INSTALLATION INSTRUCTIONS GPM SERIES LOOP PUMP MODULES

Similar documents
Operation and Maintenance Haskris LX-Series, R-Series, WW-Series, OPC-Series

QW SERIES WALL SLEEVE (THROUGH WINDOW OPENING) INSTALLATION INSTRUCTIONS. Bard Manufacturing Company, Inc. Bryan, Ohio 43506

DOUBLE O-RING GEO-PRIME TANK Non-Pressurized Flow Center System INSTALLATION INSTRUCTIONS. Model: DORGPT-1 NOTE:

INSTALLATION INSTRUCTIONS WARRANTY

INSTALLATION MANUAL GEO-BOOST GROUND LOOP HEAT EXCHANGER

INSTALLATION INSTRUCTIONS MASTER CONTROLLERS MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH

INSTALLATION MANUAL GEO-BOOST GROUND LOOP HEAT EXCHANGER

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

GEOTEC GV Series High Efficiency Geothermal/Water Source Packaged Step-Capacity Heat Pump R-410A

INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER

Refer to Installation, Operation & Maintenance Manual for More Details

INSTALLATION INSTRUCTIONS

model NO. LSS GALLON SKID MOUNTED HIGH PRESSURE SPRAYER ASSEMBLY / OPERATION INSTRUCTIONS / PARTS

INSTALLATION INSTRUCTIONS MASTER CONTROLLERS MC91AE MC92AE MC93AE MC94AE MC94AEH MC96AEH MC97AE-1

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

Sidekick Pro Rinse Assist Installation and Operation Guide

Earth Loop Fluid Temperatures Ground Water Temperatures 45-75

AQUAS POOL PACKAGE INSTALLATION INSTRUCTIONS FOR MODELS: XPN AQUAS Pool Package

INSTALLATION INSTRUCTIONS ELECTRIC HEAT PACKAGES

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

Transmission Cooling System J Operation Manual. TRANSFLOW Transmission Cooling System Service Tool J

Earth Loop Fluid Temperatures Ground Water Temperatures 45-75

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS

MODELS: Earth Loop Fluid Temperatures Ground Water Temperatures BARD MANUFACTURING COMPANY Bryan, Ohio 43506

INSTALLATION INSTRUCTIONS ELECTRIC HEAT PACKAGES EHWA02-AXD EHWA02-AXH EHWA03-AXH EHWA03-AXK EHWA05-AXH EHWA05-AXK

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Condensing Unit Installation and Operating Instructions

Installation Instructions

Installation and Owners manual

Installation, Operation, and Maintenance Information

Eccotemp L5 and L10 Comprehensive Troubleshooting Guide

2001 Smith Eastern Corporation

AIR-OPERATED OIL PUMPS 73. Air-operated pumps for distribution

2006G2 OPERATING INSTRUCTIONS. 2006G2 Pressure-Vacuum Hand Pump July 2011 SOILMOISTURE

INSTALLATION INSTRUCTIONS

ASTRO EXPRESS 2 HOT WATER DELIVERY SYSTEM

INSTALLATION INSTRUCTIONS

SYSTEMS for CATALYTIC FILTERS

Cool IR. Model C104 - Cooling System. Instruction Manual

CHILLER. Operator s & Installation Manual

P/N CC-100. Coolant Circulator. Operation manual

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION INSTRUCTIONS

OWNER S MANUAL. How to install, operate and maintain your. EcoWater Systems Automatic Sediment Filter. EcoWater Systems Poland

SYSTEM 2000 CHILLED WATER (CAC) EC SERIES -INSTALLATION OPERATIONS AND MAINTENANCE MANUAL-

AGITATOR V DO NOT OPERATE THE MACHINE UNTIL YOU HAVE READ ALL SECTIONS OF THESE INSTRUCTIONS IMPROPER USE OF THE MACHINE WILL VOID THE WARRANTY

Installation and User's Manual for Outdoor Model Residential Ice Machine. Models SCCG50M-1SS and SCCP50M-1SS

OPERATION & MAINTENANCE MANUAL TX600

INDIRECT FIRED WATER HEATERS

Commercial, Residential & Institutional Pumps, Tanks, & Accessories

Rev B, 9/2/2009. Kodiak Chiller Overview

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

SAAB 99 Series H Type Engine. Installation Guide Silicone Cooling System Hoses. Classic Silicone Hoses

AQUAS POOL PACKAGE INSTALLATION INSTRUCTIONS FOR MODELS: AP AQUAS Pool Package

HYDROGEN SULFIDE REMOVAL SYSTEMS

ISO Water Chiller HSO USER'S MANUAL

INSTALLATION INSTRUCTIONS

MAXUM 5 5 Gallon Box Extractor

TITAN FLOW CONTROL, INC.

CWA4-HW (4-Pipe) Rev. 1.2

INSTALLATION AND OPERATING INSTRUCTIONS (2 Through 10-ton Air Cooled Single Stage Chillers)

ENCLOSED UNIT TECHNICAL MANUAL Items # &

union swing check valve spring loaded check valve purging valve pressure relief valve relief valve metered balancing valve

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

REPLACEMENT PARTS MANUAL

AVAILABLE WITH ENERGY SAVING ECM MOTOR

7000BT Eye/Face Washes

OPERATION & MAINTENANCE MANUAL TC670

INSTALLATION & OPERATING MANUAL CWA2 Chilled Water Air Handler with Electric Heat 18,000 60,000 BTUH

Combo Geothermal Heat Pump

SuperStor Ultra Stainless Steel Storage Tank

SpaceKeeper Console (SKC)

USER MANUAL HACCP. Footwear Sanitizing System

INSTALLATION INSTRUCTIONS

Condensing Unit Installation and Operating Instructions

INSTALLATION AND OPERATING INSTRUCTIONS (2 Through 10-ton Air Cooled Single Stage Chillers)

Service Bulletin

INSTALLATION INSTRUCTIONS

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER

MINIATURE THERMOSTATIC VALVE

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

SERVICE MANUAL FOR 6633 SERIES PACKAGE AIR CONDITIONER

CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH

US Filtermaxx. 200,000 BTU Waste Oil Burner

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

THE HEATING BOX. Training Manual. Model KD-HBO100 & KD-HBC100. * KD-HB100 (Open-Loop System) * KD-HBC100 (Close-Loop System)

Autotrol Performa FA Valve

HDLV 55-Gallon Powder Drum Unloader

Installation Instructions. (Applicable to all front door models)

Owner s Manual Guide du propriétaire Manual de Usuario. H Rev -

INSTALLATION INSTRUCTIONS HIGH EFFICIENCY PACKAGED AIR CONDITIONER

SECTION air supply system + WARNING: + NOTE: GENERAL DESCRIPTION COMPRESSED AIR RESERVOIRS / 1.

42 X 24 FT 48 X 24 FT

HOTSPOT. Two Gallon Pump Up Spotter OPERATING & MAINTENANCE

PACKAGED AIR COOLED Product Data Catalog

Liebert Xtreme Density Chiller (XDC) Unit Warranty Inspection Check Sheet

SAFETY OPERATION & MAINTENANCE MANUAL X-405 CARPET EXTRACTOR This unit is intended for commercial use.

DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee Phone (931)

PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL

7800 Neutralizer Installation & Start-Up Guide

Transcription:

INSTALLATION INSTRUCTIONS GPM SERIES LOOP PUMP MODULES Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving, ahead just as planned. Manual: 2100-212A Supersedes: 2100-212 File: Tab 8 Date: 05-20-02

CONTENTS Safety... 1 Application... 1 Inspection... 1 Mounting the Module... 1 Piping the Module... 1 Wiring the Module... 1 Flushing and Filling the System... 4 Pressurizing the System... 5 System Startup... 6 Routine Maintenance... 6 Pumping Specifications... 6 Figures Figure 1 Module Piping... 2 Figure 2 Module Wiring... 3 Figure 3 Valve Positions Flushing the Earth Loop... 4 Figure 4 Valve Positions Flushing the Heat Pump... 4 Figure 5 Pressurizing the System... 5 Figure 6 Pressurizing the System... 5 Figure 7 GPM-1 Performance Specs... 6 Figure 8 GPM-2 Performance Specs... 6

SAFETY Please read and follow the instructions in this manual carefully before attempting to install of service this module. All installations must be done in accordance with all applicable codes. This manual should remain with the owner after installation. APPLICATION The Bard Manufacturing GPM series pump modules are designed to satisfy the fluid circulation requirements for most residential and light commercial closed-loop geothermal heating and cooling systems. Refer to Page 6 for module pumping specifications. INSPECTION At time of delivery, inspect the carton(s) for visible damage and note any damage on the shipping papers. Remove the module from the carton and inspect for damage. If the module shows signs of transit damage, file a claim with the carrier promptly. MOUNTING THE MODULE Using the mounting holes provided, mount the module to a vertical surface as close to the heat pump as possible. The module can be mounted with the flow paths either vertical of horizontal. PIPING THE MODULE Piping connections from the module to the heat pump are best done with a Bard Manufacturing hose kit. The kit consists of 12 feet of 1 ID reinforced flexible hose, tapped brass heat pump adaptors, brass module adaptors, stainless steel hose clamps, and pressure - temperature plugs to permit pressure drop and temperature measurements. Be sure to insulate the flexible hose where water condensation could be a problem. Standard 1 NPT external water connections are provided to make connection with the earth loop piping. Again, insulate the earth loop pipe indoors where water condensation could be a problem. NOTE: Always pipe the module so that the circulator(s) is (are) located between the module valves and the heat pump, never on the earth loop side of the valves. Flushing the earth loop through the circulator(s) would be very difficult or impossible. Refer to Figure 1 on Page 2. WIRING THE MODULE Bard Manufacturing GPM modules use 230VAC single phase circulator pumps. Follow all applicable electrical codes. The module should operate whenever the heat pump compressor operates. A relay will need to be field supplied to control the 203V power supply to the pump module. The 24V coil of the control relay will connect to terminals C and Y on the Bard heat pump 24V terminal Block. See Figure 2 on Page 3 for the connection diagram. Page 1 of 6

FIGURE 1 PIPING THE MODULE PIPE TO GROUND LOOP PIPE FROM GROUND LOOP PUMP MODULE WATER IN BARB X INSERT BRASS ADAPTERS OPTIONAL VISUAL FLOW METER NOTE: IF USED SUPPPORT WITH A FIELD-FABRICATED BRACKET WATER OUT HOSE CLAMPS 1 FLEXIBLE HOSE MIS-1213 Page 2 of 6

FIGURE 2 WIRING CONNECTION DIAGRAM Page 3 of 6

FLUSHING AND FILLING THE SYSTEM All earth loop systems must be flushed to remove air and debris. A high volume, high head circulator pump must be used to flush and fill an earth loop. Pump suction should be from the bottom of a large volume container. A suction line strainer should be used to prevent debris discharged into the container from being returned to the system. The pump discharge hose should be connected to one but not both of the 1 NPT water connections located on the sides of the module. This connection will serve to pump water into the system. Next, connect a return hose to the opposite side of the module to discharge air, debris, and water as the loop is flushed. The return hose should discharge below the container water level to monitor air leaving the system. Fill the container with water. Start by flushing the earth loop. Rotate the module valves as shown in Figure 3. FIGURE 3 MIS-1705 Start the pump. Add antifreeze and water to the container as necessary so that no air enters the system. At first only air will come out of the return hose into the container, followed by water mixed with air and some debris, and finally nothing but water. If you flushing pump assembly is equipped with valves to reverse flow direction through the earth loop during the flushing process, do so occasionally to help remove trapped air. WARNING: The use of calcium as antifreeze is prohibited with Bard Manufacturing loop pump modules due to its corrosive nature, and voids all warranties if used. When air bubbles stop discharging into the container from the return hose, the earth loop is flushed. Next, flush the heat pump. With the pump running, rotate the module valves as shown in Figure 4. Flush the heat pump using the same procedures as flushing the earth loop. FIGURE 4 MIS-1706 Page 4 of 6

PRESSURIZING THE SYSTEM After the earth loop and heat pump are both flushed of air and debris, with the pump running rotate only the module valve discharging into the container (the one pictured on the right) as shown in Figure 5. FIGURE 5 MIS-1707 Flow into the container should stop, and system pressure should increase quickly as the flush pump forces more water into the system. If the water level in the container falls, this indicates that air in the system is being compressed, and further purging is necessary. If purging is complete, rotate the other module valve (the one pictured on the left as shown in Figure 6. FIGURE 6 MIS-1707 MIS-1708 Now turn off the flush pump. The system should maintain pressure. Excess pressure can be released by momentarily rotating either module valve to allow a small volume of water to pass out of the system and into the container. Expect some initial low of pressure due to the expansion of the earth loop pipe under pressure. However, if the system has no leaks, the pressure will stabilize. Normal system operating pressures are 10 to 40 PSI. Positive pressure must exist at all times for the protection of the circulator(s). Remove the flush pump hoses from the module and install the pipe plugs used thread sealant. Inspect the module for leaks. Replace the module cover if you are installing a GPM with Cabinet model. Page 5 of 6

SYSTEM STARTUP After flushing, filling and pressurizing the system, start the loop pump module circulator(s) and check for proper operation. If the circulator(s) are not operating, turn off the power and diagnose the problem. Using a single water pressure gauge, measure the pressure drop at the pressure-temperature plugs across the heat pump heat exchanger. Compare the measurement of flow vs pressure drop data supplied by Bard Manufacturing to determine the actual flow rate. If the flow rate is too low, recheck the selection of the loop pump module model for sufficient capacity. If the module selection is correct. There is probable trapped air or a restriction in the flow circuit. Routine Maintenance The GPM loop pump modules do not require any routine maintenance. PUMPING SPECIFICATIONS FIGURE 7 PERFORMANCE MODEL GPM-1 LOOP PUMP MODULE FIGURE 8 PERFORMANCE MODEL GPM-2 LOOP PUMP MODULE Page 6 of 6