Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

Similar documents
Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

Test report for a Teldor Cables SLA-6-01X08- ZAHRH-DD Fibre Optic cable to IEC :1999

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Personal Protection Systems (PPS)

Department for Communities and Local Government Research Report:

Test One: The Uncontrolled Compartment Fire

EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings

AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS

DOMESTIC SMOKE ALARMS AND SPRINKLERS. Introduction. Materials and methods. Frank SWANN 1. Legislative impact. Review article

Characterising the smoke produced from modern materials and evaluating smoke detectors

Learning from incidents IFE AGM and Conference 2014 Intelligent Engineering Reducing Risk 25 th and 26 th June 2014 Stratford on Avon

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

This document is a preview generated by EVS

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

BS 5839: Part THE CHANGES

New Approaches to Design for Fire Safety - Residential sprinklers, open plan flat layouts and water mist

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Watermist nozzle issues and test methods

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

Considerations in the Design of Smoke Management Systems for Atriums

The Loss prevention Council. Phase 1 report

Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires?

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work

Research into multi-sensor detector capabilities and false alarm reduction

Technical evaluation of the Ningbo Longmax Electronic Co., Ltd LM-201A battery operated carbon monoxide (CO) Detector Type B to EN :2010.

Review of reports and data for Aero-Therm thermal reflective coating. Prepared for: Mr Craig Clement Director

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

Loss Prevention Standards

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property

Building Research Note

Fire safety and the ageing population. René Hagen, professor of Fire Safety Fire Service Academy, Netherlands European Fire Safety Alliance

Loss Prevention Standard

Using Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

BS EN : 2001 & IEC :2000

Local area fire protection using automatic suppression

Fire Suppression Performance of Manually Applied CAF and Other Water Based System

2 Examination of Cladding Panels (Laboratory)

Householders Guide to Fire Sprinklers

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

Standards and third party certification

MEDIUM-DENSITY HOUSING # 7. Fire safety

Recent BRANZFIRE enhancements and validation

Loss Prevention Standard

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

An experimental study of the impact of tunnel suppression on tunnel ventilation

Fire Risk Assessment Safety Checklist

Ventilation Effects on Fire Patterns during Post Flashover Burning

Rosepark Care Home Fire An Overview

Fire Performance of external thermal insulation for walls of multistorey buildings

Fire risk management plan. MH/05/Revised/06/17

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property

Timber escape stairs: Using timber stairs as means of escape. Summary. 1. Introduction

Effectiveness of sprinklers in residential premises:

The first tunnel fire. Benefits of fire

Fire Safety Protocol

Smoke Alarm Research at NIST

Full-scale test of fire detection in a facade using heat detection cable and flame detector

FIRE RISK ASSESSMENT AND PROTECTION

Smoke Alarm Research at NIST

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Figure 1. Structure Used For the Simulations.

Sprinkler systems. A presentation for fire brigade staff

CCTV Policy CONTENTS. 1.0 Introduction. 2.0 General Principles. 3.0 Privacy and Dignity. 4.0 Retention Policy. 5.0 Responsible Officers

Lessons Learned from the FaçadeFiasco. Dr. Jonathan Barnett Technical Director, RED Fire Engineers

Records Management. Standards. Storage of Semi-Current Records. Standards for the management of Government records RMS 3.1

8.1. Fire and Heritage. The maintenance series. Information sheet. Guidelines on Fire Safety in Heritage Buildings

Fire Protection for Printing Machines with High Pressure Water Mist

WARM WELCOME RISK ASSESSMENTS & HOMESTAY FIRE/GAS SAFETY

USER MANUAL 10 YEAR LIFE SMOKE ALARM

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist

Potential Impact of New UL Fire Test Criteria

Wellsprings Primary School. Fire Emergency Evacuation Plan

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

Fire precautions in dwellings

Development and Full-Scale Tests of a Water Mist System inside High Speed Trains

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

- CONSTRUCTION FIRE SAFETY STANDARDS

Copyright 2018 American Wood Council 1

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

DETERMINATION OF SMOKE QUANTITIES TO BE USED FOR SMOKE DETECTION PERFORMANCE GROUND AND FLIGHT TESTS

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Chapter 17, Initiating Devices

Gothenburg dance hall, Sweden, 1998

Contact person Date Reference Page Alen Rakovic P (19) Fire Research

22 BISHOPSGATE Lift Evacuation Strategy

UBS1RF OPTICAL SMOKE ALARM EN 14604:2005/AC:2008 DOP:UBS1RF-001-V1

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

FULL-SCALE FIRE TESTS OF A TWO-STORY CROSS-LAMINATED TIMBER STRUCTURE

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires Phase 1: System Design and Function Evaluation

Abstract. Introduction

SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS

Transcription:

Indicative hoarding fire experiment Prepared for: London Fire Brigade 21 May 2014 Client report number 292366

1 Hoarding fire demonstration Prepared on behalf of BRE Fire and Security by Name Dr Sung-Han Koo Phil Clark Louise Jackman Position Research Manager Senior Consultant Principal Consultant Signature Approved on behalf of BRE Fire and Security by Name Martin Shipp Position Technical Director Date 21 May 2014 Signature BRE Fire and Security BRE Global Bucknalls Lane Watford Herts WD25 9XX Customer Services: 0333 3218811 F + 44 (0) 1923 664994 E enquiries@breglobal.com www.breglobal.com This report is made on behalf of BRE Fire and Security. By receiving the report and acting on it, the client - or any third party relying on it - accepts that no individual is personally liable in contract, tort or breach of statutory duty (including negligence).

Introduction BRE Global has been in discussions and correspondence with London Fire Brigade regarding a project intended to examine the fire safety issues for occupants and fire fighters as a result of hoarding. BRE Global was commissioned by London Fire Brigade, following acceptance of BRE Proposal 292366 on 27 th February 2014, to undertake a demonstration fire experiment to assist with an appraisal of fire risks and the effectiveness of a typical sprinkler in a room containing hoarding materials. A planning meeting was held at the London Fire Brigade Headquarter on 10 th April 2014, attended by: Mark Andrews and Bob Selby London Fire Brigade Steve Mills National Fire Sprinkler Network Andy Kelleher Triangle Fire Systems Louise Jackman and Sung-Han Koo BRE Global Representatives from CFOA, housing associations and other interested parties were invited by London Fire Brigade to observe the demonstration fire experiment and to provide observed hoarding experience. Project objective The aim of this demonstration fire was to provide an initial indication of whether or not a sprinkler system is likely to be effective in controlling (or suppressing) a fire in a room involving typical hoarding materials. Methodology BRE Global provided a 4 m x 4 m x 2.5 m (high) rig constructed of timber frame and plasterboard with a single door opening. The experimental arrangements were discussed and agreed with the London Fire Brigade and their representative interested parties prior to the fire demonstration. Contents The experimental rig was filled with hoarding materials as shown in Figure 1. The contents comprised household material sourced by London Fire Brigade and included tables, chairs, cardboard boxes, clothing, papers, books, plastic bags of clean household waste, as well as a TV set. The hoarding material was provided by London Fire Brigade and installed by them to a level defined in the Clutter Index, i.e. nominally Clutter Index 6 bedroom as shown in Figure 2 and also described in: http://www.science.smith.edu/departments/psych/rfrost/hoarding_images.htm (link provided to BRE Global by the client on 12 th September 2013). The contents of the rooms were not weighed but were video recorded by BRE Global as each item was introduced. The camera was installed next to the door at about 2 m height.

Figure 1 Hoarding material in the experimental rig Figure 2 Level of hoarding material of Clutter Index 6

Set up and instrumentation Figure 3 shows the layout of the room and the location of video cameras, thermocouples and sprinklers installed. Four video cameras were installed for the demonstration fire. Camera 1 was installed next to the door at a lower height, around 30 cm from floor. CCTV cameras 2 and 3 were installed at the bottom wall in Figure 3, one observing the side wall sprinkler and the other one observing towards the TV, the ignition source. Camera 4 was installed near the centre of the room under a table looking towards the ignition source. Two thermocouples were installed; one at the ceiling height near the door to the room to measure hot layer gas temperature exiting the compartment and the other adjacent to the side wall sprinkler head to measure the temperature at sprinkler activation. Two domestic sprinkler heads were fitted in the room. An automatic 68 C side wall sprinkler head was fitted on the right hand side wall in Figure 3. A sidewall sprinkler was selected as it was considered to represent a practical installation arrangement for a sprinkler in hoarding premises. A second sprinkler head was installed on the ceiling near to the centre of the room but this was fitted with a valve (held closed) so that it could be manually activated in the event that the side wall sprinkler was not effective in suppressing the fire. Camera #4 TV Ignition Thermocouple #2 at sprinkler Side wall sprinkler Ceiling sprinkler Camera #2 Door opening Camera #3 Thermocouple #1 at ceiling Camera #1 Figure 3 Layout of experiment room instrumentation

Ignition The ignition source and its location were agreed with the London Fire Brigade. It consisted of a stainless steel wire coiled around a small piece of low density fibreboard wetted with a small amount of Heptane. It was placed near the TV set. Power was applied to the coil using a low voltage power supply which initiated heating in the coil. Figure 4 Experiment observers Results As shown in Figure 4, observers were able to monitor the demonstration via video footage taken by two CCTV cameras in real-time. The heated coil cause smouldering to occur where it was in contact with the low density fibre board and as the voltage continued to be applied, the heating caused the low density fibre board and heptane to transition to flaming. Once the primary ignition was achieved the fire quickly spread to other items in the vicinity.

The recorded data is provided below. Figure 5 shows temperature data measured at the ceiling and at a point adjacent to the side wall sprinkler head. From ignition to around 400 seconds, there was no temperature rise measured. During this period a small amount of smoke was observed floating in a thin layer near the top of the room and gradually spilling out from the room. It was noted that while smoke was produced in the early smouldering stage of the ignition, it did not have sufficient momentum to overcome the warm layer at the ceiling and as a consequence the optical smoke detector did not operate, despite smoke clearly being present. At about 464 seconds (7 minutes 44 seconds) from ignition, the optical smoke detector activated and the measured temperature at the sprinkler head and at the ceiling level rose significantly. At 494 seconds, some 30 seconds from smoke detector activation, the side wall sprinkler operated. The temperatures measured at the sprinkler head and at the ceiling were 131.3 C and 162.4 C respectively. The sprinkler was initially operated with a flow of 53 litre/min which corresponds to 3.3 mm/min. At 734 seconds (4 minutes after sprinkler operation) the flow was increased to 57 litre/min which corresponds to 3.6 mm/min. The operating sprinkler significantly reduced the temperature in the room. Steam and smoke were observed spilling out of the room throughout this period. At 1,130 seconds from ignition (approximately 10 minutes after sprinkler operation), it was agreed that the sprinkler would be temporarily turned off, to represent a 10 minute duration of available water. As shown in Figure 5, the temperature rose gradually. Consequently, the sprinkler was turned on again 2.5 minutes later, when the temperature decreased to the previous level. While the sprinkler was off much of the cool smoky steam cleared from the room; the gradual increase in the ceiling temperature indicated the potential for further fire development within the room. To observe the spray characteristics from two operating sprinklers (which shared the water supply), at 1,394 seconds (15 minutes after sprinkler operation), the second sprinkler was manually operated and the total flow was increased to 105 litre/min which corresponds to 7 mm/min. At about 1,544 seconds (17.5 minutes after sprinkler operation) the sprinklers were turned off. As shown in the figure, the temperature rose slightly. The remaining fire was manually extinguished.

250 Temperature ( C) 200 150 100 50 Sprinkler operated automatically Optical smoke detector triggered CH1 degc By sprinkler head CH2 degc On Ceiling Sprinkler turned off manually 0 0 200 400 600 800 1000 1200 1400 1600 1800 2000 Time From Ignition (s) Figure 5 Temperature data measured at sprinkler head and ceiling Table 1 shows photos taken by two cameras: Camera 1 installed at the door and Camera 4 installed below a table near to the centre of the room, at different stages of fire. At about 406 seconds (6 minutes 46 seconds) to 444 seconds (7 minutes 24 seconds) from ignition, a small flame was observed by both cameras. The flame grew rapidly and, by the time the smoke detector activated, the fire had spread to adjacent materials from the fire source, i.e. a TV. The flame then reached the ceiling and soon after the sprinkler operated. After the sprinkler operation, the flame size has significantly reduced producing lots of smoke.

Table 1 Photos taken from door camera and room camera at 5 different stages Time from ignition Door camera Room camera 0 second Ignition 406~444 seconds Flame visible from camera angle 464 seconds Fire detector activated 494 seconds Sprinkler activated 514 seconds 10 seconds after sprinkler operation

Figure 6 shows post-fire damage. Although the flames were observed to impact the ceiling, the fire did not spread significantly beyond the ignition point before the sprinkler operation occurred. Figure 6 Post-fire damage Conclusions The sprinkler duration and flow rates used in this experiment are considered to be typical for a domestic dwelling. The demonstration fire experiment showed that a sprinkler system is likely to be effective in controlling and suppressing a fire in a room involving typical hoarding materials. However, the fire did grow again when the water supply was stopped after 10 minutes. If sprinklers are to be used to protect properties with hoarding then the operational parameters for such a system may need to be more onerous than for normal domestic applications, i.e. may require a longer duration of water supply since the fire is very much shielded. This experiment was limited to a single arrangement. A future project could consider: other hoarding arrangements, different packing heights, different packing density, other ignition locations and scenarios,

other room types and sizes, other ventilation arrangements; closed door, cross flows, other sprinkler types, locations, arrangements and other suppression technologies, other sprinkler flow rates and durations, and further assessments based on temperature and smoke tenability. The report is made on behalf of BRE Global and relates only to the observations and data cited in this report. It does not constitute an approval, certification or endorsement of the product. We have no responsibility for the design, materials, workmanship or performance of the product. As cited in our standard terms and conditions this report shall only be reproduced in its entirety.