E25 (D) Automatic controls for general means of egress lighting

Similar documents
Emergency Planning for Institutional Facilities

AHC MEETING #4 PART I ROUND 1 ISSUES CODE CHANGES

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

AD HOC HEALTHCARE COMMITTEE MEANS OF EGRESS WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B MOE COMMITTEE

Defend In Place 2012 IFC Overview of Institutional Occupancies

SAF-BCF SECOND REVISIONS WITH STATEMENTS

Public. Mike Free Health. State of Alabama Department of

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

Public Health Fax: Web Site:

BCAC Egress Work Group

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control

2000 to 2012 Hospital K-tag crosswalk matrix for hospitals 2000 Tag #

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

AHC Meeting #7 July 12-13, Occupancy WG Report

AdHoc Committee on Healthcare Meeting #14 April 1-2, 2015 AHC Group A Changes (Agenda Item 5.0)

ICC Committee on Health Care Hospitals and Nursing Homes Group A Draft Proposals Revised Copyright 2017 International Code Council, Inc.

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

ICC CODE CORNER 2015 International Fire Code

Agency for Health Care Administration

For additional information regarding R-3.1 residential care facilities please contact (951)

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Residential Care Facilities Requirements

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

Residential Based Care Facility Guidelines

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

Report on First Revisions with Statement June 2014 NFPA 101

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Agency for Health Care Administration

Agency for Health Care Administration

First Revision No NFPA [ Section No ]

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

CODE TECHNOLOGIES COMMITTEE NURSING CARE FACILITIES WORK GROUP APPROVED CODE CHANGE DRAFTS CODE GROUP B

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

Agency for Health Care Administration

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES

2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

CHAPTER 7 ALTERATIONS LEVEL

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

Agency for Health Care Administration

Chapter 2: Definitions

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

New Facilities. Minimum Requirements

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Report on First Revisions with Statement June 2014 NFPA 101

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

FIRE SAFETY INSPECTION REPORT

Residential-based Care Facility R-4 Guideline

January 1, 2014 Mandatory Effective Date

2015 Recommended Building Code with Amendments. The Executive Committee of the Central Iowa Code Consortium does ordain as follows:

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA

Status Update K-tag WG 12/8/2011

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

Procedure DESCRIPTION/OVERVIEW

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

FIRE SAFETY INSPECTION REPORT

NFPA Changes

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

CHILD CARE CENTER INSPECTION CHECKLIST 06C

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

EMERGENCY PLANNING AND PREPAREDNESS

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15

Chapter Nursing Homes

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect

NFPA 101 Life Safety Code Culture change 2012

Agency for Health Care Administration

Large Family Daycare Guideline

Residential-based Care Facility R2.1 Guideline

Agency for Health Care Administration

FIRE SAFETY INSPECTION REPORT

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION GUIDELINE RESIDENTIAL CARE FACILITIES 2007 CBC/CFC (R-3.1)

Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC

Code Technology Committee Meeting #31 March 31-April 1, 2015 Care_WTC Recommendations/Elevators

FHCA 2014 Annual Conference & Trade Show

Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters

Agency for Health Care Administration

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

FIRE PREVENTION STANDARDS

Following are code change proposals submitted through Adhoc Health from General study group and related changes. General. Position.

FIRE SAFETY INSPECTION REPORT

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

Transcription:

Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress lighting 1006.1.1 (IFC [B] 1006.1.1) Occupancy sensors. Occupancy sensors shall be permitted to activate the required illumination for the means of egress provided they meet all of the following conditions: 1. The occupancy sensors operate as fail safe devices when the occupancy sensor fails; 2. Where the occupancy sensor is activated by an occupant the area served is illuminated for a minimum duration of 15 minutes; 3. The occupancy sensor operates as a fail safe device in the event of a power supply failure to the emergency lighting system required by Section 1006.3. 4. The means of egress is not required to have illumination to charge luminous egress path markings in accordance with Section 1024.5 Public comment is Request As Modified. Modify the proposal as follows: 1006.1 (IFC [B] 1006.1) Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. 5. Portions of the means of egress provided with automatic lighting controls installed in accordance with Section 1006.1.1. 1006.1.1 (IFC [B] 1006.1.1) Occupancy sensors Automatic lighting controls. Occupancy sensors Automatic lighting controls shall be permitted to activate the required illumination for the means of egress provided they meet all of the following conditions: 1. The controls shall be configured to provide the required illumination within each room or space while occupied. 2. Where provided, occupant sensors shall activate the required illumination the occupancy sensor is activated by an occupant the area served is illuminated for a minimum duration of 15 minutes. 1. 3. Where the automatic lighting controls fail, the controls shall fail in the on or operating state. The occupancy sensors operate as fail safe devices when the occupancy sensor fails; 4. Occupant sensors shall not extinguish lighting The means of egress is not required to have illumination to charge luminous egress path markings in accordance with Section 1024.5 3. 5. All designated emergency lighting luminaries in the means of egress path shall operate in the event of emergency system activation providing light levels in accordance with Section 1006.3. The occupancy sensor operates as a fail safe device in the event of a power supply failure to the emergency lighting system required by Section 1006.3. Page 1 of 7

6. The automatic lighting controls shall be tested as a component of the emergency lighting equipment in accordance with the IFC Section 604.5. Reason: The revised proposal responded to the committee s comments However, there is a concern that there are currently no standards for testing or listing of these controls specifically looking for a fail-safe device. These automatic controls should be limited to general means of egress lighting and not relied on for emergency means of egress lighting. The testing section was added in point 6 and item 5 refines how the emergency means of egress lighting if used. We refined other areas of the proposal to indicate the need to fail on and not interfere with any of the luminous marking system needs. Today s practice: Normal power ON Emergency fixture options Battery powered wall OFF as standard feature Battery back-up ceiling May be turned OFF when space unoccupied, maybe left ON depending on design Designated connected to emergency panels Mostly ON 24/7 Normal power OFF ON as standard feature ON as standard feature ON when transfer switch connects to emergency generator Change we would like to see: Emergency fixture options Battery powered wall Battery back-up ceiling Designated connected to emergency panels Normal power ON OFF as standard feature Turned OFF when space unoccupied Turned OFF when space unoccupied Normal power OFF ON as standard feature ON as standard feature ON when transfer switch connects to emergency generator E69-12(D) Exception for child abduction locks 1008.1.9.6 (IFC [B] 1008.1.9.6) Special locking arrangements in Group I-2. Approved, special egress locks shall be permitted in a Group I-2 occupancy where the clinical needs of persons receiving care require such locking. Special egress locks shall be permitted in such occupancies where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 907, provided that the doors are installed and operate in accordance with Items 1 through 7 below. center, a nursing station or other approved location. 4. A building occupant shall not be required to pass through more than one door equipped with a special egress lock before entering an exit. 5. The procedures for the operation(s) of the unlocking system shall be described and approved as part of the emergency planning and preparedness required by Chapter 4 of the International Fire Code. 6. All clinical staff shall have the keys, codes or other means necessary to operate the locking devices. 7. Emergency lighting shall be provided at the door. Exception Exceptions: 1. Items 1 through 4 shall not apply to doors to areas where persons which because of clinical needs require restraint or containment as part of the function of a psychiatric treatment area. Page 2 of 7

2. Items 1 through 4 shall not apply to doors to areas where a listed egress control system is utilized to reduce the risk of child abduction. Public comment is Request As Modified. Modify the proposal as follows: 1008.1.9.6 (IFC [B] 1008.1.9.6) Special locking arrangements in Group I-2. Approved, special egress locks shall be permitted in a Group I-2 occupancy where the clinical needs of persons receiving care require such locking. Special egress locks shall be permitted in such occupancies where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 907, provided that the doors are installed and operate in accordance with Items 1 through 7 below. center, a nursing station or other approved location. 4. A building occupant shall not be required to pass through more than one door equipped with a special egress lock before entering an exit. 5. The procedures for the operation(s) of the unlocking system shall be described and approved as part of the emergency planning and preparedness required by Chapter 4 of the International Fire Code. 6. All clinical staff shall have the keys, codes or other means necessary to operate the locking devices. 7. Emergency lighting shall be provided at the door. Exceptions: 1. Items 1 through 4 shall not apply to doors to areas where persons which because of clinical needs require restraint or containment as part of the function of a psychiatric treatment area. 2. Items 1 through 4 shall not apply to doors to areas where a listed egress control system is utilized to reduce the risk of child abduction from nursery and obstetric areas of a Group I-2 hospital. Reason: This issue of protection against child abduction is an important one for hospitals. However, we also understand the code development committee s concern that the proposed exception could be read to allow for an entire hospital to be locked down. The modification will limit these systems to the high risk areas of the nursery and obstetric areas only. E74-12(D) signage at delayed egress locks 1008.1.9.7 (IFC [B] 1008.1.9.7) Delayed egress locks. Approved, listed, delayed egress locks locking systems, shall be permitted to be installed on doors serving any occupancy except Group A, E, and H occupancies in buildings that are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 907, provided that the doors unlock in accordance with Items 1 through 6 below. A building occupant shall not be required to pass through more than one door equipped with a delayed egress lock before entering an exit. center. Page 3 of 7

4. The initiation of an irreversible process which will release the latch in not more than 15 seconds when a force of not more than 15 pounds (67 N) is applied for 1 second to the release device. Initiation of the irreversible process shall activate an audible signal in the vicinity of the door. Once the door lock has been released, by the application of force to the releasing device, relocking rearming shall be by manual means only. Exception: Where approved, a delay of not more than 30 seconds is permitted on a delayed egress door. 5. A sign shall be provided on the door located above and within 12 inches (305mm) of the release device reading: PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 (30) SECONDS. Exception: Where approved, the installation of a sign is not required when it interferes with the safety of the residents in Group I occupancies. 6. Emergency lighting shall be provided at the door. Public comment is Request As Modified. Modify the proposal as follows: IBC 1008.1.9.7 (IFC [B] 1008.1.9.7) Delayed egress locks. Approved, listed, delayed egress locking systems, shall be permitted to be installed on doors serving any occupancy except Group A, E, and H occupancies in buildings that are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 907, provided that the doors unlock in accordance with Items 1 through 6 below. A building occupant shall not be required to pass through more than one door equipped with a delayed egress lock before entering an exit. center. 4. The initiation of an irreversible process which will release the latch in not more than 15 seconds when a force of not more than 15 pounds (67 N) is applied for 1 second to the release device. Initiation of the irreversible process shall activate an audible signal in the vicinity of the door. Once the door lock has been released, by the application of force to the releasing device, relocking rearming shall be by manual means only. Exception: Where approved, a delay of not more than 30 seconds is permitted on a delayed egress door. 5. A sign shall be provided on the door located above and within 12 inches (305mm) of the release device reading: PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 (30) SECONDS. Exception: Where approved, in Group I occupancies, the installation of a sign is not required when the instructions compromise the safety of the residents in Group I occupancies where persons who because of clinical needs require restraint or containment as part of the function of the treatment area. 6. Emergency lighting shall be provided at the door. Reason: When housing dementia patient, especially first stage Alzheimer patients, reading is often still in their capabilities. They are ambulatory, often in good physical condition, but not capable of self preservation. Their greatest dangers are elopement into traffic, ice and snow, darkness and wildlife. The intent of the proposed exception is to address this important safety issue. Families are relying on these facilities to keep their loved ones safe. Page 4 of 7

The MOE committee had a concern that the instruction signage at delayed egress locks was needed for visitors. In all Group I facilities, staff is trained to assist in evacuation of all occupants, including residents and visitors. In addition, delayed egress systems already include connection to both the sprinkler system and the fire detection system, both required under this section. In the event of a fire activation of the fire alarm or sprinkler system or power failure, all delayed egress doors unlock from the inside and allow free unobstructed egress. Dementia units are staffed to assist residents and visitors in fire and weather emergencies with practiced emergency plans. Having a direct signage at the door adds to the likelihood that there will be elopements. All doors with delayed egress systems will still be required to have exit signs. Where facilities that are faced with a choice between applying for delayed egress with escape instructions at each door, or going to a full lockdown such as controlled egress, the facility will always pick pursuit of the latter due to concerns for patient safety. Several of the locking options do allow locking occupants in where there are staff releases the locks. This option would allow a facility to address patient safety without totally relying on staff to open exit doors in a fire event. G71-12 Part I (AS) change or terminology Public comment requests Disapproval. 407.4.2 Travel distance Distance of travel. The travel distance of travel between any point in a Group I- 2 occupancy sleeping room and an exit access door in that room shall be not greater than 50 feet (15 240 mm). 407.4.3.3 One intervening room. For rooms other than sleeping rooms located within a care suite, exit access travel from the care suite shall be permitted through one intervening room where the travel distance of travel to the exit access door from the care suite is not greater than 100 feet (30 480 mm). 407.4.3.4 Two intervening rooms. For rooms other than sleeping rooms located within a care suite, exit access travel within the care suite shall be permitted through two intervening rooms where the travel distance of travel to the exit access door from the care suite is not greater than 50 feet (15 240 mm). 407.4.3.5.3 Travel distance Distance of travel. The travel distance of travel between any point in a care suite containing sleeping rooms and an exit access door from that care suite shall be not greater than 100 feet (30 480 mm). 407.5 Smoke barriers. Smoke barriers shall be provided to subdivide every story used by persons receiving care, treatment or sleeping and to divide other stories with an occupant load of 50 or more persons, into no fewer than two smoke compartments. Such stories shall be divided into smoke compartments with an area of not more than 22,500 square feet (2092 m 2 ) and the travel distance of travel from any point in a smoke compartment to a smoke barrier door shall be not greater than 200 feet (60 960 mm). The smoke barrier shall be in accordance with Section 709. 408.6.1 Smoke compartments. The number of residents in any smoke compartment shall be not more than 200. The travel distance of travel to a door in a smoke barrier from any room door required as exit access shall be not greater than 150 feet (45 720 mm). The travel distance of travel to a door in a smoke barrier from any point in a room shall be not greater than 200 feet (60 960 mm). 408.8.1 Occupancy Conditions 3 and 4. Each sleeping area in Occupancy Conditions 3 and 4 shall be separated from the adjacent common spaces by a smoke-tight partition where the travel distance of travel from the sleeping area through the common space to the corridor exceeds 50 feet (15 240 mm). 422.3 Smoke compartments. Where the aggregate area of one or more ambulatory care facilities is greater than 10,000 square feet (929 m 2 ) on one story, the story shall be provided with a smoke barrier to subdivide the story into no fewer than two smoke compartments. The area of any one such smoke compartment shall be not greater than 22,500 square feet (2092 m2 2 ). The travel distance of travel from any point in a smoke compartment to a smoke barrier door shall be not greater than 200 feet (60 960 mm). The smoke barrier shall be installed in accordance with Section 709 with the exception that smoke barriers shall be continuous from outside wall to an outside wall, a floor to a floor, or from a smoke barrier to a smoke barrier or a combination thereof. Page 5 of 7

Reason: Code change G70 has rewritten this Section 407 for clarity, however, the sections continue to deal with exit access travel distance to exit a room or suite, not distance to a specific object (as indicated in Part II and III of G71). The same holds true for the smoke compartments in Group I-3 and ambulatory care facilities (Sections 408 and 422). Therefore, the Adhoc Health Care committee is asking for disapproval of Part 1 only. G77(AS) & G80(AS) G80-12 (AS) 407.11 Electrical systems. In Group I-2 occupancies, the essential electrical power for electrical components, equipment and systems shall be designed and constructed in accordance with the provisions of Chapter 27 and NFPA 99. IFC 604.2.15 (IBC [F] 2702.2.16) Group I-2 Occupancies. Essential electrical power for Group I-2 occupancies shall be in accordance with Section 407.11. Public comment request AM: 407.11 Electrical systems. In Group I-2 occupancies, the essential electrical power system for electrical components, equipment and systems shall be designed and constructed in accordance with the provisions of Chapter 27, and NFPA 99 and NFPA 101. Fuel supplies for emergency power systems shall be provided in accordance with NFPA 99 and NFPA 110. [F] 2702.2.16 Group I -2 Occupancies. Essential electrical power systems for Group I-2 occupancies shall be in accordance with Section 407.11. Reason: The intent of the modification would be to revise the term essential electrical power to use the NFPA defined term: Essential Electrical Systems is defined by NFPA 99-2012, as follows: 3.3.48 Essential Electrical System. A system comprised of alternate sources of power and all connected distribution systems and ancillary equipment, designed to ensure continuity of electrical power to designated areas and functions of a health care facility during disruption of normal power sources, and also to minimize disruption within the internal wiring Appendix commentary: A.3.3.48 Essential Electrical System. The essential electrical system can be comprised of three branches: life safety branch, critical branch, and equipment branch. In addition, the intent is to coordinate this proposal with G77. (Adhoc Health Care committee to discuss alternatives and pick one.) Option 1 - The G80 change refers back to chapter 27 which has the link to NFPA 110 for the review of the G80 includes a direct reference to NFPA 99, which would allow the use of the risk based approach supported by the committee. I believe our change covers the spirit of G77, with the exception of the 96 hour rule. Option 2 - Adding a reference to NFPA 101 will address the idea of duration. G77 12(AS) 407.9 Emergency power. A minimum of 96-hours of emergency power shall be provided to the essential electrical systems in Group I-2 hospitals and nursing homes. Emergency power shall be connected to the life safety branch and the critical branch defined in NFPA 70, and further defined as emergency power supply systems in Chapter 4 of NFPA 110. Page 6 of 7

IFC 604.2.16 (IBC [F] 2702.2.17) Group I-2 Occupancies. Emergency power shall be provided in Group I-2 hospitals and nursing homes in accordance with Section 407.9 of the International Building Code. Public comment requests Disapproval. Reason: The committee requests disapproval of this proposal based on the following three reasons. In addition, the committee feels that the proposed revisions to G80 will address at least a portion of the concerns in this proposal. First reason: G77 requires a 96 hour fuel supply. NFPA only requires this for Level 1 systems (not necessarily all nursing facilities) in a seismic risk area. This proposal would greatly increase the scope of that requirement counter to the intent of the NFPA standards. The reason statement from the committee says they would rather use a risk based approach in NFPA 99. Secondly, G77 makes a statement that technically flawed. It says that emergency power should only be connected to the critical or life safety branches it could be read to disallow the third branch of the traditional essential electrical system: the equipment branch. This is in direct conflict with NFPA 99. Thirdly, the reference to NFPA 110 for e-power connection to branches is incorrect as well NFPA 110 does not address the division of branches of e-power it addresses the performance of the system, components and switches. Chapter 4 in the 2010 version only deals with the classification of the e-power Page 7 of 7