Aspirating Smoke Detection for Duct Monitoring

Similar documents
Aspirating Smoke Detection for Large Area Coverage Applications

Aspirating Systems. Ducts. System Sensor Design Guide

FAAST PRODUCT RANGE Aspirating Smoke Detection

FAAST. Fire Alarm Aspiration Sensing Technology

FAAST. Fire Alarm Aspirating Sensing Technology

FAAST. Fire Alarm Aspirating Sensing Technology

Aspir A ation spir P R O D U C T S

Aspirating Smoke Detection PRODUCTS. Accessories Piping Conventional and Intelligent Detectors

Notifier by Honeywell: FAAST TM Fire Alarm Aspiration Sensing Technology

Aspirating Smoke Detection PRODUCTS. Accessories Piping Conventional and Intelligent Detectors

Notifier by Honeywell: FAAST TM Fire Alarm Aspiration Sensing Technology

Aspiration Detection.

DUCT SMOKE DETECTORS IQ8

Aspirating Accessories: Pipes and Fittings

The World's No. 1 Brand of Air-sampling Smoke Detector

Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector

1.1 SCOPE 1.2 APPROVALS. A. The Aspirating Smoke Detector shall be tested, approved and/or listed by: 1.3 CODE, STANDARDS, AND REGULATION

INCREASE YOUR LAB EFFICIENCY

Aspirating Detection System. Protec Aspirating Detection System Atria Design Guide. MED2199 Atria Design Guide Issue 0 Page 1 of 22

Buys Time. Aspirating Smoke Detection

and Aspirating Smoke Detection

The World's No. 1 Brand of Aspirating Smoke Detector

Buys Time. Aspirating Smoke Detection

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Code of Practice for Design, Installation, Commissioning & Maintenance of Duct Smoke Detector (DSD) Systems

Data Centers. ASD 535 Application Report

A Comparison of Aspirated Smoke Detectors

HART XL High Sensitivity Smoke Detection

INCREASE YOUR LAB EFFICIENCY

HART XL High Sensitivity Smoke Detection

GE Security. air sampling pipe networks installation and design manual

Snifter. User Manual. Distributor

TX7100. Intelligent Addressable Optical Smoke Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

ASPIRATING SMOKE DETECTION SYSTEMS

Aspirating Systems Design and Application Guide

FDA241, FDA221 Siemens ASD

Sintrol Snifter A1+ Manual. Version 1.2.2

LaserFOCUS VLF-250 Engineering Specification

INSTALLATION AND MAINTENANCE INSTRUCTIONS TC866E Series LASER ASPIRATED SMOKE DETECTOR

Aspirating Smoke Detection

FAAST Beyond Standard Methods of Detection

Instructions. Duct Mount Accessory Q Rev: 11/

Aspirated Smoke Detectors

The new detector from Rafiki

Incubators THE BENCHTOP EQUIPMENT HYGIENE SOLUTION

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Aspirating Smoke Detection (ASD) Systems Fire Detection

Protezione antincendio di dati e business critical assets nei Data Centers

E-PDD Duct Smoke Detector Installation Sheet

The World's No. 1 Brand of Aspirating Smoke Detector

Aspirating Smoke Detection

FDA241, FDA221 Siemens ASD

SPEED, STABILITY, & RELIABILITY N EW! IntelliQuad TM PLUS Combination Smoke and Carbon Monoxide (CO) Detector

VESDA ASPIRATING SMOKE DETECTION INDUSTRY GUIDE SUBSTATIONS

Desigo Fire Safety intelligent detectors for complete safety

Incubators. with BioCote antimicrobial protection

Notifier by Honeywell: SMART Detection. SMART Detection. The Ultimate in False Alarm Technology...Make the SMART choice

BSC CLASS II, TYPE A2 BIOLOGICAL SAFETY CABINET SERIES. Optimum protection of personnel, product and environment. BSC Class

TrueAlarm Analog Sensing

Metal Detection. Metal Detection Solutions For Vertical Packaging Applications SAFELINE

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670

Clean Air Laminar Flow Ceiling CG 3 A CLEAN AIR WORLD. Draft-free, comfortable room climate. Minimal, undisruptive noise level

AUTOMATIC FIRE SUPPRESSION SYSTEMS

ORION. Safety Class 2 100% exhaust. ALMOST Rocket Science

The World s No. 1 Brand of Aspirating Smoke Detection

Intelligent Signature Series Analog Detection

Consultant Specification AGILE Wireless Fire Detection System

FireNET Vapor. Pipe Network Design Guide. June 2013 Document: 25845_00 Part Number: HA

I N T E L L I G E N T A S P I R A T I N G. Intelligent Aspirating Fire Detector. Intelligent Earliest Warning Aspirating Fire Detector

Installation Instruction Venturi-Air Duct Kit. (Part No. S )

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.

ice 3000 Series Atomic Absorption Spectrometers Flame and furnace AAS analysis for routine laboratories

Thermo Scientific 1300 Series A2

ice 3000 Series Atomic Absorption Spectrometers Flame and furnace analysis for routine laboratories

TrueAlarm Analog Sensing

Snifter ATEX22 VERSION. User Manual. Distributor

Early Warning Fire Detection Engineering

INCREASE YOUR LAB EFFICIENCY

Laboratory Automation & Robotic System Enclosures

INCREASE YOUR LAB EFFICIENCY

AnaLASER II Detector. Protection Systems. A UTC Fire & Security Company. High-Sensitivity Smoke Detector (HSSD ) FEATURES DESCRIPTION

FX-PDD Duct Smoke Detector Installation Sheet

THE NEW GENERATION VACUUM PUMP SYSTEM SC

Voyager. 12½ to 25 Ton Light Commercial Packaged Units with ReliaTel Microprocessor Controls

OSID in Challenging Environments

DAIKIN Air Handling Unit Modular

FANERGY Far more than just a fan.

HEATING. Additional heating

FANERGY Far more than just a fan.

Smoke Master SMIA Compact pressurisation and smoke exhaust system

BARRIER TECHNOLOGY RABS & ISOLATORS FOR ASEPTIC PROCESSING

We know what it takes...

TIMS TIMS. Thermal Ionisation Mass Spectrometry.

INSTRUCTIONS. Duct Mount Kit Q900. Description. Operation

Heat Recovery ventilation Dee Fly Cube 550 Field of application Description Advantages Range Technical details Installation Remote controls Servicing

TX7130. Conventional Reflective Beam Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

TUNNEL FANS STANDARD AND HOT SMOKE

UNPRECEDENTED SPEED ULTIMATE POWER. EXTREME intelligence

Key Factors in Selecting a Suitable Web Cleaning System

Transcription:

Aspirating Smoke Detection for Duct Monitoring

Aspirating Smoke Detection for Duct Monitoring Ducts present a challenge for many traditional fire detectors due to environmental factors like high airflow and pressure fluctuations, creating the need for very early warning fire detection and uncompromising accuracy. Ease of installation and ongoing maintenance is also a key concern when monitoring ducts, creating the need for a flexible, user-friendly system that can reduce downtime and ongoing costs. Applications Advanced next-generation FAAST TM aspirating smoke detection can be used in all duct applications including: Heating Ventilation and Air conditioning (HVAC) systems in: - Datacenter cooling systems - Floor voids - Transformer cooling systems - Applications with overpressure, e.g. surgery rooms, clean rooms and laboratories Industrial / manufacturing extraction systems The detector can be located in an easy to access location, whilst the pipe network draws air directly to the detection chamber via sampling points. Advanced airflow monitoring, combined with intelligent dual optical detection ensures accuracy and reliability even in fluctuating environments. Features & Benefits Class Leading accuracy and performance Low-level full system test capability (single operator), with no need for additional equipment or facility downtime Reduced maintenance needs resulting in considerable operational cost efficiencies Acclimate Mode manages fluctuating environmental factors to ensure reliable detection 24/7 Remote monitoring with flexible status updates via email/smart phone/mobile Optimal detection 24/7 with no downtime Key Criteria FAAST provides the earliest and most accurate detection down to invisible smoke concentrations, allowing more time to implement counter measures and prevent full scale evacuations. FAAST XS FAAST XM www.faast-detection.com 2

Application Challenges Duct monitoring is an essential aspect of any building s fire protection; HVAC and extraction systems allow rapid transportation of smoke during fire events that can cause panic as well as delays in the intervention. FAAST TM offers state-of-the-art sensitivity combined with the reliability demanded by these challenging applications: The ability to monitor fast airflows and overcome fluctuating environmental conditions Accurate detection of tiny amounts of smoke False alarm resistant Flexible installation testing and maintenance to overcome access issues Safe and timely evacuations achieved by the earliest, most accurate warning of an issue Installation When designing an ASD system for use in these environments, a system certified for Class B applications is recommended. FAAST TM is being installed in a growing number of ducts, due to its industry-leading accuracy and earliest fire warning capability - up to 0.00095% obs/m. The system can be easily installed by mounting a sample pipe inside the duct, whilst the unit is located in a separate, easy-to-access location. Accurate detection and maximised system uptime can be achieved by considering the following guidance when installing a duct sampling point: Where to locate the pipe and the sampling points How to achieve pressure equalisation How to ensure minimised ongoing maintenance that can be carried out by a single operator Please see Figure 1. below for pipe configuration details. Direction of air flow Exhaust pipe from FAAST detector Air supply to FAAST detector Figure 1. www.faast-detection.com 3

Location of Sample Pipes Sampling pipe location is critical to total system stability and performance; incorrect positioning can result in air turbulence, increasing dust and particulate deposits and compromising HVAC efficiency. Achieving Laminar air flow To allow the airflow to become laminar (air moving at the same speed and in the same direction), the correct location of the sampling pipes is important. The sampling pipe should be located 6-10 times the duct width from the bends or branch connections. It should also be placed centrally in the duct, with the exhaust offset by 1/4 of the total height (see Figure 2. right, showing a longitudinal cut through air duct). Exhaust Pipe Figure 2. Monitoring Large Ducts Multiple rows of sampling pipes can be used for the detection of large ducts (see Figure 3. to the right, showing a longitudinal cut through air duct). Exhaust Pipe Please refer to your local standards and guidelines for further information. Accommodating HVAC Filtration To ensure benchmark sensitivity and accuracy, monitoring should be carried out before the HEPA filtration (High Efficiency Particle Arrestor). This prevents any dilution of the sample, as smoke particles may also be removed by the filter. Figure 3. www.faast-detection.com 4

Sample Holes Sample points should be positioned offset at a 20-45º angle in relation to the air flow. Mark the position of the sampling holes on the outside of the air duct to be able to identify the angle (see marking example in Figure 5. below). Please refer to the table shown below in Figure 4. for information on the number and size of sampling holes to be used, depending on duct width. Duct Width No. of Sampling Holes Hole Size Per Pipe 300mm 2 6.5mm 500mm 3 6.5mm 700mm 4 4.5mm 900mm 5 4mm 1m 6 3.5mm 1.5m 8 3mm 2m 10 3mm Pressure Equalisation To maintain the pressurisation balance, the exhaust should be returned to the duct downstream of the monitoring sample pipe. The exhaust pipe should be located 0.5m downstream from the inlet pipe and the exhaust pipe can be set up in two different configurations: A short pipe that protrudes 50-75mm into the duct (no end cap). This method promotes better overall airflow through the detector, but may be more prone to faults caused by duct airflow fluctuations A pipe with four holes that is the same length as the sampling pipe. This configuration has less air passing through the detector, but is less prone to faults. When employing this configuration position the exhaust holes directly away from the airflow Please see Figure 5. below for further information. Figure 4. Figure 3. Figure 3. Exhaust pipe from detector Intake pipe to detector Marking point for the position of the holes Capped end Direction of air flow Figure 5. www.faast-detection.com 5

Tuning the Airflow Adjusting the sampling pipe position in realtion to airflow can be achived by undertaking the following steps: With the air handling units off, power up the ASD and set the configuration using the design software PipeIQ. After the start-up sequence, allow 5 minutes for the ASD to adjust to the pipe network Set the air handling units to the highest velocity and observe the flow pendulum on the FAAST unit: if the flow is low, carefully adjust the sampling pipe so that the holes are facing the oncoming airflow. If the flow is high adjust the pipe so the holes are facing away from the airflow. A few degrees of rotation may have a significant impact. Wait at least 1 min for the airflow to stabilise and adjust until the airflow data remains in the desired range. Shut off the air handling units and observe the airflow data. It should remain at or near the desired airflow. Mark the angle of rotation on the duct, sealing and securing the sampling tube and then perform the relevant smoke test. Please see Figure 7. bottom left for additional information. Figure 6. Maintenance and Accessibility A key benefit of using FAAST is its simplified ongoing maintenence and testing capability, helping to prevent downtime and reduce costs. Test point A single operator can perform simplfied system testing by extending the sample pipe so it protrudes from the opposite side of the duct. The extended pipe should be fitted with a removable blank end cap. The use of a union socket (as shown in Figure 6. above), is recommended to allow for maintenance. It s also useful for the selection of the final orientation during system commissioning. The sampling pipe should also be installed close to inspection hatches, where possible. Due to the dilution of the smoke particles created by high air flows, a minimum sensitivity of class B is recommended (please consider regional standards and guidelines). Contact Us Figure 7. Copyright 2016 System Sensor. All rights reserved. All technical data is correct at time of publication and is subject to change without notice. All trademarks acknowledged. Installation information: in order to ensure full functionality, refer to the installation instructions as supplied. For further information and design support, please contact Felix Heck on Tel: +49 151 18965125 / Email: felix.heck@honeywell.com or visit www.faast-detection.com www.faast-detection.com 6