A Review of a White Paper on Residential Fire Sprinklers

Similar documents
Reported Fires in High-Rise Structures in Selected Occupancies with and without Automatic Extinguishing Systems by Extent of Smoke Damage

NAHB Talking Points to Sprinkler Proponent Reports

Structure Fires in Hotels and Motels

SELECTIONS FROM HOME COOKING FIRE PATTERNS AND TRENDS CHARCOAL GRILLS

BENEFITS of RESIDENTIAL FIRE SPRINKLERS:

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617)

Home Fires Involving Heating Equipment

Heating Fires in Residential Buildings

Draft Document. A 15 Year Update on the Impact and Effectiveness of the Scottsdale Sprinkler Ordinance

STUDY ISSUE PAPER ON THE RESIDENTIAL SPRINKLER ORDINANCE

Circulation Report for SIG-TMS Comments Document # 72

Economic Impact of Building Regulations

Residential Fire Injury and Death Rates in British Columbia

Multiple-Fatality Fires in Residential Buildings

HOME FIRES THAT BEGAN WITH UPHOLSTERED FURNITURE

Fire Sprinklers Working Group Final Report

Water Purveyor s Guide to 2006 Fire Sprinklers in Single Family Dwellings

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

Household Appliance Replacement Program - Impact and Tradeoffs

Estimating the Level of Free Riders in the Refrigerator Buy-Back Program

Report on First Revision June 2014 NFPA 5000

Illinois Fire Safety Alliance

U.S. STRUCTURE FIRES IN OFFICE PROPERTIES

Home Fires Are Common, Deadly and Preventable

Estimating Fires When a Product is the Primary Fuel But Not the First Fuel, With an Application to Upholstered Furniture

Secretary of State determination under article 36 of the Fire Safety Order

January 14, Via Electronic Mail to NFPA

IN HARM S WAY: HOME HEATING, FIRE HAZARDS AND LOW-INCOME HOUSEHOLDS

Re: AHRI Comments on Proposed Addendum be to ASHRAE Standard 189.1

Code Technology Committee 2006/2007 Cycle Area of study Carbon monoxide alarms Public comments

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ENGINEER AND THE TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS.

U.S. Fire Department Profile 2015

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

The Benefits of Home Fire Sprinklers

Emerging Technology Program

Tampa, FL Fire Cause Classification Task Group Tue, 14 April 2011

Sprinkler Systems and Fire Outcomes in Multi-Level Residential Buildings

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Nightclub Fires in 2000


Fire Loss in the United States During 2015

Fire Cause Determination

VILLAGE OF DOWNERS GROVE Report for the Village Council Meeting

DECLARATORY STATEMENT. THIS CAUSE came on for consideration upon the Petition for Declaratory

Smoke Alarms in U.S. Home Fires

What are the Concerns and How Can we Mitigate

The Role of Home Fire Sprinklers in CRR

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL

research highlight Canadian Housing Fire Statistics Findings

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

fjen Li^(^zi TENNESSEE MARCH 25, 1975 THE FEDERAL ROLE IN FIRE PREVENTION AND CONTROL CONTROL ADMINISTRATION U.S. DEPARTMENT OF COMMERCE

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Canadian Wood Council Fire and Safety Risks Posed by Wood Frame Residential Construction Professor / Fire Chief Len Garis July 15, 2015

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS

FIRE LOSS IN THE UNITED STATES DURING 2012

Electrical Fires in Finland

Narrative Reports As Regulated by 780 CMR, Section 903.0

Fire Outcomes by General Construction Type A Retrospective Analysis of British Columbia Reported Fires

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES

Residential Structure Match or Lighter Ignited Fires

WABO Residential Sprinkler Survey March 15, 2012

BNWAT28: Water consumption in new and existing homes

WHY BUY NEW: AVOID THE MONEY PIT THE COST OF UPGRADING OLD TO NEW

Fires How you can help prevent fires in homes or apartment buildings, with just a few easy methods.

Measure Lifetime Derived from a Field Study of Age at Replacement

Sustainable South Warrington s Thoughts on the Preferred Development Option put forward by Warrington Borough Council

General Principles of Smoke Control

Review of U.S. state-level laws in requiring carbon monoxide alarms in residential settings

Prevention Mini-Summit January 13, 2007 Washington, D.C.

HOME FIRE SPRINKLER SYSTEMS. the future of fire safety here today

Fire Test Requirements for Upholstered Furniture Used in Public Buildings

CHARACTERISTICS OF HOME FIRE VICTIMS

Issues Shaping the Outlook for the Remodeling Industry

National Radon Results: 1985 to 1999 Brian Gregory 1 Philip P. Jalbert, U.S. EPA

SCHULTE & ASSOCIATES Building Code Consultants 3500 Creighton Road, K5 Pensacola, FL

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

2016 California Building Code Adoption OC amendments Summary Title/Subject Justification/Comments Action

CALIFORNIA OFFICE OF THE STATE FIRE MARSHAL

SCHULTE & ASSOCIATES Building Code Consultants 3500 Creighton Road, K5 Pensacola, FL

Dangerous Assumptions

Smoke Alarms. Rev. A Copyright 2011 James D Peisker

Green goes mainstream! Does the evidence support it?

WHITE PAPER: THE IMPORTANCE OF ARC FAULT CIRCUIT INTERRUPTER TECHNOLOGY

The Benefits of Home Fire Sprinklers IN ONE- AND TWO-FAMILY HOMES

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STRUCTURE FIRES IN EDUCATIONAL PROPERTIES

Introduction. Perry Osberg Doug Corbett Adam Parker. President General Manager. Director Business Development. Director Technical Development

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

BEST VALUE PERFORMANCE INDICATORS CONSULTATION: INSURERS VIEWS ON ITS IMPLICATIONS A RESPONSE BY THE ASSOCIATION OF BRITISH INSURERS

INTERNATIONAL ASSOCIATION OF FIRE FIGHTERS

HOME FIRE SPRINKLER SYSTEMS. fire safety. the future of. here today

NFPA Talking Points on NFPA 1 Fire Code update to the 2015 Edition:

Performance of Smoke Detectors and Sprinklers in Residential and Health-Care Occupancies

First Revision No. 88-NFPA [ Section No. 2.4 ] Submitter Information Verification. Committee Statement. 3 of /21/2013 1:03 PM

Performance Metrics for First Responder Locating/Tracking Technologies

Structure Fires in Residential Board and Care Facilities

Transcription:

Advocacy Group A Review of a White Paper on Residential Fire Sprinklers The Advocacy Group has reviewed the white paper entitled Residential Fire Sprinklers For Life Safety by the National Fire Sprinkler Association. Following this page is the review of this paper by our Construction Codes & Standards Area and by our Housing & Finance Policy Area. The first section entitled Content Review addresses several discrepancies in the research used, as well as, a misrepresentation of information cited from several of the referenced sources. The second section entitled Economic Review addresses the poor economic analysis of the paper and presents a cost benefit analysis for sprinkler systems. Should you need further assistance with the review of this paper or on this issue in general, please do not hesitate to contact Steven Orlowski at 1-800-368-5242 X8303. Thank you.

Section 1 Content Review Overall, we believe the report misrepresents statistics/reports, information on other occupancies, and insurance costs because the data is being used to draw significant assumptions or conclusion about cost impacts and reductions in death and property damage realized by sprinkler use, yet the data is lacking in depth and scope. We found the paper to be extremely biased and inappropriate to support any mandatory requirements for the installation of fire sprinklers in one, two, and three-family residential construction. In their paper, the National Fire Sprinkler Association makes two primary arguments that we believe to be inaccurate. They are: 1) The economic effect of the increase in costs is supposedly minimal. 2) The estimated 82% reduction in fire deaths should fire sprinklers be installed in residential occupancies based on a NIST technical report. Increase in Construction Cost The first bullet in the Executive Summary states that there is only a 1% increase in construction cost due to installation of sprinklers. The NFSA estimate is based on several surveys they have conducted in different regions of the U.S. finding the range of added cost of sprinkler installation to be: $80 - $1.25 per square foot (NFSA of Patterson, New York); $.98 a square foot (Barrington, IL); $1.35 per square foot (NFSA of Chicago, IL Tinley Park); and, $1.38 a square foot (NFSA of Chicago, IL Tinley Park). Benchmarking those figures against the 10-year Scottsdale study, NAHB s 1987 Residential Fire Survey, as well as, the referenced NIST Technical Notes, the noted installation costs are within an accurate range. However, based on current NAHB Economic Group data estimating average residential construction costs at $72 per square foot, the cost increase is a minimum of 1.5% and realistically could be much higher based on more conservative installation costs. Regardless of the disputed cost increase figures, the paper fails to recognize the significant impact that even a 1% or less increase construction costs has on housing affordability.

NIST Report The paper references NBS (NIST) Technical Note 1203 (1984), A Benefit-Cost Model of Residential Fire Sprinkler Systems. The technical note provides valuable information, but is not conclusive. The technical note states that cost effectiveness of sprinklers relies on certain conditions including: The use of approved plastic pipe (i.e. NFPA 13D) Use in high risk situations, sprinklers may be uneconomical under low-to-average conditions of risk The whole community using sprinklers assuming they will be able to receive certain cost reduction or avoidance by the local government or home builder Communities which will not have additional typical water standby fees or not considered taxable similar to commercial uses And where this additional protection is needed when occupants are incapacitated and cannot respond to a smoke alarm. While Table 7 of the technical note Estimated Percentage Reductions in Fire Deaths and Injuries Attributable to Residential Sprinkler Systems shows a potential 63% reduction in deaths, the NFSA paper states that a potential 82% reduction could be realized, a 19% jump that we can find no substantiation. Furthermore, even with the inclusion of Table 7 in the NIST technical note, nowhere in the note s conclusion is there an indication of how many deaths would be prevented by the use of this type of a sprinkler system, and the 63% the table notes is also subjective. Regarding the cost effectiveness of sprinklers, there are clearly a few instances in which they could be considered cost effective, but in most low to average risk situations, we believe existing data, if viewed appropriately, continues to support our position that they are currently not cost-effective in most single family housing applications. Finally, the NFSA paper was not intended as a technical note on the impact sprinklers could have in reducing residential fire deaths and therefore simply should not address the issue to the extent it has. The NFSA paper s own conclusion states, The model in its present form is not appropriate as a decision tool for the homeowner and that, Data is needed to support applications of the models to a variety of real-life situations.

Additional Comments: An International Perspective, USFA The NFSA paper also references the United States Fire Administration (USFA (FEMA)) study, An International Perspective. The paper notes that the U.S. has shown remarkable improvement in reducing residential fire deaths, as have most other industrialized nations. However, the paper fails to note that the referenced study clearly shows the U.S. figures represent by far, the largest absolute and relative reduction in fire death rates of all the countries shown. While there is no adequate discussion of the reasons for the drop, the NFSA paper implies that based on the expenditures of other industrialized countries, the U.S. needs to focus more on fire prevention education initiatives, an implication which the paper uses to further support the need for fire sprinklers. This study clearly shows to us that fire prevention education, not fire suppression, is the means by which other industrialized countries have been able to maintain lower fire death rates, counter implications made in the NFSA paper. Failure of Smoke Detectors The perspective references two reports concerning the performance of smoke detectors: The Smoke Detector Operability Survey (CPSC) and Fire in the United States 1985-1994 (USFA). The CPSC report shows that the performance of smoke detectors or lack of performance is mostly due to disconnected or failed power sources, primarily because of occupants experiencing problems with the alarms going off as a result of normal occupant activities such as, cooking. In some cases however, the report indicates that there is a failure of the detector even when connected to a functioning power source. The report also states that further study is needed to show what other factors were involved in these instances. What the perspective fails to point out is that smoke detector technology and smoke detector requirements have improved dramatically since these reports were completed. Current location requirements in the building codes have increased, the use of hard-wired, battery backed-up detectors eliminates many of the power supply problems. Additionally, the report fails to note the flaws in sprinkler technology such as those demonstrated by the recent recalls. Specifically, there have been three (3) major recalls: The 1998 10 million recall of Omega fire sprinklers, The 1999 1 million recall of Star sprinklers, The 2001 30 million recall of Central sprinklers.

Insurance Regarding the report s statements about the reduction of residential insurance costs when sprinklers are installed, they are assumptions based on commercial applications. The only example of residential insurance cost reduction is based on one personal experience. Content Conclusion Residential Fire Sprinklers for Life Safety - An Economic and Insurance Perspective draws conclusions and makes statements that are unfounded. Much of the data the report cites is not accurate. Several written sections are irrelevant to fire sprinklers (i.e. The International Perspective). Finally, the conclusion is mostly opinion.

Section 2 Economic Review The Paper Residential Fire Sprinklers for Life Safety: An Economic and Insurance Perspective is essentially void of economic analysis. It relies on anecdotal evidence, old data, a failure to grasp the concept of present value and elasticity, a poor understanding of the speculative housing market, and a total lack of any cost benefit analysis. This paper can best be described as an opinion piece. Examples of Poor Analytical work To show what the potential benefit of installing sprinklers in residential dwellings may be, the author reports the 10-year average of all fire deaths from 1985-1994, despite a substantial and steady decline in the annual number of fire deaths during that period, and since. By doing this, the benefit of installing sprinklers is made bigger than it really is. Elsewhere, the author writes that because the price elasticity of housing is less than one the installation cost of the fire sprinkler system, will have a negligible impact, if even measurable, on sale of the new home, condominium, or townhouse. A price elasticity of less than one suggests nothing of the sort. A $2000 rise in the price of a home--the cost of installing sprinklers--will price out hundreds of thousands of households nationally. Collectively, these two errors alone render the conclusions extremely suspect. Throughout the paper the perspective ignores the fact that existing housing, to the extent that it is a substitute for new safer housing with sprinklers will rise in price, if sprinklers become required equipment in all new houses, making much of the existing stock less affordable. The author also states that it is the uncertainty of the future housing market that is the foundation of the developer s resistance to adding fire sprinklers, not the fear that a simple 1% added cost will chase away potential buyers. This statement suggests a poor understanding of the speculative housing market. The author also fails to present any sort of cost-benefit analysis to support his claim as to the value of sprinklers. In addition to the problems already highlighted, there are many other errors, oversights, and omissions that further weaken the central claim of the paper. Major Oversight The most recent issue of Fire in the United States: 1987-1996, published by the National Fire Data Center, which is part of the United States Fire Administration which is in the Federal Emergency Management Agency, mentions several times that existing data do not support the notion that the installation of sprinklers in non-residential properties offers significant protection against fire. They conclude their surprising findings with a call for additional analysis as to the effectiveness of sprinklers where they are installed. Furthermore since sprinklers are found in so few residential properties (2 %) no conclusions can currently be drawn as to their effectiveness.

Cost-Benefit Analysis In an effort to better understand this issue, a simple cost-benefit analysis is performed. All data came from the National Fire Protection Association and is from 1999 or the most recent year for which data is available. Rough estimates of the costs and benefits of installing sprinklers can be constructed using broad parameters. To estimate the number of fires and deaths in new homes, we must divide the number of residential fires and deaths between new and existing homes. Importantly, residential fire fatalities are much less likely to occur in newer homes than older ones. Based on data from the California Building Industry Association, the average fatality rate occurring in homes built after 1981 is eight times lower than for units of average age. Since no data is available concerning property damage we use the proportion of new homes to all homes as an approximation. As a result, our conclusions may overstate the benefits but not the costs. Please note that the term residential includes one and two-unit dwellings, apartment buildings, manufactured housing, hotels, motels, rooming houses, and dormitories. DATA: Number of residential structures in the USA as of 2000: 116,000,000 New residential structures built in 2000: 1,500,000 New residential structures/all residential structures in USA in 2000: 1.3% New home fatality rate/ average age home fatality rate: 1/8 Estimated cost of installing a residential sprinkler system according to the paper: $2,000 Estimate of percentage of residential lives saved if sprinklers were installed in all residential dwellings according to N.I.S.T: 63%--not 82% as reported in the paper. Residential civilian fire related deaths in 1999: 2,920 BENEFIT: (1.3% of homes are new) X (new home/average age home fatality rate of 1/8) X (63% of all residential deaths can be prevented) X (2,920 residential deaths) = 3 lives saved annually. However, sprinkler systems last a long time. Suppose they last 40 years before being totally replaced. Over their lifetime these sprinklers could save (3 people) X (40 years) = 120 persons. COST: (1,500,000 houses) X ($2,000/house) = $3,000,000,000 COST/BENEFIT = $3,000,000,000/120 = $25,000,000/life To install sprinklers we must value each life saved at $25,000,000 or greater. If we present value the lives saved in the future, the benefits would be reduced, making this intervention less advantageous.

This perspective did not examine any issues beyond this point. However, let us extend the analysis to include residential property loss. Residential fire related property damage in 1999: $5,092,000,000 ADDED BENEFIT (1.3% of fires occur in new homes) X (63% of all residential damage can be prevented) X ($5.092 billion of annual residential fire damage) = $41,703,000 in annual property savings. The present value of this 40-year stream is about $1 billion. OVERALL RESULT $3 billion in current residential sprinkler expenditures would save $1 billion in property damage and 120 lives. The value of each life saved is implicitly valued at ($2,000,000,000/120 lives) = $16,666,667/life. This analysis could be extended to cover civilian injuries, and fire fighter deaths and injuries. However, those totals are not that large. Two costs that are ignored in this analysis are the inability of many poorer households to buy any type of home, and that many buyers will necessarily purchase smaller houses than they would like to as a result of the price increases experienced by existing houses. These losses are likely to be very large, as they may be expected to conservatively impact hundreds of thousands of households per year.