Installation and operation instructions Solar stations SolarBloC midi Premium DN 20 SolarBloC maxi Premium DN 25

Similar documents
Installation and Operation Instructions Domestic hot water module FriwaMini with circulation - DN 15

Installation and Operation Instructions K36E Modular Heating Circuit - DN 25 Boiler charging set

CIRCO 6 Solar Circulation Unit

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses.

8008 CIRCULATION UNIT FOR SOLAR THERMAL SYSTEMS, FLOW AND RETURN.

HERZ Differential Pressure Control Valve 4002

AGS 2 SOLAR PUMP STATION FOR SOLAR DOMESTIC HOT WATER SYSTEMS UK/IE

Solar station DKP 6-8 / DKP Installation and Service Manual C

HKF 8180 Operating instructions

Dynalux. Floor Heating Manifolds Underfl oor heating circuit manifold

Installation and instruction manual SOLAR STATION

Commissioning a Solar Thermal Installation

HERZ Regulating valve 4002

USER S MANUAL ATH WH220

Thermostatic valves with radiator connection systems

CONNECT SOLAR MR - 7,5m

Technical Product Guide

INSTALLATION INSTRUCTIONS GEO PRIME TANK. (Patent Pending) GPC

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and

Oxiperm C 164 Fully automatic chlorine dioxide processing plant C, -6000C, -7500C, C. Service manual. Oxiperm 164C 4-10 kg Service en

Components for solar heating systems

Solar heating systems

Installation and Maintenance Manual Forbes Marshall Tracer Line Trap FMMST63

CALEFFI. Anti-condensation recirculation and distribution unit. 281 series 01224/14 GB. Replaces dp 01224/12 GB. Function

Installation instructions. Pump Group. For wall hung gas-fired condensing boiler GB162-50/65/80/ TD UK/IE (2014/09)

Instruction Manual. Automatic fuel oil de-aerator SMART-FLO 3/K B100 COMPATIBLE

E-Z Valve. Thermostatic valves with radiator connection systems For single and two-pipe heating systems

For reversed flow direction. Thermostatic Radiator Valves Thermostatic valve body with and without presetting

Flush individual room control for floor heating systems

Operating instructions

Installation and operating instructions. DK energy storage and DK energy buffer

General System Layout Sketch

Operating Manual. Model: Float-Controlled Condensate Trap, PN Safety instructions. 2 General description and usage

Installation, Operation and Maintenance Manual. 3AV 1 to 3AV 430

CONNECTION OPTIONS FOR MANIFOLDS & CONTROL UNITS

Thermostatic valve bodies

TECHNICAL NOTICE GH/GHO/GAE V

DOUBLE O-RING GEO-PRIME TANK Non-Pressurized Flow Center System INSTALLATION INSTRUCTIONS. Model: DORGPT-1 NOTE:

AGS 5/5E, AGS 10/10E INSTALLATION AND SERVICING INSTRUCTIONS SOLAR PUMP STATIONS FOR SEALED SOLAR HEATING SYSTEMS AND INDIRECT FED DOMESTIC HOT WATER

MINIATURE THERMOSTATIC VALVE

ASSEMBLY INSTRUCTIONS FOR THE PUMP AND CONTROL UNIT ZPS 18a-01

Multibox. Flush Individual Room Control for Floor Heating Systems. To be precise.

Crown Boiler Company

LYRA 1000 VVS Installation and Operation Manual LYRA 1000 VVS THERMAL STORE LYRA 1000 VVS

Installation Instructions Solar Controller Kit (Part Number AQ )

Model: 1100 Float-Controlled Condensate Trap, PN 25

General System Layout Sketch

Multilux 4-Eclipse-Set

Zeparo Cyclone. Automatic air vents and separators Dirt and magnetite separator with Cyclonic technology

Valves, controls + systems. Innovation + Quality. Stations for solar energy and solid fuel boilers Product range

DISCALDIRT deaerator-dirt separator

Design-Edition. Design-Edition Thermostatic valves and lockshields, sets

RADIANT PANEL SYSTEM CONTROL QUICK GUIDE

The Meibes concept for the specialist: Easier. Quicker. More successful.

SRCC OG-300 Certified Solar Water Heating System

Installation, Operating and Servicing Instructions

Installation & Operation Manual Models: TSU

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

regulux Radiator lockshield with drain-off facility Pressurisation & Water Quality Balancing & control thermostatic control engineering ADVANTAge

AIRTERM DIRT AND AIRTERM MAG COMBINED SELF-CLEANING DIRT SEPARATORS / DEAERATORS

Danfoss Air Heating Surfaces

Mikrotherm. Manual Radiator Valves With presetting

INSTALLATION AND SERVICING

INSTALLATION ADJUSTMENT SERVICE

Product range Code HE1 Connection and energy management compact unit without anti-condensation valve

INSTALLATION & TESTING MANUAL

Model: 1200 Model: 1200-G Model: 1200-N Float-Controlled Condensate Trap, PN 40

Regulux. Radiator lockshield with drain-off facility. To be precise.

Manual of Solar Pump Station SR882 for Split Pressurized Solar Hot water System

INSTRUCTIONS REHAU PRO-BALANCE MIXING MODULE

INSTALLATION & TESTING MANUAL

Standard. thermostatic valve body without presetting

COMPRESSED AIR DRYER. SAFETY... Page 2 MAINTENANCE... Page 5. INSTALLATION... Page 3 PARTS AND KITS... Page 6

6. Cooling System XCITING 400i. This chapter covers the location and servicing of the cooling system components for the KYMCO XCITING 400i.

Installation and maintenance instructions

Multibox. Floor Heating Controller Flush individual room control for floor heating systems

Technical information for installation and operation

Installation, Operating and Servicing Instructions

Enzo Concealed Shower Mixing Valve

INSTALLTION FOR THERMOSTATIC VALVES

DIRTMAG dirt separator with magnet, adjustable for vertical or horizontal pipe

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

Friwa Compact. Operating instructions EN

Waste water ejection unit

VC-1, VC-1-SL, VC-2-L, VC-2-SL

Calypso exact. Thermostatic Radiator Valves With stepless precision presetting

Regulux. Return Lockshield Radiator lockshield with consistent presetting and drain-off facility

Multibox 4. Floor Heating Controller Flush individual room control for floor heating systems with supply shut-off

ASSEMBLY & OPERATING INSTRUCTIONS

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

TECHNICAL DATA. Wet 26a. February 22, 2009

Roth fixed-value control set with high-efficiency pump

Electronically controlled instantaneous water heater. CEX 9-U: C models. Installation instructions

Installation & Service Guide

CONTENT. Ⅰ General information 1. Ⅱ Product description 2. System description 3. Installation 3

GRUNDFOS DATA BOOKLET. Grundfos COMFORT. Circulator pumps. 50/60 Hz

Installation, commissioning and servicing instructions

Operating instructions

SOLAR TECHNIQUE ATTACK SOLARTHERM, VAKUUMTHERM

CALEFFI. Thermostatic regulating unit for heating systems. 166 series 01238/17 GB. replaces dp 01238/15 GB. Function

Transcription:

PAW GmbH & Co. KG Böcklerstr. 11, D-31789 Hameln, Germany Phone: +49-5151-9856-0, Fax: +49-5151-9856-98 E-mail: info@paw.eu, Web: www.paw.eu Installation and operation instructions Solar stations SolarBloC midi Premium DN 20 SolarBloC maxi Premium DN 25 SolarBloC midi DN 20 SolarBloC maxi DN 25 2014/04 99768xx-mub-en V04

1 General information Item no. 99768xx-mub-en Version V04 Issued 2014/04 Translation of the original instructions We reserve the right to make technical changes without notice! Printed in Germany Copyright by PAW GmbH & Co. KG PAW GmbH & Co. KG Böcklerstraße 11 D-31789 Hameln, Germany 2 99768xx-mub-en V04 2014/04

1 General information Contents 1 General information... 4 1.1 About these instructions... 4 1.2 About this product... 4 1.3 Designated use... 5 2 Safety instructions... 6 3 Assembly and installation [specialist]... 8 4 Commissioning [specialist]... 11 4.1 Flushing and filling the solar circuit... 12 4.2 Preparations before flushing... 14 4.3 Flushing and filling... 15 4.4 Parameters: SolarBloC midi Premium / SolarBloC maxi Premium with controller SC3.6... 17 5 Maintenance [specialist]... 18 5.1 Replacing the temperature sensor in the Airstop... 18 5.2 Draining the solar installation... 19 5.3 Deinstallation... 19 6 Spare parts [specialist]... 20 6.1 SolarBloC midi Premium DN 20... 20 6.2 SolarBloC maxi Premium DN 25... 21 6.3 Connection of PWM pumps... 22 7 Assembly of the insulation... 22 8 Technical data... 23 9 Function of the check valves [specialist]... 25 10 Commissioning report... 27 2014/04 99768xx-mub-en V04 3

1 General information 1 General information Carefully read these instructions before installation and commissioning. Save these instructions in the vicinity of the installation for future reference. 1.1 About these instructions These instructions describe the installation, commissioning, function and operation of the SolarBloC midi (DN 20) and SolarBloC maxi (DN 25) solar stations with Premium equipment. The chapters called [specialist] are intended for specialists only. For other components of the solar thermal system such as pumps, collectors, storage tanks, expansion tanks and controllers, please observe the instructions of the corresponding manufacturer. 1.2 About this product The station is a premounted fitting group checked for leakage used to circulate the solar fluid in the solar circuit. It contains a preset controller as well as important fittings and safety devices for the operation of the solar thermal system: Ball valves in the flow and return line with exchangeable spindle Check valves in the flow and return ball valves Thermometers in the flow and return FlowRotor (measuring device with Hall sensor) Temperature sensors in the flow and return Pressure gauge to display the system pressure in the solar circuit Airstop to easily vent the solar circuit Flush and fill valves with caps Solar pressure relief valve High-efficiency pump 4 99768xx-mub-en V04 2014/04

1 General information 1.3 Designated use The solar station may only be used as a pump station in the solar circuit of solar thermal systems taking into consideration the technical limit values indicated in these instructions. Due to its design the station must be mounted and operated in a vertical position with upward conveying direction of the pump. Only use PAW accessories with the solar station. Improper usage excludes any liability claims. When the sun shines, the collectors can become very hot. The solar fluid in the circuit can heat up to more than 100 C. Only flush and fill the solar circuit when the collector temperatures are below 70 C. 2014/04 99768xx-mub-en V04 5

2 Safety instructions 2 Safety instructions The installation and commissioning as well as the connection of electrical components require technical knowledge commensurate with a recognised vocational qualification as a fitter for plumbing, heating and air conditioning technology, or a profession requiring a comparable level of knowledge [specialist]. The following must be observed during installation and commissioning: relevant local and national regulations accident prevention regulations of the professional association instructions and safety instructions mentioned in this manual WARNING Danger of scalding due to vapour escape! With pressure relief valves there is risk of scalding due to vapour escape. During installation, check the local conditions and if a discharge line must be connected to the safety group. Observe the instructions regarding the pressure relief valve. The pressures calculated by the installation planner for the expansion tank and the operating pressure of the installation must be set. CAUTION Risk of burns! The valves, fittings and the pump may heat up to more than 100 C during operation. The shell must remain closed during operation. 6 99768xx-mub-en V04 2014/04

2 Safety instructions CAUTION Personal injury and damage to property due to overpressure! By closing the two ball valves in the primary circuit you isolate the pressure relief valve from the heat exchanger. A rise in temperature in the storage tank will cause high pressures and could result in personal injury or damage to property! Only close the ball valves for service and maintenance. NOTICE Material damage due to mineral oils! Mineral oil products cause lasting damage to seals made of EPDM, whereby the sealant properties are lost. We do not assume liability nor provide warranty for damage to property resulting from sealants damaged in this way. It is imperative to avoid that EPDM gets in contact with substances containing mineral oils. Use a lubricant based on silicone or polyalkylene and free of mineral oils such as Unisilikon L250L and Syntheso Glep 1 of the Klüber company or a silicone spray. 2014/04 99768xx-mub-en V04 7

3 Assembly and installation [specialist] 3 Assembly and installation [specialist] NOTICE Material damage due to high temperatures! Install the fitting group at a sufficient distance from the collector field, since the solar fluid may be very hot near the collector. It may be necessary to install an intermediate tank in order to protect the expansion tank. Accessories: compression fitting 1. Push the union nut 2 and the cutting ring 3 onto the copper pipe 1. The pipe must protrude at least 3 mm from the cutting ring in order to ensure the force transmission and the sealing. 2. Insert the support sleeve 4 into the copper pipe. 3. Insert the copper pipe with the plugged-on individual parts (2, 3 and 4) all the way into the housing of the compression fitting 5. 4. First screw the union nut 2 manually. Not included in the scope of delivery! 5. Tighten the union nut 2 by rotating one full turn. Secure the housing of the compression fitting 5 against distort in order to avoid damaging the sealing ring. 1. Remove the station from the packaging. 2. Remove the insulating front shell. 8 99768xx-mub-en V04 2014/04

3 Assembly and installation [specialist] 3. Copy the mounting holes besides the thermometers to the mounting surface. 4. Drill the holes and mount the solar station to the wall with appropriate wall plugs and screws. 5. Connect the solar station to the installation: 1 return to the collector field 3 return from the storage tank 4 flow to the storage tank 5 flow from the collector field 6. Connect the pipe for the expansion tank below the pressure relief valve [1.5] and fix the bracket for the expansion tank. Pressurise the expansion tank as specified by the manufacturer and connect the expansion tank. Observe the separate instructions regarding the expansion tank! 7. Check all screw connections and tighten them if necessary. Not included in the scope of delivery! 2014/04 99768xx-mub-en V04 9

3 Assembly and installation [specialist] WARNING Risk to life and limb due to electric shock! Prior to commencing electrical work on the controller, pull the mains plug! Only after completing all installation work, flushing and filling, plug the mains plug of the controller into a socket! This avoids an unintentional start of the motors. 8. Slide the controller extension with the preassembled controller onto the solar station. 9. Connect the supply cable to the pump. Supply cable - 230 V L N PE brown blue yellow green Connect the control cable of the pump to the controller. brown Signal brown GND blue blue Connection of the control cable for the PWM pump 15 V 10. Connect the pump and the sensors to the controller. The assembly of the solar station is completed and you can put the station into operation. 10 99768xx-mub-en V04 2014/04

4 Commissioning [specialist] 4 Commissioning [specialist] Observe the following safety instructions regarding the commissioning of the station: WARNING Risk of burning and scalding! The fittings can heat up to more than 100 C. Therefore, do not clean or fill the system with the collectors heated (intense sunshine). Please note that hot solar fluid can leak from the pressure relief valve when the system pressure is too high! During venting the solar fluid may escape as vapour and cause scalding! Only flush and fill the installation when the collector temperatures are below 70 C. NOTICE Risk of frost! It often happens that the solar thermal system cannot be completely drained after flushing. Thus, there is risk of frost damage when flushing with water. Therefore, do only use the solar fluid used later to flush and fill the solar installation. Use a water and propylene glycol mixture with max. 50% of propylene glycol as a solar fluid. NOTICE Note regarding the commissioning sequence When putting the system into operation, first fill the heating circuit and then the solar circuit. This guarantees that heat that may possibly be absorbed by the collectors during commissioning can be dissipated. NOTICE Note regarding the expansion tank To prevent that the dirt particles in the solar thermal system are flushed into the expansion tank, some manufacturers recommend to disconnect the expansion tank from the solar circuit before flushing and filling. Please observe the instructions of the manufacturer. 2014/04 99768xx-mub-en V04 11

4 Commissioning [specialist] 4.1 Flushing and filling the solar circuit The fill and drain valves required to flush and fill are integrated in the solar station. Make sure not to wash dirt particles that may be present in the solar installation into the expansion tank. Disconnect the expansion tank from the solar circuit during flushing and filling, if necessary, and only use flush and fill stations with fine filters. Ball valve with integrated flow check valve (normal flow direction in the figure below: downwards) 0 45 90 Check valve is operating, flow only in flow direction. Check valve is not operating, flow in both directions. Ball valve closed, no flow. 12 99768xx-mub-en V04 2014/04

4 Commissioning [specialist] Airstop The Airstop (bleeder with plug for manual venting) serves to bleed the solar installation. To ensure perfect deaeration of the solar circuit, the flow velocity must be at least 0.3 m/s in the flow line. 4.2 Pipe diameter [mm] Flow rate at 0.3 m/s outside inside l/h l/min 15 13 ~ 143 ~ 2.4 18 16 ~ 217 ~ 3.6 22 20 ~ 339 ~ 5.7 28 25 ~ 530 ~ 8.8 The air separated from the solar fluid is collected in the upper part of the Airstop and can be released at the vent plug [4.2]. WARNING Danger of scalding due to vapour escape! The escaping fluid can have a temperature of more than 100 C and cause scalding. Carefully open the vent plug and close it again, as soon as medium escapes. Venting the solar installation after commissioning At the beginning, vent the solar installation daily and then weekly or monthly, depending on the vented air quantity. Thus, an optimum operation of the solar installation is ensured. Check the system pressure after venting and increase it to the specified operating pressure, if necessary. 2014/04 99768xx-mub-en V04 13

4 Commissioning [specialist] 4.2 Preparations before flushing The solar circuit is flushed in the direction of flow. 1. Disconnect the expansion tank from the solar installation. Observe the separate instructions regarding the expansion tank! 2. Turn the check valve in the flow ball valve [5.2] to operating position (0, see page 12). 3. Close the return ball valve [1.2] (90, see page 12). 4. The ball valve [3] in the FlowRotor must be open. 5. The drain valve [3.2] must be closed. 6. Connect the fill station to the solar station: - Pressure hose to the fill valve [1.4] - Flush hose to the drain valve [3.2] 7. Open the fill valve [1.4] and the drain valve [3.2]. 14 99768xx-mub-en V04 2014/04

4 Commissioning [specialist] 4.3 Flushing and filling 1. Put the flush and fill station into operation and flush the solar installation for at least 15 minutes. 2. Vent the solar installation several times at the vent plug of the Airstop [4.2] until the solar fluid exits without bubbles (see page 13). 3. To flush and to vent the pump line, slowly open the check valve in the return ball valve [1.2] (45, see page 12) and then close the flow ball valve [5.2] (90, see page 12). 4. Close the drain valve [3.2] with the filling pump running and increase the system pressure to about 5 bars. The system pressure can be read on the pressure gauge. 5. Check the pressure gauge to see whether the system pressure reduces and eliminate leaks where necessary. Consider the pressure relief valve (6 bars)! 6. Connect the expansion tank to the solar circuit and set the operating pressure of the solar thermal system by means of the flush and fill station (for the required operating pressure, see instructions of the expansion tank). 7. Reduce the pressure at the drain valve [3.2] to the operating pressure, if necessary. 8. Close the fill and drain valves [1.4 3.2]. 9. Turn the check valve in the return ball valve [1.2] to operating position (0, see page 12). 2014/04 99768xx-mub-en V04 15

4 Commissioning [specialist] WARNING Risk to life and limb due to electric shock! Check if the sensors and the pumps are properly connected to the controller and if the controller housing is closed. Only then should the mains plug of the controller be plugged into a socket. 10. Connect the controller to the mains and set the solar circuit pump in the manual mode to Max. according to the controller instructions. Let the solar circuit pump run at maximum rotation speed for at least 15 minutes. Meanwhile vent the solar installation several times at the vent plug of the Airstop until the solar fluid exits without bubbles (see page 13). If necessary, increase the system pressure to the operating pressure. 11. Remove the hoses of the flush and fill station and screw the sealing caps onto the fill and drain valves. The sealing caps only serve to protect the valves against dirt. They are not designed to take up high system pressures. The ball valves must be closed. 12. Mount the insulating front shell. 13. Set to automatic mode on the controller (see controller manual). The commissioning of the solar installation is now complete. Please fill in completely the commissioning report on page 27. 16 99768xx-mub-en V04 2014/04

4 Commissioning [specialist] 4.4 Parameters: SolarBloC midi Premium / SolarBloC maxi Premium with controller SC3.6 The parameters for the sensors and pumps of system 1.1 are preset. If you want to use special functions, you might need to change the system. If you select and save another system, the parameters are reset to the factory setting. In this case you need to set the following parameters in the menu. In this way you make sure that the installation will work properly. SolarBloC midi Premium / SolarBloC maxi Premium Menu Parameters Settings after reset / Change of system Change to Note Para P18 OFF HE Pump output 1 Curve: AA SC: on Func F05 OFF Type 1 Heat quantity measurement (FlowRotor) Sensor hot: T4 Sensor cold: T5 2014/04 99768xx-mub-en V04 17

5 Maintenance [specialist] 5 Maintenance [specialist] WARNING Risk of burning and scalding! The valves, fittings and solar fluid can reach temperatures of more than 100 C. The solar fluid can escape as vapor and cause scalding. Only carry out maintenance work when the collector temperatures are below 50 C. Wait until the solar fluid has cooled down to max. 50 C. 5.1 Replacing the temperature sensor in the Airstop 1. Drain the solar circuit as described in 5.2 Draining the solar installation. 2. Pull out the fixation clip of the sensor. 3. Pull the sensor [4.1] to the front out of the Airstop. 4. Make sure that there is a sealing ring in the groove of the new sensor. Make sure that the sealing ring is in place when you insert the sensor. 5. After inserting the sensor, fix it using the clip. 6. Connect the sensor cable. 7. Close the drain valve [3.2]. 8. Fill the solar circuit as described in 4.2 Preparations before flushing and 4.3 Flushing and filling. 18 99768xx-mub-en V04 2014/04

5 Maintenance [specialist] 5.2 Draining the solar installation 1. Switch off the controller and make sure that a restart is not possible. 2. Open the check valves in the flow and return ball valve [5.2 1.2], by turning them to position 45 (see page 12). 3. Connect a heat-resistant hose to the lowest drain valve of the solar thermal system (or to drain valve [3.2]). Make sure that the solar fluid is collected in a heat-resistant container. WARNING Danger of scalding due to hot solar fluid! The escaping fluid may be very hot. Place and fix the heat-resistant collecting container so that people standing nearby are not endangered when the solar installation is being emptied. 4. Open the drain valve at the lowest point of the solar thermal system. 5. To accelerate draining of the solar circuit, you can open the bleeding device, if present, at the highest point of the solar thermal system. 6. Dispose of the solar fluid observing the local regulations. 5.3 Deinstallation 1. Drain the solar thermal installation as described above. 2. Disconnect the pipe joints with the solar thermal system. 3. To remove the solar station from the mounting plate, pull the clips to the side using a screwdriver. 4. Pull out the station towards the front. 2014/04 99768xx-mub-en V04 19

6 Spare parts [specialist] 6 Spare parts [specialist] NOTICE Complaints and requests/orders of spare parts will only be processed with information on the serial number! The serial number can be found on the safety group of the solar station. In case of a complaint, please send us the completely filled commissioning report on page 27. 6.1 SolarBloC midi Premium DN 20 Pumps DN 20 Wilo-Yonos PARA ST 15/7.0 PWM, high-efficiency Wilo-Stratos TEC ST 15/1-11.5 PWM, high-efficiency Grundfos Solar PM2 15-65, high-efficiency Grundfos Solar PM2 15-85, high-efficiency Grundfos Solar PM2 15-145, high-efficiency Item number E123207MO E12394071 E12164 E121618 E12162 20 99768xx-mub-en V04 2014/04

6 Spare parts [specialist] 6.2 SolarBloC maxi Premium DN 25 Pumps DN 25 Wilo-Stratos TEC ST 25/1-7 PWM, high-efficiency Wilo-Stratos PARA 25/1-11 PWM, high-efficiency Grundfos Solar PM2 25-105, high-efficiency Grundfos Solar PML 25-145, high-efficiency Item number E12395072 E12395115 E1216310 E1216314 2014/04 99768xx-mub-en V04 21

7 Assembly of the insulation 6.3 Connection of PWM pumps DN 20 / DN 25 PWM GND brown blue 7 Assembly of the insulation 1. 2. 22 99768xx-mub-en V04 2014/04

8 Technical data 8 Technical data Dimensions SolarBloC midi (DN 20) SolarBloC maxi (DN 25) Height (with controller) 560 mm 656 mm Width (total) 334 mm 334 mm Depth (total) 150 mm 160 mm Centre distance flow - return 100 mm 100 mm Pipe connections ¾" internal thread 1" internal thread Connection for expansion tank ¾" external thread, flat sealing Outlet pressure relief valve ¾" internal thread Operating data Max. admissible pressure 6 bars Max. operating temperature 120 C Max. stagnation temperature 140 C Max. propylene glycol content 50 % Operating temperature of sensors -25 C to +120 C Equipment Pressure relief valve 6 bars Pressure gauge 0-6 bars FlowRotor 0.5-15 l/min 1-35 l/min Sensors 1 collector sensor, 2 storage tank sensors Check valves (integrated in the ball valves) 2 x opening pressure 200 mm wc, can be opened manually Material Valves and fittings Brass Gaskets EPDM Check valves Brass Insulation EPP, λ = 0,041 W/(m K) 2014/04 99768xx-mub-en V04 23

8 Technical data SolarBloC midi Premium (DN 20) Pressure [m wc] Pressure [kpa] Flow rate [l/h] SolarBloC maxi Premium (DN 25) Pressure [m wc] Pressure [kpa] Flow rate [l/h] 24 99768xx-mub-en V04 2014/04

9 Function of the check valves [specialist] 9 Function of the check valves [specialist] Within their application range, the check valves in this station prevent unwanted gravity circulation. The efficiency of the check valves depends on: the installation height the temperature difference between the storage tank and the collector the type of heat transfer medium In the diagram below you can see whether the check valves integrated in the station are sufficient. If the check valves are not sufficient, you need to install additional components to prevent gravity circulation. You can mount components such as syphons ("heat traps"), 2-way valves (zone valves) or additional check valves. Example: The station comprises two check valves (2 x 200 mm wc = 400 mm wc). You use a mixture of water and 40% of propylene glycol as a solar fluid. The installation height between the collector and the storage tank is 10 m. Installation height in m Circulation Solar fluid Result: Temperature difference storage tank/collector in K The check valves prevent gravity circulation up to a temperature difference of about 62 K. If the temperature difference between the collector and the tank is larger, the difference in density of the solar fluid will be so large, that the check valves are pushed open. 2014/04 99768xx-mub-en V04 25

9 Function of the check valves [specialist] Do you need to know it exactly? The density of the solar fluid decreases with rising temperature. In high installations with large temperature differences, the difference in density will cause gravity circulation. This circulation can cool down the storage tank. Calculation example: Δp = Δρ * g * h Collector temperature: Storage tank temperature: 5 C Density solar fluid ρ 1 = 1042 kg/m³ 67 C Density solar fluid ρ 2 = 1002.5 kg/m³ Δρ = ρ 1 - ρ 2 = 39.5 kg/m³ g = 9.81 m/s² Installation height h = 10 m Δp = 3875 Pa = 395 mm wc The two check valves in the station (2 x 200 mm wc) are sufficient for an installation height of 10 m and a temperature difference between the collector and the tank of up to 62 K. 26 99768xx-mub-en V04 2014/04

10 Commissioning report 10 Commissioning report Installation operator Location of installation Collectors (number / type) Collector surface m² Installation height m (Difference in height between station and collector field) Pipes = mm l = m Venting (collector field) Not existent Vented Manual vent valve Automatic deaerator Airstop (station) Vented Solar fluid (type) % glycol Antifreeze tested up to: C Serial numbers Flow rate Pump (type) l/m Station Pump speed level Flow rate sensor System pressure mbars Temperature Expansion tank (type) Initial pressure Pressure relief valve Checked mbars sensors Controller Check valves Checked Software version Plumbing company Date, signature 2014/04 99768xx-mub-en V04 27

PAW GmbH & Co. KG Böcklerstraße 11 D-31789 Hameln, Germany www.paw.eu Phone: +49 (0) 5151 9856-0 Fax: +49 (0) 5151 9856 98 99768xx-mub-en V04 2014/04