LETTER OF TRANSMITTAL FRANK A. ANZALONE Date: FAA Job No. 157 GENERAL CONTRACTOR Attention: Mr. Brent Guilbeau - Coleman Partners 1401 Derek Drive, Suite B Hammond, LA 70403 3377 North Boulevard Phone: (985) 542-2744 Baton Rouge, LA 70806 Fax: (985) 230-0614 RE: 157 - Mayfield Elementary School Additions Air Handlers, Energy Recovery Ventilators, ATUs WE ARE SENDING YOU Attached Under Separate Cover Via Shop Drawings Change Order Other Product Data Samples Specifications Prints ITEM NO. COPIES DESCRIPTION 001 1 Central Station Air Handler - Shop Drawings/Data 002 1 Energy Recovery Ventilators - Shop Drawings/Data 003 1 Air Terminal Units THESE ITEMS ARE TRANSMITTED: For Approval For Your Use As Requested Appoved As Submitted Approved As Noted Returned For Correction For Review and Comment Revise and Resubmit REMARKS: Brent: Please see the attached Mechanical Submittals for Review. SIGNED: Wilson Alvarez
SUBMITTAL DATA Henry Mayfield Elementary Equipment Included: (3) York Solution XTI Air Handling Units (8) Enviro-Tech Model HLE,HLP,VHC Fan Coil Units (17) Single Duct Model SDR Variable Air Volume Boxes (33) L.G. Thru-the Wall Terminal Air Conditioning Units Frank A. Anzalone, General Contractor, Inc JOB # FILE DATE REVIEWED BY COMMENTS MADE YES NO APPROVED FOR SUBMITTAL TO ARCHITECT YES NO THIS SUBMITTAL HAS BEEN REVIEWED FOR GENERAL CONFORMANCE WITH CONTRACT DOCUMENTS; VENDOR IS RESPONSIBLE FOR ACCURACY IN ACCORDANCE WITH ALL CONTRACT DOCUMENTS. Prepared For: ARC Mechanical 36408 LA-433 Slidell, LA 70460 Prepared By: Schully Strawn & Assoc. 2839 Hessmer St., Ste 100 Metairie, LA 70002 Date: June 8, 2016
York Solution Model XTI Air Handling Unit General Notes 1. All of the York Solution Model XTI on this project shall be provided with the following: 2 Inch Double Wall Construction Foam Injected Insulation with R Insulation Value of 13 1% Leakage at +/- 8 Inches ESP L/240 Panel Deflection Thermal Break Access Doors (Downstream of Cooling Coil) Belt Drive, Housed Airfoil Fan Wheels on MUA Units 2 Inch Internal Spring Isolation Inverter Duty, Premium Efficiency, ODP Fan Motor Chilled Water Cooling Coil Galvanised Steel Coil Casing 304 Stainless Steel IAQ Drain Pan Filter Section with (2) Sets of 2, 30% MERV-8 Filters, Magnehelic Gauges. 6 Inch Base Rails 60 Month Parts & Labor Warranty Beginning at Startup 2. We are not providing any of the following: Air Flow Measuring Stations Controls or Control Valves 3. All coil hand connection locations, fan discharge arrangements and access door location shall be coordinated with mechanical contractor before release of equipment.
AHU-1 1 Indoor Air Handler 45 x 60 6270 Unit Sequence Tier 2 FS /\ Tier 1 VC <<< XA <<< FF Basic Unit Options Insulation Type: Base Rail Height: Performance: (Refer to Each Segment) 6" Formed Steel High Performance Statement of compliance of standard units. Solution XT AHU's meet IBC seismic requirements for non-critical equipment (Ip = 1.0) for locations with design spectral response Sds <= 0.43. Units must be rigid mounted. The anchorage of the unit to the ground or building structure needs to be evaluated by and is the responsibility of the engineer of record. Specification of seismic requirements is the responsibility of the project design engineer. If formal certification is required, please contact your sales representative and/or application engineer for review. Certain application and site requirements may require additional cost and/or lead time. Unit Special Quotes None *Note:Component locations are listed as Segment Hand (Unit Hand) : ex. Left (Right) See Submittal Drawing for additional details Printed: 4/27/2016 10:33:09 AHU-1Performance Unit Folder: AHU1 4/18/2016 1:33:14 PM Page 1 of 8
AHU-1 1 Indoor Air Handler 45 x 60 6270 Segments Listed Starting At Air Inlet FF Flat Filter Segment Filter Media Detail Filter Segment Options (Quantity)Filter Sizes: (2)24x24; (2)24x12 Interior STD Ga. G-90 Galvanized Liner Filter Loading: Side Insulation: R-13 2" Foam Filter Depth: 2" STD Ga. G-90 Galvanized Floor Liner Filter Media Type: Pleated 30% (MERV 8) Exterior STD Ga. G-90 Galvanized Liner Filter Area (ft²): 12.0 Galvanized Blankoff Material Filter Air Pressure Drop (in. w.g.): 0.29 Access Doors on Both Sides 39H x 10W Dirty Filter Allowance (in. w.g.): 0.25 Standard Door Latch, No Lock, Outward Opening Optimized Filter Arrangement Spare Filter Media: Spare Filter Quantity Set(s): Pleated 30% (MERV 8) 1 XA Access Segment Access Segment Details Access Segment Options Segment Length: 3 " Interior STD Ga. G-90 Galvanized Liner Insulation: R-13 2" Foam STD Ga. G-90 Galvanized Floor Liner Exterior STD Ga. G-90 Galvanized Liner VC Vertical Coil Segment Coil Segment Details Coil Segment Options Coil Space: 10" Interior STD Ga. G-90 Galvanized Liner Insulation: R-13 2" Foam STD Ga. G-90 Galvanized Floor Liner Exterior STD Ga. G-90 Galvanized Liner Coil Pull: None 19" IAQ Drain Pan Left (Left) Stainless Steel Access Doors on Both Sides 39H x 18W Standard Door Latch, No Lock, Outward Opening Bulkhead Material Galvanized Coil Supports Galvanized UV Surface Decontamination Detail None Printed: 4/27/2016 10:33:09 AHU-1Performance Unit Folder: AHU1 4/18/2016 1:33:14 PM Page 2 of 8
AHU-1 1 Indoor Air Handler 45 x 60 6270 FS - Supply Fan Segment Segment Details Fan Segment Options Segment Air Pressure Drop (in. w.g.): 0.00 2" Spring Isolator Air Flow per Fan (CFM): 6270 Osha Belt Guard Air Flow Total (CFM): 6270 Interior STD Ga. G-90 Galvanized Liner Altitude (ft.): 75 Insulation: R-13 2" Foam TSP/ESP (in. w.g.): 2.03/ 1.00 STD Ga. G-90 Galvanized Floor Liner Air Inlet: Bottom Exterior STD Ga. G-90 Galvanized Liner Fan Discharge: Top External Light Switch Access Door on Left Side(Left) 33H x 18W Multi-Point Door Latch, No Lock, Outward Opening Fan Detail Type: AF Size: 15-15 Construction: S Bearing Options: Extended Lube Fan RPM: 2076 BHP: 4.47 Fan BHP w/ Belt Loss: 4.78 Outlet Velocity (ft/min): 2739 Motor Detail (per motor) Motor Type: WEG ODP Premium Efficiency HP 7.5 Voltage/Phase/Frequency: 460/3/60 Hz Insulation Class: F Motor RPM: 1800 Frame Size: 213 Location: Left(Left) Drive Type: Belt Drive Type: Belt Drive Fixed Full Load Amps (FLA): 9.25 Efficiency: 91.0% Printed: 4/27/2016 10:33:09 AHU-1Performance Unit Folder: AHU1 4/18/2016 1:33:14 PM Page 3 of 8
AHU-1 1 Indoor Air Handler 45 x 60 6270 Coils & Spacers Listed Starting In Direction Of Air Flow VC Coil - 01 Coil General/Physical Details Air Side Performance Fluid Side Performance Location: Tag: 0 AirCoil Rows: Fins Per Inch: 6 8 Air Flow (acfm): Altitude (ft.): 6270 75 EWT ( F): LWT ( F): GPM: 45.0 55.0 32.5 Application: Cooling Tubes Per Circuit: 12 EAT-DB ( F): 74.4 WPD (ft): 12.8 Coil Type: Water Finned Height (in.): 35.00 EAT-WB ( F): 62.6 FPS: 4.0 Face Type: Full Finned Length (in.): 48 LAT-DB ( F): 55.3 Fluid Type: Wate Tube Diameter: 1/2" BDW Coil Face Area 11.7 LAT-WB ( F): 53.5 Fluid Weight(lb): r (ft²): Fluid 67.0 Tube Material: Copper Coil Conn. Loc.: Left(Left) FV (ft/min): 536 Volume(ft³): 1.1 Tube Wall Thickness:.016" Supp Conn Size: 2" SMBH: 130.0 Fouling Factor 0.00000 Rtn Conn Size: 2" TMBH: 163.2 (hft² F/btu): Fin Type: Corrugated # of Supply Conn. (per coil): 1 APD (in. w.g.): 0.48 Fin Thickness:.006" Fin Material: Aluminum Casing Material: Galvanized Connection Material: Steel* Connection Type: MPT Coating: None *Johnson Controls suggests using red brass or copper connectors when the coil is to be attached to a copper or brass piping system. Ratings are for coils manufactured by Johnson Controls, Inc., 507 E. Michigan St., Milwaukee WI 53202. BDW Tube Spacing: 1.25" x 1.08" AHRI Messages: This coil is certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the range of Standard rating conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Coil Dll Version: 7.3b.003 Static Pressure Summary Segment Component Supply (in. w.g.) Return Fan (in. w.g.) FF Flat Filter VC Vertical Coil 2" Pleated 30% (MERV 8) Dirty Filter Allowance Cooling 6 rows 8 fins Turning Air Pressure Drop 0.29 0.25 0.48 0.01 Printed: 4/27/2016 10:33:09 AHU-1Performance Unit Folder: AHU1 4/18/2016 1:33:14 PM Page 4 of 8
AHU-1 1 Indoor Air Handler 45 x 60 6270 FS-DWDI Supply Fan External Static Pressure - User Entered Pressure Drop 1.00 Total 2.03 0.00 Air handling unit parameters vary depending on conditions. Parameters such as airflows, air pressure drops, and coil capacities are shown for design conditions. Section FF Flat Filter Segment XA Variable Length Access Segment VC Vertical Coil Segment FS-DWDI Supply Fan Segment Dimension & Weights Summary Length* Width** (in.) 13 3 38 - (in.) 60 60 60 60 Height (in.) 45 45 45 39 Weight (lbs.) 267 24 972 904 Overall: 54 60 84 2167 *The length includes bottom tier segments only. **The width does not include coil connection extensions or door latches that extent beyond the unit casing. The width does not include the depth of any pipe chases. Printed: 4/27/2016 10:33:09 AHU-1Performance Unit Folder: AHU1 4/18/2016 1:33:14 PM Page 5 of 8
Shipping Skid (VC XA FF FS-DWDI) SOLUTION XT AIR HANDLING UNIT AHU-1 1 Indoor Air Handler 45 x 60 6270 Shipping Skid Summary Length* Width** Height*** Weight (in.) (in.) (in.) (lbs.) 54 68 95 2167 Ship Loose: None *The length includes any mounted rain-hoods, discharge flanges, tie-down brackets, shipping wood-blocks, front dampers, split connectors, electrical/control components, outrigging extensions, isolation dampers, inlet baskets **The width includes any door handles, coil connections, drain connections, lifting lugs, mounted pipe-chases, electrical/control components, tie-down brackets, side dampers ***The height includes any base-rails, shipping wood-blocks, roof peak, discharge flanges, mounted gas-furnace flue pipes Shipping Skid Sequence Tier 2 Tier 1 FS) /\ VC < XA < FF) Printed: 4/27/2016 10:33:09 AHU-1Performance Unit Folder: AHU1 4/18/2016 1:33:14 PM Page 6 of 8
AHU-1 1 Indoor Air Handler 45 x 60 6270 Sound Summary Octave Band Sound Power Levels (db Re. 1 picowatt) 63 125 250 500 1000 2000 4000 8000 dba Ducted Discharge Top-1, FS 91 91 92 90 87 82 76 71 Return Air INLET, FF 86 83 83 84 79 74 67 60 Sound data tested in accordance with AHRI-260 (2001), Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. Notes: 1. The overall A-weighted sound power level is only applicable to sound radiation outdoors and casing radiated sound. This metric does not apply to ducted components 2. Return air sound powers are estimated using 100% of unit flow. Printed: 4/27/2016 10:33:09 AHU-1Performance Unit Folder: AHU1 4/18/2016 1:33:14 PM Page 7 of 8
AHU-1 1 Indoor Air Handler 45 x 60 6270 Recommended Trap Height Summary Applicable Fan TSP Positive or Calculated Dimensions Recommended Base Rail Segment Fan [in H 2 O] Negative H X H + X H H + X Height VC Supply Fan 2.03" Negative 3.03" 1.51" 4.54" 3.25" 5.00" 6" Notes: Formulas and calculations are recommendations only. Contractor shall determine actual dimensions required for each trap based on jobsite conditions, and application requirements. Refer to section 2 (Installation) of the IOM for more information. Printed: 4/27/2016 10:33:09 AHU-1Performance Unit Folder: AHU1 4/18/2016 1:33:14 PM Page 8 of 8
AHU-2 1 Indoor Air Handler 45 x 63 6320 Unit Sequence Tier 2 FS /\ Tier 1 VC <<< XA <<< FF Basic Unit Options Insulation Type: Base Rail Height: Performance: (Refer to Each Segment) 6" Formed Steel High Performance Statement of compliance of standard units. Solution XT AHU's meet IBC seismic requirements for non-critical equipment (Ip = 1.0) for locations with design spectral response Sds <= 0.43. Units must be rigid mounted. The anchorage of the unit to the ground or building structure needs to be evaluated by and is the responsibility of the engineer of record. Specification of seismic requirements is the responsibility of the project design engineer. If formal certification is required, please contact your sales representative and/or application engineer for review. Certain application and site requirements may require additional cost and/or lead time. Unit Special Quotes None *Note:Component locations are listed as Segment Hand (Unit Hand) : ex. Left (Right) See Submittal Drawing for additional details Printed: 4/27/2016 10:33:29 AHU-2Performance Unit Folder: AHU2 4/18/2016 10:38:03 AM Page 1 of 8
AHU-2 1 Indoor Air Handler 45 x 63 6320 Segments Listed Starting At Air Inlet FF Flat Filter Segment Filter Media Detail Filter Segment Options (Quantity)Filter Sizes: (2)24x24; (2)24x12 Interior STD Ga. G-90 Galvanized Liner Filter Loading: Side Insulation: R-13 2" Foam Filter Depth: 2" STD Ga. G-90 Galvanized Floor Liner Filter Media Type: Pleated 30% (MERV 8) Exterior STD Ga. G-90 Galvanized Liner Filter Area (ft²): 12.0 Galvanized Blankoff Material Filter Air Pressure Drop (in. w.g.): 0.29 Access Door on Left Side(Left) 39H x 10W Dirty Filter Allowance (in. w.g.): 0.25 Standard Door Latch, No Lock, Outward Opening Optimized Filter Arrangement Spare Filter Media: Spare Filter Quantity Set(s): Pleated 30% (MERV 8) 1 XA Access Segment Access Segment Details Access Segment Options Segment Length: 3 " Interior STD Ga. G-90 Galvanized Liner Insulation: R-13 2" Foam STD Ga. G-90 Galvanized Floor Liner Exterior STD Ga. G-90 Galvanized Liner VC Vertical Coil Segment Coil Segment Details Coil Segment Options Coil Space: 10" Interior STD Ga. G-90 Galvanized Liner Insulation: R-13 2" Foam STD Ga. G-90 Galvanized Floor Liner Exterior STD Ga. G-90 Galvanized Liner Coil Pull: None 19" IAQ Drain Pan Left (Left) Stainless Steel Access Doors on Both Sides 39H x 18W Standard Door Latch, No Lock, Outward Opening Bulkhead Material Galvanized Coil Supports Galvanized UV Surface Decontamination Detail None Printed: 4/27/2016 10:33:29 AHU-2Performance Unit Folder: AHU2 4/18/2016 10:38:03 AM Page 2 of 8
AHU-2 1 Indoor Air Handler 45 x 63 6320 FS - Supply Fan Segment Segment Details Fan Segment Options Segment Air Pressure Drop (in. w.g.): 0.00 2" Spring Isolator Air Flow per Fan (CFM): 6320 Osha Belt Guard Air Flow Total (CFM): 6320 Interior STD Ga. G-90 Galvanized Liner Altitude (ft.): 75 Insulation: R-13 2" Foam TSP/ESP (in. w.g.): 1.96/ 1.00 STD Ga. G-90 Galvanized Floor Liner Air Inlet: Bottom Exterior STD Ga. G-90 Galvanized Liner Fan Discharge: Top External Light Switch Access Door on Left Side(Left) 33H x 18W Multi-Point Door Latch, No Lock, Outward Opening Fan Detail Type: AF Size: 15-15 Construction: S Bearing Options: Extended Lube Fan RPM: 2065 BHP: 4.46 Fan BHP w/ Belt Loss: 4.77 Outlet Velocity (ft/min): 2761 Motor Detail (per motor) Motor Type: WEG ODP Premium Efficiency HP 7.5 Voltage/Phase/Frequency: 460/3/60 Hz Insulation Class: F Motor RPM: 1800 Frame Size: 213 Location: Left(Left) Drive Type: Belt Drive Type: Belt Drive Fixed Full Load Amps (FLA): 9.25 Efficiency: 91.0% Printed: 4/27/2016 10:33:29 AHU-2Performance Unit Folder: AHU2 4/18/2016 10:38:03 AM Page 3 of 8
AHU-2 1 Indoor Air Handler 45 x 63 6320 Coils & Spacers Listed Starting In Direction Of Air Flow VC Coil - 01 Coil General/Physical Details Air Side Performance Fluid Side Performance Location: Tag: 0 AirCoil Rows: Fins Per Inch: 6 8 Air Flow (acfm): Altitude (ft.): 6320 75 EWT ( F): LWT ( F): GPM: 45.0 55.0 29.7 Application: Cooling Tubes Per Circuit: 12 EAT-DB ( F): 73.0 WPD (ft): 11.4 Coil Type: Water Finned Height (in.): 35.00 EAT-WB ( F): 61.0 FPS: 3.7 Face Type: Full Finned Length (in.): 51 LAT-DB ( F): 54.4 Fluid Type: Wate Tube Diameter: 1/2" BDW Coil Face Area 12.4 LAT-WB ( F): 52.6 Fluid Weight(lb): r (ft²): Fluid 71.0 Tube Material: Copper Coil Conn. Loc.: Left(Left) FV (ft/min): 510 Volume(ft³): 1.1 Tube Wall Thickness:.016" Supp Conn Size: 2" SMBH: 127.2 Fouling Factor 0.00000 Rtn Conn Size: 2" TMBH: 149.0 (hft² F/btu): Fin Type: Corrugated # of Supply Conn. (per coil): 1 APD (in. w.g.): 0.41 Fin Thickness:.006" Fin Material: Aluminum Casing Material: Galvanized Connection Material: Steel* Connection Type: MPT Coating: None *Johnson Controls suggests using red brass or copper connectors when the coil is to be attached to a copper or brass piping system. Ratings are for coils manufactured by Johnson Controls, Inc., 507 E. Michigan St., Milwaukee WI 53202. BDW Tube Spacing: 1.25" x 1.08" AHRI Messages: This coil is certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the range of Standard rating conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Coil Dll Version: 7.3b.003 Static Pressure Summary Segment Component Supply (in. w.g.) Return Fan (in. w.g.) FF Flat Filter VC Vertical Coil 2" Pleated 30% (MERV 8) Dirty Filter Allowance Cooling 6 rows 8 fins Turning Air Pressure Drop 0.29 0.25 0.41 0.01 Printed: 4/27/2016 10:33:29 AHU-2Performance Unit Folder: AHU2 4/18/2016 10:38:03 AM Page 4 of 8
AHU-2 1 Indoor Air Handler 45 x 63 6320 FS-DWDI Supply Fan External Static Pressure - User Entered Pressure Drop 1.00 Total 1.96 0.00 Air handling unit parameters vary depending on conditions. Parameters such as airflows, air pressure drops, and coil capacities are shown for design conditions. Section FF Flat Filter Segment XA Variable Length Access Segment VC Vertical Coil Segment FS-DWDI Supply Fan Segment Dimension & Weights Summary Length* Width** (in.) 13 3 39 - (in.) 63 63 63 63 Height (in.) 45 45 45 39 Weight (lbs.) 278 25 1008 923 Overall: 55 63 84 2234 *The length includes bottom tier segments only. **The width does not include coil connection extensions or door latches that extent beyond the unit casing. The width does not include the depth of any pipe chases. Printed: 4/27/2016 10:33:29 AHU-2Performance Unit Folder: AHU2 4/18/2016 10:38:03 AM Page 5 of 8
Shipping Skid (VC XA FF FS-DWDI) SOLUTION XT AIR HANDLING UNIT AHU-2 1 Indoor Air Handler 45 x 63 6320 Shipping Skid Summary Length* Width** Height*** Weight (in.) (in.) (in.) (lbs.) 55 71 95 2234 Ship Loose: None *The length includes any mounted rain-hoods, discharge flanges, tie-down brackets, shipping wood-blocks, front dampers, split connectors, electrical/control components, outrigging extensions, isolation dampers, inlet baskets **The width includes any door handles, coil connections, drain connections, lifting lugs, mounted pipe-chases, electrical/control components, tie-down brackets, side dampers ***The height includes any base-rails, shipping wood-blocks, roof peak, discharge flanges, mounted gas-furnace flue pipes Shipping Skid Sequence Tier 2 Tier 1 FS) /\ VC < XA < FF) Printed: 4/27/2016 10:33:29 AHU-2Performance Unit Folder: AHU2 4/18/2016 10:38:03 AM Page 6 of 8
AHU-2 1 Indoor Air Handler 45 x 63 6320 Sound Summary Octave Band Sound Power Levels (db Re. 1 picowatt) 63 125 250 500 1000 2000 4000 8000 dba Ducted Discharge Top-1, FS 91 91 92 90 87 82 76 71 Return Air INLET, FF 86 83 83 84 79 74 67 60 Sound data tested in accordance with AHRI-260 (2001), Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. Notes: 1. The overall A-weighted sound power level is only applicable to sound radiation outdoors and casing radiated sound. This metric does not apply to ducted components 2. Return air sound powers are estimated using 100% of unit flow. Printed: 4/27/2016 10:33:29 AHU-2Performance Unit Folder: AHU2 4/18/2016 10:38:03 AM Page 7 of 8
AHU-2 1 Indoor Air Handler 45 x 63 6320 Recommended Trap Height Summary Applicable Fan TSP Positive or Calculated Dimensions Recommended Base Rail Segment Fan [in H 2 O] Negative H X H + X H H + X Height VC Supply Fan 1.96" Negative 2.96" 1.48" 4.44" 3.00" 4.50" 6" Notes: Formulas and calculations are recommendations only. Contractor shall determine actual dimensions required for each trap based on jobsite conditions, and application requirements. Refer to section 2 (Installation) of the IOM for more information. Printed: 4/27/2016 10:33:29 AHU-2Performance Unit Folder: AHU2 4/18/2016 10:38:03 AM Page 8 of 8
AHU-1 Gym 1 Indoor Air Handler 60 x 78 10350 Unit Sequence Tier 2 FS /\ Tier 1 VC <<< XA <<< FF Basic Unit Options Insulation Type: Base Rail Height: Performance: (Refer to Each Segment) 6" Formed Steel High Performance Statement of compliance of standard units. Solution XT AHU's meet IBC seismic requirements for non-critical equipment (Ip = 1.0) for locations with design spectral response Sds <= 0.43. Units must be rigid mounted. The anchorage of the unit to the ground or building structure needs to be evaluated by and is the responsibility of the engineer of record. Specification of seismic requirements is the responsibility of the project design engineer. If formal certification is required, please contact your sales representative and/or application engineer for review. Certain application and site requirements may require additional cost and/or lead time. Unit Special Quotes None *Note:Component locations are listed as Segment Hand (Unit Hand) : ex. Left (Right) See Submittal Drawing for additional details Printed: 4/27/2016 10:33:48 AHU-1 GymPerformance Unit Folder: AHUGYM 4/25/2016 9:48:08 AM Page 1 of 9
AHU-1 Gym 1 Indoor Air Handler 60 x 78 10350 Segments Listed Starting At Air Inlet FF Flat Filter Segment Filter Media Detail Filter Segment Options (Quantity)Filter Sizes: (4)24x24; (2)20x24 Interior STD Ga. G-90 Galvanized Liner Filter Loading: Side Insulation: R-13 2" Foam Filter Depth: 2" STD Ga. G-90 Galvanized Floor Liner Filter Media Type: Pleated 30% (MERV 8) Exterior STD Ga. G-90 Galvanized Liner Filter Area (ft²): 22.7 Galvanized Blankoff Material Filter Air Pressure Drop (in. w.g.): 0.23 Access Door on Left Side(Left) 54H x 10W Dirty Filter Allowance (in. w.g.): 0.25 Standard Door Latch, No Lock, Outward Opening Optimized Filter Arrangement Spare Filter Media: Spare Filter Quantity Set(s): Pleated 30% (MERV 8) 1 XA Access Segment Access Segment Details Access Segment Options Segment Length: 3 " Interior STD Ga. G-90 Galvanized Liner Insulation: R-13 2" Foam STD Ga. G-90 Galvanized Floor Liner Exterior STD Ga. G-90 Galvanized Liner Printed: 4/27/2016 10:33:48 AHU-1 GymPerformance Unit Folder: AHUGYM 4/25/2016 9:48:08 AM Page 2 of 9
AHU-1 Gym 1 Indoor Air Handler 60 x 78 10350 VC Vertical Coil Segment Coil Segment Details Coil Segment Options Coil Space: 10" Interior STD Ga. G-90 Galvanized Liner Insulation: R-13 2" Foam STD Ga. G-90 Galvanized Floor Liner Exterior STD Ga. G-90 Galvanized Liner 0" Downspout Coil Pull: None 19" IAQ Drain Pan Left (Left) Stainless Steel Access Doors on Both Sides 54H x 18W Standard Door Latch, No Lock, Outward Opening Bulkhead Material Galvanized Coil Supports Galvanized UV Surface Decontamination Detail None Printed: 4/27/2016 10:33:48 AHU-1 GymPerformance Unit Folder: AHUGYM 4/25/2016 9:48:08 AM Page 3 of 9
AHU-1 Gym 1 Indoor Air Handler 60 x 78 10350 FS - Supply Fan Segment Segment Details Fan Segment Options Segment Air Pressure Drop (in. w.g.): 0.00 2" Spring Isolator Air Flow per Fan (CFM): 10350 Osha Belt Guard Air Flow Total (CFM): 10350 Interior STD Ga. G-90 Galvanized Liner Altitude (ft.): 75 Insulation: R-13 2" Foam TSP/ESP (in. w.g.): 2.55/ 1.50 STD Ga. G-90 Galvanized Floor Liner Air Inlet: Bottom Exterior STD Ga. G-90 Galvanized Liner Fan Discharge: Top External Light Switch Access Door on Left Side(Left) 45H x 18W Multi-Point Door Latch, No Lock, Outward Opening Fan Detail Type: AF Size: 20-20 Construction: S Bearing Options: Extended Lube Fan RPM: 1592 BHP: 6.54 Fan BHP w/ Belt Loss: 6.90 Outlet Velocity (ft/min): 2185 Motor Detail (per motor) Motor Type: WEG ODP Premium Efficiency HP 10.0 Voltage/Phase/Frequency: 460/3/60 Hz Insulation Class: F Motor RPM: 1800 Frame Size: 215 Location: Left(Left) Drive Type: Belt Drive Type: Drive Options: Belt Drive Fixed Multiple Belt Full Load Amps (FLA): 12.40 Efficiency: 91.7% Printed: 4/27/2016 10:33:48 AHU-1 GymPerformance Unit Folder: AHUGYM 4/25/2016 9:48:08 AM Page 4 of 9
AHU-1 Gym 1 Indoor Air Handler 60 x 78 10350 Coils & Spacers Listed Starting In Direction Of Air Flow VC Coil - 01 Coil General/Physical Details Air Side Performance Fluid Side Performance Location: Tag: 0 AirCoil Rows: Fins Per Inch: 6 10 Air Flow (acfm): Altitude (ft.): 10350 75 EWT ( F): LWT ( F): GPM: 45.0 55.0 71.0 Application: Cooling Tubes Per Circuit: 8 EAT-DB ( F): 75.4 WPD (ft): 11.7 Coil Type: Water Finned Height (in.): 50.00 EAT-WB ( F): 63.6 FPS: 4.1 Face Type: Full Finned Length (in.): 66 LAT-DB ( F): 52.5 Fluid Type: Wate Tube Diameter: 1/2" BDW Coil Face Area 22.9 LAT-WB ( F): 51.5 Fluid Weight(lb): r (ft²): Fluid 140.0 Tube Material: Copper Coil Conn. Loc.: Left(Left) FV (ft/min): 452 Volume(ft³): 2.2 Tube Wall Thickness:.016" Supp Conn Size: 3" SMBH: 257.5 Fouling Factor 0.00000 Rtn Conn Size: 3" TMBH: 357.0 (hft² F/btu): Fin Type: Corrugated # of Supply Conn. (per coil): 1 APD (in. w.g.): 0.56 Fin Thickness:.008" Fin Material: Aluminum Casing Material: Galvanized Connection Material: Steel* Connection Type: MPT Coating: None *Johnson Controls suggests using red brass or copper connectors when the coil is to be attached to a copper or brass piping system. Ratings are for coils manufactured by Johnson Controls, Inc., 507 E. Michigan St., Milwaukee WI 53202. BDW Tube Spacing: 1.25" x 1.08" AHRI Messages: This coil is certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the range of Standard rating conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Coil Dll Version: 7.3b.002 Static Pressure Summary Segment Component Supply (in. w.g.) Return Fan (in. w.g.) FF Flat Filter VC Vertical Coil 2" Pleated 30% (MERV 8) Dirty Filter Allowance Cooling 6 rows 10 fins Turning Air Pressure Drop 0.23 0.25 0.56 0.01 Printed: 4/27/2016 10:33:48 AHU-1 GymPerformance Unit Folder: AHUGYM 4/25/2016 9:48:08 AM Page 5 of 9
AHU-1 Gym 1 Indoor Air Handler 60 x 78 10350 FS-DWDI Supply Fan External Static Pressure - User Entered Pressure Drop 1.50 Total 2.55 0.00 Air handling unit parameters vary depending on conditions. Parameters such as airflows, air pressure drops, and coil capacities are shown for design conditions. Section FF Flat Filter Segment XA Variable Length Access Segment VC Vertical Coil Segment FS-DWDI Supply Fan Segment Dimension & Weights Summary Length* Width** (in.) 13 3 46 - (in.) 78 78 78 78 Height (in.) 60 60 60 51 Weight (lbs.) 378 31 1567 1447 Overall: 62 78 111 3423 *The length includes bottom tier segments only. **The width does not include coil connection extensions or door latches that extent beyond the unit casing. The width does not include the depth of any pipe chases. Printed: 4/27/2016 10:33:48 AHU-1 GymPerformance Unit Folder: AHUGYM 4/25/2016 9:48:08 AM Page 6 of 9
AHU-1 Gym 1 Indoor Air Handler 60 x 78 10350 Shipping Skid (VC XA FF) (FS-DWDI) Shipping Skid Summary Length* Width** (in.) 62 57 (in.) 87 83 Height*** (in.) 70 56 Weight (lbs.) 1976 1447 Ship Loose: None *The length includes any mounted rain-hoods, discharge flanges, tie-down brackets, shipping wood-blocks, front dampers, split connectors, electrical/control components, outrigging extensions, isolation dampers, inlet baskets **The width includes any door handles, coil connections, drain connections, lifting lugs, mounted pipe-chases, electrical/control components, tie-down brackets, side dampers ***The height includes any base-rails, shipping wood-blocks, roof peak, discharge flanges, mounted gas-furnace flue pipes Shipping Skid Sequence Tier 2 Tier 1 (FS) /\ (VC < XA < FF) Printed: 4/27/2016 10:33:48 AHU-1 GymPerformance Unit Folder: AHUGYM 4/25/2016 9:48:08 AM Page 7 of 9
AHU-1 Gym 1 Indoor Air Handler 60 x 78 10350 Sound Summary Octave Band Sound Power Levels (db Re. 1 picowatt) 63 125 250 500 1000 2000 4000 8000 dba Ducted Discharge Top-1, FS 89 90 93 88 85 78 73 68 Return Air INLET, FF 84 79 83 79 75 71 65 59 Sound data tested in accordance with AHRI-260 (2001), Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment. Notes: 1. The overall A-weighted sound power level is only applicable to sound radiation outdoors and casing radiated sound. This metric does not apply to ducted components 2. Return air sound powers are estimated using 100% of unit flow. Printed: 4/27/2016 10:33:48 AHU-1 GymPerformance Unit Folder: AHUGYM 4/25/2016 9:48:08 AM Page 8 of 9
AHU-1 Gym 1 Indoor Air Handler 60 x 78 10350 Recommended Trap Height Summary Applicable Fan TSP Positive or Calculated Dimensions Recommended Base Rail Segment Fan [in H 2 O] Negative H X H + X H H + X Height VC Supply Fan 2.55" Negative 3.55" 1.77" 5.32" 3.75" 5.75" 6" Notes: Formulas and calculations are recommendations only. Contractor shall determine actual dimensions required for each trap based on jobsite conditions, and application requirements. Refer to section 2 (Installation) of the IOM for more information. Printed: 4/27/2016 10:33:48 AHU-1 GymPerformance Unit Folder: AHUGYM 4/25/2016 9:48:08 AM Page 9 of 9