TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS

Similar documents
ENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) Signature of Bidder 1 of 11 EPI


Fire Protection & Fire Fighting System

PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM

Following are the systems proposed as per NBC & Local Fire Authority:

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion

The EN54 Part 2 and 4 Fire System

DESIGN PHILOSOPHY FOR FIRE ALARM & DETECTION SYSTEM

Consultant Specification AGILE Wireless Fire Detection System

Annexure - 1. Detectors: Fire Alarm Control Panel :

Part: I TECHNICAL SPECIFICATION

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

3.1 Introduction. 3.1 Introduction

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

DESIGN GUIDELINE SBA 5.11

GAS FLOODING SYSTEM FOR CIFF AT BASEMENT

System 800 Addressable Fire Detection & Alarm System

SUPPLY,INSTALLATION,TESTING AND COMMISSIONING OF SPRINKLER SYSTEM AND FIRE ALARM SYSTEM FOR AIR INDIA LIMITED AT SHAMSHABAD, HYDERABAD.

Quick Selection Guide Fire Systems LSN Periphery

TECHNICAL DATA OBSOLETE

Fire detection and alarm

TrueAlarm ES Analog Sensing

Securing your safety

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Technical Specification For Design and supply of Water Mist cum CAFS (Compressed Air Foam System) Backpack Fire Fighting System

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

MAZAGON DOCK SHIPBUILDERS LIMITED

TrueAlarm Analog Sensing

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions

The EN54 Part 2 & 4 Fire System

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

FOAM CHAMBER MODEL - FCA & FCA-S TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100. Stainless Steel Construction

SOUTH AFRICAN NATIONAL STANDARD

SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD.

SOL-LX-W, SOL-LX-C, RoLP-LX, RoLP Sounder, beacon, and sounderbeacon

A GUIDE TO FIRE DETECTION AND ALARM SYSTEMS

Specification/ Data Sheet

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Winnipeg Fire Department Fire Prevention Branch

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC

Commercial and Light Industrial Fire Alarm Control Panel

Design & Construction Standards, Revised January

LaserFOCUS VLF-250 Engineering Specification

APC Refrigeration Distribution Unit (RDU) Guide Specifications

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Fire Alarm System Fundamentals

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Excel-EN Conventional Fire Control Panel

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

Smoke and Fire Curtains

ESP TECHNOLOGIES LIMITED

XP95 Sounder VAD Base

UV Flame Supervision System

DC POWER DISTRIBUTION BOARD

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

DH500ACDC Intelligent Air Duct Smoke Detector Housing

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

1 NOS. 25mm x 4 mm thick with PVC sleeving e) 1Set, RYB, indicating lamps & CT

D. Reference Standards (Utilize latest editions available):

Bold items are particular to the City of Euless

AlarmLine Linear Heat Detector

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION

Vocia VACIE. Reference Guide

esfr pendent sprinkler vk510 (k25.2)

Aircraft Hangars DESCRIPTION. A single fire area not larger than 40,000 sq. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409

Xenex Conventional Fire Detection & Alarm System

DH100ACDCI Ionization Air Duct Smoke Detector

SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF PORTABLE FIRE EXTINGUISHER- PERFORMANCE AND CONSTRUCTION AS PER IS 15683: 2006

VACIE REFERENCE GUIDE REVISION 1.2.6

Report on First Revision June 2014 NFPA 5000

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

NEVER ACTIVATE THE STROBE WITH THE PCB OUT OF ITS PROTECTIVE CASE. EXTREME CARE IS ADVISED TO REMOVE THE RISK OF ELECTRIC SHOCK.

HEAD OFFICE, SECURITY DEPARTMENT

Conventional Smoke Detectors KFAPO

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

Tel: +44(0) Fax: +44(0) /17 LGM Products Ltd. Web: ISO 9001:2015 certified

MacroAir by Blue Giant AirVolution HVLS Fans

TRIMAX ASIA ENGINEERING & CONSTRUCTION (PG U )

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

EVD-1 Installation, Operation, and Instruction Manual

SECTION NURSE CALL SYSTEM

GAS SUPRESSION CONTROL PANEL:

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

Introduction. Our team

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

Multi-Point Peripherals

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

Transcription:

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS GETCO/ENGG/TS/ Fire detection & Alarm system Dt.06.08.14 1

FIRE DETECTION AND ALARM SYSTEM 1.00.0 INTENT OF SPECIFICATION This section covers the design and performance requirements of the following types of fire alarm systems & extinguishers; a. Fire Detection and alarm System b. Portable Fire Extinguishers c. Wheel/ Trolley mounted Fire Extinguishers 1.00.1 The system design and equipment shall conform in all respects to high standard of engineering, design and workmanship and shall be capable of performing in continuous commercial operation in a manner acceptable to the Owner. The system design shall also conform to TAC/ NFPA norms. 1.00.2 Fire Detection and Alarm system This system shall be provided for GIS room, control room building and Switchyard panel rooms of substations. 1.00.2.1 Suitable fire detection system using smoke detectors and/or heat detectors shall be provided for the entire building, including corridor and toilets. Fire detectors shall be located at strategic locations in various rooms of the building. Each Switchyard panel room shall be considered a separate zone. Adequate number of extra zones shall be provided for Switchyard panel rooms for future bays identified in Single line diagram of the substation. The operation of any of the fire detectors/ manual call point should result in the following; 1. A visual signal exhibited in the annunciation panels indicating the area where the fire is detected. 2. An audible alarm sounded in the panel, and 3. An external audible alarm sounded in the building, location of which shall be decided during detailed engineering. 4. If the zone comprises of more than one room, a visual signal shall be exhibited on the outer wall of each room. 1.00.2.2 Each zone shall be provided with two zone cards in the panel so that system will remain healthy even if one of the cards becomes defective. 1.00.2.3 Coverage area of each smoke detector shall not be more than 80 m 2 and that of heat detectors shall not be more than 40 m 2. Ionisation type smoke detectors shall be provided in all areas except pantry room where heat 2

detectors shall be provided. If a detector is concealed, a remote visual indication of its operation shall be provided. Manual call points (Break glass Alarm Stations) shall be provided at strategic locations in the control room building. All cabling shall be done through concealed conduits. 1.00.2.4 Cables used should be exclusively for fire detection and alarm system and shall be 2Cx1.5sq.mm Cu. cables. Un-armoured PVC insulated FR cables conforming to IS 1554 (Part 1) shall be used. 1.00.3 Portable and Wheel/ Trolley mounted Fire Extinguishers 1.00.3.1 Portable Fire Extinguishers Adequate number of portable fire extinguishers of pressurized water, dry chemical powder, and Carbon dioxide type shall be provided in suitable locations in control room building and FFPH building as indicated in the drawing. In addition to this one (1) CO2 type fire extinguisher of 4.5kg capacity shall be provided for each Switchyard panel room. These extinguishers will be used during the early phases of fire to prevent its spread and costly damage. The design, construction & testing of portable fire extinguishers shall meet the requirements as per clause 1.00.5. 1.00.3.2 Wheel/ Trolley mounted Fire Extinguishers Wheel/Trolley mounted Mechanical foam type fire extinguishers of 50litre capacity, conforming to IS:13386, shall be provided for the protection of the following: 1. Transformers and reactors in 220kV and 132 kv substations where Hydrant/HVWS system is not available. Two (2) nos. for each 220kV or 132kV transformer and reactor. 2. LT transformers in all substations. One (1) no. for each LT transformer. The design, construction & testing of Mechanical foam type 50 litre capacity shall meet the requirements of relevant IS Codes and clause 1.00.5. of this specification. 1.00.3.3 Annunciation Panels a) Location: Control Room i) Indicating lamps showing power supply "ON". ii) Annunciation windows complete with buttons. Details are as follows: Sl. No. Description Number 3

1. Fire in smoke detection system zone (Common Fire Signal) ----------------------------------------------------------------------------------------- b) Location: Substation Control Room ii) Each Switchyard panel room shall be considered as separate zone for fire detection and alarm system. iii) Following annunciations shall be provided. Sl. No. Description Number 1. Fire/Fault (zone alarm module) 1+1(duplicate) For each zone as applicable 2. Spare windows complete in all respect, with relays -- 10 nos. 3. Spare zone alarm modules considering spare bays as per SLD ------------------------------------------------------------------------------------------------- c) Each annunciation panel shall be provided with a hooter. A separate hooter in parallel to the main hooter in fire panel shall be provided in the security room of substation for alert in case of fire. d) Indication for fault in respective areas shall also be provided. Each zone alarm module shall exhibit 'FIRE and 'FAULT' conditions separately. e) Provision for sending data to Remote Control Unit for the following (i) Fire/Fault in Control Room /GIS room/ LCC /Relay Panel Room. 1.00.3.4 All the detectors installed shall be tested for actuation by bringing a suitable source of heat/smoke near the detector and creating a stream of hot air/ smoke over the detector. The exact procedure of this test shall be detailed out by the Employer to the successful Bidder. 1.00.4 HEAT DETECTORS/FIRE DETECTORS 1.00.4.1 Fire Detectors (Used in fire detection and alarm system) 1.00.4.1.1 Fire detectors shall be approved by FOC-London or similar international authorities. 1.00.4.1.2 Both smoke and heat type fire detectors shall be used. Bidder shall clearly 4

indicate the mode of operation of detectors in his proposal. 1.00.4.1.3 The set point shall be selected after giving due consideration for ventilating air velocity and cable insulation. 1.00.4.1.4 Fire detectors shall be equipped with an integral L.E.D. so that it shall be possible to know which of the detectors has been operated. The detectors, which are to be placed in the space above the false ceiling or in the floor void shall not have the response indicators on the body but shall be provided with remote response indicators. 1.00.4.1.5 Approval from Department of Atomic Energy (DAE), Government of India shall be made available for ionization type smoke detectors. All accessories required to satisfy DAE shall also be included in the scope of supply. 1.00.4.1.6 Fire detectors shall be guaranteed to function properly without any maintenance work for a period of not less than ten (10) years. 1.00.5 PORTABLE AND WHEEL/ TROLLEY MOUNTED FIRE EXTINGUISHERS 1.00.5.1 This specification lays down the requirement regarding fire extinguishers of following types : Portable fire extinguishers. a) Pressurized water type. b) Dry chemical powder type c) Carbon Dioxide type Wheel/ Trolley mounted fire extinguishers. a) Mechanical foam type 1.00.5.2 All the extinguishers offered by the Bidder shall be of reputed make and shall be ISI marked. 1.00.5.3 Design and Construction 1.00.5.3.1 All the portable extinguishers shall be of freestanding type and shall be capable of discharging freely and completely in upright position. 1.00.5.3.2 Each extinguisher shall have the instructions for operating the extinguishers on its body itself. 1.00.5.3.3 All extinguishers shall be supplied with initial charge and accessories as required. 1.00.5.3.4 Portable type extinguishers shall be provided with suitable clamps for mounting on walls or columns. 5

1.00.5.3.5 All extinguishers shall be painted with durable enamel paint of fire red colour conforming to relevant Indian Standards. 1.00.5.3.6 Pressurization of water type fire extinguishers shall either be done by compressed air or by using gas cartridge. Both constant air pressure and the gas pressure type shall conform to IS 15683:2006. Both these extinguishers shall be ISI marked. 1.00.5.3.7 Dry chemical powder type portable extinguisher shall conform to IS 15683:2006. 1.00.5.3.8 Carbon Dioxide type portable extinguisher shall conform to IS:15683:2006 and Carbon Dioxide type trolley mounted extinguisher shall conform to IS:2878. 1.00.5.3.9 Wheel/ trolley mounted fire extinguishers of 50 litre capacity Mechanical foam type shall conform to IS: 13386. 1.00.5.4 Painting Each fire extinguisher shall be painted with durable enamel paint of fire red colour conforming to relevant Indian Standards. DATA SHEET FOR HEAT DECTECTOR 1.0 Principle of operation Rate of rise-cum-fixed temperature type. 2.0 Set point of operation o o 5 C per minute / 55 C 3.0 Max. recommended spacing 6 m. 4.0 Normal operating temperature o o -20 C to 70 C 5.0 Guaranteed to function properly without Yes. Accumulated dust to be removed any maintenance work for a period of not periodically by blowing air. less than ten (10) years 6.0 Approval of detector FM of USA, UL of USA, LPCB of U.K. or VDS of Germany 7.0 Cabling. 2C x 1.5 sq.mm. Un-armoured PVC insulated FR cables conforming to IS 1554 (Part 1). 6

DATA SHEET FOR IONISATION SMOKE DECTECTOR 1.0 Principle of operation Ionisation of air by Radio-active source. 2.0 Radio-active source Americium - 241 3.0 Max. recommended spacing 9 m. 4.0 Normal operating temperature o o -10 C to 60 C 5.0 Guaranteed to function properly Yes. Accumulated dust to be removed without any maintenance work for a periodically by blowing air. period of not less than ten (10) years 6.0 Approval of detector FM of USA, UL of USA, LPCB of U.K. or VDS of Germany 7.0 Cabling. 2C x 1.5 sq.mm. Un-armoured PVC insulated FR cables conforming to IS 1554 (Part 1). DATA SHEET FOR FIRE ALARM SOUNDER (HOOTER) 1.0 Construction Deep drawn sheet steel 2.0 Type Dual tone/ Single tone 3.0 Operating Voltage 24V DC ± 10% 4.0 Output Not less than 80dB(A) but not more than 120dB(A) at 1.5m distance. 5.0 Output frequency range 500Hz. to 1000 Hz. 6.0 Operating time 50 minutes (Minimum) 7

7.0 Material of housing. M.S. 18 Gauge 8.0 Colour FIRE RED 9.0 Marking FIRE ALARM. 8