Pump technology: Improved energy efficiency in refrigeration plants. Dr. R. Krämer

Similar documents
1900 Series In-Line Pump

Centrifugal and Positive Displacement Pumps for Hygienic Applications

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

GRUNDFOS DATA BOOKLET UPS2. Circulator pumps. 50/60 Hz

Selection and Operational Considerations. Harold Streicher, Vice President Sales Hansen Technologies, Inc.

Multifunction pump for handling gaseous liquids in process engineering

GRUNDFOS DATA BOOKLET. Grundfos COMFORT. Circulator pumps. 50/60 Hz

Monitoring Pump Performance with Vibration. Mitchell Stansloski, PhD, PE

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP

CORNELL PUMP COMPANY. Quality Choices Dependable Solutions. Refrigeration Pumps

International Journal of Engineering Research & Science (IJOER) ISSN: [ ] [Vol-2, Issue-11, November- 2016]

CR A-F-A-E-HQQE 3x400/ HZ

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

Case 8 Basic Performance of Screw Compressor

Design And Analysis Of Centrifugal Pump

GRUNDFOS IndustrY ENGINEERING MANUAL. Industrial Boilers

SIHI LPH-X - Liquid Ring Vacuum Pump One Stage

CRN A-F-G-E-HQQE 3x400D 50 HZ

CR32-4 A-F-A-E-HQQE 3x400D 50 HZ

CR A-F-A-V-HQQV 3x400D 50 HZ

CR64-1 A-F-A-E-HQQE 3x400D 50 HZ

CR A-F-A-E-HQQE 3x400D 50 HZ

Experiment 2: Test on Domestic Refrigerator for evaluation of EER.

Performance Assessment of Water Cooled Condenser Refrigeration System

Technical Development Program

CRN90-1 A-F-G-V-HQQV 3x400D 50 HZ

Wash and Clean By Michael Rasmussen, Industry application team, Grundfos, Denmark

Fan Selection. and Energy Savings

PUMPS & PUMPING SYSTEMS FOR THE CHEMICAL PROCESSING & HEATING & AIR CONDITIONING INDUSTRY

CVGF. Water Cooled Centrifugal Chillers

Copy Right By: Thomas T.S. Wan

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Chapter 4 Compressors Overview & System Annual Power Consumption

HVAC Water chiller selection and optimisation of operation

CORNELL PUMP COMPANY REFRIGERATION EFFICIENT BY DESIGN

SIHI LPH-X - Liquid Ring Vacuum Pump One Stage

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

How to Cut Chiller Energy Costs by 30%

our contribution for Sealless Magnetic Coupled, Heavy Duty Side-Channel Pumps environmental protection Type SCM PN40

Heating and Air-Conditioning Testing II. Climatic Test Bench

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

EN aquatech.piovan.com

In the name of God. Jami Institute of Jami - Mehdi Rasti

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components:

CR5-9 A-FGJ-A-E-HQQE 1x220/240 50HZ

CR10-16 A-FJ-A-E-HQQE 3x400D 50 HZ

CHECK VALVES INSTALLATION

Multistage Centrifugal Pumps with Shaft Sealing Type HZ / HZA / HZAR

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Refrigerant Glide and Effect on Performances Declaration

Fans and Pumps I. Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong

SL S.S.N.51D

New Bitzer factory: Higher precision with air conditioning

Condenser Water Pump Calculator Guide

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

GT Series Single-Stage, Double Suction Horizontal Split Case Pumps

GRUNDFOS DATA BOOKLET MTB. Centrifugal machine tool pumps 50/60 Hz

TEPZZ _87768A_T EP A1 (19) (11) EP A1 (12) EUROPEAN PATENT APPLICATION. (43) Date of publication: Bulletin 2017/27

Modern vacuum and overpressure generation for pneumatic conveying

BUNGARTZ CENTRIFUGAL PUMPS

System Modeling of Gas Engine Driven Heat Pump

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Air-Cooled Condensers

L14 ENVIRONMENTAL CONTROL TECHNICAL DATA

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Air Conditioning Components

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Küba SG commercial

Partial Load Performance Of Refrigeration System

SCA 620C AIR COOLED SCREW CHILLER

Public Services Building 155 N First Avenue Hillsboro, OR March 2012

TP /4-A-F-A-BQQE 400D 50HZ

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor

FI / SFI Frame-Mounted End Suction Pumps

Torad Rotary Spool Compressor

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

Air-Cooled Condensing Units with Compact Screw Compressors

Modelling the Performance of a Diffusion Absorption Refrigeration System

The pump. A pump is a device that moves fluids (liquids or gases), or sometimes slurries, by mechanical action.

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Pumps for Florida Irrigation and Drainage Systems 1

BN-ACCMX MAR 2016 Replaces BN-TB-ACCMX MAR Air-Cooled Condenser. with Microchannel Coil Technology Models NRG NRJ

COMPACT CO 2 /NH 3 REFRIGERATION UNIT FOR THE COLD STORAGE

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

Fundamentals of Hydronic Design

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

CR20-07 A-F-A-E-HQQE 3x400/ HZ

CRU 200 and 500 Series Condensate Recovery Units

Combi Modular System. Standardised centrifugal pumps EN 733 ISO 2858 ISO 5199 API 610

CR A-F-A-E-HQQE 3x400/ HZ

KV Vertical Inline Pumps Taco Vertical Inline Pumps meet the latest standards for hydraulic performance and dimensional

Discover ebm-papst in commercial kitchen equipment. Durable and reliable products for constant use.

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

GEA Blu chillers. GEA BluAstrum, GEA BluGenium, GEA BluAir: A new generation of compact ammonia chillers

Vacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager

GFD. GVD V-shape coil condenser. Güntner Info. 8 additional basic models for container transport!w. V-shape coil drycooler

NEW SECTION: ROTARY HEAT EXCHANGER WITH A HEAT PUMP Effective and smart!

Transcription:

Technical Report Improved energy efficiency in refrigeration plants

According to the European EDL directive (final energy efficiency and energy services), 9 % energy savings over a nine-year-period in comparison to a reference period should be possible through targeted measures. A current topic is energy savings in industrial refrigeration plants taking natural refrigerants such as NH 3 and CO 2 as a basis. Up to 70 % of the pump energy consumption can be saved if a frequency converter with a p-differential pressure control unit for the pump drive is used instead of a 50 Hz mains operation. View of a CO 2 refrigeration plant with a pump system Cooling water Compressor Condenser Flow control valve Separator Q min -Orifice HERMETIC pump Figure 1: Schematic representation of a large refrigeration plant Evaporator Q max -Orifice or constant fl ow regulator The preferred design for large refrigeration plants today (Figure 1) is a pumping station with forced recirculation of the refrigerant on the low-pressure side. This has several advantages over other systems: savings of power due to lower temperature differences with direct vaporisation reliable distribution and control of the refrigeration capacity with many evaporators, even ones that are at a distance simplification of the pipework and reduction of its dimensions improved heat transfer to the evaporators concentration of the most important machine units in one room. Refrigerant pumps must be suitable for pumping refrigerant when it is boiling, be insensitive to cavitation to a great extent, have high operational reliability, and be maintenance-free. Hermetic pumps without shaft sealing allow broad use of refrigerant pumps independent of the refrigerant for the first time. Figure 2: Diagram of a hermetic refrigerant pump, type CAM Figure 2 shows a hermetically sealed refrigerant pump for pumping the liquid cooling medium. The thin-walled stainless steel can serves as a hermetic seal of the pump unit to the outside and protects the winding from the effects of the refrigerant. The motor is liquid cooled. A cooling stream is tapped from the side of the pump that is under pressure to the rotor space, and then fed back into an area of higher pressure after absorbing the motor s dissipated heat through the hollow shaft between the second and third impeller. This prevents vaporisation of the motor cooling stream. Page 2 of 7

Hermetic refrigerant pumps in a supermarket For some time now, more and more NH 3 /R404 refrigeration plants are being replaced by more environmentally friendly CO 2 /R744 refrigeration plants. They supply the freezers in supermarkets, for example. Due to the resulting high pressure, usually only hermetically sealed refrigerant pumps (pressure stage PN40 or PN64) come into question. The following example describes the use of a refrigerant pump in a supermarket with 60 freezers and an overall length of approx. 180 m. CO 2 /R744 at a temperature of 4 C is used as a refrigerant. The pump is designed for 12 m 3 /h with a pump head of 26 m. The task was to control the pump in an efficient and energy-saving way with the help of a frequency converter. In the process, the pump was to adjust independently to different refrigeration consumption. A calculation algorithm was used for the design of the pump, which permitted the conversion of the 50 Hz performance curve to smaller frequencies with the help of the similarity laws: Q~n, h~n^2, P2~n^3 as well as NPSH~n^4/3. There were hardly any problems with the conversion. Clarifying the following questions was more difficult: What restrictions are there as a consequence of the changed heat balance between the pump and motor? The vapour pressure of CO 2 at 4 C is still 30 bar. What losses does the motor have at low speeds? What is the situation with the load rating of the slide bearings? Is the motor capacity sufficient even for the maximum refrigeration capacity of the plant? How does changing the speed affect Q min und Q max and / or the NPSH (Net Positive Suction Head)? Page 3 of 7

H (m) 100 90 80 70 60 50 40 30 20 10 Q min min night day Figure 3: Characteristic curves, 30-60 Hz Top: H-Q characteristic curves with limiting curves to prevent vaporisation of the motor cooling stream (blue) and to prevent cavitation (red) respectively. Bottom: P-Q characteristic curves. Equally calculated and measured operating points for Qmin and Qmax, as well as operating points for day and night operation. max Q max p = 2,50 bar 0 0 1 4 6 8 10 12 14 16 Q (m 3 /h) 60Hz 55Hz 50Hz 45Hz 40Hz 35Hz 30Hz P2(kW) at density ρ 4,5 4,0 3,5 3,0 2,5 2,0 max 1,5 day 1,0 min night 0,5 0 0 1 4 6 8 10 12 14 16 Q (m 3 /h) 60Hz 55Hz 50Hz 45Hz S-Hmin SNPSH p 40Hz 35Hz 30Hz Heat input By including the speed as a new degree of freedom, the calculation is mathematically more difficult as the problem becomes multidimensional. The pump head H is a 2-dimensional function of Q and f. Likewise, the shaft power P2 is a 2-dimensional function of Q and f. With the help of the calculation algorithm, it is possible to show the pump head H and the shaft power P2 as 2-dimensional cubic spline functions of the variables Q and f. With these spline functions, it was possible to interpolate in any way in the characteristic curve family. Hence, f could be calculated for a stipulated Q and H, or alternatively Q could be calculated from f and H. A minimum speed of approx. 1800 rpm corresponding to a minimum frequency of 30 Hz resulted from the bearings load rating calculation taking the CO 2 viscosity into consideration. The 50 Hz characteristic curve of the pump, the equivalent circuit of the motor, as well as the physical properties of CO 2 depending on the temperature were used as input values for the calculation program. In addition, there were specifications for the geometry, the outlet of the motor cooling stream, minimum security S-min against vaporisation of the side stream and a minimum security SS-min = NPSHa NPSHp (plant pump) against cavitation. Observation of the motor frequency The result is the characteristic curve family shown in Figure 3, which also takes the slippage of the motor into consideration. First of all, the heat balance calculation results in a blue limiting curve. This reflects the operating points at which the minimum security S is still 3 m. S is greater than 3 m for all points inside the blue curve. Physically, this means that vaporisation of the motor side stream is not to be expected for all points inside the blue limiting curve. It can be seen that the motor frequency cannot be lowered arbitrarily. The frequency range is limited to approx. 30 Hz by the blue curve. 30 Hz is also the lower limit for the bearings load rating of the slide bearings with CO 2. Page 4 of 7

TS2 DPT TS1 PT JT ST Figure 4: Differential pressure diagram: DPT differential pressure, TS1 suction-side temperature, TS2 pressure-side temperature, PT pressure on the suction side, ST frequency (at the converter), JT power consumption (at the converter) A second criterion concerns NPSHa and NPSHr. For small rates of delivery, NPSHr increases again as a consequence of the heat generated in the first impeller. If a minimum clearance SS-min = 0.3 m is required between NPSHa and NPSHr, then this results in the red limiting curve in the chart. The pump is cavitation-free inside the curve. Cavitation is to be expected outside the curve. One can see that the red curve determines the minimum rate of delivery in this case. In contrast, the maximum rate of delivery in the characteristic curve family is defined by the blue curve. Adaptation of the pump to the plant Practically, the differential pressure between the suction and pressure flange is used (see differential pressure diagram Figure 4) as a controlled variable for the frequency converter. The converter regulates the frequency in accordance with the required rate of delivery or alternatively the refrigeration capacity so that the differential pressure remains constant across the entire control range. Hence, Q becomes a clear function of the frequency. To save energy, the differential pressure must be set to a setpoint in the lower range of the characteristic curve family (Figure 3). There, the pump energy consumption P2 are proportionally ~n 3 smaller. However, in order to allow the largest possible control range, the frequency should not be too low, or alternatively too close to the minimum of the blue curve. In our example, the setpoint was defined as 26.6 m, corresponding to 2.5 bar pressure differential. The minimum rate of delivery is then the result of the intersection of the H = 26.6 m curve and the red curve for Q min = 1.07 m 3 /h at 32.7 Hz. The maximum rate of delivery is the intersection of the H = 26.6 m curve and the right blue curve for 12.0 m 3 /h at 47.3 Hz. 65% energy savings The operating points for day and night operation that were actually measured in the plant were on the p = 2.5 bar lines and are also shown in Figure 3. The operating point during the day was 38.7 Hz / 6.8 m 3 /h and 35.0 Hz / 3.9 m 3 /h at night. Thereby, Q nearly changes by factor 2. Both operating points are sufficiently away from Q min and Q max. The energy efficiency is obvious. The shaft power at night was only 0.66 kw compared to 1.91 kw at 47.2 Hz. Page 5 of 7

Operating Point Min Night Day Max Frequency (Hz) 32.70 35.00 38.70 47.20 Rate of delivery (m 3 /h) 1.07 3.93 6.81 12.00 Pump head (m) 26.60 26.60 26.60 26.60 NPSH pump (m) 0.11 0.16 0.32 0.78 Pump head reserve above vapour pressure (m) 4.28 9.89 8.97 3.87 NPSH reserve above NPSH-pump (m) 0.64 1.25 1.14 0.69 Motor cooling stream (m 3 /h) 0.92 0.92 0.92 0.92 Heating of motor cooling streem ( K) 1.53 0.94 1.03 1.58 Efficiency of pump (%) 17.00 41.00 47.11 43.41 Efficiency of motor (%) 58.70 64.65 68.40 71.42 Min. pump head at cooling stream outlet (m) 18.57 18.57 18.57 18.57 Increase of vapour pressure height (m) 14.29 8.68 9.59 14.70 Total heating of the delivery stream ( K) 1.00 0.31 0.23 0.25 Power dissipation (kw) 0.67 0.75 0.99 1.85 Current consumption (A) 2.53 2.87 3.36 4.63 Power consumption (kw) 0.74 1.03 1.46 2.68 Shaft power (kw) 0.44 0.66 1.00 1.91 Speed (1/min) 1913 2031 2226 2674 Torque (Nm) 2.18 3.12 4.29 6.83 Chart 1: Calculated numerical values for operating points for min, nights, days, and max Q (m 3 /h) 14 12 10 8 6 4 2 0 30 35 40 45 50 f (Hz) Figure 5: Dependency of the rate of delivery Q (m 3 /h) on the converter frequency f (Hz) This means an energy savings of 65 %. Compared to 50 Hz mains operation, that would be even greater savings, i. e. 70 %. The total heat input into the system is reduced to 0.75 kw at 35 Hz compared to 1.85 kw at 47.2 Hz, which means savings of 59 %, or even 65 % compared to 50 Hz mains operation. Although the rate of delivery Q cannot be measured directly, it can be simply calculated from the frequency with a constant differential pressure. To do this, form a quadratic regression Q vs. f for the above four operating points thereby obtaining the functional connection. Q (m 3 /h) = 61.596 + 2.74 * f 0.025 * f 2 This equation only applies for a differential pressure of 2.5 bar. It can be used to calculate the rate of delivery from the measured frequency, and can possibly be shown directly on the converter or tapped externally. Hence, trouble-free pump operation is ensured for the following parameters and within the following operating limits: Differential pressure: 2.5 bar Rate of delivery Q (m 3 /h): 1.1-12.0 m 3 /h Converter frequency f (Hz): 32.7-47.2 Hz Pump speed n (rpm): 1913-2674 rpm Under these conditions, there is sufficient pump head reserve (S >3 m) compared to vaporisation of the motor cooling stream. Likewise, there is sufficient NPSH reserve (S >3 m) to exclude cavitation of the suction side of the pump. The pump speeds are also sufficient to ensure the bearings load rating of the slide bearings. The Max operating point corresponds to the intersection point of the blue curve with the p lines according to Figure 3, thereby giving the condition of maximum refrigeration capacity of the plant. Mathematically, this results in the numerical values for this operating point that are given in chart 1 under the Max operating point. This also corresponds to the design data of the pump. Page 6 of 7

Conclusion The use of a frequency converter with p control can save up to 70 % of the pump energy consumption compared to a 50 Hz mains operation. The heat carried into the refrigeration system is also reduced by 65 % in the process. This also means that the necessary refrigerating capacity of the compressors is reduced accordingly. The speed control of the pump therefore results in a double benefit. Both the pump as well as the compressors experience an efficiency increase and hence contribute to the energy savings of the entire refrigeration plant. Page 7 of 7