MANDATORY MEASURES MANDATORY LIGHTING CONTROLS (a) Area Controls: Manual controls that control lighting in each area separately

Similar documents
MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130)

Here we see the list of auto shutoff controls we will cover in the next few slides

Code Compliance. Lightcloud. Guides for California Title 24 & ASHRAE

TITLE 24 ICONOGRAPHY. Iconography System

Code Review TITLE PRESENTED BY POURIA NIKNAM

INSPECTION REQUIREMENTS: ENERGY CODE LIGHTING & ELECTRICAL NON-RESIDENTIAL

California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings

Note: A summary of the applicable code sections is shown in the CEC _Table100A.

California Title Design Guide for Smart Lighting Control and Energy Solutions

Code Compliance Commercial Application Guide

WSA120: New Energy Codes and Lighting Controls

Dissecting Lighting Control Requirements ANSI/ASHRAE/IES Standard & 2013

ASHRAE October 18, 2013

Hospitality Title Solutions

Are LED s ready for Prime Time?

Education Title Solutions

MANDATORY MEASURES DAYLIGHTING. (Reference: Sub-Chapter 4, Section 130)

Office Title Solutions

Codes and Controls Commercial Building Energy Code Requirements for Light Control. Michael Jouaneh, CEM, LEED AP September 20, 2012

What s New in the 2013 Energy Code? Changes to mandatory Title 24 lighting requirements

Decoding 2016 Title 24, Part 6

Healthcare Title Solutions

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Ceiling Mount Sensors B4-B9. Occupancy and Vacancy Sensors B10-B15 B16-B17. Wall Mount Occupancy Sensors B-1

Wireless Lighting Control Made Easy

Lighting Control Strategies. to meet code requirements save energy and improve building performance

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Lighting Summary - Interior

SENSORS. Vacancy Sensors. Occupancy Sensors A4-A7 A-1

visual environment technologies etcconnect.com

Reduce lighting energy costs with controls

Aesthetic, energyefficient. control solutions for hospitality facilities QUICK GUIDE TO LIGHTING CONTROL FOR HOTELS

MANDATORY MEASURES. There are two major steps for exterior spaces to comply with Title 24:

CA TITLE 24 QUICK SOLUTIONS GUIDE FOR

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

WELCOME TITLE 24 REQUIREMENTS & THE MAXLITE PRODUCT LINE. 9/5/14 Webinar Presented by: Greg Murphy

Lighting Controls. Energy-Saving Solutions For Efficient Buildings

ANSI/ASHRAE/IES

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2012

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ Tel

Energy Codes. Connected Lighting simplified by Eaton. design and application guide

Table of Contents. Fast Fact. Sensor Models 2 Advantages of Sensors 3 FAQs 4-5

B. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.

PRESCRIPTIVE APPROACH

Lighting Application Guide for K-12 Classrooms

ANSI/ASHRAE/IES

MANDATORY MEASURES OUTDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.2)

Best practices in lighting design to comply with California s Title 24 energy code

2015 IECC. Design Guide for Smart Lighting Control and Energy Solutions

Best practices in lighting design to comply with California s Title 24 energy code

2017 Lighting Incentive

600 Watt Dimmer Install Guide

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 26 ELECTRICAL

A Guide for Applicants and Lighting Designers

Demand Responsive Lighting Controls

Lighting Control Solutions for Parking Facilities

Oregon Non-Residential Building Energy Code

Technology. Occupancy & Vacancy Sensors & Timers. Technology. Occupancy & Vacancy Sensors & Timers L-2

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors

F series. echoflex. Slim Line Dimming Controller. Product Overview ER1S-FC

Applied Lighting Controls

2018 IECC Electrical & Lighting Systems

Pacific Gas and Electric Company Energy Efficiency Rebates for Your Business. Lighting Rebate Catalog Saving energy for a brighter future

SECTION LIGHTING CONTROL DEVICES AND CONTROL PANELS

Advanced Lighting Control for High Building Performance

Application Guide to CA Title 24

Dimming Ballast + Controls and CALCTP Bonus. New Product Overview

F series. Complete Room Controller. echoflex Powered by ETC. Product Overview ERDRC-FC

For additional information regarding R-3.1 residential care facilities please contact (951)

CS1200 WHT Pir Ceiling Mount Occupancy Sensor

Advances in Lighting Controls and the Impact of ASHRAE Requirements. Rich Rattray, LC OSRAM SYLVANIA

Time Warner Center at Columbus Circle, the home of Related s offices. Credit: Green Light New York

Good-Better-Best LED Retrofit Guide

August 15, 2013 Page 1 of 19

Dimmable General Area Use High Bay 320 Watt LED Light Fixture - Low Profile - High Efficiency

Wireless Indoor Lighting Control System

A Guide to the Commercial Building Tax Deduction. Effective: January 1, 2006 to December 31, 2008 HL /07

Hubbell Controls Application Guide to CA Title 24 A SUPPLEMENTAL GUIDE TO CODE REVISIONS IMPACTING LIGHTING CONTROL

C A L I F O R N I A E N E R G Y C O M M I S S I O N

DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD

Energy Management. The Smart Choice for Lighting Control and Energy Solutions

What You Need to Know About California Compliance T20, T24 and JA8 Chris Primous VP OEM National Accts and Industry Relations April 18, 2018

LIGHTING CONTROLS

2017 Michigan Energy Code Changes Electrical Provisions-Commercial Michigan Energy Code Training and Implementation Program

Versatile wall switch sensors maximize payback and simplify code compliance

Sensors and Timers P&S. designed to be better. A COMPLETE LINE FOR ENERGY SAVINGS AND CONVENIENCE.

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Distributed Low-Voltage Power System. design and application guide

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Advances in Non-Residential Lighting Technologies

Lighting Control. Sensor Daylight 2. Daylight+Motion 3. Daylight+Motion+Control 4. Daylight+Motion+Control IP67 5

Supporting the Requirements of EPAct 2005 Tax Deductions

visual environment technologies etcconnect.com

Advanced Lighting For Office

COMcheck Software Version Interior Lighting Compliance Certificate

A Simpler and Smarter Wireless Lighting Control Solution. Design & Application Guide

FROM THE WORLD S FIRST GFCI RECEPTACLE TO OUR GAME-CHANGING LINE OF PASS & SEYMOUR PLUGTAIL DEVICES, PASS & SEYMOUR PRODUCTS HAVE A REPUTATION FOR

Transcription:

MANDATORY MEASURES INDOOR LIGHTING CONTROLS (Reference: Sub-Chapter 4, Section 130.1) MANDATORY LIGHTING CONTROLS 1. 130.1 (a) Area Controls: Manual controls that control lighting in each area separately 2. 130.1 (b) Multi-level Controls: Dimmability. Allow occupants to choose the appropriate light level for each area 3. 130.1 (c) Shut-off Controls: Automatically shut off lighting or reduce light levels when illumination is not needed 4. 130.1 (d) Automatic Daylighting Controls: Adjust electric lighting in response to the presence of daylight 5. 130.1 (e) Automated Demand Response: Receive and automatically respond to demand response (DR) signals Section 130.1 50

SLIDE 51 SECTION 3 MANUAL ON/OFF CONTROLS An area is a space enclosed by ceiling-height partitions. All lighting in each area must be controlled separately from luminaires in other areas by manual on/off lighting controls that are: 1. Readily accessible 2. Located in the same room or area as the lighting they control and with the lighting in view 3. Able to provide any required dimming or multi-level controls steps in addition to on/off 4. General lighting is separately controlled from all other lighting systems in same area 5. Track, display, ornamental, and special effect lighting systems are controlled separately Section 100.1 52

EXCEPTIONS May use a manual control that is NOT accessible to general public for the following spaces: Public restrooms with more than 2 stalls Parking areas Stairwells and corridors Section 130.1 (a)2 53 EGRESS LIGHTING Up to 0.2 w/ft² of lighting in any area within a building may be continuously illuminated during occupied times Unoccupied times: 0.1 w/ft² lighting OFF 0.1 w/ft² lighting ON Section 130.1 (a) 54

MULTI-LEVEL LIGHTING CONTROLS Title 24 sets a minimum number of control steps and illuminance uniformity requirements for most major luminaire types (see TABLE 130.1-A). These requirements are required in addition to any mandatory manual, daylight, shutoff, or demand response controls. Dimmable luminaires shall be controlled by a dimmer control that is capable of achieving the required multi-level steps and ON/OFF functionality. The criteria in 130.1 (b) applies to general lighting for enclosed areas that: Are at least 100 ft 2 in size Have a connected lighting load over 0.5 W/ft 2 Have more than one luminaire or more than two lamps Section 130.1 (b) 55 TABLE 130.1-A 56

TABLE 130.1-A 57 MULTI-LEVEL EXCEPTIONS Classrooms with a connected general lighting load of 0.7 watts per square feet or less and public restrooms shall have at least one control step between 30-70 percent of full rated power. An area enclosed by ceiling height partitions that has only one luminaire with no more than two lamps. The areas specified in Sections 130.1(c)6 and 7 are not also required to meet the requirements of Section 130.1(b). Areas where full or partial OFF occupant sensing controls are required Areas where partial OFF occupant sensing controls are required Section 130.1 (b) 58

SHUT-OFF CONTROLS Automatic shut-off controls turn lights off when a space is unoccupied. All lighting must be controlled by one or more of the following: 1. Occupant sensing control 2. Automatic time-switch control 3. Building Energy Management System 4. Other control mechanism capable of automatically shutting off all lights for vacant periods A single control may not monitor more than 5,000 ft 2 Photo: Lutron Section 130.1 (c) 59 SHUT-OFF CONTROLS In the following spaces, 100% shut-off controls MUST be occupancy sensing: 1. Offices 250 ft 2 or smaller 2. Multipurpose rooms smaller than 1,000 ft 2 3. Conference rooms of any size 4. Classrooms of any size Section 130.1 (c) 60

SHUT-OFF CONTROLS When multi-level controls are required: Partial-on occupancy or vacancy sensors shall be used When multi-level controls are not required: Lighting is turned 100% off with occupancy controls Section 130.1 (c) 61 SHUT-OFF CONTROLS Countdown timer switches may only be used in: 1. Single-stall bathrooms smaller than 70 ft 2 (Max timeout 10 minutes) 2. Closets smaller than 70 ft 2 (Max timeout 10 minutes) 3. Aisles in server rooms smaller than 500 ft 2 (Max timeout 30 minutes) If time-based controls are used, occupants there after hours must be able to activate lighting as needed: Manual switch Temporary override Occupancy-based control Section 130.1 (c) 62

FULL OR PARTIAL-OFF OCCUPANCY CONTROLS Adaptive controls in secondary spaces: Stairwells/corridors, Aisleways and open areas in warehouses, and Library book stacks 10 feet of longer Controls must be capable of: Partially reducing lighting power during hours of operation by at least 50% when vacant Providing 100% of light when someone is detected in the space Section 130.1 (c) 63 CASE STUDY: ADAPTIVE CORRIDOR LIGHTING Latham Square (Oakland, CA) In January 2012, CLTC installed adaptive (bi-level) lighting controls on 12 floors of the Latham Square office building 174 Luminaires retrofitted with 64W T8 fluorescents Average energy savings: 86% 64

MIXED-USE BUILDINGS For mixed-use buildings (e.g. high-rise residential, hotels, and motels) with a total interior common area that is greater than 20 percent of the floor area of that building, the common areas must comply with the Nonresidential Lighting Standards, while dwelling units must comply with the Residential Lighting Standards. 65 SHUT-OFF CONTROLS EXCEPTIONS Spaces that are exempt from automatic shut-off controls requirements: 1. Buildings with lighting in continuous use 24 hours/day, 365 days/year 2. Areas where partial on/off controls are required instead of shut-off controls (such as stairwells and corridors) 3. Electrical equipment rooms 4. Emergency egress lighting Section 130.1 (c) 66

AUTOMATIC DAYLIGHTING CONTROLS Automatic daylight controls adjust electric lighting power when ample daylight is available. Ample daylight is defined by the standards as 150% of the designed light level for electric lighting. Automatic daylighting controls are required for luminaires that: 1. Provide general lighting 2. Are at least half in a skylit or sidelit area 3. Are in an area where the total installed general lighting power is at least 120 watts 4. Are located in an area which has at least 24 ft 2 of glazing Photo: Lutron Section 130.1 (d) Photo: Lutron 67 AUTOMATIC DAYLIGHTING CONTROLS Automatic daylighting controls requirements: 1. Controlled lighting with an LPD greater than 0.3 W/ft 2 must have multi-level lighting in accordance with Table 130.1-A. 2. Controlled lighting + daylight must equal or exceed the controlled electric lighting level without daylight. 3. When there is ample daylight detected, the general lighting power in that space must be reduced by at least 65%. Section 130.1 (d) 68

DEMAND RESPONSE When the demand for electricity threatens to exceed supply, the power grid becomes less stable and the risk of outages increases. Demand response (DR) programs allow end users to temporarily reduce their electricity use in response to a notice or automated signal sent from a utility, independent system operator (ISO) or other power provider. This flexibility helps reduce peak demand and maintain grid stability. Currently, participating customers also receive financial incentives. Image: Lutron Section 130.1 (e) 69 DEMAND RESPONSE Lighting is extremely well-suited to DR 1. Peak demand periods typically overlap daylight hours 2. Research indicates illuminance levels can be reduced by as much as 20% without occupants detecting the change 3. Light levels can be immediately restored when DR events end Buildings larger than 10,000 ft 2 must be capable of responding to a DR signal by automatically reducing lighting power at least 15% below the total installed lighting power while maintaining the uniformity requirements listed in Table 130.1-A. Spaces that use less than 0.5 W/ft 2 are exempt and cannot be counted toward ADR compliance. Section 130.1 (e) 70

DEMAND RESPONSE What is a DR-capable system? A DR system reduces electricity demand in response to a notice or automated signal from utilities, independent system operators or other power providers. Manual DR Requires occupant to manually adjust lighting systems in response to a phone call, e-mail, system notification, etc. Automatic DR The removal of human interaction from the process allows faster reaction to DR events. An electronic DR message will be broadcasted to energy management control systems when an electricity grid experiences high period of high demand or limited supply. 71 CHECK YOUR UNDERSTANDING: DEMAND RESPONSE An 80,000 ft 2 building is being constructed. It will contain 10 tenant spaces, each 8,000 ft 2 in size. Do these tenant spaces need to comply with the requirements for automatic demand response? 72

PARKING GARAGES Parking garages are considered interior nonresidential spaces, except for the top level of each multi-tier garage. General lighting must have occupant sensing controls with at least one control step between 20% and 50% of design lighting power No more than 500 watts of rated lighting power may be controlled together Parking garage areas with at least 36 ft 2 of glazing or opening must have automatic daylighting controls Section 130.1 (e)7b 73 DAYLIGHT CONTROLS EXEMPTIONS IN PARKING GARAGES Luminaires in the following areas do not need to use photocontrols: Daylight transition zone: The pathway vehicles use to enter a parking garage. Dedicated ramps: Driveways specifically meant to move vehicles between the floors of a parking garage and which have no adjacent parking. Some sidelit zones: If the primary sidelit zone uses less than 60W of lighting power, the combined primary and secondary sidelit zones do not require daylight controls. Section 130.1 (e)7b 74

SUMMARY OF MANDATORY LIGHTING CONTROLS DISCUSSION: What types of controls will office spaces typically require? 1. Manual controls What needs to be switched separately? 2. Automatic shut-off controls Where are they required? 3. Automatic daylighting controls Which lighting systems must comply? 4. ADR When a signal is received, what should occur? Section 130.1 (e)7b 75