Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux

Similar documents
Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Low GWP Refrigerants for Air Conditioning Applications

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Air-Cooled Heat Exchanger Performance for R410A

Investigation of Evaporator Performance with and without Liquid Overfeeding

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Performance Testing of Unitary Split-System Heat Pump with an Energy Recovery Expansion Device

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Developing Two-Phase Flow Distribution in Horizontal Headers With Downward Minichannel-Branches

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Purdue e-pubs. Purdue University

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Experimental Study on the Performance of Twisted Capillary Tube

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Study of R161 Refrigerant for Residential Airconditioning

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Geothermal ORC Systems Using Large Screw Expanders

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Heat Pump Clothes Dryer Model Development

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Real Time Upright Freezer Evaporator Performance Under Frosted Conditions

Sub-Critical Operation of the CO2 Expander/ Compressor

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge

II. OBJECTIVE OF RESEARCH

Design Optimization of Variable Geometry Microchannel Heat Exchangers

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Techniques of Heat Transfer Enhancement and their Application. Chapter 4. Performance Evaluation Criteria for Two-Phase Heat Exchangers

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Refrigerant Mass and Oil Migration During Start-up Transient

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

High Efficiency R-134a Compressor for Domestic Refrigerator

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Recovery of Waste Thermal Energy in U.S. Residential Appliances

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux Anna Fenko GE Appliances, United States of America, anna.fenko@ge.com Ellen Brehob GE Appliances, United States of America, ellen.brehob@louisville.edu Andrea Kelecy GE Appliances, United States of America, andrea.kelecy@ge.com Follow this and additional works at: http://docs.lib.purdue.edu/iracc Fenko, Anna; Brehob, Ellen; and Kelecy, Andrea, "Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux" (2016). International Refrigeration and Air Conditioning Conference. Paper 1642. http://docs.lib.purdue.edu/iracc/1642 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2189, Page 1 Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux Anna FENKO 1 *, Dr. Ellen BREHOB 2, Dr. Andrea KELECY 3 1 GE Appliances, Refrigeration Louisville, KY, USA 850-420-7161, anna.fenko@yahoo.com 2 University of Louisville, Department of Mechanical Engineering Louisville, KY, USA 3 GE Appliances, Technical Development University of Louisville, Department of Mechanical Engineering Louisville, KY, USA * Corresponding Author ABSTRACT This study was conducted to evaluate pressure drop at extremely low velocity refrigerant flow through smooth circular evaporator tubes in household refrigeration systems. Experimental data was taken at mass fluxes under 70 kg/m 2 s for two refrigerants, R134A and R600A, internal diameters of aluminum evaporators ranging from 0.186 inches (4.72 mm) to 0.317 inches (8.05 mm), U-bend internal radii ranging from 0.342 inches (8.69 mm) to 0.750 inches (19.05 mm) in horizontal and vertical orientations of evaporators. The geometry of the samples closely resembled a commonly used serpentine shape with multiple U-bends experiencing both, up- and down-flow of the refrigerant. Horizontal orientation test results with double the number of the U-bends suggest that horizontal U- bends (at least in tested geometries) at low mass fluxes less than 70 kg/m 2 s do not play a significant role in a total frictional pressure drop in horizontal evaporators. A Curvature Ratio study showed no two-phase frictional pressure drop dependence on the curvature ratio of the U-bends. Main geometrical properties affecting two-phase frictional pressure drop in evaporators at low flows are internal diameter of the tube and a total length of evaporator tube. And main physical properties of the refrigerant flow affecting two-phase frictional pressure drop in evaporators at low flows are the type of refrigerant and its mass flow rate. Experimental databank of nearly 100 points collected within this study can be used to extend the application of the currently available two-phase pressure drop correlations or to develop a new one specifically for low mass fluxes. 1. INTRODUCTION A 1⁰ C saturation temperature drop as the result of the pressure drop through the evaporator reduces the COP of the common compressor by close to 1%, which increases annual energy usage by approximately $7.68 million, assuming12 million household refrigerators in the US by 2017. Thus, the cost of energy required to compensate for the pressure loss through the system tubing needs to be understood as it is also a part of the overall performance of the appliance which must be competitive in the market. Furthermore, evaporator tube geometry is optimized for material and manufacturing cost savings as well as energy and environmental considerations. Thus, lowering inner diameter of the tube to achieve material savings leads to pressure drop and higher energy usage concerns. Also in the desire to reduce space taken by the sealed system by tightening of the bend curvature ratio leads to experiments with evaporator shape and orientation. In addition, a reduction in internal diameters of the refrigerant system components allows decreasing the amount of refrigerant

2189, Page 2 used, which should be recovered and recycled after the life of the refrigerator in order to decrease greenhouse effect. Deeper understanding of the diameter reduction tradeoffs will allow common usage of R600A refrigerant in the United States in the near future. This refrigerant provides 60-70 % higher cooling capacity compared to commonly used R134A, but it is being regulated to a maximum charge of 57 g per refrigerator due to its higher flammability. At this time there are no available two-phase pressure drop correlations designed specifically for extremely low mass fluxes (less than 70 kg/m 2 s) due to the complexity of measurement of these low pressure drops. There is also no available experimental data that could be used to create a new correlation or extend the application of existing ones. Therefore, this study was conducted to investigate this low mass flux regime. Experimental data were taken at mass fluxes under 70 kg/m 2 s for two refrigerants, R134A and R600A, for internal diameters of aluminum evaporators ranging from 0.186 inches (4.72 mm) to 0.317 inches (8.05 mm), and with U-bend internal radii ranging from 0.342 inches (8.69 mm) to 0.750 inches (19.05 mm) in both horizontal and vertical orientations. The geometry of the samples closely resembled a commonly used serpentine shape with multiple U-bends experiencing both upand down-flow of the refrigerant. 2. SCOPE OF WORK The databank developed for this study is based on a full size evaporator with multiple U-bends in various orientations. The inlet and outlet refrigerant properties are controlled to reflect actual saturation properties commonly found in the modern bottom freezer refrigerator. Four internal diameters, four curvature ratios, two evaporator orientations and two refrigerants were tested. A detailed description of test samples is available in Table 1. Table 1: Databank description Data set reference number Refrigerant type Tube internal diameter d, mm Tube U-bend internal radius R internal, mm Total evaporator length L, m Evaporator orientation Total number of U-bends Vertical orientation study 1 R134A 8.00 14.61 10.10 Vertical 12V, 1H 2 R600A 8.00 14.61 10.10 Vertical 12V, 1H 3 R134A 6.78 13.46 10.06 Vertical 12V, 1H 4 R600A 6.78 13.46 10.06 Vertical 12V, 1H 5 R134A 6.17 13.46 10.01 Vertical 12V, 1H 6 R600A 6.17 13.46 10.01 Vertical 12V, 1H 7 R134A 4.72 13.46 9.95 Vertical 12V, 1H 8 R600A 4.72 13.46 9.95 Vertical 12V, 1H Vertical curvature ratio study 9 R134A 8.00 19.05 10.31 Vertical 12V, 1H 10 R134A 8.00 14.61 10.10 Vertical 12V, 1H 11 R134A 6.78 19.05 10.27 Vertical 12V, 1H 12 R134A 6.78 13.46 10.06 Vertical 12V, 1H 13 R134A 6.78 8.69 9.78 Vertical 12V, 1H Horizontal orientation study 14 R134A 6.78 13.46 10.06 Horizontal 13H 15 R600A 6.78 13.46 10.06 Horizontal 13H Double horizontal U-bend study 16 R134A 6.78 13.46 9.76 Horizontal 26H 17 R600A 6.78 13.46 9.76 Horizontal 26H

2189, Page 3 Most of the data were taken for vertical orientation of the evaporator as it is the most common installation method in household refrigerators. This largest set of data was taken with a moderate U-bend radius, various tube internal diameters, and for both refrigerants (Data sets 1-8 in Table 1). Further, a few samples were remade with different U- bend sizes and tested vertically once again to capture the effects of the U-bend curvature ratio on the total pressure drop (Data sets 9-13). Next, some configurations were tested horizontally to understand the static pressure drop effect and to eliminate the vertical U-bends from the system (Data sets 14 and 15). And lastly, a double horizontal U-bend configuration was tested, where the same length of the evaporator was packed in the smaller space by doubling the number of horizontal U-bends (Data sets 16 and 17). Note that the total length L of the evaporator tube varies slightly from approximately 9.78 to 10.31 meters for different samples. This is due to intentional equality of the straight tubes lengths between adjacent U-bends (0.63 meters for all samples); while this dimension was kept the same, the U-bend length differed based on its radius. Another contribution to the total length difference was the length of the inlet/outlet ports of the evaporator. These ports were also participating in the heat exchange and total pressure drop through the evaporator, and local pressure drop through these was calculated using appropriate correlations. Thus, this databank was created to understand most of the geometrical options considered during the design of the evaporator in a common refrigerator. 3. TEST FIXTURE 3.1 Test Fixture Description The test fixture diagram is shown in Figure 1. It consists of a complete sealed system using the components of a household refrigerator. Figure 1 below shows the schematic of the test fixture used in this study. Charging Port Charging Port Mixing Fan Site Glass Main Compressor Condenser T, P sub Coriolis Flow Meter Backflow valve Secondary Compressor dp (0-5 psi) Dryer Accumulator dp (0-1 psi) Constant Expansion Valve T, P Outlet dp (0-5 psi) Evaporator T, P Inlet Precision Constant Expansion Valve Heater Mixing Fans Figure 1: Experimental Fixture Diagram For all tests the fixture was located in a temperature controlled chamber maintained at 32.2⁰ C. Temperature control is used to avoid small fluctuations in the heat flux and helped increase the effectiveness of the heater control. 32.2⁰ C ambient temperature provides an additional heat load used to compensate for door openings in the actual refrigerator. Each evaporator being tested was located in an insulated enclosure consisting of thick foam panels covered with fiberglass sheets and vacuum panels. The enclosure is schematically shown in Figure 1 with a green rectangle. Heat transfer into the evaporator was achieved by evenly wrapping a flexible heater to the tube using

2189, Page 4 aluminum tape around the full length of the evaporator. The insulation was needed to assure that all heat from the heater was effectively into the evaporator. Two constant speed fans were installed inside of the insulation box to help mix the air for even heat flux distribution from the heater. The inlet and outlet refrigerant conditions were measured using Omega 4-wire RTDs and Setra absolute pressure gauges with 0-100 psia (0 to 689.5 kpa) ratings. Two Setra differential pressure gauges were installed in parallel to measure the pressure drop over the length of the evaporator. The operation ranges of these gauges, 0-1 psid (0-6.89 kpa) and 0-5 psid (0-34.47 kpa), were selected to maximize the accuracy of the measurements for the range of tested samples. Upstream of the compressor an accumulator was used to prevent the liquid refrigerant entering the intake tube of the compressor. Two compressors in parallel were used to increase the flow range of the system. Low and high pressure charging ports were located on both sides of the main compressor to assist with servicing of the fixture. A secondary compressor was used in addition to the main one during testing with R600A. A backflow prevention valve was installed on the outlet of the secondary compressor to avoid potentially damaging backflow occurring during operation of the main compressor alone. Another Setra 0-5 psid (0-34.47 kpa) differential pressure gauge was installed across the condenser, and a mixing fan was used to enhance the heat rejection from the condenser. Upstream of the condenser, a site glass was used for visual control of the refrigerant subcooling. Another set of Omega 4-wire RTD and Setra absolute pressure gauge (0-300 psia, 0-2068.4 kpa) were located downstream from the condenser for quantification of subcooled refrigerant properties. A Coriolis flow meter was located further down the system for measurement of the all-liquid mass flow. A filter dryer was a part of the system downstream of the flowmeter and helped with the removal of the moisture from the system during operation. 3.2. Test Configurations Figure 2 shows a sample of vertically tested evaporator with 12 vertical U-bends and a single horizontal U-bend. The direction of the flow was set up for mostly liquid to climb up one side of the evaporator through 6 vertical U- bends and 7 straight passes, cross over the horizontal U-bend at the top and flow down through 6 vertical U-bends and 7 straight passes to all vapor quality at the exit. This direction of the flow allowed higher differential pressure drops and improved accuracy of pressure drop measurements because the system operated closer to the midrange of the pressure transducers. All U-bends in a single evaporator were made with the same bend radius configured per Table 1. All straight passes of evaporators were oriented horizontally; portions of vertical straight tubes at the inlet and outlet of the evaporators were accounted for in calculations using corresponding straight tube pressure drop correlations including static pressure losses. Figure 2: Twelve vertical and one horizontal U-bends in vertical evaporator orientation (samples 1-7 in Table 1) Figure 3 represents all horizontal evaporator configurations with 13 horizontal U-bends. The horizontality and flatness of the evaporator set up was ensured with C-clamps and levels. As for the vertical configuration, the whole length of the evaporator tube between two differential pressure taps was accounted for in calculations.

2189, Page 5 Figure 3: 13 horizontal U-bends in horizontal evaporator orientation (sample 8 in Table 1) Finally, Figure 4 represents the double U-bend horizontal configuration (26 U-bends). This configuration complicated the design of the insulating box due to its increased size in one direction. Thus, it was decided to fold this evaporator in two resulting in approximately 1.5 inches increase in elevation between the bottom and top layer of the 26 U-bends. This increase in elevation was assumed to be negligible. As for the 13 horizontal U-bend configurations, this set up was also clamped and leveled (not shown in Figure 4) Figure 4: 26 horizontal U-bends in horizontal evaporator orientation (sample 9 in Table 1) 4. EXPERIMENTAL RESULTS The experimental results are presented based on the orientations of the studies outlined in Table 1. For all graphical presentations of the data the plots created using R134A refrigerant are shown in solid lines and round markers, while plots created using R600A refrigerant are presented by dashed lines and diamond markers. Further, the data taken from the same evaporator are color coded the same for better visual analysis of the results. All pressure drop plots

2189, Page 6 have an additional point added at dp = 0 psid (kpa) and lb m/hr (g/s) assuming no pressure drop at no flow conditions. This point is used in determining a cubic trendline for each set of data which was shown to have the best graphical fit to the experimental data. The trendlines are purely for easier visualization of the results. 4.1 Vertical Orientation Study Figure 5 shows measured two-phase pressure drop values through vertical evaporators with twelve vertical and one horizontal U-bend (data sets 1-8 in Table 1). This is the most complex part of the overall study conducted in this research. Overall, this data set shows some similarities between two-phase pressure drop tendencies of R134A and R600A. Both refrigerants have minimal changes of the pressure drops for lower flows and larger tube internal diameters. As the flow increases pressure drop starts to climb and its gradient increases with decreasing internal tube diameter. For both sets of data, for R134A and R600A, maximum tested flow is limited to a certain value for several reasons. For R600A testing maximum mass flow rate is governed by the abilities of the two parallel compressors to run with lower density refrigerant; density of R600A vapor is approximately 30% of the R134A vapor density. For R134A, the maximum tested mass flow is determined by the range of the largest differential pressure transducer used in the study (5 psid, (34.47 kpa)) and the goal to test with flows commonly used in the household refrigerators (normally 6-8 lb m/hr, 0.76-1.00 g/s). Figure 5: Vertical evaporator orientation study with 12 Vertical and 1 Horizontal U-bends per data sets 1-12 from Table 1

2189, Page 7 4.2 Vertical Curvature Ratio Study Based on data sets 9-13 in Table 1, Figure 6 shows the results for several curvature ratios of the vertical evaporator configuration for R134A using tube internal diameters of 0.315 inches (8.00 mm) and 0.267 inches (6.81 mm). Four U-bend internal radii were tested: 0.750, 0.575, 0.530 and 0.342 inches (19.05, 14.61, 13.46 and 8.69 mm). The curvature ratio, D/d was calculated using equation below. An example calculation for the first data set with R134A, d = 0.315 inches (8 mm), R internal = 0.750 inches (19.05 mm) is also shown below: Thus, a curvature ratio for this data set equals 5.95. In the above equation t stands for tube thickness. Figure 6 shows that the pressure drop data points for same tube sizes are located in a very near proximity to each other seemingly independent from the curvature ratio of the samples. Thus for clarity of the plot only one trendline is plotted for each of the tube sizes internal diameter, since trendlines for other curvature ratios would be located in close proximity. It is evident from the U-bend curvature ratio study that there is no clear defined relationship between the total twophase pressure drop through the evaporator in the household refrigerator and the U-bend curvature ratio of the samples. However, a much stronger relationship is apparent for data sets with the same internal diameter of the tubes. This relationship is also evident in Figure 5 for data sets 1-12. D/d = 5.95 D/d = 4.84 D/d = 6.80 D/d = 5.16 D/d = 3.75 Figure 6: Vertical evaporator orientation study with 12 Vertical and 1 Horizontal U-bends per data sets 9-13 from Table 1.

2189, Page 8 4.3 Horizontal Orientation and Double U-Bends Study Figure 7 represents the data for horizontal orientation of the evaporators in the 13 U-bend and 26 U-bend configurations. The data corresponds to data sets 14 to 17 in Table 1. In the horizontal orientation of the U-bends the total pressure drop appears to be only slightly dependent on the number of the U-bends: the trendlines of the data points for 13 and 26 horizontal U-bends for the evaporators of very similar length are almost coincident. It appears that at low flows under 9.50 lb m/hr (1.20 g/s) for R134A and 7.00 lb m/hr (0.88 g/s) for R600A horizontal evaporators with U-bend radii at least as low as 0.5 inches (12.70 mm) have two-phase pressure drop that is independent of the number of the U-bends and can be treated as straight continuous horizontal tubes. Furthermore, the close overlay of two curves, one with 13 U-bends and the other with 26 U-bends, for each of the refrigerants is evidence of the repeatability of the test process adopted for this research. Two different evaporators were used to collect this data and their manufacturing and installation, as well as test conditions, appeared to have a high accuracy and repeatability based on these results. Figure 7: Horizontal evaporator orientation study with 13 Horizontal U-bends per data sets 14-15 and Double U- bend horizontal evaporator study with 26 Horizontal U-bends per data sets 16-17 in Table 1. For future studies a simplifying assumption can be made based on this data that a single horizontal U-bend present in the geometry of the vertical evaporators at low flows can be treated as a part of the straight horizontal tube.

2189, Page 9 5. CONCLUSION AND FUTURE WORK The goal of the work was to extend the current experimental data bank for refrigerant pressure drop during evaporation to conditions and geometries common for household refrigerators that could be used to extend the application of currently available two-phase frictional refrigerant correlations with a good accuracy or create a new correlation. Horizontal orientation tests with double the number of the U-bends showed that horizontal U-bends (at least in tested geometries) at low mass fluxes less than 70 kg/m 2 s do not play a significant role in a total frictional pressure drop in horizontal evaporators. A Curvature Ratio study showed no two-phase frictional pressure drop dependence on the curvature ratio of the U-bends. The main geometrical properties affecting total two-phase frictional pressure drop in evaporators at low flows are internal diameter of the tube and a total length of evaporator tube. And the main physical properties of the refrigerant flow affecting total two-phase frictional pressure drop in evaporators at low flows are the type of refrigerant and its mass flow rate. Refrigerant properties that might have some of the most significant effect are, perhaps, density and viscosity; however, the level of their influence needs to be further studied in the future work. The next steps in studying two-phase frictional pressure drop at low flows is taking a more intricate approach towards adjusting one or more of the established two phase pressure drop models in order to extend their application to this range of flows. The data bank of nearly 100 data points created within this study can be used to check the prediction accuracy of two-phase frictional models such as Grönnerud (1979) and Müller-Steinhagen & Heck (1986) or one of the latest phenomenological models like Silva Lima & Thome (2012). Furthermore, a brand new empirical correlation could be potentially considered for this region of flows; however, it may require an increase in the data bank size for good accuracy. Overall, the experimental data itself is very useful for future designs of evaporators in domestic refrigerators since the flows, geometries and orientations tested here are being commonly used today. ACKNOWLEDGEMENT I would like to thank my advisors Dr. Ellen Brehob, Dr. Sam Park, and Dr. Andrea Kelecy for their help and guidance throughout this project. My specials thanks to Brent Junge and Mike Kempiak for helping me build the testing fixture and guiding me through data collection. REFERENCES ASHRAE, 1993. 1993 ASHRAE Handbook Fundamentals, America Soiety of Heating, Refrigerating and Air Conditioning Engineers, Inc., Atlanta. Embraco, 2015. VEGD6H Compressor Technical Sheet. Energy.gov. 2015. Estimating appliance and home electronic energy use, <http://energy.gov/energysaver/estimatingappliance-and-home-electronic-energy-use>. Grönnerud, R., 1979. Investigation of liquid hold-up, flow-resistance and heat transfer in circulation type evaporators, Part iv: two phase flow reisistance in boiling refrigerants. In: Annexe 1972-1, Bull. de1 Inst du Froid. Müller-Steinhagen, H., and K. Heck. 1986. A simple friction pressure correlation for two-phase flow in pipes. Chemical Engineering and Processing: Process Intensification 20:297-308. Silva Lima, R.J., and J.R. Thome. 2010. Two-phase frictional pressure drops in adiabatic horizontal circular smooth u-bends and contiguous straight pipes (RP-1444), HVAC&R Research 16:383-98. Silva Lima, R.J., and J.R. Thome. 2012a. Two-phase frictional pressure drops in U-bends and contiguous straight tubes for different refrigerants, orientations, tube and bend diameters: Part 1. Experimental results (RP- 1444), HVAC&R Research 18:1047-71. Silva Lima, R.J., and J.R. Thome. 2012b. Two-phase frictional pressure drops in U-bends and contiguous straight tubes for different refrigerants, orientations, tube and bend diameters: Part 2. New models (RP-1444), HVAC&R Research 18:1072-97.