeds 135 C (275 F) for 10 minutes within the last hour. Control power fuse (F3A or F3B) is open. Restrictions in the refrigeration system. Filter Drier Condenser Fan Non condensables in the refrigeration system. Ensure Liquid Line Service Valve is fully open. Check the filter drier, if it is iced up or very cold it indicates that the filter drier needs replacement. Check Condenser Fan for proper operation. With the unit off allow system to stabilize to ambient temperature. Check system pressure against PT Chart for 134a, refer to Table 6 6. Open Liquid Line Service Valve as needed. Replace the filter drier if needed, refer to FILTER DRIER Service Section 6.8. Correct as required. Correct as required, refer to Refrigerant Charge Section 6.3.5. Refrigerant Check refrigerant level. Correct as required, refer to Refrigerant Charge Section 6.3.5. Restrictions in the refrigeration system. Non condensables in the refrigeration system. Additional Alarms such as AL16, AL24. Check F3A, if the fuse is open: Check F3B, if the fuse is open: Check Voltage at QC1: Ensure the Service Valve is fully open. Check the unit for air flow restrictions. With the unit off allow system to stabilize to ambient temperature. Check system pressure against PT Chart for 134a, refer to Table 6 6. Check compressor operation. Check PA, PB, CH coils for short to ground, if short is found: Check ESV coil resistance at TP7 to TP9, if short to ground, or if resistance is less than 4 ohms, coil is Check CF, ES, EF, HR coils for short to ground, if short is found, coil is If voltage is present, it indicates a defective microprocessor. Open the Service Valve as needed. Clean or remove any debris from coils. Correct as required, refer to Refrigerant Charge Section 6.3.5. If the alarm persists, it may indicate a failing compressor, replace the compressor, refer to Ser- COMPRESSOR vice Section 6.4. Replace the defective coil. Replace the fuse. Replace the defective coil. Replace the fuse. Refer to Controller Service Section 6.17. 3 26

Table 3 6 Controller Alarm Indications (Sheet 4 of 8) AL21 One of the 18 VAC System Sensors Check system sensors for Replace defective Control Circuit controller fuses short to ground. sensor(s) Fuse (F1/F2) (F1/F2) is open. Refer Wiring Check wiring for short to Repair as needed. to Cd08. ground. AL22 Evaporator IP AL23 Loss of Phase B AL24 IP AL25 Condenser IP AL26 All Sensors : Supply/Return Probes AL27 Analog to Digital Accuracy AL28 Low Suction Evaporator motor internal protector (IP) is open. Controller fails to detect current draw. internal protector (IP) is open. Condenser fan motor internal protector (IP) is open. Sensors out of range. Controller AD converter faulty. Suction pressure too low for normal operation. Controller Evaporator Motor Controller may have an internal short. Shut down unit, disconnect power, & check Evaporator Motor IP at plug connection pins 4 & 6. Incoming Power Check incoming power source. Insufficient Air Flow Condenser Fan Motor All sensors. detected as out of range Controller Shut down unit disconnect power, & check resistance of compressor windings at contactor T1 T2, T2 T3. Shut down unit and check condenser fan for obstructions. Shut down unit, disconnect power, & check Condenser Fan Motor IP at plug connection pins 1 & 2. Power cycle the unit. If the alarm persists, it indicates a defective microprocessor. Replace controller, refer to Controller Service Section 6.17. Replace defective evaporator fan motor, refer to EVAPORATOR FAN MOTOR Service Section 6.10. Correct power source as required. Monitor unit, if alarm remains active or is repetitive replace the compressor at the next available opportunity, refer to COMPRESSOR Service Section 6.4. Remove obstructions. Replace defective condenser fan motor, refer to Condenser Fan Motor Assembly Service Section 6.7. Replace defective microprocessor, refer to Controller Service Section 6.17. N/A Power cycle the unit. Resetting the unit may correct problem, monitor the unit. Suction Transducer (SPT) Confirm accurate SPT Replace SPT if 3 27

Table 3 6 Controller Alarm Indications (Sheet 5 of 8) AL50 VPS Sensor out of Vent Position Make sure VPS is secure. Manually tighten panel. Air Vent range. Sensor (VPS) If the alarm persists, Replace VPS. Position Sensor (VPS) replace the sensor or the assembly. AL51 EEPROM AL52 EEPROM Alarm List Full AL53 Battery Pack AL54 Primary Supply Sensor (STS) AL56 Primary Return Sensor (RTS) AL57 Ambient Sensor (AMBS) AL58 High Safety (HPS) Controller Memory Controller Pressing the ENTER key when CLEAr is displayed will result in an attempt to clear the alarm. Power cycle the unit. If the alarm persists, it indicates defective controller memory. Alarm list queue is full. Active Alarms Repair any alarms in the queue that are active. Indicated by AA. Battery voltage low Battery If this alarm occurs on start up, allow a unit fitted with rechargeable batteries to operate for up to 24 hours to charge rechargeable batteries sufficiently. Once fully charged, the alarm will deactivate. Invalid Supply Sensor (STS) reading. Invalid Return Sensor (RTS) reading. Invalid Ambient Sensor (AMBS) reading. High pressure safety switch remains open for at least one minute. Supply Sensor (STS) Return Sensor (RTS) Ambient Sensor (AMBS) High Switch (HPS) Refrigeration System Test the AMBS, refer to Sensor Checkout Procedure Test the HPS; refer to Checking High Switch, Section 6.5.1. Check unit for air flow restrictions. If action is successful (all alarms are inactive), alarm 51 will be reset. Replace defective controller, refer to Controller Service Section 6.17 Clear alarms, refer to CONTROLLER ALARMS Section 3.5. To clear the alarm press ENTER and ALT simultaneously at the startup of Cd19 (Battery Check). If alarm persists, replace the battery pack, refer to Section 6.17.5 Battery Replacement. Replace AMBS if TEMPERATURE Replace HPS if Sensor Replacement, Section 6.5.2. Clean or remove any debris from coils. 3 28

Table 3 6 Controller Alarm Indications (Sheet 6 of 8) AL59 Heat Termination Heat Termination Thermostat (HTT) is Thermostat (HTT) open. Heater Termination Thermostat (HTT) AL60 Defrost Sensor (DTS) AL61 Heater Current Draw Fault AL63 Current Limit AL64 Sensor (CPDS) AL65 Transducer (DPT) AL66 (SPT) Suction Transducer, (EPT) Evaporator Transducer of the Defrost Sensor (DTS) to open. Improper current draw during heat or defrost mode. Unit operating above current limit. sensor out of range. Transducer is out of range. Suction Transducer (SPT) out of range. Defrost Sensor (DTS) Heater(s) Contactor Refrigeration System Power supply Current limit set too low. temperature sensor (CPDS). Suction Transducer (SPT) Check for 24 volts at test point TP10, if no voltage at TP10 after unit has reached set point HTT is open. Test the DTS; refer to Sensor Checkout Procedure While in heat or defrost mode, check for proper current draw at heater contactors, refer to ELECTRICAL DATA Section 2.3. Check voltage at heater contactor on the heater side. If no voltage present: Check unit for air flow restrictions. Check unit for proper operation. Confirm supply voltage/frequency is within specification and balanced according to ELECTRICAL DATA Section 2.3. Check current limit setting Code Cd32. Test the CPDS; refer to Sensor Checkout Procedure, Section 6.19.1. Confirm accurate EPT and SPT pressure readings, refer to MANIFOLD GAUGE SET Performing a Pre trip 5 9 test will also check the transducers. Monitor Replace HTT if Sensor Replacement 2. Replace the DTS if Sensor Replacement 2. Replace heater(s) if section 6.9.2 Evaporator Heater Removal and Replacement. Replace heater contactor if Clean or remove any debris from coils. Repair as needed. Correct power supply. The current limit can be raised (maximum of 23 amps) using Cd32. Replace the CPDS if Sensor Replacement 2. Replace EPT/SPT if If the alarm persists, it may indicate a failing compressor, refer to COMPRESSOR Service Section 6.4. 3 29

Table 3 6 Controller Alarm Indications (Sheet 7 of 8) AL67 Humidity Sensor (HS) Humidity Sensor Make sure the humidity Monitor, replace HS if Humidity reading out of range. (HS) sensor is properly connected in the socket. alarm persists. Sensor Make sure the humidity sensor wires have not been damaged. AL69 Evaporator Temp Sensor (ETS1) AL70 Secondary Secondary Supply Sensor (SRS) AL71 Secondary Return Sensor (RRS) AL72 Control Temp Out of Range Evaporator Sensor (ETS1) out of range. Supply Sensor (SRS) is out of range. Secondary Return Sensor (RRS) is out of range. After the unit goes in range for 30 minutes then out of range for a continuous 120 minutes. Evaporator Sensor (ETS1) Secondary Supply Sensor (SRS) Secondary Return Sensor (RRS) Refrigeration System Test the ETS1, refer to Sensor Checkout Procedure 1. Ensure unit is operating correctly. Replace Evaporator Sensor (ETS1) if Power cycle unit. Control is in In range. Any Pre Trip mode, resets the timers. 3 30

Table 3 6 Controller Alarm Indications (Sheet 8 of 8) NOTE If the controller is configured for four probes without a DataCORDER, the DataCORDER alarms AL70 and AL71 will be processed as Controller alarms AL70 and AL71. Refer to Table 3 10, page 3 38. The controller performs self check routines. If an internal failure occurs, an ERR alarm will appear on the display. This is an indication the controller needs to be replaced. ERROR DESCRIPTION ERR 0 RAM failure Indicates that the controller working memory has failed. ERR 1 Program Memory failure Indicates a problem with the controller program. ERR Internal # Microprocessor Entr StPt LO Enter Set point (Press Arrow & Enter) Low Main Voltage (Function Codes Cd27 38 disabled and NO alarm stored.) ERR 2 Watchdog time out ERR 3 N/A ERR 4 N/A ERR 5 A D failure The controller program has entered a mode whereby the controller program has stopped executing. N/A N/A The controller s Analog to Digital (A D) converter has failed. Internal program/update failure. Internal version/firmware incompatible. ERR 6 IO Board failure ERR 7 Controller failure ERR 8 DataCORDER failure Internal DataCORDER memory failure. ERR 9 Controller failure Internal controller memory failure. In the event that a failure occurs and the display cannot be updated, the status LED will indicate the appropriate ERR code using Morse code as shown below. E R R 0 to 9 ERR0 =..... ERR1 =..... ERR2 =........ ERR3 =..... ERR4 =............ ERR5 =..... ERR6 =.............. ERR7 =..... ERR8 =.......... ERR9 =...... The controller is prompting the operator to enter a set point. This message will be alternately displayed with the set point whenever the supply voltage is less than 75% of its proper value. 3 31