Ramp It Up VAV Ramps and Controller Possiblities

Similar documents
VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

A state-of-the-art humidifier improves indoor air quality, enhances a family's health and comfort while protecting valuable objects in a home!

State of the Art. Exceptional Reliability

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor

Modulating Controls. Principle of Operation

Job Name Control Systems Description Date

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

TDU Series LCD Thermostat For EFCB and EVCB Controllers. Models. Features. Functions. Onboard Sensors. Model # Temp RH CO2 Color.

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

SEQUENCE OF OPERATIONS

45 Commerce Ave., Unit #2 South Burlington, VT tel: fax:

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

Networkable Fan Coil Controller Specification and Installation Instructions

Verasys System Operation Overview Technical Bulletin

terminal unit accessories

Model APD. Remote alarm panel for diesel motor driven fire pump. Drawing Submittal Package

Humidity Controller Specification and Installation Instructions. Model HRO20

Room Temperature Controller

Digital Precise Air Control - DPAC

Networkable VAV Controller Specification and Installation Instructions. Controller Model EVCB14NIT4X (4 TRIACS / independent / external motor)

I N STALL AT ION & O PERATIO N MANUAL TA 1/ TA 2 CONTROLLER. Redefine your comfort zone.

Your Home. Jacco & Assoc.

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

T6984 A,D,E Electronic Floating Control Thermostats

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

T7984 A,B,C Electronic Modulating Control Thermostats

1.0 Digital Controller

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

INSTALLATION INSTRUCTIONS

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

York 25-Ton VAV Rooftop Unit

Flush-mounted room thermostat

Reference Guide for Microprocessor Controller

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

Options for Diesel Fire Pump Controllers

10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager.

COMcheck Software Version Review Mechanical Compliance Certificate

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

Reference Guide for Microprocessor Controller

Wall-mounted room thermostat with LCD

1. Packaged Variable Air Volume (VAV) Rooftop Units (RTU) with Hot Water Reheat. 2. Geothermal Heat Pump VAV Rooftop Units with Hot Water Reheat

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH,

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

PROJECT: CUSTOMER: ENGINEER: DRAWING CONTENTS: WIRING

Semi flush-mount room thermostat

1.0 Digital Controller

T6984F,G Electronic Floating Control Thermostats

Networkable VAV Controller Specification and Installation Instructions

Fan Coil Unit (FCU) Application Guide

Reference Guide for Microprocessor Controller

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control

Appendix 13. Categories of Cooling and Heating systems

BACnet Programmable TEC (PTEC) VAV Chilled Beam with Demand Control Ventilation (CO2) and Floating or Analog Output Owner s Manual

READ AND SAVE THESE INSTRUCTIONS

CONTENTS. Installation Guide. VT7200 Series

Hydronic & HVAC Control Systems

Better Design, Better Control, Better Systems.

VT8300 Series Installation Guide 24 Vac Low Voltage

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

4Up to 40kW per sq. ft. (24 kw per sq. ft.) 4Modulating, ON/OFF or staging 4Standard from 0.5 to 1000 kw, larger loads available

2017 products.koer.com Page 1 of 14

SE7200 Series Installation Guide

Pressurized Condensate Return System (PCR)

ASHRAE JOURNAL ON REHEAT

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Rosemount High Density Temperature Measurement. Simplify Your Project

INSTALLATION INSTRUCTIONS FOR FANLESS MAKE-UP AIR MODEL NER (USA)

SERIES FAN VAV TERMINAL BOXES TYPE CVFB & SFTB

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

CLN 3 ATTRACTIVE JOINABLE LINEAR PROFILE UP TO 8 SLOT TRACKS AVAILABLE HEATING AND COOLING TERMINAL REHEAT AVAILABLE

Control Sequence Number

Reciprocating Chiller

Direct Steam Injection Humidifier

Rosemount 3051S Electronic Remote Sensors

Modeling projects that require very tight space temperature control

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

MINERVA MX. 800 Series Ancillary Equipment

Neptronic Toll Free: TEL: (514) Fax:(514)

HVAC Controls Upgrades: Requirement Details ( )

Multi-Steam HDR* SKD-R Series Direct Steam Injection Humidifier with Integrated Re-Evaporator. Installation Instructions and User Manual

Control Equipment PTC PTC. modulating wall thermostat. NEP04/

- Essay Control Functions and Benefits

Zoned Rooftop Systems. Light commercial packaged rooftop systems from Trane

ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat

SKR series Steam Humidifier with SDU module (Patent Pending)

T6572A, T6573A,B, T6992A,B, T6993B Digital Fan-Coil Thermostats

EC Series Wall Unit Humidifier

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM

Hot Yoga Climate Tower

FEATURES AND BENEFITS

Feature Summary. I. System

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

VCM-X Controller Technical Guide

Transcription:

Head Office Neptronic 400 Lebeau Blvd. Montreal, Quebec, Canada H4N R6 Tel.: (54) -4 Fax: (54) -6 Toll Free: -800-6-08 Ramp It Up VAV Ramps and Controller Possiblities The following article explains the various VAV ramps available on our products. Not all controllers come with the same options. Refer to the Specification and Installation Instructions of each controller for appropriate information. The first section concerns motor ramps, which are the type of action taken by the damper actuator of the VAV box. The second section covers the duct reheat, baseboard and sub-cool sequence of operation. The third section shows the possibilities and limitations of each controller able to control a VAV box. Motor Ramps Cooling Only The central system can only deliver cool air to the VAV box. All the heat will come from the reheat and baseboard. Cooling Only Application Kfactor Max Cool Min Cool When the zone is calling for cool, the cooling loop output is mapped to the airflow setpoint from the cooling minimum to cooling maximum airflow setpoints. When the zone is in the dead band mode, the airflow setpoint shall be the cooling minimum airflow setpoint. When the zone is calling for heat, the airflow setpoint shall be the cooling minimum airflow setpoint. Heating Only The central system can only deliver hot air to the VAV box. Heating Only Application Kfactor Max Heat Min Heat When the zone is calling for cool, the airflow setpoint shall be the heating minimum airflow setpoint. When the zone is in the dead band mode, the airflow setpoint shall be the heating minimum airflow setpoint. When the zone is calling for heat, the heating loop output is mapped to the airflow setpoint from the heating minimum to heating maximum airflow setpoints. USA NEP Inc. P.O. Box 5 Medford Oregon, USA 9750 Tel.: (54) 5-5746 Middle East & Asia NEP International FZE P.O. Box 5687, Dubai, UAE Tel.: +9755 885487 Fax: +974 4677 Singapore Neptronic Pte Ltd Office D6, #0-8, Mountbatten Square 9, Mountbatten Road, Singapore 98 007 Mobile: +65 88 484 Tel: +65 6650 6 Fax: +65 649 64

Cooling & Heating (Changeover) The central system can deliver cool and hot air to the VAV box. A changeover sensor/switch is required. Changeover (Cooling & Heating) Application Kfactor Max Cool Min Cool Sequence of Operation - System in Cooling When the zone is calling for cool, the cooling loop output is mapped to the airflow setpoint from the cooling minimum to cooling maximum airflow setpoints. When the zone is in the dead band mode, the airflow setpoint shall be the cooling minimum airflow setpoint. When the zone is calling for heat, the airflow setpoint shall be the cooling minimum airflow setpoint. Kfactor Max Heat Min Heat Sequence of Operation - System in Heating DB Cool When the zone is calling for cool, the airflow setpoint shall be the heating minimum airflow setpoint. When the zone is in the dead band mode, the airflow setpoint shall be the heating minimum airflow setpoint. When the zone is calling for heat, the heating loop output is mapped to the airflow setpoint from the heating minimum to heating maximum airflow setpoints. Heat CH The central system can only deliver cool air to the VAV box. When there is a demand for heat, the controller uses the maximum and minimum heating airflow setpoints and activates reheat. This ramp is only supported by the EVCB series. CH (4 airflow setpoints) Application Kfactor Max Cool Max Heat Min Heat Min Cool When the zone is calling for cool, the cooling loop output is mapped to the airflow setpoint from the cooling minimum to cooling maximum airflow setpoints. When the zone is in the dead band mode, the airflow setpoint shall be the cooling minimum airflow setpoint. When the zone is calling for heat, the heating loop output is mapped to the airflow setpoint from the heating minimum to heating maximum airflow setpoints. This sequence can only operate if an output is configured in heating. Heating output activation level Output must be set on Heat Ramp in order to activate the heating airflows Note that the EVCB series controllers can also be configured as CAV (Constant Air Volume). HVAC Controls

Cooling and Heating Ramps Reheat refers to the heating device located after the VAV box. It can either be a water coil or it can be electric. Signals vary based on the type of heater. The supported signals are: On/Off or Stage Heating 00% 80% 60% 40% 0% 0% When the zone is calling for cool, the heating outputs are disabled. When the zone is in the dead band mode, the heating outputs are disabled. When the zone is calling for heat, the heating output is energized to maintain zone setpoint. Stage Heating 00% 80% 60% 40% 0% 0% When the zone is calling for cool, the heating outputs are disabled. When the zone is in the dead band mode, the heating outputs are disabled. When the zone is calling for heat, the heating output is energized to maintain zone setpoint. If temperature continues to drop, the second heating stage is energized. Stage Heating 00% 80% 60% 40% 0% 0% When the zone is calling for cool, the heating outputs are disabled. When the zone is in the dead band mode, the heating outputs are disabled. When the zone is calling for heat, the heating output is energized to maintain zone setpoint. If temperature continues to drop, the second and third heating stages are energized according to the heating demand. HVAC Controls

4 Stage Heating 00% 80% 60% 40% 0% 0% When the zone is calling for cool, the heating outputs are disabled. When the zone is in the dead band mode, the heating outputs are disabled. When the zone is calling for heat, the heating output is energized to maintain zone setpoint. If temperature continues to drop, the second, third and fourth heating stages are energized according to the heating demand. Modulating, Pulse and/or Floating 00% 80% 60% 40% 0% 0% When the zone is calling for cool, the heating outputs are disabled. When the zone is in the dead band mode, the heating outputs are disabled. When the zone is calling for heat, the heating output modulates to maintain zone setpoint. Note that the cooling ramps can be in the same format as the heating ramps, except for pulse signals (heating only). Baseboard refers to the heating devices located on the exterior walls of a building. They are used to maintain temperature for external zones and are great to cut the cold drafts generated by the windows in winter time. Baseboards can be supplied by hot water or they can be electric. The signals supported are the same as the reheat (except for stages). Note that the reheat and baseboards can be activated at the same time or offset from one another. Some prefer setting the baseboards as a first stage and other prefer the reheat as the first stage. Sub-cool refers to the cooling devices located after the VAV box. In terminal unit applications, these are water coils, but DX coils are possible. We do not have many requests for this type of control, but it is available. The supported signals are: - On/Off or Stage (water and DX) - Stages (DX only) - Stages (DX only) - 4 Stages (DX only) HVAC Controls

- Modulating 0-0Vdc & -0Vdc which includes 0-0mA & 4-0mA with a 500Ω resistance (water only) - Floating (water only) Possible configurations based on the controller model for single duct applications Controller models are identified on the top of the page. Application drawing shows the possible configurations and required input/output(s). The controller at the bottom of the page represents the input/outpoint point count and configurations supported. HVAC Controls