Enfinity Vertical Water Source Heat Pumps

Similar documents
McQuay Enfinity Horizontal Water Source Heat Pumps R-410A Refrigerant

Console Water Source Heat Pumps

Enfinity Large Vertical Water Source Heat Pumps with R-410A Refrigerant

Console Water Source Heat Pumps

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

Enfinity Large Horizontal Water Source Heat Pumps with R-410A Refrigerant

McQuay Enfinity (R-410A) and Standard (R-22) Horizontal Water Source Heat Pumps

Vertical Water Source Heat Pump & Cooling Only Units

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps

Installation and Maintenance Manual OM

Catalog Enfinity Large Horizontal Water Source Heat Pumps with R-410A Refrigerant

Engineered for flexibility and performance

Enfinity Horizontal Ceiling Catalog Water Source Heat Pumps

Vertical Stack Water Source Heat Pumps

Catalog McQuay Enfinity Horizontal & Vertical Water Source Heat Pumps

McQuay Horizontal Water Source Heat Pump 1/2 to 6 Ton

McQuay Enfinity TM. Horizontal & Vertical Water Source Heat Pump 1/2 to 5 Ton. Catalog

Enfinity Vertical Water Source Heat Pumps Catalog

Enfinity Console Water Source Heat Pumps 1/2 to 1½ Ton

Large Horizontal Water Source Heat Pump Units Size 070, 090, 120 Model CDD, CDE, CDL, CDS, CME, CMG, CMS

SmartSource Single Stage Horizontal & Vertical Water Source Heat Pumps

Vertical Water Source Heat Pump And Cooling Only Unit

LCU Series. Large Commercial Series Water Source Heat Pumps. Installation, Operation & Maintenance Instructions

McQuay. Vertical Water Source Heat Pump. FCV, FCG, FCW 036, 042 Vintage A. Last Manufactured: 1993

Catalog SmartSource Compact Vertical Water Source Heat Pumps. Model GCV - Vertical Unit Sizes (1/2 thru 6 tons)

McQuay. Ceiling Concealed Horizontal Water Source Heat Pump. CCH, CCG, CCW 048, 060 Vintage A. Last Manufactured: 1995

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Installation and Maintenance Manual IM

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

McQuay. Enfinity Vertical Water Source Heat Pump. WFCV, WFCW Design 1. Replacement Parts List No Revision D 03/2018

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

Digital Precise Air Control - DPAC

BasicTroubleshooting Information and Guidelines

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80

Installation and Maintenance Manual IM

Catalog SmartSource Two-Stage Horizontal & Vertical Water Source Heat Pumps

AAF. Water Source Heat Pump Ceiling Mounted. CCW Vintage E. Last Manufactured: Replacement Parts List No Revision D 08/2016

DXair Pool Dehumidifiers

Installation and Maintenance Manual IM

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

T-Series Air Conditioner T15 Model

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

G Series. G Series 7-25 Tons Installation Manual. Water Source/Geothermal Heat Pump Commercial 7-25 Tons. Installation Information

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

Model 1750A/ 1770A Dehumidifier Installation Instructions

Your safety and the safety of others are very important.

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

*20D082-05NN* 20D082-05NN

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Emerson Blue Easy Set 1H/1C

SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS

McQuay. Large Vertical Water Source Heat Pump. LGP, LHP, LWP Vintage C. Last Manufactured: 1994

Rev B, 9/2/2009. Kodiak Chiller Overview

CXM/DXM. Application, Operation & Maintenance Instructions 97B0003N08 Revision: 01/10/05. CXM/DXM Digital Heat Pump Controllers.

CAUTION WARNING INSTALLATION INSTRUCTIONS FOR HEALTHY CLIMATE WHOLE HOME DEHUMIDIFIER MODEL HCWH-065 (Y3013) DEHUMIDIFIERS

INSTALLATION MB SERIES MANUAL TABLE OF CONTENTS MB SERIES ( INSTALLATION ) UNIT DESCRIPTION. FHP MB series are available in two models: VH CABINET:

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents

McQuay. Concealed Ceiling Water Source Heat Pump. WCAE, WCAS, WCDA, WCDL, WCDS, WCMS 024, 030 Design A (1)

Direct Drive Fluid Coolers

Installation and Maintenance Manual IM 1102

UNIT DIGITAL CONTROLS APPLICATION, OPERATION & MAINTENANCE

INSTALLATION INSTRUCTION

Daikin McQuay. Enfinity Console Water Source Heat Pump. WMHC, WMHW 007, 009, 012 Design 1. Replacement Parts List No Revision M 11/2017

I/O ZONE 560/583 USERS GUIDE

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

Reinventing Energy Efficiency

WaterFurnace FX10 Application Guide Reversible Chiller

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Installation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015

Table of Contents. Commercial Horizontal & Vertical Packaged Water-Source Heat Pumps

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Owner's Manual TABLE OF CONTENTS

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

KR Series Air Defrost Unit Coolers Operating and Installation Manual

Installation and Maintenance Manual IM

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER

Mammoth Water Source Heat Pumps

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

This manual should be maintained in legible condition and kept adjacent to the heat pump or in a safe place for future use.

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

Installation Instructions

Daikin McQuay. Enfinity Console Water Source Heat Pump. WMHC, WMHW 015, 018 Design 1. Replacement Parts List No Revision O 11/2017

Greensource Residential Water Source Heat Pumps. Simply Smart. i Series: SV Model. boschheatingandcooling.com

Liebert Xtreme Density Chiller (XDC) Unit Warranty Inspection Check Sheet

ThinLine 3G Vertical Unit Heaters

WIRING DIAGRAM. This manual describes the unit features and explains how to set-up, operate and maintain these AirPac Models. COOLIT2600 COOLIT2900

WineZone Ceiling Mount Ductless Split 15

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

USERS INFORMATION MANUAL

Transcription:

Installation & Maintenance Data IM 930-3 Group: WSHP Part Number: 668996503 Date: November 2011 Enfinity Vertical Water Source Heat Pumps Model VFC Standard Range & VFW Geothermal Unit Sizes 007 070 / R-410A Refrigerant 2011 McQuay International

Contents Receiving and Storage...3 Pre-Installation...3 Locating The Unit...4 Unit Installation...5 Ductwork and Attenuation...5 Discharge Ducting...5 Return Air Ducting...5 Ventilation Air...6 Cleaning & Flushing Water System...6 Operating Limits...7 Piping...8 Electrical Connections...9 MicroTech III Unit Controller...12 Remote Reset Feature...12 I/O Expansion Module...13 Features...14 MicroTech III Controller With LonWorks Communication Module...14 MicroTech III Controller with BACnet Communication Module...15 Changing PSC Fan Motor Speed...17 Start-up...18 Typical Wiring Diagrams...19-23 MicroTech III Unit Controller (Standalone) 208/230/460/575/60Hz/3-Phase...19 MicroTech III Unit Controller with Optional ECM Motor, Desuperheater and I/O Expansion Module...20 208/230/265/277/60 Hz/1-Phase...20 MicroTech III Unit Controller with Optional ECM Motor, Desuperheater, Electric Heat Coil & I/O Expansion Module 208/230/460/60 Hz/3-Phase...21 MicroTech III Unit Controller with Optional ECM Motor, Desuperheater, and I/O Expansion Module 208/230/460/60/3-Phase...22 MicroTech III Unit Controller with PSC Motor, Desuperheater and I/O Expansion Module for Hot Gas Reheat Control (Unit Sizes 019-070) 208/230/60/1-Phase...23 Thermostat Connections...24 Non-Programmable Electronic Thermostat (P/N 668375401)...24 Optional Remote Sensor (P/N 66720401)...24 MicroTech III Wall-Mounted Room Temperature Sensors (Kit P/N 669529101, 669529201, 669529001)...24 Wiring Sensors to the MicroTech III Unit Controller...25 Additional Accessories General...25 Pump Restart Relay Kit P/N 061419001...26 Multiple Unit Control (up to 3 units) (P/N 056794201)...26 Hot Gas/Water Reheat Dehumidification (Option) (Unit Sizes 019 070)...26 Desuperheater (Option) For VFC/VFW (019-070)...27 Troubleshooting...28 The in and outs of R-410A...28 Lubrication...28 Charging...28 General Maintenance...28 Troubleshooting Refrigeration Circuit...29 Troubleshooting the Water Source Heat Pump Unit...30 Troubleshooting the MicroTech III...31 Unit Controller...31 Model Nomenclature Vertical Floor Unit (Size *007-070) NOTE: For illustration purposes only. Not all options available with all models. Please consult McQuay Sales Representative for specific availability. W VFC 1 009 B E Y L T Product Category W = WSHP Product Identifier VFC = Floor Mounted/Standard Range VFW = Floor Mounted/Geothermal Design Series 1 = A Design 2 = B Design 3 = C Design 4 = D Design Nominal Capacity *007 = 7,000 BTU/h 009 = 9,000 BTU/h 012 = 12,000 BTU/h 015 = 15,000 BTU/h 019 = 19,000 BTU/h 024 = 24,000 BTU/h 030 = 30,000 BTU/h 036 = 36,000 BTU/h 042 = 42,000 BTU/h 048 = 48,000 BTU/h 060 = 60,000 BTU/h 070 = 70,000 BTU/h Controls B = MicroTech III Unit Controller C = MicroTech III Unit Controller w/lonworks Communication Module D = MicroTech III Unit Controller w/bacnet Communication Module *Unit size 007 not available at time of publication. Please consult your local McQuay Representative for specific availability. Discharge Air T = Top Return Air L = Left R = Right Future (None) Voltage A = 115/60/1 E = 208-230/60/1 F = 208-230/60/3 J = 277-265/60/1 K = 460/60/3 L = 575/60/3 Page 2 of 32 / IM 930-3

Receiving and Storage CAUTION Sharp edges can cause personal injury. Avoid contact with them. Use care and wear protective clothing, safety glasses and gloves when handling parts and servicing heat pumps. Upon receipt of the equipment, check carton for visible damage. Make a notation on the shipper s delivery ticket before signing. If there is any evidence of rough handling, immediately open the cartons to check for concealed damage. If any damage is found, notify the carrier within 48 hours to establish your claim and request their inspection and a report. The Warranty Claims Department should then be contacted. Do not stand or transport the machines on end. For storing, each carton is marked with up arrows. In the event that elevator transfer makes up-ended positioning unavoidable, do not operate the machine until it has been in the normal upright position for at least 24 hours. Temporary storage at the job site must be indoor, completely sheltered from rain, snow, etc. High or low temperatures naturally associated with weather patterns will not harm the units. Excessively high temperatures, 140 F (60 C) and higher, may deteriorate certain plastic materials and cause permanent damage. IMPORTANT This product was carefully packed and thoroughly inspected before leaving the factory. Responsibility for its safe delivery was assumed by the carrier upon acceptance of the shipment. Claims for loss or damage sustained in transit must therefore be made upon the carrier as follows: VISIBLE LOSS OR DAMAGE Any external evidence of loss or damage must be noted on the freight bill or carrier s receipt, and signed by the carrier s agent. Failure to adequately describe such external evidence of loss or damage may result in the carrier s refusal to honor a damage claim. The form required to file such a claim will be supplied by the carrier. CONCEALED LOSS OR DAMAGE Concealed loss or damage means loss or damage which does not become apparent until the product has been unpacked. The contents may be damaged in transit due to rough handling even though the carton may not show external damages. When the damage is discovered upon unpacking, make a written request for inspection by the carrier s agent within fifteen (15) days of the delivery date and file a claim with the carrier. Pre-Installation WARNING WARNING The installer must determine and follow all applicable codes and regulations. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can result in property damage, severe personal injury or death. This equipment must be installed by experienced, trained personnel only. 1. To prevent damage, do not operate this equipment for supplementary heating and cooling during the construction period. 2. Inspect the carton for any specific tagging numbers indicated by the factory per a request from the installing contractor. At this time the voltage, phase and capacity should be checked against the plans. 3. Check the unit size against the plans to verify that the unit is being installed in the correct location. 4. Before installation, check the available closet dimensions versus the dimensions of the unit. 5. Note the location and routing of water piping, condensate drain piping, and electrical wiring. The locations of these items are clearly marked on submittal drawings. 6. The installing contractor will find it beneficial to confer with piping, sheet metal, and electrical foremen before installing any unit. Note: Check the unit data plate for correct voltage with the plans before installing the equipment. Also, make sure all electrical ground connections are made in accordance with local code. 7. The contractor shall cover the units to protect the machines during finishing of the building. This is critical while spraying fireproofing material on bar joists, sandblasting, spray painting and plastering. 8. The overall opening of the doorway to mechanical room must be 2" wider than the unit for easy installation and/or removal. Table 1: Overall Unit Dimensions Unit Size Dimensions *007 012 22¼"D x 20"W x 37"H 015 024 24¼"D x 23"W x 46½"H 030 036 24¼"D x 23"W x 50½"H 042 048 32½"D x 25"W x 46½"H 060 070 32½"D x 25"W x 58½"H Notes: Dimensions are approximate. * Not available at time of publication. Please consult your McQuay Representative for specific availability. IM 930-3 / Page 3 of 32

Locating The Unit 1. Locate the unit in an area that allows for easy removal of the filter and access panels, and has enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connections. 2. Make sure that sufficient access has been provided for installing the unit, including clearance for duct collars and fittings at water and electrical connections. 3. Allow adequate room around the unit for a condensate piping. 4. The unit can be installed free standing in an equipment room. However, closet installations are more common for small vertical type units. Generally, the unit is located in the corner of a closet with the non-ducted return air facing 90 to the door and the major access panels facing the door as in Figure 1. Alternatively, the unit can have a ducted return air with the opening facing the door and the major access panels facing 90 to the door as in Figure 2. 5. Unit must be located on top of a vibration absorbing material such as a rubber (Isolation pad) that is the same size as the base of the unit, to minimize vibration and noise. See Figure 9 on page 8. Minimum distance requirement from return air duct collar to wall for non-ducted units. Model Distance 007 012...5 inches 015 024...5 inches 030 036...6 inches 042 048...8 inches 060 070...10 inches A - Condensate B - Desuperheater Water Return (Optional) C - Desuperheater Water Supply (Optional) D - Water Return E - Water Supply Figure 1: Typical closet installation with louver door return (non-ducted) Return Air Duct & Grille Figure 2: Typical closet installation with ducted return Heat Pump with Left-Hand Return Air Arrangement Risers A - Condensate B - Desuperheater Water Return (Optional) C - Desuperheater Water Supply (Optional) D - Water Return E - Water Supply F - Low Voltage Control Wiring (Electric Entrance) G - Line Voltage Unit Power (Electric Entrance) Figure 3: Unit Electrical and Piping Locations Control Access Panel Heat Pump with Right-Hand Return Air Arrangement Return Air Duct & Grille Left-Hand Return Air Arrangement Return Air Right-Hand Return Air Arrangement Return Air Return Air Thru Louvered Door Return Air Thru Louvered Door Risers Page 4 of 32 / IM 930-3

Unit Installation Ductwork and Attenuation Discharge ductwork is normally used with these units. Where return air ductwork is required, the unit is supplied with a 1" filter rack/duct collar for connection of return air ductwork. An optional 2" return air duct collar filter rack is available as a field-installed accessory or a factory-installed, selectable option. The 2" filter rack allows tool less entry for easy filter replacement. Figure 4: Sizes 007 thru 070 Optional 2" Return Air Duct Collar Filter Rack Discharge Ducting All ductwork should conform to industry standards of good practice as described in ASHRAE Systems Guide. A field supplied discharge duct system will normally consist of a flexible connector at the unit, a non-insulated transition piece to the full duct size, a short run of duct, an elbow without vanes, and a trunk duct teeing into a branch circuit with discharge diffusers as shown in Figure 5. Figure 5: Suggested Unit Ducting Square Elbow (Both Sides Internally Lined With Acoustic Insulation) Trunk Duct The transition piece must not have an angle greater than 30 or severe loss of air performance can result. Do not connect the full duct size to the unit without using a transition piece down to the size of the discharge collar on the unit. With metal duct material, the sides of the elbow and entire branch duct should be internally lined with acoustic insulation for sound attenuation. Glass fiber duct board material is more absorbing and may permit omission of the flexible connector. The ductwork should be laid out so that there is no line of sight between the unit discharge and the distribution diffusers. Return Air Ducting Return air ducts can be brought in through a wall grille and then to the unit. The return duct system will normally consist of a flexible connector at the unit and a trunk duct to the return air grille. With metal duct material, the return air duct should be internally lined with acoustic insulation for sound attenuation. Glass fiber duct board material is more absorbing and may permit omission of the flexible connector. Return air ductwork to the unit requires the 1" (25mm) standard return air duct collar or the optional 2" (51mm) filter rack kit (see Figure 4). The 2" filter rack kit allows for side filter removal. A flexible duct collar can then be attached between a duct transition and the return air ductwork. The return air duct transition must be the same size as the return air coil face area. Connections of supply and return air ductwork should be made at the duct collar of the unit. Do not puncture the unit cabinet with sheet metal screws as this can damage the drain pan or the coil. Figure 6: Suggested Return Air Unit Ducting Transition Duct Discharge Duct Flexible Duct Collar Flexible Duct Collar Branch Duct (Internally Lined) Duct Transition 2 ft. x 2 ft. Diffuser Flexible Duct Collar Discharge Collar Full Vibration Isolation Pad Heat Pump IM 930-3 / Page 5 of 32

Ventilation Air Outside air may be required for ventilation. The temperature of the ventilation air must be controlled so that mixture of outside air and return air entering the unit does not exceed application limits. It is also general practice to close off the ventilation air system during unoccupied periods (night setback). The ventilation air system is generally a separate building subsystem with distribution ductwork. To provide thorough mixing of the outside and return air, introduce the outside air in close proximity to the return air plenum inlet. Do not duct outside air directly to the unit inlet. See "Operating Limits" on page 7. CAUTION Prior to making piping connections, contractor must clean and flush water loop system. Failure to clean/flush system may result in nuisance tripping and premature component failure. Cleaning & Flushing Water System 1. Prior to first operation of any unit, the water circulating system must be cleaned and flushed of all construction dirt and debris. If the units are equipped with water shutoff valves, either electric or pressure operated, the supply and return runouts must be connected together at each unit location. This will prevent the introduction of dirt into the unit. See Figure 7. Figure 7: Connect the runouts together Flexible Hose Return Runout Supply Runout Mains Runouts Initially Connected Together 2. Fill the system at the city water makeup connection with all air vents open. After filling, close all air vents. The contractor should start main circulator with the pressure reducing valve open. Check vents in sequence to bleed off any trapped air, ensuring circulation through all components of the system. Power to the heat rejector unit should be off, and the supplementary heat control set at 80 F (27 C). While circulating water, the contractor should check and repair any leaks in the unit and surrounding piping. Drains at the lowest point(s) in the system should be opened for initial flush and blow-down, making sure city water fill valves are set to make up water at the same rate. Check the pressure gauge at pump suction and manually adjust the makeup to hold the same positive steady pressure both before and after opening the drain valves. Flush should continue for at least two hours or longer until the drain water is clean and clear. CAUTION Units must be checked for water leaks upon initial water system start-up. Water leaks may be a result of mishandling or damage during shipping. Failure by the installing contractor to check for leaks upon start-up of the water system could result in property damage. 3. Shut off supplemental heater and circulator pump and open all drains and vents to completely drain down the system. Short circuited supply and return runouts should now be connected to the unit supply and return connections. Do not use sealers at the swivel flare connections of hoses. 4. Flush system with water for 2 hours or longer until water is clean. 5. Refill the system with clean water. Test the water using litmus paper for acidity, and treat as required to leave the water slightly alkaline (ph 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Do not use automotive grade antifreeze. Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Note: Contact a local water treatment company to confirm water clarity prior to unit operation. Dirty water will result in system wide degradation of performance and solids may clog system-wide valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life or causes premature failure. 6. Set the loop water controller heat add setpoint to 70 F (21 C) and the heat rejection setpoint to 85 F (29 C). Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season) and the vented air and loop temperatures have been stabilized, each of the units will be ready for check, test and start-up, air balancing, and water balancing. Page 6 of 32 / IM 930-3

Operating Limits Environment This equipment is designed for indoor installation only. Sheltered locations such as attics, garages, etc., generally will not provide sufficient protection against extremes in temperature and/or humidity, and equipment performance, reliability, and service life may be adversely affected. Table 2: Air Limits Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating Min. Ambient Air 50 F/10 C 50 F/10 C 40 F/5 C 40 F/5 C Normal Ambient Air 80 F/27 C 70 F/21 C 80 F/27 C 70 F/21 C Max. Ambient Air 100 F/38 C 85 F/29 C 100 F/38 C 85 F/29 C Min. Entering. Air 50 F/10 C 50 F/10 C 50 F/10 C 40 F/5 C Normal Entering Air, 80 F/67 F 70 F 80 F/67 F 70 F db/wb 27/19 C 21 C 27/19 C 21 C Max. Entering Air 100/83 F 80 F 100/83 F 80 C db/wb 38/28 C 27 C 38/28 C 27 C Table 3: Water Limits Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating Min. Entering. Water 55 F/13 C 55 F/13 C 30 F/-1 C 20 F/-6 C Normal Entering. Water 85 F/29 C 70 F/21 C 77 F/25 C 40 F/5 C Max. Entering. Water 110 F/43 C 90 F/32 C 110 F/43 C 90 F/32 At ARI flow rate. Maximum and minimum values may not be combined. If one value is at maximum or minimum, the other two conditions may not exceed the normal condition for standard units. Extended range units may combine any two maximum or minimum conditions, but not more than two, with all other conditions being normal conditions. Table 4: Antifreeze Correction Factors Ethylene Glycol 10% 20% 30% 40% 50% Cooling Capacity 0.9950 0.9920 0.9870 0.9830 0.9790 Heating Capacity 0.9910 0.9820 0.9770 0.9690 0.9610 Pressure Drop 1.0700 1.1300 1.1800 1.2600 1.2800 Propylene Glycol 10% 20% 30% 40% 50% Cooling Capacity 0.9900 0.9800 0.9700 0.9600 0.9500 Heating Capacity 0.9870 0.9750 0.9620 0.9420 0.9300 Pressure Drop 1.0700 1.1500 1.2500 1.3700 1.4200 Methanol 10% 20% 30% 40% 50% Cooling Capacity 0.9980 0.9720 Heating Capacity 0.9950 0.9700 Pressure Drop 1.0230 1.0570 Ethanol 10% 20% 30% 40% 50% Cooling Capacity 0.9910 0.9510 Heating Capacity 0.9950 0.9600 Pressure Drop 1.0350 0.9600 IM 930-3 / Page 7 of 32

Piping 1. All units should be connected to supply and return piping in a two-pipe reverse return configuration. A reverse return system is inherently self-balancing and requires only trim balancing where multiple quantities of units with different flow and pressure drop characteristics exist in the same loop. Check for proper water balance by measuring differential temperature reading across the water connections. For proper water flow, the differential temperature should be 12 F to 14 F (5 C to 8 C) for units in cooling mode. A direct return system may also work, but proper water flow balancing is more difficult to achieve and maintain. 2. The piping can be steel, copper or PVC. Note: If using PVC (schedule-40) construction grade pipe or better, use the manufacturers recommended high temperature adhesive. With PVC piping the appropriate number of hanger brackets must be used to help prevent sagging. 3. Supply and return runouts usually join the unit via short lengths of high pressure flexible hose which are sound attenuators for both unit operating noise and hydraulic pumping noise. One end of the hose should have a swivel fitting to facilitate removal for service. Hard piping also can be brought directly to the unit. This option is not recommended since no vibration or noise attenuation can be accomplished. The hard piping must have unions to facilitate unit removal. See Figure 8, Figure 9, and Figure 10 for typical piping details. Figure 8: Typical Vertical Unit Piping 7. Condensate piping can be steel, copper or PVC. Each unit includes a condensate connection. 8. Units are internally trapped. 9. Do not locate any point in the drain system above the drain connection of any unit. 10. Automatic flow controlled devices must not be installed prior to system cleaning and flushing. 11. A high point of the piping system must be vented. 12. Check local code for the need for dielectric fittings. Note: Do not over-torque fittings. The maximum torque without damage to fittings is 30 foot pounds. If a torque wrench is not available, use as a rule of thumb, finger-tight plus one quarter turn. Figure 9: Typical Vertical Installation and Unit Piping 4. Some flexible hose threaded fittings are supplied with sealant compound. If not, apply Teflon tape for a tight seal. 5. Supply and return shutoff valves are required at each unit. The return valve is used for balancing and should have a memory stop so that it can always be closed off but can only be reopened to the proper position for the flow required. 6. Do not connect any unit to the supply and return piping until the water system has been cleaned and flushed completely. After the cleaning and flushing has taken place, the initial connection should have all valves wide open in preparation for water system flushing (see "Cleaning & Flushing Water System" on page 6). 1 - Supply Air Ducting 2 - Acoustical Thermal Lining (10 ft.) 3 - Line Voltage - 7/8" (22 mm) Hole 4 - Low Voltage - 7/8" (22 mm) Hole 5 - Flexible Duct Collar 6 - Louvered Door for Return Air 7 - Condensate Drain Connection 8 - Flexible Return Hose with Flow Controller/Ball Valve (3/4" FPT) 9 - Flexible Supply Hose with Y-Strainer/Ball Valve (3/4" FPT) 10 - Access Panel to Controller 11 - LED Annunciator Status Lights 12 - Vibration Isolation Pad Page 8 of 32 / IM 930-3

Electrical Connections Note: Installation and maintenance must be performed only by qualified personnel who are familiar with local codes and regulations, and are experienced with this type of equipment. WARNING Hazardous Voltage! The installer must determine and follow all applicable codes and regulations. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can result in property damage, severe personal injury or death. CAUTION Sharp edges can cause personal injury. Avoid contact with them. Figure 10: Unit Electrical and Piping Locations Control Access Panel A - Condensate B - Desuperheater Water Return (Optional) C - Desuperheater Water Supply (Optional) D - Water Return E - Water Supply F - Low Voltage Control Wiring (Electric Entrance) G - Line Voltage Unit Power (Electric Entrance) Operating Voltages 115/60/1...104 volts min.; 127 volts max. 208-230/60/1...197 volts min.; 253 volts max. 265/60/1.........238 volts min.; 292 volts max. 460/60/3.........414 volts min.; 506 volts max. 575/60/3.........515 volts min.; 632 volts max. General 1. Verify the compatibility between the voltage and phase of the available power and that shown on the unit data plate. Line and low voltage wiring must comply with local codes or the National Electrical Code, whichever applies. 2. Apply correct line voltage to the unit. A 7 8" (22mm) hole. A disconnect switch near the unit is required by code. Power to the unit must be sized correctly and have dual element (Class RK5) fuses or an HACR circuit breaker for branch circuit overcurrent protection. See the data plate for correct ratings. 3. Connect the thermostat/subbase wiring with the power off to the unit. 230 Volt Operation All 208-230 volt single-phase and three-phase units are factory wired for 208 volt operation. For 230 phase operation, the line voltage tap on the 24-volt transformer must be changed. Disconnect and cap the red lead wire and interchange it with the orange lead wire on the primary of the 24-volt transformer. Fan Assembly All fan motors are multi-speed PSC or optional ECM (sizes 019-070) type with integral mounting brackets and thermal overload protection. The motor is isolated from the fan housing for minimum vibration transmission. PSC Fan motors have a terminal strip on the motor body for simple motor speed change without going back to the control box. See "Changing PSC Fan Motor Speed" on page 17. All the fan/motor assemblies have a removable orifice ring on the housing to accommodate motor and fan wheel removal without disconnecting the ductwork. The fan housing protrudes through the cabinet allowing adequate material for connection of flexible duct. Each model unit is shipped from the factory for maximum performance and minimum sound requirements. Fan sound levels and performance can be affected by external static pressure. Note: Voltages listed are to show voltage range. However, units operating with over voltage and under voltage for extended periods of time will experience premature component failure. Three phase system unbalance should not exceed 2%. IM 930-3 / Page 9 of 32

Table 5: MicroTech III Unit Controller Terminals Locations and Descriptions H1-1 24 24 VAC Power Input H1-2 C 24 VAC Common H2-1 SL1 Fan Output - Switched L1 H2-2 Blank Terminal H2-3 N Fan Neutral H3-1 HP1-1 High Pressure Switch 1 Input Terminal 1 H3-2 HP1-2 High Pressure Switch 1 Input Terminal 2 H4-1 Discharge Air Temp Common H4-2 Discharge Air Temp Signal H4-3 Leaving Water Temp Common H4-4 Leaving Water Temp Signal H5-1 1 I/O Exp Module Common (Gnd) H5-2 I/O Exp Module Common (Gnd) H5-3 I/O Exp Module +5 VDC H5-4 I/O Exp Module SPI CE1 H5-5 I/O Exp Module SPI CLK H5-6 I/O Exp Module SPI OUT H5-7 I/O Exp Module SPI IN H5-8 I/O Exp Module +12 VDC H5-9 I/O Exp Module 24 VAC H5-10 I/O Exp Module 24 VAC H5-11 Spare H5-12 Spare H6-1 1 Condensate Overflow Signal Input H6-2 Low Temp 1 Sensor Common H6-3 Low Temp 1 Sensor Signal H6-4 Low Pressure Switch 1 Source Voltage H6-5 Low Pressure Switch 1 Signal H6-6 Reversing Valve 1 Common H6-7 Reversing Valve 1 Output H7-1 1 Dummy Terminal H7-2 Dummy Terminal H7-3 Red LED Output H7-4 Green LED Output H7-5 Yellow LED Output H7-6 Red-Green-Yellow LED Common H8-1 1 Isolation Valve/Pump Request Relay N/O H8-2 Isolation Valve/Pump Request Relay N/C H8-3 24 VAC Common H9-1 1 Return Air Temperature Signal H9-2 Return Air Temperature Common TB1-1 1 Room Sensor LED Output TB1-2 2 Fan Mode / Heat-Cool-Auto Input TB1-3 3 Setpoint Adjust Input TB1-4 4 Room Temperature Sensor / Tenant Override TB1-5 5 DC Signal Common Test-1 R 24 VAC Test-2 W2 Heat Stage 2 Input Test-3 W1 Heat Stage 1 Input Test-4 Y2 Cool Stage 2 Input Test-5 Y1 Cool Stage 1 Input Test-6 G Fan TB2-1 R 24 VAC TB2-2 A Alarm Output TB2-3 W2 Heat Stage 2 Input TB2-4 W1 Heat Stage 1 Input TB2-5 Y2 Cool Stage 2 Input TB2-6 Y1 Cool Stage 1 Input TB2-7 G Fan Input TB2-8 O Tenant Override Input TB2-9 C 24 VAC Common TB3-1 E Mark IV Emergency Shutdown Input TB3-2 U Mark IV Unoccupied/Occupied Input L1-1 L1-1 Line Voltage Terminal 1 L1-2 L1-2 Line Voltage Terminal 2 L1-3 L1-3 Line Voltage Terminal 3 N1 N1 Neutral Terminal 1 N2 N2 Neutral Terminal 2 N3 N3 Neutral Terminal 3 Table 6: Configuration Jumper Settings Jumper Description Options JP1 Mode Open for normal operation mode Shorted for service/test operation mode JP2 Fan operation only applies to Open for continuous fan operation network controls Shorted for cycling fan operation JP3 Freeze protection Open for water freeze protection Shorted for antifreeze protection JP4 Future spare Future spare JP5 Set point adjustment range only Open for adjustment range of -3.0 to +3.0 F applies to network controls with a Shorted for 50 to 90 F adjustment range room temperature sensor JP6 Room control type Open for thermostatic room control Shorted for room temperature sensor control, MicroTech III only JP7 Future spare Future spare JP8 Future spare Future spare Page 10 of 32 / IM 930-3

Note: A random start delay time between 180 and 240 seconds is generated at power up. Figure 12: Location of Configuration Jumpers on the MicroTech III Unit Controller Figure 11: MicroTech III Unit Controller Terminal Locations IM 930-3 / Page 11 of 32

MicroTech III Unit Controller The MicroTech III Unit Controller includes built-in features such as random start, compressor time delay, shutdown, condensate overflow protection, defrost cycle, brownout, and LED/fault outputs. Table 7 shows the LED and fault output sequences. The unit has been designed for operation with a microelectronic wall thermostat selected by the manufacturer. Do not operate the unit with any other type of wall thermostat. Each unit has a printed circuit board control system. The low voltage output from the low voltage terminal strip is AC voltage to the wall thermostat. R is A/C voltage output to the wall stat. The 24 volt low voltage terminal strip is set up so R-G energizes the fan, R-Y1 energizes the compressor for cooling operation, R-W1 energizes the compressor and reversing valve for heating operation. The reversing valve is energized in the heating mode. The circuit board has a fan interlock circuit to energize the fan whenever the compressor is on if the thermostat logic fails to do so. The output to the wall stat is AC current. Terminal (R) on the wall stat can be connected to terminal (R) on the PC board for AC voltage. R = AC current R to G = fan only R to Y1 = cooling R to W1 = heat The MicroTech III unit controller has a lockout circuit to stop compressor operation if any one of its safety switches opens (high pressure switch and low pressure switch on unit sizes 024 through 060). If the low temperature switch opens, the unit will go into the cooling mode for 60 seconds to defrost any slush in the water-to-refrigerant heat exchanger. After 60 seconds the compressor is locked out. If the condensate sensor detects a filled drain pan, the compressor operation will be suspended only in the cooling mode. The unit is reset by opening and closing the disconnect switch on the main power supply to the unit in the event the unit compressor operation has been suspended due to low temperature (freezestat) switch, high pressure switch, or low pressure switch on unit sizes 048 thru 060. The unit does not have to be reset on a condensate overflow detection. The MicroTech III unit controller fault output sends a signal to an LED on a wall thermostat. Table 7 shows for which functions the fault output is on (sending a signal to the LED). Table 7: MicroTech III unit controller LED & fault outputs Mode / Fault Status LED s Thermostat Alarm Light Yellow Green Red Output-Terminal A Occupied, Bypass, Standby, or Tenant Off On Off Energized Override Unoccupied On On Off Energized Condensate Overflow On Off Off De-engergized High Pressure 1 Fault Off Off Flash De-energized Low Pressure 1 Fault Off Off On De-energized Low Temperature 1 Fault Flash Off Off De-energized Brownout Off Flash Off De-energized Emergency Shutdown Off Flash Off De-energized Room/Return Air or Low Temp Sensor 1 Failure Flash Flash On De-engergized Service Test Mode Enabled 1 On On Off De-energized Serial EEPROM Corrupted On On On De-energized Network Offline Received Off Off Off De-enegized 1 Compressor relay/compressor terminal is labeled COMP, switched line of the same electric input as any of the L1 terminals. Remote Reset Feature The Remote Reset feature provides the means to remotely reset automatic lockouts generated by high-pressure and/ or low-temperature (in heating) faults. When the MicroTech III unit controller is in automatic lockout due to one of these faults, and the cause of the fault condition has been alleviated, energizing the O-terminal for 10 seconds or more will force the MicroTech III unit controller to clear the lockout. A unit power cycle can also be used to clear an automatic lockout if the conditions causing the fault have been alleviated. The Intelligent reset feature helps to minimize nuisance trips of automatic reset lockouts caused by high-pressure and/or low-temperature (in heating) faults. This feature clears faults the first two times they occur within a 24-hour period and triggers an automatic lockout on the 3rd fault. The retry count is reset to zero every 24 hours. The MicroTech III unit controller has built-in night setback operation. A grounded signal to the U terminal on TB3 of the unit control puts the unit into the unoccupied mode for night setback operation. Fan operation terminates and unit control will only respond to signal at the W2 terminal. Daytime heating and cooling operation is locked out. +24VAC to W2 energizes the compressor and reversing valve for heating operation. Night setback operation can be overridden for two hours by energizing the O on the TB2 terminal of the unit control for 3 seconds. Day thermostat setpoints then control the heating and cooling operation. The MicroTech III unit controller also accommodates shutdown operation on receipt of a grounded signal to the E input, respectively, on TB3 input terminal of the unit control. The IV/PR(H8) terminals of the MicroTech III unit controller are used for motorized valve / pump restart. This terminal passes a voltage signal whenever the unit compressor is turned on. This signal is detected by a pump restart relay providing a N.O. or N.C. set of contacts for heat pump loop circulation pump or motorized valve control. When used with a system control (by others), the relay operation accommodates turning off circulation pumps during unoccupied periods with Page 12 of 32 / IM 930-3

a safety override dependent, at minimum, on WSHP s need. The IV/PR(H8) terminals may be daisy chained between 200 units. I/O Expansion Module This manual covers the installation of a McQuay Vertical Floor Unit - Model VFC, VFW Water Source Heat Pump. For installation and operation information on MicroTech III unit controller and other ancillary components, see: IM 927 - MicroTech III Unit Controller for Water Source Heat Pumps (LONWORKS). The I/O Expansion Module is a field-installed option. It is an extension of the MicroTech III unit controller and provides extra functionality. The I/O Expansion Module has 4 main purposes: The MicroTech III unit controller in combination with the I/O Expansion Module will be the standard control system for two-stage Water Source Heat Pump equipment. (i.e. large vertical units). The I/O Expansion Module has outputs to control electric heat on a standard Water Source Heat Pump. The I/O Expansion Module has outputs for multi-speed fans on a standard Water Source Heat Pump. The I/O Expansion Module has an independent LED annunciator to identify operational fault conditions on second stage equipment. Adding an I/O Expansion Module (with an interconnect cable) to the main controller allows two-stage operation of the Water Source Heat Pump. Table 8: I/O Expansion Module LED & Fault Outputs Notes: 1 Boilerless electric heat only 2 Alarm/fault LED indications take precedence over service test mode LED indication. The controller shall use service test mode if the service test mode jumper is installed, even if the LED s indicate an alarm/fault. Table 9: I/O Expansion Module Configuration Jumper Settings Jumper Description Options JP1 Number of Open for single compressor Compressors Shorted for dual compressor JP2 Hot Gas/ Open to disable reheat Water Reheat Shorted to enable reheat JP3 and JP4 open for no supplemental heat JP3 Supplemental JP3 open, JP4 shorted for & JP4 Heat Type boilerless electric heat JP3 and JP4 shorted is an invalid setting JP5 and JP6 open for single-speed fan JP5 open, JP6 shorted for JP5 Fan Speed three-speed fan & JP6 Selection JP5 shorted and JP6 open for two-speed fan JP 5 and JP6 shorted is an invalid setting JP7 Compressor Open for single-speed compressor Speed Type Shorted for two-speed compressor JP8 Future Spare Figure 13: I/O Expansion Module Configuration Jumper Terminals Jumper Terminals Mode / Fault Status LED's Yellow Green Red Thermostat Alarm Light Output Terminal A Invalid Configuration Jumper Setting Flash Flash Off De-energized Base Board Communication Fail Off Flash Flash N/A High Pressure #2 Fault Off Off Flash De-energized Low Pressure #2 Fault Off Off On De-energized Low Suction Temp #2 Fault Flash Off Off De-energized Sensor Failures Low Suction Low Suction Temp #2, Flash Flash On De-energized 1 EWT (w/ Boilerless EH only) 2 Service Test Mode Enabled Flash Flash Flash De-energized Unoccupied Mode On On Off Energized Occupied, Bypass, Standby, or Tenant Off On Off Energized Override Modes Note: Mode / Faults are listed in order of priority. IM 930-3 / Page 13 of 32

Features Second Circuit High pressure switch Low pressure switch Low suction line temperature sensor Compressor output Reversing valve Standard Heat Pumps / Single Circuit Units Monitors entering water temperature for boilerless electric heat control Outputs for medium and high speed fan controls. MicroTech III Controller With LonWorks Communication Module This manual covers the installation of a McQuay Vertical Floor Unit - Model VFC, VFW Water Source Heat Pump. For installation and operation information on LonWorks Communication Module and other ancillary control components, see: IM 927 - MicroTech III Water Source Heat Pump LonWorks Communication Module IM 933 - LonMaker Integration Plug-in Tool: For use with the MicroTech III Unit Controller IM 955 - MicroTech III Wall Sensor for use with Microtech III Unit Controller Figure 14: LonWorks Communication Module The LonWorks communication module will plug into the Microtech III unit controller at the CN_LON1 Header (see Figure 16 on page 16). Each McQuay water source heat pump can be equipped with a LonWorks communication module. The controller is microprocessor-based and is designed to communicate over a LonWorks communications network. The unit controller is factory programmed and tested with all the logic required to monitor and control the unit. The wall thermostat sets the unit mode of operation. The unit controller monitors water and air temperatures, and can communicate fault conditions to a LonWorks communications network. The MicroTech III unit controller with communication module includes a unit-mounted return air, discharge air and leaving water temperature sensor. Wall mounted temperature sensors include setpoint adjustment and tenant override. The user has the capability of substituting the wall sensor with a duct-mounted return air sensor. Each unit controller orchestrates the following unit operations: Enable heating and cooling to maintain setpoint based on a room sensor. Enable fan and compressor operation. Monitor all equipment protection controls. Monitor discharge air temperature. Monitor leaving water temperature. Relay status of all vital unit functions. Support optional control outputs. An amber, on-board status LED aids in diagnostics by indicating the water source heat pump operating mode and alarm conditions. If there are no current alarm conditions, the LED will indicate the unit operating mode. If there are one or more alarm conditions present, the LED will flash to indicate an alarm condition. MicroTech III heat pumps with a MicroTech III unit controller are LonMark certified and designed to be linked with a centralized building automation system through a LonWorks communications network for centralized scheduling and management of multiple heat pumps. Wall-mounted room sensors are available to control the heating and cooling operation of each MicroTech III Water Source Heat Pump Unit Controller. Available room sensors include: room sensor with LED status and tenant override button, room sensor with LED status, timed-override button, room sensor with LED status, timedoverride button, and setpoint adjustment, and room sensor with LED status, timed-override button, setpoint adjustment. The MicroTech III water source heat pump unit controller provides control of McQuay water source heat pumps. The controller enables the mode of operation, monitors the water and air temperatures, and indicates fault conditions. Each unit controller is factory programmed, wired, and tested for effective operation of your McQuay water source heat pump. The MicroTech III water source heat pump controller uses LonWorks technology. One of the following two versions of the application software is loaded into the controller at the factory. LonMark 3.4 certified application code is the current standard application code for MicroTech III units. Page 14 of 32 / IM 930-3

MicroTech III Controller with BACnet Communication Module For installation and operation information on MicroTech III unit controller and other ancillary components, see: IM 928 - MicroTech III BACnet Communication Module OM 931 - MicroTech III Unit Controller for Water Source Heat Pumps Operation and Maintenance Manual IM 955 - MicroTech III Wall Sensor For use with Microtech III Unit Controller McQuay water source heat pumps are available with McQuay BACnet MS/TP communication module that is designed to communicate over a BACnet MS/TP communications network to a building automation system (BAS). It can be factory or field-installed. The unit controller is programmed and tested with all the logic required to monitor and control the unit. An optional wall sensor may be used with the communication module to provide limited local control of the water source heat pump. The unit controller monitors water and air temperatures and passes information to the communication module. The module communicates with the BAS, to provide network control of the water source heat pump. The module makes operational data and commands available on a communications network using BACnet objects and properties: The network cable is a shielded twisted-pair cable Network communications run up to 76.8 Kbps DIP switches on the controller enable the MS/TP MAC address to be set in the range 0-127 Four green status LEDs on the communication module indicate communication activity on the MS/TP communication network and with the unit controller Figure 15: MicroTech III BACnet Water Source Heat Pump Snap-in Communication Module MicroTech III Unit Controller with BACnet MS/TP Communication Module orchestrates the following unit operations: Enable heating and cooling to maintain setpoint based on a room sensor Enable fan and compressor operation Monitors all equipment protection controls Monitors room and discharge air temperatures Monitors leaving water temperature Relays status of all vital unit functions The MicroTech III unit controller with communication module includes: Return Air Temperature sensor (RAT)(field-installed) Discharge Air Temperature sensor (DAT)(field-installed) Leaving Water Temperature sensor (LWT) Note: Refer to IM 956-X for details to install (RAT) & (DAT) sensors. CAUTION When an optional wall-mounted room temperature sensor is connected to the unit controller, the Return Air Temperature (RAT) sensor must not be installed. A wall-mounted room temperature sensor and the return air temperature sensor must not be connected simultaneously or the unit will not operate properly. The communication module provides access to setpoints for operational control Available wall sensors include: Room sensor with LED status and tenant override button Room sensor with LED status, tenant override button, and ±3 F setpoint adjustment Room sensor with LED status, tenant override button, 55 to 90 F setpoint adjustment IM 930-3 / Page 15 of 32

Figure 16: LonWorks Communication Module Placement on MicroTech III Unit Controller Page 16 of 32 / IM 930-3

Changing PSC Fan Motor Speed The fan motor can be changed from high to low speed or vice versa by interchanging the wires on the black and red labeled terminals on the motor terminal block. WARNING Hazardous Voltage! The installer must determine and follow all applicable codes and regulations. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can result in property damage, severe personal injury or death. CAUTION Sharp edges can cause personal injury. Avoid contact with them. Table 10: Fan Motor Voltage and Terminal Slots VFC, VFW R410-A Volts and Number of Terminal Slots Factory Unit Size 208V 460V 575V Fan Speed *007 n/a n/a n/a n/a 009 n/a n/a n/a Low 012 n/a n/a n/a High 015 n/a n/a n/a Low 019 4 Low 024 4 4 High 030 4 4 High 036 4 6 High 042 4 6 6 High 048 4 6 6 Low 060 4 6 6 High 070 4 6 6 High Notes: n/a = Not Available *Not available at time of publication Unit Size 009 through 015 (115/60/1), (208/230/60/1) and (265/60/1 To change between high and low speed; interchange the red and black wires. Figure 17: Sizes 009 through 015 (115/60/10, (208/230/60/1), (265/60/1) Figure 18: Sizes 019 through 036 (208/230/60/1), (265/60/1) Unit Size 030 and 036 (460/60/1) Fan motors on unit sizes 030 and 036, 460/60/1 (Figure 19) have a four-position terminal block. High and low speeds can be interchanged by switching the wires on the black and red terminals. Figure 19: Sizes 030 through 036 (460/60/1) Unit Size 042 through 070 Fan motors on unit sizes 042-070 (Figure 20 & 21) have a six-position terminal block. Motors for these sizes are factory wired for high speed. For low speed operation, move the black terminal (3) to the red terminal (6) and the black and blue terminals (3 & 4) receive a jumper. Figure 20: Sizes 042-070 (460/60/1) Figure 21: Sizes 042-070 (575/60/1) Unit Size 019 through 036 (208/230/60/1) and (265/60/1) Fan motors on unit sizes 019-036, in both 208/230/60/1 and 265/60/1 voltages (Figure 18) have a four-position terminal block. To change between high and low speed, interchange the red and black wires. IM 930-3 / Page 17 of 32

Unit Size 042 through 070 (265/60/1), (208/230/1) & (208/230/3) Fan motors on unit sizes 042-070 in voltages 265/60/1, 208/230/1 and 208/230/3 (Figure 22) all have a five-position terminal block. In order to change between high and low speed, interchange the wires on the black and red terminals. Figure 22: Sizes 042-070 (265/60/1), (208/230/1) (208/230/3) Unit Size 024 through 036 (208/230/3) Fan motors on unit sizes 024-036 in voltages 208/230/3 (Figure 23) all have a four-position terminal block. In order to change between high and low speed, interchange the wires on the black and red terminals. Figure 23: Sizes 024-036 (208/230/3) Notes: All motors have a wiring label that is keyed for proper wiring operation. Check unit wiring diagram (on electrical access panel) for proper unit operation. Not all labels are the same. Units leaving the factory are wired for high or low fan speed (see Table 10 on page 17 for fan speed settings). Label is located on the back of the terminal block. (Optional) ECM Motor The ECM motor will maintain the rated airflow as static pressure increases or decreases within the unit s operating range. Contact the factory at 315-253-2771 or 800-432-1342 if an alternate airflow setting is required. Start-up CAUTION Units must be checked for water leaks upon initial water system start-up. Water leaks may be a result of mishandling or damage during shipping. Failure by the installing contractor to check for leaks upon start-up of the water system could result in property damage. 1. Open all valves to full open position and turn on power to the unit. 2. Set the thermostat for "Fan Only" operation by selecting "Off" at the system switch and "On" at the fan switch. If "Auto" fan operation is selected, the fan will cycle with the compressor. 3. For those units that have two-speed motors, reconnect for low speed operation if necessary. 4. Set thermostat to Cool. If the thermostat is an automatic changeover type, simply set the cooling temperature to the lowest temperature. On manual changeover types, additionally select Cool at the system switch. Again, many units have time delays help protect the compressor(s) against short cycling. After a few minutes of operation, check the discharge grilles for cool air delivery. Measure the temperature difference between entering and leaving water. It should be approximately 1-1 2 times greater than the heating mode temperature difference. For example, if the cooling temperature difference is 15 F (8 C), the heating temperature difference should be 10 F (5 C). Without automatic flow control valves, target a cooling temperature difference of 10 F to 14 F (5 C to 8 C). Adjust the combination shutoff/balancing valve in the return line to a water flow rate which will result in the 10 F to 14 F (5 C to 8 C) difference. 5. Set thermostat to Heat. If the thermostat is the automatic changeover type, set system switch to the Auto position and depress the heat setting to the highest temperature. Some units have built-in time delays which prevent the compressor from immediately starting. With most control schemes, the fan will start immediately. After a few minutes of compressor operation, check for warm air delivery at discharge grille. If this is a cold building start-up, leave unit running until return air to the unit is at least 65 F (18 C). Page 18 of 32 / IM 930-3

MicroTech III Unit Controller (Standalone) 208/230/460/575/60Hz/3-Phase Typical Wiring Diagrams Table B 208V RED 230V ORG *Drawing No. 668991201 Shown with optional desuperheater pump wiring. Legend Item Description C1 Capacitor-Compressor C2 Capacitor-Fan CC Compressor - Contactor CM Compressor - Motor CDS Condensate Overflow Sensor DAT Discharge Air Temp Sensor EWT Entering Water Temp Sensor HP High Pressure Switch HTR Electric Heater Cartridge IOEXP I/O Expansion Board / Harness ISO-NC Isolation Valve - Normally Closed ISO-NO Isolation Valve - Normally Open LED1 LED Annunciator / Harness LED2 LED Annunciator / Harness LP Low Pressure Switch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board R1 Relay - Fan Motor R2 Relay - Electric Heat RAT Return Air Temp Sensor RV Reversing Valve Solenoid TB1 Power Terminal Block X1 Transformer Standard Unit Wiring Optional Wiring (by others) Notes: 1. Main board jumpers: No jumpers shorted. All open. 2. I/O expansion board jumpers: Jumper JP4 shorted. Transformer: Unused wire to be capped. Desuperheater only available on 115-208-230V applications. Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT), Discharge Air (DAT) and Return Air (RAT) Temperature sensors are shipped or are field installed on units configured with a communication module. *Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit. IM 930-3 / Page 19 of 32

Typical Wiring Diagrams MicroTech III Unit Controller with Optional ECM Motor, Desuperheater and I/O Expansion Module 208/230/265/277/60 Hz/1-Phase Table B 208V RED 230V ORG 265V BRN 277V BRN *Drawing No. 668991501 Legend Item Description C1 Capacitor-Compressor C2 Capacitor-Fan CC Compressor - Contactor CM Compressor - Motor CDS Condensate Overflow Sensor DAT Discharge Air Temp Sensor EWT Entering Water Temp Sensor HP High Pressure Switch HTR Electric Heater Cartridge IOEXP I/O Expansion Board / Harness ISO-NC Isolation Valve - Normally Closed ISO-NO Isolation Valve - Normally Open LED1 LED Annunciator / Harness LED2 LED Annunciator / Harness LP Low Pressure Switch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board R1 Relay - Fan Motor R2 Relay - Electric Heat RAT Return Air Temp Sensor RV Reversing Valve Solenoid TB1 Power Terminal Block X1 Transformer Standard Unit Wiring Optional Wiring (by others) Notes: 1. Main board jumpers: No jumpers shorted. All open. 2. I/O expansion board jumpers: Jumper JP4 shorted. Transformer: Unused wire to be capped. Desuperheater only available on 115-208-230V applications. Note: The gray tinted areas in the wiring diagram; Discharge Air (DAT) and Return Air (RAT) Temperature sensors are field-installed on units configured with a communication module. The Leaving Water (LWT) sensor is unit-mounted from the factory. *Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit. Page 20 of 32 / IM 930-3

Typical Wiring Diagrams MicroTech III Unit Controller with Optional ECM Motor, Desuperheater, Electric Heat Coil & I/O Expansion Module 208/230/460/60 Hz/3-Phase Table B 208V RED 230V ORG 460V BLK/RED *Drawing No. 668991301 Legend Item Description C1 Capacitor-Compressor C2 Capacitor-Fan CC Compressor - Contactor CM Compressor - Motor CDS Condensate Overflow Sensor DAT Discharge Air Temp Sensor EWT Entering Water Temp Sensor HP High Pressure Switch HTR Electric Heater Cartridge IOEXP I/O Expansion Board / Harness ISO-NC Isolation Valve - Normally Closed ISO-NO Isolation Valve - Normally Open LED1 LED Annunciator / Harness LED2 LED Annunciator / Harness LP Low Pressure Switch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board R1 Relay - Fan Motor R2 Relay - Electric Heat RAT Return Air Temp Sensor RV Reversing Valve Solenoid TB1 Power Terminal Block X1 Transformer Standard Unit Wiring Optional Wiring (by others) Notes: 1. Main board jumpers: No jumpers shorted. All open. 2. I/O expansion board jumpers: Jumper JP4 shorted. Transformer: Unused wire to be capped. Desuperheater only available on 115-208-230V applications. Note: The gray tinted areas in the wiring diagram; Discharge Air (DAT) and Return Air (RAT) Temperature sensors are field-installed on units configured with a communication module. The Leaving Water (LWT) sensor is unit-mounted from the factory. *Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit. IM 930-3 / Page 21 of 32

Typical Wiring Diagrams MicroTech III Unit Controller with Optional ECM Motor, Desuperheater, and I/O Expansion Module 208/230/460/60/3-Phase Table B 208V RED 230V ORG 460V BLK/RED *Drawing No. 668991401 Legend Item Description C1 Capacitor-Compressor C2 Capacitor-Fan CC Compressor - Contactor CM Compressor - Motor CDS Condensate Overflow Sensor DAT Discharge Air Temp Sensor EWT Entering Water Temp Sensor HP High Pressure Switch HTR Electric Heater Cartridge IOEXP I/O Expansion Board / Harness ISO-NC Isolation Valve - Normally Closed ISO-NO Isolation Valve - Normally Open LED1 LED Annunciator / Harness LED2 LED Annunciator / Harness LP Low Pressure Switch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board R1 Relay - Fan Motor R2 Relay - Electric Heat RAT Return Air Temp Sensor RV Reversing Valve Solenoid TB1 Power Terminal Block X1 Transformer Standard Unit Wiring Optional Wiring (by others) Notes: 1. Main board jumpers: No jumpers shorted. All open. 2. I/O expansion board jumpers: Jumper JP4 shorted. Transformer: Unused wire to be capped. Desuperheater only available on 115-208-230V applications. Note: The gray tinted areas in the wiring diagram; Discharge Air (DAT) and Return Air (RAT) Temperature sensors are field-installed on units configured with a communication module. The Leaving Water (LWT) sensor is unit-mounted from the factory. *Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit. Page 22 of 32 / IM 930-3

Typical Wiring Diagrams MicroTech III Unit Controller with PSC Motor, Desuperheater and I/O Expansion Module for Hot Gas Reheat Control (Unit Sizes 019-070) 208/230/60/1-Phase Table B 208V RED 230V ORG *Drawing No. 669007101A Legend Item Description C1 Capacitor-Compressor C2 Capacitor-Fan CC Compressor - Contactor CM Compressor - Motor COS Condensate Overflow Sensor DAT Discharge Air Temp Sensor EWT Entering Water Temp Sensor HP High Pressure Switch HTR Electric Heater Cartridge IOEXP I/O Expansion Board / Harness ISO-NC Isolation Valve - Normally Closed ISO-NO Isolation Valve - Normally Open DSHP Desuperheater Pump HGRH 3-Way Valve Solenoid P1 24 VAC Supply I/O Expansion Brd. LED1 LED Annunciator / Harness LED2 LED Annunciator / Harness LP Low Pressure Switch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board R1 Relay - Fan Motor R2 Relay - Electric Heat RAT Return Air Temp Sensor RV Reversing Valve Solenoid TB1 Power Terminal Block X1 Primary 24 VAC Transformer X2 Secondary 24 VAC Transformer Standard Unit Wiring Optional Wiring (by others) Notes: 1. Main Board Jumpers: JP3 Geothermal. 2. I/O Expansion Board Jumpers: JP4 Hot Gas Reheat. JP3 Supplemental EH. JP4 Boilerless EH. JP5 2-Speed Fan Transformer: Unused wire to be capped. Note: The gray tinted areas in the wiring diagram; Discharge Air (DAT) and Return Air (RAT) Temperature sensors are fieldinstalled on units configured with a communication module. The Leaving Water (LWT) sensor is unit-mounted from the factory. *Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit. IM 930-3 / Page 23 of 32

Thermostat Connections 7-Day Programmable Electronic Thermostat (P/N 668375301) MicroTech III Unit Control Board Low Voltage Terminal Strip (Circuit 1) 24VAC Common Tenant Override Fan Cool 1 Cool 2 Heat 1 Heat 2 Alarm Output 24VAC TB2 C O G Y1 Y2 W1 W2 A R Thermostat Terminals - C + R W1 Y1 W2 Y2 G Do not run remote sensor wire in conduit with other wires. Wire 1 should run between the S1 terminal on the thermostat and the S1 terminal on the remote sensor Wire 2 should run between the S2 terminal on the thermostat and the S2 terminal on the remote sensor Connect the shielding of the wire to the S2 terminal on the thermostat 5. Disable the main sensor (R12) on the thermostat by cutting it from the circuit board. Figure 24: Optional Remote Sensor Wiring Thermostat S1 S2 Remote Sensor S1 S2 Notes: Includes Thermostat and Wall Plate. Refer to the installation, operation & application guide (LIA265) for thermostat 668375301. Cut R12 from circuit board Wire 2 Wire 1 Non-Programmable Electronic Thermostat (P/N 668375401) MicroTech III Unit Control Board Low Voltage Terminal Strip (Circuit 1) MicroTech III Wall-Mounted Room Temperature Sensors (Kit P/N 669529101, 669529201, 669529001) 24VAC Common TB2 C Thermostat Terminals Figure 25: MicroTech III Wall-Mounted Room Temperature Sensors (669529201 Not Shown) Tenant Override O - C Fan G + R Cool 1 Y1 W1 Cool 2 Y2 Y1 Heat 1 Heat 2 Alarm Output 24VAC W1 W2 A R W2 Y2 G O *Override (Optional) Sensor 669529101 Sensor 669529201 Not Shown Sensor 669529001 Note: Includes Thermostat and Wall Plate. Refer to the installation, operation & application guide (LIA266) for thermostat 668375401. *When remote reset of a lockout condition is required at the wall thermostat, it will be necessary to utilize a conductor between terminal "O" on the wall thermostat to terminal "O" on the MicroTech III unit controller (non-programmable stat only). Optional Remote Sensor (P/N 66720401) 1. Remove cover from remote sensor housing. 2. Select an appropriate location for mounting the remote sensor. 3. Mount remote sensor unit using hardware provided. 4. Install two strand shielded wire between remote sensor and thermostat. Shielded wire must be used. General Microtech III Wall-Mounted Room Temperature Sensors provide electronic sensing of room temperatures at wall locations. All sensor models feature a thermistor (10kΩ) and a green LED for unit status. Tenant override, setpoint adjustment potentiometer, thermometer, and a communications port are optional features available in any combination This manual provides general information for the Microtech III Wall-Mounted Room Temperature Sensors. For installation instructions refer to IM 955 Page 24 of 32 / IM 930-3

Figure 26: MicroTech III Wall Sensor Details Figure 28: Temperature Sensor Wiring to MicroTech III Unit Controller (669529001) 0 to 10 K ohm Potentiometer Temperature Sensor Terminals 4.59" Status LED (Green) Fan Control Slide Switch Mode Control Slide Switch Tenant Override Momentary Push Button Switch MicroTech III Unit Controller TB1 Terminals Specifications Thermistor resistance (10kΩ) (Conforms to advance thermal products curve 2) Ambient Temperature Limits: Shipping and Storage: 40 F to 160 F ( 40 C to 71 C) Operating: 40 F to 140 F (4 C to 60 C) Humidity: 5 to 95% RH, non-condensing Locations: NEMA Type 1, Indoor only Connections: Color Coded Leads Wiring Sensors to the MicroTech III Unit Controller Figure 27: Temperature Sensor Wiring to MicroTech III Unit Controller (669529101, 669529201) Additional Accessories General Motorized Isolation Valve & Relay The motorized valve kit is available as a factory-installed and wired option or may be ordered as a field-installed accessory. Wired as shown in Figure 29, the motorized valve will open on a call for compressor operation. Valves for unit sizes 007 to 019 are 1/2" while unit sizes 024 to 070 are 3/4". Using a Normally Closed (N/C), power open valve, wire as illustrated in Figure 29. Figure 29: Normally Closed, Power Open Motorized Valve & Relay Wiring Actuator & Valve Assembly Anti-short Bushing Anti-short Bushing Temperature Sensor Terminals Connector Conduit Connector Pin(s), female plug into receptacle configuration below MicroTech III Unit Controller TB1 Terminals Note: Connectors on valve must be cut off and stripped back and the wires twisted to make connections to the IV/ PR Terminals IM 930-3 / Page 25 of 32

Pump Restart Relay Kit P/N 061419001 The MicroTech III unit controller has an internal Pump Restart Relay connected to H8, Pin 2 for the Normally Open (N/O) terminal of the internal relay. Connect to H8, Pin 1 for the Normally Closed (N/C) terminal of the internal relay. The output of the internal pump restart relay is 24- volts AC and the output is not available when the H8 connection is used to control a motorized valve. Multiple Unit Control (up to 3 units) (P/N 056794201) The multiple unit control board is an accessory used when up to 3-units are controlled from a single thermostat. Typically the control panel and board is centrally mounted between the units and thermostat. A maximum of 2 boards may be used together if up to 6-units must be connected and controlled from a single thermostat. For detailed installation instructions refer to IM 952. This version of the control uses VAC relays and should not be used in combination with any other accessories or equipment that require VDC connections. Figure 30: Multiple Unit Control Panel and Board Figure 31: Wiring Multiple Unit Control Board (MUCP) Multiple Unit Control Panel Circuit Board K3 K2 K1 TB3 R Y G W R Y G W R Y G W TB2 TB1 TB4 R Y G W C MicroTech III Unit Control Board Low Voltage Terminal Strip R A W2 W1 Y2 R R A W2 W1 Y2 A W2 W1 Y2 Y1 G O C Y1 G O Y1 G O TB2 - Unit #1 C C Thermostat Terminals G Y2 W2 Y1 W1 TB2 - Unit #2 TB2 - Unit #3 Notes: Dotted lines represent low voltage (Class II) wiring; a color-coded thermostat cable is recommended. MUCP may be mounted horizontally or vertically on heat pump cabinet or any convenient surface. Do not use if using night setback. Thermostat must be A.C. voltage. Hot Gas/Water Reheat Dehumidification (Option) (Unit Sizes 019 070) Hot Gas Reheat (HGRH) allows superior humidity control by utilizing a second air coil to provide dehumidification and tempered air to the conditioned space. A field supplied humidistat is required. Wire the humidistat to the dual terminal block (TB1) on the I/O expansion module. Note: Hot Gas Reheat (HGRH) utilizes high fan speed. + R - C The multiple unit control board provides the components necessary to protect the MicroTech III unit controller from electrical damage that may occur when using standard offthe-shelf relays. Do not use the unoccupied (U-terminal) feature with the multiple unit control board. Page 26 of 32 / IM 930-3

Desuperheater (Option) For VFC/VFW (019-070) A desuperheater heats water for domestic use by pumping water though a coaxial heat exchanger so that it passes by superheated refrigerant gas. 1. Turn off gas supply or electric supply to water heater tank. 2. Close water supply valve on water heater tank. 3. Connect hose to drain on water heater tank. Run hose to suitable drain. 4. Open drain valve on tank and pull pressure relief valve to assist draining. Let tank drain completely. 5. Flush tank of sediment by opening water supply valve until clear water flows from hose. 6. Close supply valve. Once tank is empty, close pressure relief and water tank drain valves. 7. Drain tank by opening drain valve on the bottom of the tank, then open pressure relief valve or hot water faucet. 8. Once drained, the tank should be flushed with cold water until the water leaving the drain hose is clear and free of sediment. 9. Close all valves and remove the drain hose. 10. Install piping for desuperheater following the guidelines below: For piping length up to 15 feet: Use 3/8" O.D. (or larger) copper tube. For piping lengths of 15 feet to 60 feet: Use 1/2" O.D. copper tube. Notes: All exposed water lines must be insulated with 3/8" wall closed-cell insulation. Install shut-off valves on desuperheater supply and return lines. 11. Refill tank by opening the water tank supply valve. 12. Vent air from the system by opening a hot water faucet. Close faucet when air is purged from system. 13. Check for water leaks and repair as necessary 14. Restore gas supply or electric supply to water heater tank. CAUTION Units with the desuperheater option must be drained prior to exposure to temperatures that will cause the water to freeze, resulting in damage to the desuperheater. Damage from freezing is not covered under the McQuay product warranty. WARNING All Federal, State and local codes should be followed when installing the desuperheater. Installation must be performed by a qualified plumber and electrician. CAUTION Sufficient water flow must be provided. Damage to the desuperheater pump from lack of water flow is not covered by the McQuay product warranty. Figure 32: Typical Connection diagram for VFC/VFW 1. Desuperheater water supply with stainless steel flexible hose with Y-strainer/ball valve 2. Desuperheater water return with stainless steel flexible hose with flow controller/ball valve 3. Flexible duct collar 4. Isolation pad 5. Low voltage control wiring (electric entrance) 6. Line voltage - unit power (electric entrance) 7. Water heater tank drain valve 8. P/T relief valve 9. Hot water out 10. Cold water in 11. Discharge air to space 12. Return air IM 930-3 / Page 27 of 32

Troubleshooting The in and outs of R-410A R-410A is a non-ozone depleting blend of two refrigerants - HFC-125 and HFC-32 in a fifty percent mixture. R-410A exhibits higher operating pressure and refrigeration capacity than R-22. R-410A is intended for use in new air conditioning applications that have traditionally been used HCFC-22 (R- 22). Due to higher capacity and pressure of R-410A, it must not be used in existing R-22 systems. Although R-410A is non-flammable at ambient temperature and atmospheric pressure, it can become combustible under pressure when mixed with air. Note: R-410A should not be mixed with air under pressure for leak testing. Pressure mixtures of dry nitrogen and R-410A can be used for leak testing. Lubrication R-410A should be used only with polyester (POE) oil. The HFC refrigerant components in R-410A will not be compatible with mineral oil or alkylbenzene lubricants. R-410A systems will be charged with the OEM recommended lubricant, ready for use with R-410A. Charging Due to the zeotropic nature of R- 410A, it should be charged as a liquid. In situations where vapor is normally charged into a system, a valve should be installed in the charging line to flash the liquid to vapor while charging. Make certain that the recycle or recovery equipment used is designed for R-410A. The pressure of R-410A refrigerant is approximately 60 percent greater than that of R-22. Pressure gauges require a range up to 800 PSIG high side and 250 PSIG low side. Recovery cylinders require a 400 PSIG rating do not put R-410A in a 300 PSIG rated cylinder. Note: Because a water source heat pump operates under a wide range of water and air temperatures, the values printed below are to be taken as suggested pressure and temperatures.) All McQuay water source heat pumps are designed for commercial use. The units are designed for the cooling mode of operation and fail safe to cooling. The reversing valve is energized for the heating mode of operation. General Maintenance 1. Normal maintenance on all units is generally limited to filter changes. Units are provided with permanently lubricated motors and require no oiling even though oil caps may be provided. 2. Filter changes are required at regular intervals. The time period between changes will depend upon the project requirements. Some applications such as motels produce a lot of lint from carpeting and linen changes, and will require more frequent filter changes. Check filters at 60- day intervals for the first year until experience is acquired. If light cannot be seen through the filter when held up to sunlight or a bright light, it should be changed. A more critical standard may be desirable. 3. The condensate drain pan should be checked annually and cleaned and flushed as required. 4. Record performance measurements of volts, amps, and water temperature differences (both heating and cooling). A comparison of logged data with start-up and other annual data is useful as an indicator of general equipment condition. 5. Periodic lockouts almost always are caused by air or water problems. The lockout (shutdown) of the unit is a normal protective result. Check for dirt in the water system, water flow rates, water temperatures, airflow rates (may be a dirty filter), and air temperatures. If the lockout occurs in the morning following a return from night setback, entering air below machine limits may be the cause. Superheat Head Pressure Water Delta T 8 to 14 degrees 335-355 PSIG 10 to 14 All information above is based on ISO standard 13256-1 and tested at these conditions. Page 28 of 32 / IM 930-3

Troubleshooting Refrigeration Circuit Head Suction Compressor Super Symptom Pressure Pressure Amp Draw Heat Subcooling Air Water Safety Temp (loops) Temp Lock Differential Differential Out Charge Undercharge System Low Low Low High Low Low Low Low Pressure (Possible Leak) Overcharge System High High High Normal High Normal Low Normal High Pressure Low Air Flow Heating High High High High Normal Low High Low High Pressure Low Air Flow Cooling Low Low Low Low Normal High High Low Low Temp Low Water Flow Heating Low Low Normal Normal Low Low High Low High Low Temp Low Water Flow Cooling High High High High Low Low High High Pressure High Air Flow Heating Low Low Low Low High Low Low Low Temp High Air Flow Cooling Low High Normal High Low Low Normal High Pressure High Water Flow Heating Normal Low Normal High Normal Normal Low High Pressure High Water Flow Cooling Low Low Low Low High Normal Low Low Temp Normal TXV Restricted High Low High High Low Low Low Figure 33: Cooling Mode Figure 34: Heating Mode Coil Air to Refrigerant Heat Exchanger Return Air Thermal Expansion Valve Coaxial Heat Exchanger Water In Water Out Coil Air to Refrigerant Heat Exchanger Return Air Thermal Expansion Valve Coaxial Heat Exchanger Water In Water Out Sensing Bulb and Capillary Tube Compressor Sensing Bulb and Capillary Tube Compressor Blower Blower Reversing Valve Reversing Valve Conditioned Air (Cooling) Conditioned Air (Heating) Cooling Refrigeration Cycle When the wall thermostat is calling for COOLING, the reversing valve directs the flow of the refrigerant, a hot gas, leaving the compressor, to the water-to-refrigerant heat exchanger. Here the heat is removed by the water and the hot gas condenses to become a liquid. The liquid then flows through a thermal expansion metering system to the air-torefrigerant heat exchanger coil. The liquid then evaporates becoming a gas, at the same time absorbing heat and cooling the air passing over the surfaces of the coil. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle. Heating Refrigeration Cycle When the wall thermostat is calling for HEATING, the reversing valve directs the flow of the refrigerant, a hot gas, leaving the compressor, to the air-to-refrigerant heat exchanger coil. Here the heat is removed by the air passing over the surfaces of the coil and the hot gas condenses to become a liquid. The liquid then flows through a capillary thermal expansion metering system to the water-to-refrigerant heat exchanger. The liquid then evaporates becoming a gas, at the same time absorbing heat and cooling the water. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle. IM 930-3 / Page 29 of 32