A Study on Improvement of Fire Protection Systems based on Failure Characteristics accodrding to Yearly Variation in Old Commercial Buildings

Similar documents
Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

A Study on Power Consumption of Household Appliances for Life Conduct Activity of Single Household in University Town

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

A Study on Improving Safety Performance through Efficient Prioritization for Fire and Evacuation Safety in Commercial Buildings

The Development of Automatic Fire Alarm Standards and Related Products in China

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China

OPWDD Fire Safety Level One Post Test

Outline of Measures for Fire Prevention and Safety under the Laws and Regulations of Fire Fighting

Research on Decision Tree Application in Data of Fire Alarm Receipt and Disposal

DESIGN AND IMPLEMENTATION OF THE SMART FIRE EXTINGUISHER SYSTEM SHIN-HYEONG CHOI, GYU-HEE LEE, MIN-KYUNG KIM, MIN-JU KIM, JI-HAE DAN & HONG-HEE CHUN

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

Establishing the Risk Basis of Building Size Limits

Comparative Study of Technological Trend between DAIKIN and Panasonic in the Field of Air Conditioner

Today, we re going to talk about emergency action and fire prevention. We hope we never have to face an emergency situation like a fire in our

New fire control system design for fire fighting and rescue equipment Jianguo LUO1, a, Zehao BU2, b

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Based on NFPA 1001: Standard for Fire Fighter Professional Qualifications, 2013 Edition.

CFD Analysis of Fire Characteristics on Subway Junction Station

Date and Time of Incident. Feb. 13, 1964 Breakout at15:33 (approx.) Noticed at 15:27 Notified by emergency call. Extinguished by 21:07

F.R.A.M.E. EVENT NETWORKS used in "FRAME".

Analysis of Availability of Fire Fighting Equipment in Selected Knitting Garment Factories in Bangladesh

2012 International Symposium on Safety Science and Technology Factor analysis of high-rise building fires reasons and fire protection measures

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS

A Survey on the Sense of Fire Safety and Evacuation Guide System

Design of Multi-Sensors Cooperation Control System for Intelligent Building

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN

Fire and Gas Detection and Mitigation Systems

Prereq: FOD 131 or Instructor Permission

SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG

and Sprinkler System in Resalat Tunnel of Tehran

Development of Smart Phone Applications Linked with Fire Alarm Control Panel in Automatic Fire Detection System

COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

The basic fire theory says that a fire needs four main elements in order to start: heat, fuel, oxygen, and a chain reaction. This theory is known as t

A Study on Smart City Development Project for Regional Innovation: Co-creation and Design Thinking Approach

2010 Fire Log Fire Log. Annual Fire Safety Report

Relay Performance Index for a Sustainable Relay Replacement Program

Early Warning Fire Detection Engineering

Upward Evacuation Experiment for Estimating Evacuation Speed in Water Disaster

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

Simulation study of evacuation in high-rise buildings

ISSN: [Agcaoili S. O., 7(3): March, 2018] Impact Factor: 5.164

The Development of Fire Risk Assessment Method for Heritage Building

Development of a Slope Stability Program for Transmission Towers

How design fires can be used in fire hazard analysis

Riverside Fire Department

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

LIQUEFIED PETROLEUM GAS DIFFUSER Home automation based fire security.

West Chester Fire Dept. Fire Code Maintenance Handbook. Fire Prevention Saves Lives and Property

Advanced diagnostics embedded in a pressure transmitter can detect integrity issues

INSPECTOR I SKILLS ADMINISTRATION

FIR 3305, Fire Protection Structure and Systems Course Syllabus. Course Description. Course Textbook. Course Learning Objectives.

Forecasting the Number of Fire Accidents in the Philippines through Multiple Linear Regression

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Available online at ScienceDirect. New Framework of Intelligent Evacuation System of Buildings

Considerations in the Design of Smoke Management Systems for Atriums

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

Emergency Response Plan

MASTER COURSE OUTLINE

Fire Protection Systems FST 209. COURSE SYLLABUS Fire Protection Systems FST 209 [Semester] CRN 3 Credits

CONSERVATION PLAN BASED ON THE CONCEPT OF INTEGRITY

5123: information. The graphic plan shall include, but may not be limited to: (a) A primary and secondary means of exit from each floor;

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Fire Safety Register

EASTERN ARIZONA COLLEGE Fire Department Operations II

Fire protection on chemical manufacturing sites

Winnipeg Fire Department Fire Prevention Branch

RESEARCH ON THE MAIN CRITERIA OF DECISION-MAKING FACTORS THAT AFFECT CONSUMERS' PURCHASE OF RESIDENTIAL FIRE ALARMS

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

The Application of Double-deck Inorganic Composite Fire Resisting Shutters in Constructional Engineering Bai-Xia ZHOU*

Received: 26 th Feb-2014 Revised: 29 th March-2014 Accepted: 30 th March-2014 Research article

Enclosure 4- RISK ASSESSMENT

International Journal of Advance Engineering and Research Development

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

Thermo 230 / 231 / 300 / 301 / Troubleshooting

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

Reaction of Non Combustible Materials with Fire to Safe Guard Lives and Property in Building Environment

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

Experimental Research on Monomial Cooling Measure of Greenhouse in Summer

A Study on Hierarchy of Spatial Configuration in Outpatient Department of General Hospital

Fire Situations and Prevention Measures of residential building

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

Fire Dynamics Simulation and Evacuation for a Large Shopping Center (Mall), Part II, Evacuation Scenarios

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Austin Independent School District Police Department Policy and Procedure Manual

Module 9: Ontario Building Code Fire Fighting Provisions

ICC CODE CORNER 2015 International Fire Code

MODULE 2. Water-Based Suppression System Basics

SELECTIONS FROM HOME COOKING FIRE PATTERNS AND TRENDS CHARCOAL GRILLS

FIRE PROTECTION PROGRAM

4/13/2015. Everything a firefighter wants to tell a design professional or building code official, in one hour.

Full Service Central Station Fire Alarm Listing Evaluation

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Transcription:

Indian Journal of Science and Technology, Vol 9(24), DOI: 10.17485/ijst/2016/v9i24/96032, June 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 A Study on Improvement of Fire Protection Systems based on Failure Characteristics accodrding to Yearly Variation in Old Commercial Buildings Wook-Jung Na* Department of Fire and Disaster Prevention Engineering, Changshin University, Korea; wooksna@gmail.com Abstract Background: Safety assessment of fire protection system is very important. Especially, Fire Protection system is central to minimizing damage to human lives and property. They re not in demand at normal times but are definitely needed in times of fire or other disasters. Concerns of performance loss or failure owing to yearly variation remain but the nature of fire protection system challenges users from detecting equipment failure or defects early on. Methods: This study sets a certain inspection score to defect probability, which is calculated by quantitative defect probability arising from yearly variation in fire protection systems by part of fire protection systems observed by time and use the score as the basis to determine replacement and inspection of parts. This study also aims at suggesting hazard calculation associated with aging based on criticality and yearly variation of fire protection systems. This method can realize active and quantitative management and the old fire protection system. Findings: Presented in this study Performance Assessment Tool allows a more effective replacement and inspection of firefighting equipment in structures and eventually calculate hazard of firefighting equipment performance in a quantitative manner, thereby serves as an effective diagnosis tool for maintaining and improving performance of aging firefighting equipment. Improvements: For improvements of this study, data on defect rate of fire protection systems should be recorded to deliver higher reliability and aging of fire protection systems arising from time variance should also be monitored by building detailed data to come up with a methodology that ensures reliable management. Keywords: Failure Characteristics Characteristic, Fire Protection System, Old Commercial Building, Yearly Variation 1. Introduction Objective of fire protection systems is to keep off fire or other kinds of disasters in advance or keep damage to minimum. It should be readily able to do its job in all cases in response to changes in the surrounding environment. Any inconvenience associated with fire protection systems is hardly recognized by users as they are not used all the time and a rather long period until disuse or renewal makes it difficult to predict defects arising from yearly variation or environmental changes. All structures in Korea are subject to legal and periodical inspection, which varies by size and structures purpose, but their performance until the next inspection cycle is not fully guaranteed since their repair and replacement are determined only by checking how well they work during inspection. Small and medium-sized structures shall ensure performance guarantee of fire protection systems through supervisor s safety control activities. There is a need to introduce replacement cycle standard that accounts for greater yearly variation and environmental changes in order to secure reliability. Put in another way, fire protection systems should be guaranteed of their performance at all times and quantitative analysis method should be applied during replacement and inspection period. Based on this understanding, this study aims to propose performance diagnosis methodology for fire protection systems by examining quantitative defect *Author for correspondence

A Study on Improvement of Fire Protection Systems based on Failure Characteristics accodrding to Yearly Variation in Old Commercial Buildings ratio owing to yearly variation from the year a particular structure is completed and determining criticality of each equipment and part. 2. Operation of Fire Protection Systems and Methodology 2.1 Operation of Fire Protection Systems Study on the fire protection systems analysis has been studied continuously from the past. Typically, the NFPA has been presented to the scientific concept of fire safety systems 1. Fire safety systems research until recently has become a study on the reasonable quantification method of fire safety systems 2 and evaluation methods 3. But performance improvement of fire protection systems has more to do with improvement in physical/functional performance loss of equipment and system than with performance loss arising from economic and environmental aging. This suggests the importance of performance guarantee. It is, therefore, highly important to develop an effective maintenance solution to ensure they properly perform during fire by inspecting and replacing equipment at the right time. Figure 1. The cause of greater combustion during fire accidents in Korea (2011~2015). An analysis into identifying cause of greater combustion during fire accidents in Korea over the last five years (2011 ~ 2015) points to rapid combustion of combustible materials as the primary culprit 4. This indicates failure by fire protection systems to put out fire in the early stage, which is their most important job (Figure 1). Figure 2 presents operation status of major fire protection systems in the last five years 4. There are still many cases of fire protection systems and system not working properly at times of fire accidents when they are most direly needed. In particular, fire alarm system and automatic fire detection system fail to work in over 25% of the cases. Figure 2. Operation status of major fire protection systems(2011~2015). 2.2 Performance Diagnosis Methodology Performance of fire protection systems shall therefore be guaranteed at all costs yet they re not being properly replaced and repaired as they are not always in use. Hence, this study aims at proposing supervisor-led performance diagnosis to support proper replacement and repair of fire protection systems and solutions for improvement. To this end, the basis in this study is elements of performance loss owing to yearly variation of fire protection systems. Aging of fire protection systems has many causes that include quality issues, surrounding environment and construction capabilities but it is impossible to classify and analyze all causes of aging. Recognizing such limitations, this study limited aging of fire protection systems caused by yearly variation to defect rate of fire protection systems applied to actual buildings. In other words, performance diagnosis of fire protection systems proposed in this study classifies each fire protection systems by equipment and part. It also encourages proactive control by users and supervisors, particularly firefighting safety supervisors and building owners, based on defect rate of fire protection systems by yearly variation and criticality by equipment and part. Figure 3 shows concept of fire protection systems performance diagnosis proposed in the study. 3. Performance Diagnosis Method of Fire Protection Systems 3.1 Performance Diagnosis Method of Fire Protection Systems Performance diagnosis of aging fire protection systems proposed in this study grants a certain diagnosis score to defects rate of each part in fire protection systems that occurs with time variance based on quantitative defect rate associated with yearly variation of fire protection 2 Indian Journal of Science and Technology

Wook-Jung Na Table 1. Defect rate of each part caused by yearly variation Fire protection systems Automatic fire detection equipment Parts Defect function formula using trend curve R2 value (Coefficient of determination) Key inspection points Receiver(P type) f(x) =0.46692x 0.47 Spare charging equipment, line, short circuit Alarm(sound) system f(x) =0.30653x 0.95 Volume, tone Transmitter f(x) =0.70013x 0.72 Touch button, lamp Smoke detector* f(x) =0.97249x 0.85 Status of operation/installation Thermal detector* f(x) =0.42888x 0.76 Status of operation/installation Water-based fire extinguishing equipment Wiring, power f(x) =0.21796x 0.71 Wiring, short circuit Pipeline** f(x) =0.73235x 0.87 Pipeline damage, corrosion Valve f(x) =0.47535x 0.66 Status of operation, corrosion Pump performance f(x) =0.53393x 0.87 Defect by pump performance test value Water source/water tank** f(x) =0.81082x 0.61 Valve status, water gauge Sprinkler System Head f(x) =1.0179x 0.98 Head status, performance Water flow device f(x) =0.73714x 0.63 Water flow device, power switch solenoid, status of water gauge Control panel f(x) =0.52286x 0.71 Status of supervisory control panel, power control panel Indoor fire hydrant equipment Control panel f(x) =1.0058x 0.78 Status of signal lamp/switch, emergency power conversion Fire hydrant box f(x) =0.31229x 0.58 Status of fire extinguishing hose, signal lamp Fire extinguisher*** Evacuation exit light Status, operation f(x) =0.93287x 0.68 Status of power, fire extinguishing agent, exterior Light source f(x) =0.90714x 0.66 Lighting of light source (two-wire, three-wire) Emergency power f(x) =0.74848x 0.77 Emergency power status Inspection switch f(x) =0.89357x 0.75 Fuse status * Defect on placement distance and detection area size are excluded ** Anti-freeze defect is excluded *** Defect on unit capacity, installation distance, adaptability, signal and status of supervision is excluded Indian Journal of Science and Technology 3

A Study on Improvement of Fire Protection Systems based on Failure Characteristics accodrding to Yearly Variation in Old Commercial Buildings Figure 3. The concept of performance improvement in fire protection equipment. Figure 4. Defect-function of the of fire protection system according to of use in building. systems. The score is then used as the basis to determine replacement and inspection of parts of fire protection systems. Defect rate of each part is calculated as defect rate of each fire protection systems and hazard rate of fire protection systems in a structure is presented numerically in accordance with criticality of fire protection systems. This is one of the methodologies to support effective performance improvement by comparing each firefighting-equipment and driving performance improvement of each part. Defect rate caused by yearly variation is based on Na s study 5 results. Figure 4 is a diagram of scoring method in fire protection systems performance diagnosis. It is based on defect rate of each fire protection systems and internal part caused by yearly variation, which was empirically researched and analyzed in Na s study 5. Elapsed time (from installation period to examination period of fire protection systems and parts) is supervisor s input variance. Define Linear trend curve in which defect rate of each part caused by yearly variation as shown in Table 1 is set at section 0 is used to functionalize for performance diagnosis method. Also, defect rate of each part is put in as data. Defect rate data examined in Na s study 4 that has nothing to do with yearly variation is excluded. Aside from receiver based on defect rate trend curve, coefficient of determination (R 2 ) in all functional formulas is above 0.5, an indication of defect rate increase in proportion to yearly variation. However, not all fire protection systems in structures have defects in their parts in a certain year as suggested in function by yearly variation in Table 1. Instead, defect rate from the function is used as a data to effectively support information related to replacement and inspection to the supervisor. By entering variance of elapsed time of all fire protection systems and parts in the structures, the supervisor can forecast probability of defect at the time of examination. In addition, inspection and replacement are graded into four stages according to defect rate in order to assist supervisor with the right decision-making on performance improvement and effective maintenance. Highest grade (grade 4) by part means part replacement in which each part in the fire protection systems as described above has reached above 120% in use years or has a defect rate above 20%. Lowest grade (grade 1) means continuous use of parts in which its use years reached 30% and defect rate is less than 5%. Guidelines in inspection and replacement by each grade are defined in Table 2. Supervisors can determine when to replace and inspect parts of fire protection systems based on elapsed period of each part. Performance diagnosis as proposed in the study relies on variance of elapsed period of fire Table 2. Performance improvement standard set in accordance with the fire protection systems faulty grade Grade 1 Grade 2 Grade 3 Grade 4 Defect probability Less than 5% 5 10% 11 19% More than 20% Life span[3] Life span within 30% Life span within 60% Life span within 90% Life span above 120% Replacement and inspection Continuous use Inspection subject (high sustainability) Inspection subject (High replacement probability) Replacement subject 4 Indian Journal of Science and Technology

Wook-Jung Na protection systems components to automatically calculate defect probability of fire protection systems and grade them accordingly. This grading system enables supervisor to figure out which parts need to be replaced and inspected. Furthermore, an automated system makes it easier to effectively respond to replacement and inspection. Figure 5 proposes guidelines for replacement and sustained use by tapping into results of performance diagnosis. in structures can be scored based on criticality and performance matrix examined in Na s study 6. In other words, each system is scored according to defect probability and criticality of system applied to structures, which is then translated into performance diagnosis score. Aggregate of score for each system in fire protection systems can be calculated as hazard score through performance diagnosis of fire protection systems. This enables effective replacement and inspection of fire protection systems in aging structures. Moreover, degree of hazard for performance of aging fire protection systems calculated quantitatively will be hopefully used as a great tool for maintenance and effective diagnosis for performance improvement Figure 5. Examples of automated diagnostic performance of the fire protection systems. 3.2 Calculation of Risk in Structures with Fire Protection Systems Performance diagnosis of each system equals average defect probability of each part, which is calculated with formula (1). F system : firefighting system f : defect probability of parts making up firefighting system n : number of parts making up firefighting system Degree of hazard of fire protection systems applied to structures can be determined by defect probability. Degree of hazard associated with fire protection systems Figure 6. Risk matrix according to the importance and probability of failure of the fire-fighting facilities. 4. Conclusion This study proposed supervisor-driven performance diagnosis method to fire protection systems in structures based on results from existing studies. This is an automated solution suggesting when to inspect each part of the fire protection systems, which can be regarded as an objective and concrete performance improvement tool to support supervisors to decide on what and when to replace or inspect or on the order of replacement. This way, limitations of performance improvement methods associated with previous inspections can be cleared. Therefore, the methodology proposed in this study can be put to use for a more effective and proactive management of fire protection systems in structures. In addition, data on defect rate of fire protection systems should be recorded to deliver higher reliability and aging of fire protection systems arising from time variance should also be Indian Journal of Science and Technology 5

A Study on Improvement of Fire Protection Systems based on Failure Characteristics accodrding to Yearly Variation in Old Commercial Buildings monitored by building detailed data to come up with a methodology that ensures reliable management. 5. Acknowledgement This research was supported by the Fire Fighting Safety & 119 Rescue Technology Research and Development Program funded by the Ministry of Public Safety and Security (MPSS- Fire-Safety-2015-75). 5. References 1. NFPA. NFPA 550 guide to the fire safety science concepts tree 1995 Edition, MA, USA; 1995 2. Albrecht C. Quantifying life safety. Part II: quantification of fire protection systems. Fire Safety Journal. 2014; 64:81 6. 3. Huang Y-B, Han B, Zhao Z. Research on assessment method of fire protection system. Procedia Engineering. 2011; 11:147 55. 4. Fire statistics Status (National Fire Information Center) [Internet]. [Cited 2016 Mar 03]. Available from: http:// www.nfds.go.kr/fr_fact_0101.jsf. 5. Na Wook-Jung, Ho-Young L, Won-Hwa H. A study on the annual variations of fire protection system and malfunctioning characteristics in commercial buildings. Journal of the Architectural Institute of Korea. 2011 Dec; 27(12):325 32. 6. Wook-Jung N, Son B-H, Gyu-Yeob J. A study on improving safety performance through efficient prioritization for fire and evacuation safety in commercial buildings. Indian Journal of Science and Technology. 2015 Oct; 8(25):1 9. DOI: 10.17485/ijst/2015/v8i25/80839. 6 Indian Journal of Science and Technology