R-407A R-448A R-449A

Similar documents
Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

REFRIGERANT CHANGEOVER

Scroll Chillers Transition from HCFC-22 to HFCs

Refrigerant changeover guidelines

Chapter 2. Alternatives to HCFCs and their Characteristics

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane.

Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Positively Innovative R32 R32. Instructions for Use and Handling

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

10/4/2013. The Changing State of Refrigerants

The Essentials Of Working With R-410A

APPLICATION & SERVICE GUIDE

R-404A Alternative with Low Compressor Discharge Temperature

Solstice 452A (R-452A) Reduced GWP and Discharge Temperature for Transport Refrigeration, Plug-Ins and Condensing Units

Gary Parker Refrigerants Product Manager

Opteon XP10. Opteon XP10 Retrofit Guidelines to Replace R-134a. Refrigerant. Introduction. Important Safety Information

Gary Parker Refrigerants Product Manager

Opteon XP40. Opteon XP40 Retrofit Guidelines to Replace R-404A/R-507. Refrigerant. Introduction. Important Safety Information

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION

Energy Use in Refrigeration Systems

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

Seminar 34 Refrigerants Today, Tomorrow, and Beyond

4/19/2013. The Changing State of Refrigerants

Chillers and Refrigerants. Purpose of Today s Presentation. Agenda. GLHN Architects & Engineers, Inc. APPA Institute Session 322 EU

Sustainable Refrigerant Solutions for HVAC-R. Laurent Abbas, Wissam Rached, Brett Van Horn

Specifications for Fluorocarbon Refrigerants

March 10, 2016 San Joaquin Valley RETA Meeting

CHAPTER 1 INTRODUCTION

BRA FACT FINDER Number 19

The complete approach to the care and management of A/C & refrigeration systems

Honeywell Refrigerants. Retrofit Guidelines. R-404A/R-507A to: R-448A Solstice N40

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Specifications for Fluorocarbon Refrigerants

14. The center port of the manifold is used for evacuation, charging and refrigerant recovery.

Harold Ag & Mobile Products

DuPont ISCEON 9 Series Refrigerants

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Specifications for Refrigerants

Aspects of the. Following these key guidelines during a compressor changeout can ensure a successful, more efficient replacement.

New Refrigerants & Selecting Capital Equipment

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

The Current Path of Refrigerants

Low GWP Refrigerants for Air Conditioning Applications

The First 100+ Terms

Refrigerant Glide and Effect on Performances Declaration

A Primer on HFOs. Hydrofluoro-olefins Low-GWP Refrigerants. Brett Van Horn, PhD Arkema Inc.

Refrigerants Management & Retrofits. Mike Saunders & Randy Tebbe Emerson Climate Technologies

The Changing State of Refrigerants. Gary Parker Refrigerants Product Manager

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Worldwide Marine and Offshore Services A GUIDE TO RS REFRIGERANTS FROM STAR INTERNATIONAL. Second Edition

Bert A. McJimsey, Ph.D. Research Engineer The Trane Company Tyler, Texas. Dick Cawley, P.E. UPG Technology Team Leader The Trane Company Tyler, Texas

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

Study of R161 Refrigerant for Residential Airconditioning

Chapter 6. Do s & Don ts in Refrigeration & Air-Conditioning Servicing

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

Air Conditioning Operation and Troubleshooting Matt Dunham

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

CHAPTER 1 INTRODUCTION

NZQA Expiring unit standard 3397 version 4 Page 1 of 5. Convert an automotive air conditioning system from R-12 to R-134a

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

Refrigeration Systems and Accessories

LPG Refrigerator. October 2017 IJIRT Volume 4 Issue 5 ISSN:

COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

System Considerations for Refrigerant Blends with Temperature Glide

Development of centrifugal chiller and heat pump using low GWP refrigerant

A Comparison Between Refrigerants Used In Air Conditioning

Retrofit and High Glide Refrigerants

Opteon XP40. Opteon XP40 Retrofit Guidelines to Replace R-402A (HP80) and R-408A. Refrigerant (R-449A) Introduction. Important Safety Information

PREPARE FOR CHANGE LOW GWP ALTERNATIVES. November 17

ENERGY EFFICIENCY PERFORMANCE SAVINGS SERVICE MANUAL R-290

Development of centrifugal chiller and heat pump using low GWP refrigerant

HVACR Refrigeration

ELIMINATOR Hermetic filter drier for CO₂ DMSC for Sub-critical and DMT for Trans-critical application

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

Refrigerants for commercial refrigeration applications

Specifications for Refrigerants

AIRAH Victoria Refrigerants Update

AMERICAN TRAINCO. CALL ( TRAIN) AMERICAN TRAINCO. Formerly Offered Through Martin Learning, Inc.

1998 Expedition/Navigator Workshop Manual

Cooling Fundamentals

Update on Refrigerant Blends

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

Development of HFC-134a Compressor for Domestic Refrigerator

National Maritime Center

DDNCY (Temporary use)

Use of R1234yf, R744 (CO 2 ) and R134a in automotive air conditioning

Sporlan Valve Division Parker Hannifan/CIC Group

The R-404A Challenge. Commercial Opteon Refrigerant Solutions - The New Industry Standard

DAIKIN's Experience in the production with R32

APPLICATION OF HYDROCARBON REFRIGERANTS IN LOW TEMPERATURE CASCADE SYSTEMS

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

Transcription:

GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9

R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants for R-404A in Low and Medium temperature applications. R-407A, R-448A, and R-449A are zeotropic blends of hydro fluorocarbon or HFC compounds, with some comprised of a different percentage of HFC and HFO compounds. They have no chlorine content, no ozone depletion potential, and a modest direct global warming potential. R-407A, R-448A, and R-449A are NOT drop-in replacements for R-404A. There are differences that must be considered when handling, processing, and applying to new and existing equipment. These guidelines are offered to assist in understanding the differences. R-407A, R-448A, and R-449A should only be used in Tecumseh hermetic compressors and condensing units approved for these refrigerants. REFRIGERANT PROPERTIES A) Pressure / Temperature Table of R-404A vs. R-407A, R-448A, and R-449A is shown in Figure 1. Figure 1 Temperature Pressure F C PSIG KPa R-404A R-407A R-448A R-449A R-404A R-407A R-448A R-449A -40-40.0 4.3-0.9 4.9 4.5 29.6-6.2 33.8 31.3-30 -34.0 9.6 3.2 10.4 9.9 66.1 22.0 71.6 68.4-20 -28.0 16.0 8.4 17.0 16.4 110.2 57.9 117.1 113.2-10 -23.0 23.6 14.8 24.9 24.2 162.6 102.0 171.4 166.7 0-18.0 32.6 22.5 34.2 33.4 224.6 155.0 235.6 229.9 10-12.2 43.1 31.6 45.1 44.1 297.0 217.7 310.7 303.8 20-9.0 55.3 42.3 57.8 56.6 381.0 291.4 397.9 389.7 30-1.0 69.3 54.8 72.3 70.9 477.5 377.6 498.4 488.7 40 4.4 85.3 69.3 89.0 87.4 587.7 477.5 613.3 602.0 50 10.0 103.6 86.0 108.0 106.1 713.8 592.5 744.0 730.8 60 15.6 124.2 105.2 129.4 127.2 855.7 724.8 891.7 876.5 70 21.1 147.4 126.9 153.5 151.0 1015.6 874.3 1057.7 1040.3 80 26.7 173.4 151.5 180.5 177.6 1194.7 1043.8 1243.4 1223.5 90 32.2 202.4 179.3 210.5 207.2 1394.5 1235.4 1450.1 1427.6 100 37.8 234.6 210.4 243.7 240.1 1616.4 1449.7 1679.3 1654.0 110 43.3 270.3 245.2 280.5 276.4 1862.4 1689.4 1932.4 1904.1 120 48.9 309.8 284.0 320.9 316.3 2134.5 1956.8 2211.0 2179.6 130 54.4 353.5 327.1 365.3 360.2 2435.6 2253.7 2516.6 2482.0 140 60.0 401.7 375.0 413.8 408.3 2767.7 2583.8 2850.9 2813.0 150 65.6 455.0 428.3 466.7 460.7 3135.0 2951.0 3215.5 3174.4 Black = Saturated Vapor Green = (in Hg) Vacuum Bold = Saturated Liquid 2018 Tecumseh Products Company LLC. All rights reserved. Page 2 of 9

REFRIGERANT PROPERTIES (Cont d) B) Data Comparing R-404A to R-407A, R-448A, and R-449A. See figure 2. Figure 2 Refrigerant Comparison R-404A R-407A R-448A R-449A ASHRAE Safety Designation A1 A1 A1 A1 GWP 3922 2107 1273 1397 Approved Oil POE POE POE POE Temperature Glide ( C / F) -1 / 2-4 / 8-13.8 / 7-14 / 6.8 Boiling point at 1 bar ( C / F) -46.5 / -51.7-38.9 / -38.0-45.9 / -50.7-46.0 / -50.7 Critical temperature ( C / F) 72.1 / 161.8 82 / 179.6 83.6 / 182.6 81.5 / 178.7 Critical pressure (bar abs / PSIG) 37.3 / 541 45.2 / 654.8 45.5 / 660.9 44.1 / 640.3 1. R-407A, R-448A, and R-449A are non-flammable. They have been assigned an A1 safety classification under ASHRAE 34 and EN 378 standards. A1 means that the substance is classified non-dangerous with the following nomenclature. A = Low toxicity 1 = No flame propagation at 18 C / 64.4 F, 101300 Pa / 14.7 psi. 2. However, because R-407A, R-448A, and R-449A contain R-32 which is mildly flammable, they should not be mixed with air to check for system leaks. This type of mixture can become combustible. See Figure 3. Figure 3 Composition R-404A R-407A R-448A R-449A R-134a 4% 40% 21% 26% R-125 44% 40% 26% 25% R-143a 52% 0% 0% 0% R-32 0% 20% 26% 24% R-1234yf 0% 0% 7% 25% R-1234ze 0% 0% 20% 0% C) Chemical Stability When decomposed, refrigerants generate fluoride ions and organic acids, causing POE oil degradation (PVE is less a concern), leading to corrosion of expansion valves, capillary tube plugging, and compressor bearing wear. 2018 Tecumseh Products Company LLC. All rights reserved. Page 3 of 9

D) Compatibility R-407A, R-448A, and R-449A are compatible with all materials used in Tecumseh hermetic compressors and condensing units. E) Refrigerant Glide Blend refrigerants such as R-407A, R-448A, and R-449A boil and condense at varying temperatures for a given pressure. The range over which the temperature varies is referred to as temperature glide. F) Bubble and Dew Point For blend refrigerants, such as R-407A, R-448A, and R-449A use the dew (vapor) pressure to calculate superheat. To calculate subcooling use the bubble (liquid) pressure. POLYOL ESTERS (POE s) and POLYVINYL ETHERS (PVE s) A) Miscibility 1. Miscibility is the ability of the lubricant and the refrigerant to mix. This miscibility is a very important factor in providing proper heat transfer and in returning lubricant to the compressor in a refrigeration system over its range of operating temperatures. 2. R-407A, R-448A, and R-449A are not miscible with Mineral oils (MO), and Alkylbenzene (AB) oils 3. Polyol Ester (POE) as well as Polyvinyl Ether (PVE) oils are miscible with R-407A, R-448A, and R-449A. B) Moisture 1. Polyol ester and polyvinyl ether oils are 100 times more hygroscopic (ability to absorb moisture) than MO or AB oils. This moisture is difficult to remove even with heat and vacuum. 2. Utmost care must be taken to prevent moisture from getting into the refrigeration system. Do not leave the compressor or system open to the atmosphere for longer than 10 minutes maximum. The preferred method of assembly would be to remove system component plugs and caps just prior to brazing. The maximum system moisture content after completing system processing should be 80 PPM. After running the system with the appropriate drier installed, the system moisture level should be 10 PPM or less. These levels are based on measuring moisture in liquid refrigerant samples taken from the system. 3. Always use an appropriate drier in the system when using R-407A, (See System Cleanliness). C) Compatibility Extensive investigation and testing have been conducted by Tecumseh to determine that Polyol ester and Polyvinyl ether lubricants approved by Tecumseh are compatible with all materials used in Tecumseh hermetic compressors. Contact your Tecumseh sales representative for the latest list of approved oils or see (Policy Bulletin No. 105). SYSTEM DESIGN A) Compressor Selection Only use Tecumseh compressors approved for use with R-407A, R-448A, and R-449A. B) Expansion Valve Selection Expansion valve manufacturers have designed products specifically for use with R-407A, R-448A, and R-449A. Consult the manufacturers for their recommendations. 2018 Tecumseh Products Company LLC. All rights reserved. Page 4 of 9

C) Capillary Tubes Capillary tubes are not recommended when using R-407A, R-448A, and R-449A in low temperature applications. The higher operating temperatures can result in capillary tube plugging. Tecumseh recommends the use of thermostatic expansion valves. D) Driers Tecumseh requires that an appropriate drier be used on every R-407A, R-448A, and R-449A system. See the next section on system cleanliness for more information on driers. SYSTEM CLEANLINESS A) Driers 1. Synthetic lubricants (POE, PVE) are prone to hydrolyze with moisture resulting in the formation of acids. Tecumseh requires that an appropriate drier be used in every R-407A, R-448A, and R-449A application. 2. The types of driers which should be used are the molecular sieve or solid core types that are compatible with R-407A, R-448A, and R-449A. Loose fill driers are not recommended. 3. For specific drier selection, contact your drier supplier. SYSTEM PROCESSING A) Compatibility 1. Polyol ester and Polyvinyl ether oils are good solvents and have a tendency to wash system processing materials such as drawing components, rust inhibitors, and cleaning compounds from system surfaces. Care must be taken to remove such processing materials from all the system components. 2. Residual chlorinated materials should be considered system contamination and eliminated from all internal surfaces of the refrigeration system. B) Evacuation 1. The evacuation levels for R-407A, R-448A, and R-449A systems should be the same as R-404A systems (minimum of 200 microns at the system and pulled from both the low and high pressure sides of the system). If care is not taken to prevent moisture from entering the system components prior to assembly, evacuation time could take longer to achieve acceptable limits of system moisture and non-condensable. Tecumseh recommends a maximum of 2% non-condensable and 80 PPM moisture. The completed system should have a moisture level of 10 PPM or less after running with an appropriate drier installed. These levels are based on measuring moisture in liquid refrigerant samples taken from the system. 2. Polyol ester and Polyvinyl ether oils vaporize much less than mineral oils at the same level of heat and vacuum. Therefore, if oil vaporization was not a problem with the R-404A system processing, it should not be a problem with the R-407A, R-448A, and R-449A system processing. C) Leak Testing Use normal service practices to check the system for leaks. Many leak detector manufacturers have detectors on the market designed for R-407A, R-448A, and R-449A. Consult these manufacturers for their recommendations on the appropriate equipment. 2018 Tecumseh Products Company LLC. All rights reserved. Page 5 of 9

D) Refrigerant Charging 1. R-407A, R-448A, and R-449A are zoetrope refrigerants and must be charged in the liquid state into the liquid line or receiver. Vapor charging can change the refrigerant composition which will change system performance and could result in damage to the system. 2. When pressure testing confirms that the system is free of leaks, evacuate the system thoroughly. Air, moisture and non-condensables must be removed to ensure long term reliability. 3. Break the system vacuum by charging R-407A, R-448A, and R-449A as a liquid refrigerant into the liquid line or receiver. CAUTION: Never start the compressor while it is under a deep vacuum. E) Pressure Controls It may be necessary to adjust the pressure cutouts for low and high pressure controls. This is very important as the controls must be adjusted so the system operating pressures do not exceed the compressors operating window. See Compressor Reliability for approved operating limits. F) Line Sizing Due to the difference in density and mass flow when compared to R-404A the refrigerant line size should be checked when using R-407A, R-448A, and R-449A. This will confirm there are no negative effects on system capacity and oil return. COMPRESSOR RELIABILITY A) Discharge Line Temperature 1. Laboratory testing has proven that R-407A, R-448A, and R-449A have a higher discharge temperature compared to R-404A especially at low evaporating temperatures. Because of this, certain precautions must be followed to maintain compressor reliability. 2. Tecumseh requires that discharge gas temperatures are maintained below 120 C (248 F). 3. If discharge temperatures cannot be maintained within acceptable limits a TREV (temperature responsive expansion valve) will be required to keep return gas temperatures down. 4. A discharge thermostat is also recommended to protect the compressor from high discharge temperatures. B) Return Gas Temperatures / Superheat See Compressor Operating Window pages 7-9 for limits. C) Compressor Cooling For any application using R-407A, R-448A, and R-449A we highly recommend sufficient compressor fan cooling especially at low evaporating temperatures. D) Sound Blankets Do not insulate the compressor with a sound blanket or other means as it will result in elevated discharge temperatures. 2018 Tecumseh Products Company LLC. All rights reserved. Page 6 of 9

E) Liquid Vapor Heat Exchange Do not apply liquid / vapor heat exchangers (also known as desuperheaters) as it will result in elevated discharge temperatures. F) Performance Comparison Reference Figures 4 and 5 below for an estimated compressor capacity and efficiency comparison to R-404A. The information is based on calorimeter data at AHRI (LBP/MBP) rating points. The results may vary depending on the compressor platform. Figure 4 Capacity Relative to R-404A Refrigerant Evaporator Temperature Low Medium R-407A 90% 104% R-448A 96% 106% R-449A 96% 106% Figure 5 COP Relative to R-404A Refrigerant Evaporator Temperature Low Medium R-407A 102% 112% R-448A 104% 108% R-449A 104% 108% COMPRESSOR OPERATING WINDOW A) Return Gas Temperatures / Superheat The operating windows shown on pages 8-9 are provided as guidelines only and need to be adjusted based on the specific compressor applied and the overall design of the refrigeration system. In general terms, limiting superheat to a maximum temperature of 10K (18 F), the operating window is fully or mostly usable with R-407A, R-448A, and R-449A. Note: For additional information on Compressor Operating Limits Reference Policy Bulletin 130 2018 Tecumseh Products Company LLC. All rights reserved. Page 7 of 9

R-407A, R-448A, R-449A Application Boundaries F 2018 Tecumseh Products Company LLC. All rights reserved. Page 8 of 9

R-407A, R-448A, R-449A Application Boundaries C 2018 Tecumseh Products Company LLC. All rights reserved. Page 9 of 9