FST DFS Notifier Onyx 640

Similar documents
FieldServer Driver - Serial FS Notifier NCA

Driver Manual. FS (Notifier NFS-640 NFS-320 NFS2-640)

FieldServer Driver - Serial FS SBT-FSI (Siemens Building Technologies Foreign Systems Interface)

FieldServer FS Secutron

FieldServer FS Fike Cheetah

FS Mircom FX2000 Fire Alarm Panel

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

IntesisBox BACnet/IP Server - Notifier ID3000 series

Installation Manual GalaXy G2 / G3 / GD. o Settings GalaXy o Linking with iprotect o Keymap

FS Fike Cheetah

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

FieldServer Driver - Serial FS Grinnell TFX Minerva

ModBus DE-1 INSTALLATION AND USER MANUAL

ICC INDUSTRIAL CONTROL COMMUNICATIONS, INC.

Figure 1. Proper Method of Holding the ToolStick. Figure 2. Improper Method of Holding the ToolStick

User Manual Doc.Ref : JA-KNX-UM. JA-KNX Jablotron KNX Interface ELAUSYS JA-KNX. KNX Interface for Jablotron alarm system.

AES FireTap Model 7770

FS Mircom PRO2000 Fire Alarm Panel

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

Rev Flame Detection Sensor. TF100 User Manual

Simplex Panel Interface Guide

P2267 NETWORK INTERFACE

User manual. KNXgal. version

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

ICC. Macurco Modbus Monitor Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc.

SEC 3500 OI- StatCast RS232 Gas Status Text Broadcast Configuration Manual

GPS Evaluation Kit EVA1037/1080

FIRECLASS Networking. Addressable Fire Alarm Control Panels From Software version 21. Product Application and Design Information FC-A-FCNET-A

User manual. KNXpar. version

IRIS Touch Firmware Enhancements and Additions from Version to Version

Metasys Integrator Compu-Aire Application

Instruction Manual Model Backup Switch, 1 for 8

EIA-232D Protocol And Data Formats for the AFP-200 Fire Alarm Control Panel

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

Laptop / PC Programming Manual

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

User Manual Doc.Ref : EVO-KNX-UM. EVO-KNX Paradox KNX Interface ELAUSYS EVO-KNX. KNX Interface for Paradox alarm system. User Manual.

ECO N DATE DESCRIPTION OF CHANGE CHG

Modbus RTU RS485 Manual

UNC100 Integra Manual

LCF Touch Modbus Datasheet Application Security Advice Caution

M1000 Alarm Annunciator

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

Metasys Integrator TITUS Application

Ei600ZW Z-Wave Module for 10 Year Smoke Sensor with Siren

SETTING UP A VIRTUAL KEYPAD WITH A DSC POWERSERIES ALARM SYSTEM

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Discovery 4 Loop Analogue Addressable Control Panel (NVI & NVA series Protocols)

Addendum to the DVC/DAA Manual (52411) for H Manual Revisions

Smoke Detector and Siren. Manual

PowerLogic ION Setup Meter Configuration Software Configuration Guide

ACTIVE INFRARED BARRIER

ACCURATE ELECTRONICS INC

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D

XLH210: controller for gas leak detectors

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

Configuration and Operation Manual for the Unipos

SyringeHeater.com. Syringe Heater. Thermo-Kinetic Heat Clamping. Model: HEATER-KIT-1LG HEATER-KIT-5SP

TLS-300 UST Monitoring and Leak Detection System

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

FCD-wire Contents. List of Figures

FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators reference guide

INSTALLATION MANUAL DV8OOO. Software Version 1.0

4590 Tank Side Monitor. Service Manual. WM550 Communication Protocol. Software Versionv2.03 SRM011FVAE0808

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

POP_ Smoke Detector

PTE0705 Electric Fence Monitor

Fire control panel detect 3004 plus and accessories

FIB_FGBS-001 Universal Binary Sensor

Fire control panels FC360

TOTALFLOW Technical Bulletin 139

POP_ Smoke Detector

ID3000 intelligent. fire alarm panel

Standard VistaNET GCC Software: 803V029-(VER)(REV)

4100 Programming Instructions-Ver. 8.01

OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL

TECHNICAL DATA SHEET ADDRESSABLE FIRE ALARM SYSTEMS FIRE ALARM CONTROL PANEL LF-6100 A 1/2

OEM REFRIGERANT GAS SENSORS for Leak Detection & Measurement

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

Section 9 System Operation

Ovation Alarm Management System

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter

Intelligent Single Loop Fire Alarm Control Panel

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM. ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM February 2017

Intelligent 2 & 4 Loop Fire Alarm Control Panels

ONYXWORKS AND FIRSTVISION. Version 4

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring

Contents Overview...1 Characteristics...1 Scope of application...2 Working principle... 2 Technical Parameters... 3 Power requirement... 4 About servi

APPLICATION NOTE. Document Type. Application Note. Document Title. Date January Version DS0167/Iss 2. ESP Technical Summary

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

DMFPM-2R MULTIFUNCTIONAL

Concepts for the secure networking of large building complexes

Operator's Handbook. Interactive Fire Alarm System Release 3. Information Panel, BV-320. Protecting life, environment and property...

10 Year Smoke Detector and Siren

Section 8 System Operation

VersAlarm. Installation & Operation Manual

USER MANUAL FOR OPERATING SYSTEM

Metasys Integrator Cleaver-Brooks Application

Transcription:

1 DESCRIPTION The NFS-640 Serial driver allows the FieldServer to record data from Notifier Onyx Series NFS-640, NFS2-640 and NFS-320 Fire Panels over RS-232. The FieldServer primarily acts as a Passive Client receiving unsolicited messages and updating the status of a Notifier Fire Alarm Panel. The FieldServer can actively request that the Notifier panel send the status of all points, devices and zones on a periodic basis. The main purpose of this driver is to record the status of Fire Alarm System detectors and modules in a bit oriented Data Array. It is limited by the information that the Notifier Panel broadcasts in the form of text messages through its RS-232 communication port. The accuracy and timeliness of the data is therefore limited by the frequency of update messages that the Notifier Fire Panel issues, as well as the frequency of the read status requests that the FieldServer makes. The request for status of all points and zones occurs every 10 min by default; this period can be reduced to 5 min or increased to any value with no upper bounds. The types of Notifier messages supported by this driver are summarized in this fact sheet. A detailed table showing each type of panel message the FieldServer recognizes and the effect that it has on the status of points in the data array is also presented. Finally, the device status to the data array mapping is also provided. It is possible to connect through the CRT Port. The disadvantage of doing this is that the use of this port restricts the use of Notifier Networking, thus a fire panel connected to a Noti-Fire-Net will not be supported. If the NFS-640 or NFS2-640 CRT port is used, the FieldServer can actively request that the Notifier panel send the status of all points, devices and zones on a periodic basis. This status request occurs every 10 min by default; and can be reduced to 5 min or increased to any value with no upper bounds. Note that communication through this port does not equate to Port Supervision. The panel must output messages in English. For Notifier 640 Onyx firmware with Spanish firmware (as sold in Mexico and other Central and South American markets) please refer to the fact sheet FST_DFS_Notifier_NFS-640 (Onyx)(Spanish) FieldServer Mode Nodes Comments Client Only one Notifier Panel may be connected to any single RS-232 FieldServer port. 2 FORMAL DRIVER TYPE Serial Client Only Page 1 of 6

3 COMPATIBILITY MATRIX FieldServer Model FS-x2010 FS-x2011 FS-x25 FS-x30 FS-x40 SlotServer QuickServer FS-QS-1010 QuickServer FS-QS-1011 ProtoCessor FPC-FO2 ProtoCessor FPC-FD2 Compatible with this driver 4 CONNECTION INFORMATION 4.1 NFS-640 TB14 Printer Port; NFS2-640/NFS-320 TB12 Printer port Connection type: Baud Rates: Data Bits: Stop Bits: Parity: Multidrop Capability RS-232 or RS-485 (with converter) 2400, 4800, 9600 (Vendor Limitation) (Note 4800 is not applicable for NFS-640) 7 (Vendor Limitation) 1 (Vendor Limitation) Even (Vendor Limitation) No 4.2 NFS-640 TB15 CRT Port; NFS2-640/NFS-320 TB12 CRT Port Connection type: Baud Rates: Data Bits: Stop Bits: Parity: Multidrop Capability RS-232 or RS-485 (with converter) 9600 (Vendor Limitation) 8 (Vendor Limitation) 1 (Vendor Limitation) None (Vendor Limitation) No 5 DEVICES TESTED Device NFS-640 NFS2-640 Tested (Factory, Site) Factory Factory Page 2 of 6

6 CONNECTION CONFIGURATIONS The FieldServer is connected to the Notifier Onyx NFS-640 Panel as shown below. Configure the Notifier Onyx NFS-640 Panel according to manufacturer s instructions. Note that the recommended connection through the printer port is depicted in the diagram. If preferred, connection can be made through the CRT port.. The default setting for the CRT port is off thus the port must be enabled before this driver can be used. Notifier Mother Board Terminal Block 15 ONYX SERIES NFS-640 Tx Rx REF TB15 Printer PORT 2 RX 3 TX 5 GND Blue/white Orange/White Brown FieldServer Part # 8917-16 Pigtail for RJ45 Port Connect to one of the RS-232 Ports on the FieldServer RJ45 8 1 FieldServer P1 Figure 1: Diagram showing connection to the NFS-640 Printer Port. Page 3 of 6

The FieldServer is connected to the Notifier Onyx NFS2-640 Panel as shown below. Configure the Notifier Onyx NFS2-640 Panel according to manufacturer s instructions. Note that the recommended connection through the printer port is depicted in the diagram. If preferred, connection can be made through the CRT port. Notifier Mother Board Terminal Block 12 ONYX SERIES NFS2-640 Printer Tx Rx Ref PC/CRT Tx Rx Ref TB12 2 RX 3 TX 5 GND Blue/white Orange/White Brown FieldServer Part # 8917-16 Pigtail for RJ45 Port Connect to one of the RS-232 Ports on the FieldServer RJ45 8 1 FieldServer P1 Figure 2: Diagram showing connection to the NFS2-640 Panel Printer Port Page 4 of 6

7 COMMUNICATIONS FUNCTIONS - SUPPORTED FUNCTIONS AT A GLANCE: 7.1 Message Types Supported The purpose of this driver is to record the status of devices connected to the Notifier Panel by interpreting text messages sent to the printer or CRT port. Messages that do not directly pertain to device status are not reported. When a read point status is performed, points that have their status reported as TEST are regarded as being in a TROUBLE state. The following subset of event and read status messages is recognized: Active Events SYSTEM NORMAL ALARM: TROUBL/CLR TB ACTIVE/CLR ACT PREALM/CLR PAL DISABL/ENABLE TROUBL IN SYSTEM/CLR TB IN SYSTEM TEST Read Point Status ON/OFF NORMAL ALARM TEST TBL 7.2 Panel Status: Data Array Mapping Parameter Detector Alarm (loop 1) eg 2D001 -> 201 Zone Alarms (software) (special) (releasing) eg Z01 -> 801 F07 -> 907 R00 -> 910 Detector Trouble (loop 1) Bell Circuit Trouble eg B01 -> 1891 B04 -> 1894 Detector Pre-Alarm (loop 1) Module Disable (loop 1) Bits 0-199 200-399 800-899 900-909 910-919 1000-1199 1200-1399 1890-1899 2300-2499 2500-2699 3100-3299 3300-3499 Panel Circuit Disable 3500-3589 On/Off status Panel Circuit 4000-4089 On/Off status Zone (software) (special) (releasing) 4100-4199 4200-4209 4210-4219 Parameter Trouble status Zone (software) (special) (releasing) Parameter Module Alarm (loop1) (loop2) Panel Circuit Trouble eg P1.1 -> 1811 P8.8 -> 1888 Module Trouble (loop 1) Active Monitor Modules (loop 1) Detector Disable (loop 1) On/Off status Module (loop 1) Bits 4500-4599 4600-4609 4610-4619 Bits 400-599 600-799 1800-1889 1400-1599 1600-1799 1900-2099 2100-2299 2700-2899 2900-3099 3600-3799 3800-3999 Bell Circuit Disable 3590-3599 On/Off status Bell Circuit 4090-4099 SystemTrouble 4499 = unknown system trouble 4300+ = listed system troubles 4300-4499 Disable Zone (software) 4700-4799 Page 5 of 6

7.3 Zone Status: Information about zone status will be recorded if incorporated with point status messages. Some messages (e.g. Trouble messages) do not contain zone status information. If the device belongs to multiple zones, only the zone status of the first zone is reported. This limits the accuracy of zone data based on event generated messages, however, when the status is read, the zone status will be valid. 8 DRIVER LIMITATIONS & EXCLUSIONS This driver depends on the stability of the messages received by the printer/crt ports. Should Notifier modify their message protocol, problems can be expected with this driver. The accuracy in recording the Notifier Panel status is dependent on synchronization with the FieldServer. Upon startup, the FieldServer polls the panel for the status of all points and is then fully synchronized. Event messages sent from the Notifier CRT port will also update the recorded status. Some status changes, e.g. zone information do not result in an explicit message to the port, therefore, the FieldServer's record may not be accurate until the next full read status request. When connected via the CRT port, the driver cannot support a fire panel connected to a Noti-Fire-Net, as the Network port (NUP port) cannot be used in conjunction with the CRT port. This driver does not support multi-dropped or networked Notifier panels. Active event messages such as ALARM: include primary zone information; however, a point device such as a detector or module can be associated with a listing of zones, of which only the first is identified in the message. The status of this zone will be recorded by the driver. To update the status of other zones, a read point status poll needs to be sent to the panel. Communication through the CRT port was not designed as a supervised port. Should Notifier wish to make this a supervised port, then this feature will need to be added to the FieldServer. Logic and evaluating equation status was not recorded by FieldServer's driver. These could be added at a later date. Percentage of detector alarms (smoke detectors for instance) is provided in detector status messages but was not implemented in this driver. If requested, this information can be provided as an addition at a later date Page 6 of 6