Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Similar documents
International Journal of Engineering Research & Technology (IJERT) ISSN: Vol. 2 Issue 10, October

Effect of Louvered Strips on Heat Transfer in a Concentric Pipe Heat Exchanger

Experimental analysis of condensation heat transfer enhancement of steam at low pressures using modified twisted tape insert

ANALYSING THE EFFECTIVENESS OF THE HEAT EXCHANGER BY INCREASING OVERALL HEAT TRANSFER COEFFICIENT

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Performance Study of Triple Concentric Pipe Heat Exchanger

Design, Development & Testing of Double Pipe Heat Exchanger With Heat Transfer Enhancement Liners

A REVIEW ON HEAT TRANSFER ENHANCEMENT BY PASSIVE METHODS

2. HEAT EXCHANGERS MESA

Heat Transfer Enhancement in Shell and Tube Condenser

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Falling Film Heat Exchangers for Solar Water Heaters

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Experimental Study And CFD Based Simulation of Closed Loop Pulsating Heat Pipe Using of Refrigerants (R-134a)

Sant Gadge Baba Amravati University. Amravati, Maharashtra, India, Maharashtra 2

CHAPTER 3 EXPERIMENTAL SETUP AND PROCEDURE

Performance investigation of Air-conditioning system using ejector as expansion device

Thermal Analysis of Concentric Tube Heat Exchanger Using Louvered Strip Inserts

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

In the name of God. Jami Institute of Jami - Mehdi Rasti

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Raman et al., International Journal of Advanced Engineering Technology E-ISSN

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

ENSC 388: Engineering Thermodynamics and Heat Transfer

[Jhansi, 5(10): October 2018] ISSN DOI /zenodo Impact Factor

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Solar air heater duct having triangular protrusions As roughness elements on absorber plate

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Design & Development of Tube in Tube Helical Coil Heat Exchanger

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Gandhinagar Institute of Technology Mechanical Engineering (Thermal Engineering) Semester II. Design of Heat Exchange Equipments [ ]

Compression of Fins pipe and simple Heat pipe Using CFD

American International Journal of Research in Science, Technology, Engineering & Mathematics

Design, Development and Experimental Investigation of Volumetric Air Receiver

A Review on Comparative Study of Thermal Performance of Artificially Roughened Solar Air Heaters

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

a Heat Exchanger using FEA Tool

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

A STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Experimentation of Heat Pipe Used In Nano-Fluids

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array

1, 2

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Thermal Performance of a Loop Thermosyphon

Global Journal of Engineering Science and Research Management

Design and Development of Water Cooled Condenser for Domestic Refrigerator

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

EXPERIMENTAL INVESTIGATION OF HYBRID NANOFLUID ON THERMOSYPHON TYPE WICKLESS HEAT PIPE HEAT EXCHANGER THERMAL PERFORMANCE

HEAT TRANSFER ENHANCEMENT IN SHELL AND TUBE HEAT EXCHANGERS USING INSERTS

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) AN EXPERIMENTAL STUDY OF HEAT TRANSFER IN A CORRUGATED PLATE HEAT EXCHANGER

THERMOHYDRAULIC PERFORMANCE OF AN EQUILATERAL TRIANGULAR DUCT WITH ARTIFICIAL ROUGHNESS USED IN SOLAR AIR HEATER

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Analysis of CPU cooling using liquid with different type of heat sinks

DESIGN AND ANALYSIS OF PIPE HEAT EXANGERS WITH INSIDE FINS

Modified Air Cooler with Split Cooling Unit

Convection Heat Transfer from Horizontal Rectangular Fin Array having Triangular Perforations

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser

To investigate the surface properties for increasing efficiency of solar water heater

THERMAL ENGINEERING LABORATORY II. To train the students with principles and operation of thermal Engineering equipments.

IMPROVE THE EFFICIENCY OF HEAT EXCHANGER IN OIL COOLER.

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

[Vali*, 5(2): February, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

Experimental Study on Waste Heat Recovery from the Pyrolysis Stack using Heat Pipe

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER

Recovery Using Heat Pipe Heat Exchanger with Hybrid Nanofluid

TITLE: Improvement in Heat Transfer Rate and Dynamics of Shrouded Fanned Radiator System

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Enhancement of COP in Vapour Compression Refrigeration System

International Engineering Research Journal Experimental Investigation of Effect of length on Performance of Axially Grooved Heat Pipe.

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

International Engineering Research Journal Performance Analysis of Ejector Based Solar Air Conditioning System

Experimental assessment of a PCM to air heat exchanger storage system for building ventilation applications

Pressure drop analysis of Condenser using refrigerants R-134a, R-407C

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Experimental Analysis on Effect of Design Parameters on the Performance of Single Loop Pulsating Heat Pipe

Jurnal UMP Social Sciences and Technology Management Vol. 3, Issue. 3,2015

Investigation and Optimization of Air Cooled Condenser of Chillers by Replacing Cu to Al Tubes

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Physical Mechanism of Convection. Conduction and convection are similar in that both mechanisms require the presence of a material medium.

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

Transcription:

International Journal of Current Engineering and Technology E-ISSN 2277 416, P-ISSN 2347 5161 216 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts Shravani A. Phule * and Kundlik V. Mali Department of Mechanical Engineering, Sinhgad College of Engineering, Pune, India Department of Mechanical Engineering, MAEER s MIT College of Engineering, Pune, India Accepted 2 March 216, Available online 15 March 216, Special Issue-4 (March 216) Abstract In the present study, heat transfer from hot water to cold water by double pipe heat exchanger for plain tube and plain tube with twisted wire brush inserts is experimentally investigated. The experiments were carried out for counter flow configuration with hot water in the inner tube and cold water flowing in the annulus through outer tube. All the experiments were conducted by varying hot water Reynolds number at constant cold water Reynolds number in the laminar flow region. The horizontal double pipe heat exchanger is made from straight copper tube with inner tube and outer tube diameters of 15 and 25 mm, respectively. The twisted wire brush inserts were fabricated by winding a.2 mm diameter of the copper wires over a 2 mm diameter two twisted iron core-rods. All the required parameters like inlet and outlet temperature of hot and cold water, flow rates of both hot and cold water were measured using appropriate instruments. Effect of inlet fluid temperature and other relevant parameters on heat transfer characteristics and pressure drop were studied. The convective heat transfer coefficient of double pipe heat exchanger under various operating conditions was determined. Keywords: Twisted wire brush inserts, double pipe heat exchanger, Heat transfer enhancement 1. Introduction 1 Heat exchangers have several industrial and engineering applications. Heat exchangers also find its application in various processes like conversion, utilization and recovery of thermal energy in industrial, commercial and domestic applications. The design of heat exchangers is quite complicated as it requires exact analysis of heat transfer rate and pressure drop apart from its efficient performance and economy of the system. The major challenge while designing is to achieve high heat transfer with decreased pressure drop and minimum pumping power along with a compact design of a heat exchanger. Use of heat transfer enhancement techniques lead to increase in heat transfer coefficient but at the cost of increase in pressure drop. Wide range of inserts such as tapered spiral insert, packing, rings, discs, streamlined shapes, mesh inserts, spiral brush inserts, conical-nozzles and V-nozzles have been widely used to minimize the size of heat exchanger and thereby reduce the capital cost for a given load. Paisarn Naphon et al. (211) investigated the heat transfer characteristics and the pressure drop of the horizontal concentric tube with twisted wires brush inserts. The plain tube with full-length twisted wires *Corresponding author: Shravani A. Phule brush and regularly spaced twisted wires brush with 3 cm spacer length inserts were tested. Cold and hot water were used as working fluids for counter flow configuration, respectively. The effect of twisted wires density, inlet fluid temperature, and relevant parameters on heat transfer characteristics and pressure drop were studied. It was found that the twisted wire brush inserts have a large effect on the enhancement of heat transfer, however, the pressure drops also increase. P. Promvonge et al. (27) experimentally investigated the heat transfer, friction factor and enhancement efficiency characteristics in a circular tube fitted with conical-ring turbulators and a twisted-tape swirl generator. The heat transfer test section is heated electrically. In the experiments, two enhancement heat transfer devices were used. One is the conical-ring used as a turbulator and placed in the tested tube and the other is the twisted-tape swirl generator placed at the core of the conical-ring. Air was used as a working fluid. It was found that there is significant increase in heat transfer value and the enhancement efficiency tends to decrease with the rise in Reynolds number. Also, correlations were developed to predict Nusselt number, friction factor for circular tube using the conical ring turbulator and swirl generator. K. V. 27 MIT College of Engineering, Pune, India, AMET 216, INPRESSCO IJCET Special Issue-4 (March 216)

Shravani A. Phule et al Sharma et al. (29) conducted experiments to evaluate heat transfer coefficient and friction factor for flow in a tube and with twisted tape inserts in the transition range of flow with Al 2O 3 nanofluid. It was found that there is considerable enhancement of convective heat transfer with Al 2O 3 nanofluids as compared to water. The heat transfer coefficient of nanofluid flowing in a tube with.1% volume concentration is 23.7% higher when compared with water at number of 9. Heat transfer coefficient and pressure drop with nanofluid has been determined with tapes of different twist ratios. A regression equation was developed to estimate the Nusselt number which was valid for both water and nanofluid flowing in circular plain tube and with tape inserts. M.M.K. Bhuiya et al. carried out experimental study on the heat transfer performance and friction factor characteristics in a circular tube using twisted wire brush inserts. The study was conducted for flow in turbulent region. The results indicated that the presence of twisted wire brush inserts led to a large effect on the enhancement of heat transfer with corresponding increase in friction factor for the plain tube. It was also found that there was considerable increase in Nusselt number value with increasing Reynolds number. Further correlations were also developed to predict heat transfer, friction factor, and thermal performance factor for turbulent flow through a circular tube fitted with the twisted wire brush inserts in terms of wire density (y), Reynolds number (Re), and Prandtl number (Pr). M. A. Akhavan- Behabadi et al. (21) carried out investigation to study the enhancement in heat transfer coefficient by coiled wire inserts during heating of engine oil inside a horizontal tube. The test-section was a double pipe counter-flow heat exchanger. The engine oil flowed inside the internal copper tube, while saturated steam, used for heating the oil, flowed in the annulus. The data was obtained for heated engine oil flowing through the plain tube. The effects of Reynolds number and coiled wire geometry on the heat transfer enhancment and fanning friction factor were studied. Empirical correlations were developed to predict the heat transfer enhancement of these coiled wire inserts. According to the results obtained, it was seen that wire coil inserts with lower wire diameters give better performance at low Reynolds numbers. 2. Experimental apparatus and method The important parts of experimental set-up are the test section, hot and cold water tanks, rotameters, monoblock pumps, whose selection is already discussed in previous section. All these instruments are selected as per the requirements depending upon their measuring range, accuracy and availability in the market. The test section is made up of copper tubes as it has higher thermal conductivity. The proposed experimental set-up is shown in Fig.1 which is fabricated for water to water single phase heat exchanger system. 1. Double pipe heat exchanger (Test section) 2. Hot water storage tank 3. Cold water storage tank 4. Rotameters 5. Monoblock pumps 6. Flow control Valve 7. Water heater Fig.1 Schematic diagram of proposed experimental setup 2.1 Technical details of twisted wire brush inserts The geometrical configuration and details of the twisted wires brush inserts are shown in Fig. 2. The test section is the horizontal double pipe heat exchanger. It is made from straight copper tube with inner tube and outer tube diameters of 15 mm and 25 mm, respectively. The plain tubes with full-length twisted wires and with regularly spaced twisted wires brush inserts are tested. The twisted wires brush inserts are fabricated by winding a.2 mm diameter of the copper wires over a 2 mm diameter two twisted iron core-rods. Fig.2 Geometric details of twisted wire brush inserts 2.2 Experimental Apparatus The schematic diagram of the experimental apparatus is shown in Fig.3. It consists of a test section, hot water loop, cold water loop and data acquisition system. The experimental set-up is a concentric double pipe heat exchanger which is well equipped with required instruments and gives heat transfer between hot water flowing through inner pipe and cold water flowing through outer pipe. The heat exchanger includes two concentric copper tubes with twisted wire brush inserts in inner tube. The test section and the piping 28 MIT College of Engineering, Pune, India, AMET 216, INPRESSCO IJCET Special Issue-4 (March 216)

Shravani A. Phule et al system were designed in such a way that all parts can have easy access and repaired easily. A full set of instruments was used to measure and control temperature and flow rates of water and are located at desired points in the set-up. The hot water was adjusted to desired level and is controlled with the help of dimmerstat. Two way flow control valves were used to maintain the flow rate of water both in inner as well as outer tube. These valves were selected for half inches piping. Galvanised pipes were used for the tubing connection in set-up. The inlet and outlet temperatures of water in inner and outer tube were measured with PT-1 type of thermocouples located at desired points for temperature measurement. The accuracy of thermocouple is ±.1º C. To determine the pressure drop across the test section, manometer having range 1--1 mm was used. Depending upon the variation of Reynolds number from 5 to 3 suitable Rotameter having a range of 15 to 15 LPH is selected. data acquisition system. The experiments were performed for various flow rates and constant inlet temperature of hot water entering test section. The water flow rate was increased in small increments by keeping the cold water flow rate, inlet cold water temperature and hot water temperature constant. The inlet hot water temperature was adjusted to desired level by using electric heater and the corresponding temperature was controlled by using dimmerstat. Before noting down the observations, the system was allowed to approach steady state. The experiments were carried out for the concentric plain tube and the concentric plain tube with full length twisted wire brush inserts. The flow rates of water were controlled by operating the flow control valve and by two rotameters. The water temperatures at inlet and outlet sections as well as average tube wall temperatures were measured by PT-1 type thermocouples. A caliberated U-tube manometer was employed to measure pressure drop across the test section. For the experimentation the cold water flow rates were varied from 3 LPH to 7 LPH while hot water flow rates were varied from 15 LPH to 75 LPH. The inlet cold and hot water temperatures are taken in operating range of 24 26 o C and 4 45 o C, respectively. 3. Data reduction The data was collected for plain tube as well tube with twisted wire brush inserts. The different flow rates for cold water and hot water are taken for counter flow heat exchanger. Fig.3 Experimental Set-up diagram The characteristic dimensions of double pipe heat exchanger with twisted wire brush inserts are presented in Table.1 Table 1 Characteristic dimensions of double pipe heat exchanger and wire brush inserts The heat transfer rate for cold water in the test section, Q c [1}, can be expressed as, Q c = m cc pc (T co - T ci ) (1) Where, m c is the flow rate of cold water, C pc is the specific heat of water; T co and T ci are outlet and inlet cold water temperatures respectively. The heat transfer rate for hot water in the test section, Q h [1], can be expressed as, Parameters Dimensions Diameter of the inner plain tube (Di ), mm 15 Diameter of the outer plain tube (Do), mm 25 Length of plain tube, m 2 Number of twisted core rod 2 Twisted wire brush length, m 2 Twisted wire diameter, mm.2 2.3 Experimental procedure The experimental set-up was installed for water-towater single phase heat exchanger system. It consists of double pipe heat exchanger, hot water tank, cold water tank, pumping device, U-tube manometer, and Q h = m hc ph (T hi T ho) (2) Where, m h is the flow rate of hot water, C ph is the specific heat of water, T ho and T hi are outlet and inlet hot water temperatures respectively. All the fluid thermophysical properties are calculated at the average of inlet and outlet hot fluid temperatures. The average heat transfer rate obtained by is calculated for hot and cold water which is used to calculate the inner convective heat transfer coefficient. The thermal equilibrium test showed that the heat transfer rate on cold side is less than heat transfer rate obtained for hot water. This indicates that there are some heat losses on the outer surface of test section. 29 MIT College of Engineering, Pune, India, AMET 216, INPRESSCO IJCET Special Issue-4 (March 216)

Nu Shravani A. Phule et al The average heat transfer rate, Q ave [1] is determined as follows, Q ave = (Q c + Q h) / 2 (3) This average heat transfer rate can be used to calculate inner convective heat transfer coefficient. The heat transfer coefficient can be calculated using various methods such as using Wilson plot technique. But, in the present study, the tube side heat transfer coefficient for the inner tube can be evaluated from the average heat transfer rate obtained from the equation as follows, Q ave = h i A i (T h, ave T s, ave) (4) where, T s,ave is the average tube wall temperature, T h,ave is the average hot water temperature, A i is the inside surface area of the inner tube and h i is the convective heat transfer coefficient of inner tube. The experimental Nusselt number can be calculated from the equation given as below, Nu = h i D i k (5) A number of correlations are developed for laminar flow region, but the one most widely recommended is the Hausen correlation[1] which is taken for reference and is given as, di.668re Pr L Nu 3.65 di 1.4Re Pr L.66. 14 i w (6) where, Re is hot water Reynolds number, Pr is hot water Prandtl number, d i is inner tube diameter, length of inner tube, µ i is the fluid viscosity in inner pipe and µ w is the wall viscosity of inner pipe. The friction factor correlations can be referred from available literature review, which are as follows, 4. Results and discussion This section includes experimental study for concentric plain tube and tube with twisted wire brush inserts. The double pipe heat exchanger is analyzed in terms of temperature variation, heat transfer rate, friction factor and pressure drop. Various tests were performed for water to water heat transfer in double pipe having counter flow configuration with hot water flowing in inner tube and cold water flowing through outer tube. The results obtained from the experimental study of heat exchanger which was carried out at various operating conditions is discussed and presented in detail in the next section. A successful attempt is made to achieve maximum possible heat transfer from hot water to cold water using twisted wire brush inserts inside the pipe. 4.1 Comparison of Nusselt number obtained from plain tube and with full length twisted wire brush inserts Fig. 4 represents the comparison between experimental results of plain tube and tube with twisted wire brush inserts. It also shows the relation between inside Nusselt number and inside Reynolds number. It can be observed that there is an increase in Nusselt number value with corresponding increase in Reynolds number. The inside Nusselt number for tube with twisted tube inserts is higher as compared to plain tube inside Nusselt number value. There is approximately 1% increase in Nusselt number for tube with twisted wire brush inserts as compared to plain tube value. 3 25 2 15 1 5 Nu for plain tube Nu for plain tube with inserts f =.448 Re -.275 (7) The above correlation is known as Blausius equation which is the proposed relation to determine friction factor. The experimental correlation for the friction factor is given as, Pd h f (8) 2 2lv Where, l is the length of heat exchanger, d h is the hydraulic diameter, P is pressure drop across heat exchanger, ρ is the density of fluid, v is the velocity of fluid. 5 1 15 2 25 3 Fig.4 Variation of Nusselt number with Reynolds number for plain tube and plain tube with twisted wire brush inserts Fig. 5 shows the variation of inner Nusselt Number with various mass flow rates for plain tube and tube with twisted wire brush inserts. It can be seen that inner tube side Nusselt number increases with increase in mass flow rate of hot water which flows through inner tube. The values of Nusselt number for tube with inserts are higher than values for plain tube. The 3 MIT College of Engineering, Pune, India, AMET 216, INPRESSCO IJCET Special Issue-4 (March 216)

Qavg(W) Friction factor (f) hi (W/m2º C) Nu Shravani A. Phule et al performance of tube with twisted wire brush inserts is better than plain tube heat exchanger. The mass flow rate on hot water tube side is varied while mass flow rate on cold water side is kept constant. 35 3 25 2 15 1 5 Fig.5 Variation of inner Nusselt Number with various mass flow rates for plain tube and tube with twisted wire brush inserts 4.2 Effect on Average heat transfer rate for plain tube and tube with twisted wire brush inserts Fig. 6 shows the variation of average heat transfer rate with hot water Reynolds number for plain tube with full length twisted wire brush inserts.it is observed that at specific temperature of hot and cold water entering the heat exchanger, the heat transfer rate increases with increasing hot water Reynolds number. The reason for this is the heat transfer rate across the test section depends upon the heating capacity of hot water. It is observed from the Fig. 6 that the heat transfer from plain tube with full length twisted wire brush inserts is higher than those from the plain tube without twisted wire brush inserts. It is also found that when inlet hot and cold water temperatures, and cold water mass flow rate are kept constant, the average heat transfer rate increases with increasing hot water Reynolds number. This means that Nusselt number also increases. Comparing with Fig.4, it is observed that the variation of Nusselt number with hot water Reynolds number are similar to the trends of heat transfer rate and same explanation can be given. 1 9 8 7 6 5 4 3 2 1.1.2.3 Mass flow rate (Kg/s) 5 1 15 2 25 3 4.3 Effect on inner convective heat transfer coefficient for plain tube and tube with twisted wire brush inserts Fig. 7 shows the relation between inner convective heat transfer coefficient with Reynolds number for plain tube and tube with twisted wire brush inserts. The inner convective heat transfer coefficient on tube side increases with increasing hot water Reynolds number. Approximately there is 1-12 % increase in inner convective heat transfer coefficient value for tube with full-length twisted wire brush inserts in comparison to plain tube values. This indicates the corresponding increase in value of Nusselt number values for tube without and with twisted wire brush inserts. 14 12 1 8 6 4 2 Fig.7 Variation of inner convective heat transfer coefficient with Reynolds number for plain tube and tube with twisted wire brush inserts 4.4 Comparison of friction factor for plain tube and tube with twisted wire brush inserts Fig. 8 also shows the comparison of the friction factor between plain tube without twisted wire brush inserts and plain tube with full length twisted wire brush inserts..8.7.6.5.4.3.2.1 5 1 15 2 25 3 5 1 15 2 25 3 Fig.8 Variation of friction factor with Reynolds number for plain tube and with twisted wire brush inserts Fig.6 Variation of average heat transfer rate with Reynolds number for plain tube and tube with twisted wire brush inserts It was clearly observed that the friction factor continues to decrease with hot water Reynolds number. The flow characteristics through the plain 31 MIT College of Engineering, Pune, India, AMET 216, INPRESSCO IJCET Special Issue-4 (March 216)

Shravani A. Phule et al tube with twisted wire brush inserts is quite complicated than plain tube. This friction factor of the plain tube with twisted wire brush inserts is produced due to swirl generated because of inserts, drag forces exerted on the flow field by the twisted wire inserts and turbulence augmentation. As expected the friction factor obtained from plain tube with full length twisted wire brush inserts is higher than plain tube. But tha values of friction factor in both the cases are almost close. Conclusions An experimental study is conducted to investigate the heat transfer performance and friction factor characteristics for laminar flow through a tube by means of twisted wire brush inserts. The mass flow rates in inner tube and in annulus are varied during experimentation. Single phase water- water heat transfer study is performed and tested for counter flow configuration. Effect of inlet fluid temperature and relevant parameters on heat transfer characteristics and friction factor are considered. The study revealed that the twisted wire brush inserts provided significant enhancement of heat transfer with the corresponding increase in friction factor, however the pressure drop also increases too. Due to the turbulence created and swirl flow generated, the convective heat transfer obtained from the tube with twisted wire brush inserts is higher than that with the plain tube without twisted wire brush inserts. References Paisarn Naphon, Tanapon Suchana, (211), Heat transfer enhancement and pressure drop through the horizontal concentric tube with twisted wire brush inserts, International Communications in Heat and Mass transfer, 38, pp. 236-241. P. Promvonge, S. Eiamsa-ard, (27), Heat transfer behaviors in a tube with combined conical-ring and twisted-tape insert, International Communications in Heat and Mass Transfer, 34, pp.849 859. Sarma. K. V., Sundar. L. S., Sarma. P. K, (29), Estimation of heat transfer coefficient and friction factor in the transition flow with volume concentration of Al2O3 nanofluid flowing in a circular tube and twisted tape insert, International Communications in Heat and Mass transfer, 36, pp. 53-57. M.M.K. Bhuiya, M.S.U. Chowdhury, Heat transfer performance evaluation for turbulent flow through a tube with twisted wire brush inserts, International Communications in Heat and Mass Transfer, 39, pp. 155-1512. M.A. Akhavan-Behabadi, Ravi Kumar, M.R. Salimpour, R. Azimi, (21), Pressure drop and heat transfer augmentation due to coiled wire inserts during laminar flow of oil inside a horizontal tube, International Journal of Thermal Sciences, 49, pp.373 379. 32 MIT College of Engineering, Pune, India, AMET 216, INPRESSCO IJCET Special Issue-4 (March 216)