G UPFLOW GAS FURNACE

Similar documents
KGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

TGA/KGA024, 030, 036, 048, 060, 072, 090 (2, 2 1/2, 3, 4, 5, 6, and 7 1/2 TONS)

EL195DFE SERIES GAS FURNACE WARNING

G61MPV SERIES GAS FURNACE WARNING

EL195UH SERIES GAS FURNACE WARNING

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

WARNING FIRE OR EXPLOSION HAZARD.

ML180UH SERIES GAS FURNACE WARNING WARNING

WARNING FIRE OR EXPLOSION HAZARD.

READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

USER S INFORMATION MANUAL

EL195UHE SERIES GAS FURNACE WARNING WARNING

SLP98UH SERIES VARIABLE CAPACITY GAS FURNACE WARNING WARNING

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

USER S INFORMATION MANUAL

RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE :$51,1*

EL296UHV SERIES GAS FURNACE WARNING WARNING

P.O. Box , Dallas, TX USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces

MANUAL WARNING FIRE OR EXPLOSION HAZARD. SL280UHNV SERIES WHAT TO DO IF YOU SMELL GAS:

USER S INFORMATION MANUAL SLP98UHV SERIES

RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE :$51,1*

LGA/LGC036, 042, 048, 060, 072 (3, 3-1/2, 4, 5, and 6 TONS) LGA/LGC090, 102, 120, 150, (7-1/2, 8-1/2, 10, and 12-1/2 TONS)

DT-2 & DR-2 MERIT SERIES

DT/DTH/DR/DRH MERIT SERIES

USER S INFORMATION MANUAL (2,4)SG13B

USER S INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S INFORMATION MANUAL

Bosch 80% AFUE Gas Furnace BGS80 Model

SERVICE FACTS WARNING M801-SF-1C. Gas Furnaces Upflow & Downflow Induced Draft 1 Stage Heat Models: DISCONNECT POWER BEFORE SERVICING M801P040AU24AA

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

UPFLOW/DOWNFLOW/HORIZONTAL 80% GAS FURNACES WARNING WARNING WARNING ! WARNING

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL

UPFLOW/DOWNFLOW/HORIZONTAL CONDENSING GAS FURNACES

USER'S INFORMATION MANUAL

User s Information Manual

USER'S INFORMATION MANUAL

INDUCED DRAFT HIGHBOY AND COUNTERFLOW/HORIZONTAL GAS FURNACE

USER S INFORMATION MANUAL

This document was created with FrameMaker 4.0.4

OWNER S MANUAL HIGH EFFICIENCY VARIABLE SPEED GAS-FIRED FURNACES

NOTE TO INSTALLER: This manual must be left with the equipment user. Model 480BAV Upflow and 481BAV Downflow/Horizontal

HOME OWNER S INFORMATION Induced Combustion Gas Furnace

USER'S INFORMATION MANUAL

USER'S MANUAL PGE Single Package Rooftop

User s Information Manual

USER S INFORMATION MANUAL

USER'S INFORMATION MANUAL

User s Information Manual Models: 45, ,000 Btu/hr

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL

GAS FURNACE. User's Information Manual for the operation and maintenance of model GB1AAV or GB3AAV Gas Furnace

Owner's Manual. Induced Combustion Gas Furnace ! WARNING NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

Model RGAC/SGAC Self Contained Cooling/Gas Heat MODELS RGAC & SGAC - R22 USER'S INFORMATION, MAINTENANCE AND SERVICE MANUAL

USER'S INFORMATION MANUAL

USER S INFORMATION MANUAL

User s Information Manual

80% and 95% furnace models feature aluminized steel heat exchangers to conduct heat quickly and increase durability.

User s Information Manual

MODELS 373LAV, 376CAV DOWNFLOW/HORIZONTAL and 383KAV, 395CAV UPFLOW GAS FURNACE

USER S INFORMATION MANUAL

GAS UNITS KITS AND ACCESSORIES 505,172M 08/06

User s Information Manual

Combination Cooling/Gas Heat Package Units

Aqua Balance. User s Information Manual. WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water

DF Series Furnace. Models DFSAD12, DFSD12, DFSD16, DFSD20, DFMD16, DFMD20, DFMD25, DFMD30, DFMD35, DFLD35, DFLD40, DFLA35, DFLA40

TO DO IF YOU SMELL GAS

Owner s Manual. ama PG9MXA TWO --- STAGE CONDENSING GAS FURNACE ! WARNING NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

Universal Fire Tube Boiler Wall Mount Models

Tankless Water Heater

User s Information Manual

User s Information Manual

OIL FIRED WARM AIR FURNACE. Homeowner Instructions

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Owner s Manual CONDENSING GAS FURNACE ! WARNING NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

Installation Manual. For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC )

Owner s Manual. Condensing Gas Furnace ! WARNING NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

HOME OWNER S INFORMATION High Efficiency Condensing Gas Furnace

HOME OWNER S INFORMATION High Efficiency Condensing Gas Furnace

Owner's Manual. Condensing Gas Furnace ! WARNING NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

HWX GAS BOILERS USER S INFORMATION MANUAL

User s Information Manual

Owner s Manual PG9MAB ! WARNING. Condensing Gas Furnace NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

Owner s Manual CONDENSING GAS FURNACE ! WARNING NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

Owner s Manual CONDENSING GAS FURNACE ! WARNING NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

User s Information Manual

Model BW9 Gas-Fired Direct Vent Condensing Water Boiler

UNITARY PRODUCTS GROUP

G95V NATURAL AND PROPANE GAS TWO STAGE HIGH EFFICIENCY (CONDENSING) WARM AIR FURNACE USER S INFORMATION MANUAL

FIRE OR EXPLOSION HAZARD. Failure to follow this warning could result in injury, death and/or property damage.

Fig. 1 - Unit PGD4, PGS4, WPG4

OIL FURNACE USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW OIL-FIRED FURNACE

User's Information Manual Customer Property: Contains wiring and service information.

User s Information Manual Galaxy GG/GX Series, Sentry S/SX Series and Sentinel SE Series Gas Boilers with Continuous Burning Pilot

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

Owner s Manual. Induced Combustion Gas Furnace ! WARNING NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

Owner s Manual. Induced Combustion Gas Furnace ! WARNING NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER.

Transcription:

PRODUCT LITERATURE 2003 Lennox Industries Inc. Dallas, Texas 503,614M 7/2003 Supersedes 1/98 G24 200 UPFLOW GAS FURNACE READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE Litho U.S.A. FIRE OR EXPLOSION HAZARD Failure to follow safety warnings ex actly could result in serious injury death or property damage. WHAT TO DO IF YOU SMELL GAS: Do not try to light any appliance. Do not store or use gasoline or other Extinguish any open flames. flammable vapors and liquids in the Do not touch any electrical switch; do not vicinity of this or any other appliance. use any phone in your building. Installation and service must be per Leave the building immediately. formed by a qualified installer, ser Immediately call your gas supplier from a vice agency or the gas supplier. neighbor s phone. Follow the gas suppli er s instructions. If you cannot reach your gas supplier, call the fire department. 07/03 Page 1 503,614M

G24 200 HEAT SECTION AND CABINET (THIS UNIT CONTAINS TWO HEAT SECTIONS. EACH HEAT SECTION CONTAINS ONE OF THESE ITEMS.) CABINET TOP LIMIT CONTROL* LEFT SIDE PANEL* FLUE BOX GASKET* COMBUSTION AIR BLOWER* FLUE BOX* BURNER RETENTION BRACKET* FLAME ROLLOUT SWITCH* PRESSURE SWITCH* HEAT EXCHANGER ASSEMBLY* FLEXIBLE CONNECTOR PRESSURE SWITCH* IGNITION CONTROL* REAR PANEL TOP BURNER MTG BRACKET* SENSOR* IGNITOR* GAS VALVE* (two stage) REAR PANEL BOTTOM RIGHT SIDE PANEL MAKE UP BOX* HEATING COMPARTMENT ACCESS PANEL* BLOWER COMPARTMENT ACCESS PANEL CENTER MULLION Page 2

G24 200 BLOWER SECTION SHAFT CUT OFF PLATE BLOWER HOUSING BLOWER PULLEY DRIVE BELT (Drive Kit) MOTOR (Drive Kit) BEARING WHEEL MOTOR PULLEY (Drive Kit) MOTOR BASE ADJUSTMENT ARM BASE ASSEMBLY MOTOR BASE VIBRATION ISOLATOR LOCATING ROD Page 3

Safety Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. Danger of electrical shock, explosion and fire. Improper servicing could result in dangerous operation, serious inujry, death or property damage. Danger of explosion and fire. Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.) Fiberglass wool may also cause respiratory, skin, and eye irritation. To reduce exposure to this substance or for fur ther information, consult material safety data sheets available from address shown below, or contact your supervisor. P.O. Box 799900 Dallas, TX 75379 9900 Danger of explosion. Can cause injury or product or property damage. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply. IMPORTANT Any additions, changes, or conversions re quired in order for the appliance to satisfactorily meet the application needs must be made by a Lennox service technician using factory speci fied and approved parts. CAUTION Label all wires prior to disconnection when servic ing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Do not use this furnace if any part has been under water. A flood damaged furnace is extremely dan gerous. Attempts to use the furnace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and to replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary. SMOKE POTENTIAL The heat exchanger in this unit could be a source of smoke on initial firing. Take precautions with re spect to building occupants and property. Vent ini tial supply air outside when possible. Danger of explosion. Can cause injury or death. Do not attempt to light manually. Unit has a direct spark ignition system. 1 Keep the furnace area clear and free of combustible material, gasoline, and other flammable vapors and liq uids. If installed in an insulated area, furnace must be kept free of insulating material. Insulating material may be combustible. Inspect furnace venting system to make sure it is in place, physically sound, and without holes, corrosion, or blockage. Inspect furnace return air duct connection to ensure duct is sealed to the fur nace and terminates outside the space containing the furnace. Inspect the physical support of the furnace to guarantee that it is sound without sagging, cracks or gaps around base and it maintains seal between base and support. 2 DO NOT obstruct air flow to unit. Unit must receive an unobstructed flow of combustion and ventilating air. Page 4

3 DO NOT store chlorine or fluorine products near unit or introduce these products into the combustion air. These products can cause furnace corrosion. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it, call a qualified service techni cian. Force or attempted repair may result in a fire or ex plosion. Lighting Information and Operation 1 STOP! Read the safety information at the beginning of this section. 2 Set thermostat to the lowest setting. See figure 1. 3 Turn off all electrical power to furnace. 4 This furnace is equipped with two ignition devices which automatically light the burners. Do not try to light burners by hand. 5 Remove control access panels. THERMOSTATS 7 Wait five minutes to clear out any gas. If you then smell gas, STOP! Immediately call your gas suppli er from your neighbor s phone. Follow the gas sup plier s instructions. If you don t smell gas go to next step. 8 Perform the following to both gas valves: turn knob on gas valve 180 either way to ON position. 9 Replace control access panels. 10 Turn on electrical power to furnace. 11 Set thermostat to desired setting. 12 Both combustion air blowers will start. Burners in both heat sections will light after a 30 second pre purge. 13 If furnace does not light first time (gas line not fully purged) it will attempt up to two more ignitions be fore locking out. 14 If lockout occurs, repeat steps 1 through 10. 15 If the furnace will not operate, follow the instructions To Turn Off Gas To Unit" and call your service techni cian or gas supplier. B To Turn Off Gas To Unit 1 Set thermostat to lowest setting. 2 Turn off all electrical power to furnace if service is to be performed. 3 Remove control access panels. FIGURE 1 WHITE RODGERS 36E TWO STAGE GAS VALVE INLET PRESSURE TAP (SIDE) LOW HEAT MANIFOLD PRESSURE FACTORY SET, NOT FIELD ADJUSTABLE. 4 Perform the following to both gas valves: White Rodg ers 36E series valves: turn knob on gas valve 180 either way to OFF. Do not force. Service Reminder Call your Lennox service technician if unit is inoperative. Before calling, always check the following to be sure ser vice is required. 1 Check that electrical disconnect switches are ON. 2 Check room thermostat for proper setting. GAS VALVE KNOB SHOWN IN OFF" POSITION FIGURE 2 HIGH FIRE ADJUSTMENT MANIFOLD PRESSURE TAP (SIDE) 6 Perform the following to both gas valves: turn knob on gas valve 180 either way to OFF. Do not force. 3 Replace any blown fuses or reset circuit breakers. 4 Gas valves should be ON. 5 Air filters should not be plugged limiting air flow. 6 Is gas turned on at meter? 7 Is manual main shut off valve open? To keep your Lennox gas heating system in peak operat ing condition year after year, contact your independent Lennox dealer about a planned service program. Page 5

Service A qualified service technician should inspect the com plete system each season (heating and cooling). The fol lowing maintenance procedures should only be con ducted by a qualified service technician. Do not attempt to service the unit in any way. ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could re sult in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous op eration, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to dis connecting. Take care to reconnect wires correctly. Verify proper operation after servicing. Venting System Asphyxiation Hazard The exhaust vent for this furnace must be securely connected to the furnace flue collar at all times. For your safety and to fulfill the terms of the limited warranty, a qualified service technician must annu ally inspect this furnace and its vent system. Annually (before heating season) inspect furnace venting system, vent cap, heat exchanger, and burners for corro sion, deterioration, or deposits of debris. Remove any ob structions. Inspect the furnace for obvious signs of deterioration. Inspect the furnace venting system to make sure it is in place, physically sound, and without holes, corrosion, or blockage. Vent pipe must be clear and free of obstructions and must slope upward away from the furnace. Inspect the furnace return air duct connection to ensure duct is sealed to the furnace and terminates outside the space containing the furnace. During a seasonal check the service technician will in spect the indoor blower, burner flames and electrical con nections along with the venting system. Burner Flame CAUTION To ensure proper operation, a qualified technician should annually check the burner flame. Blowers Check the blower wheels for debris and clean if neces sary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed. Blower shaft bearings are prelubricated. For extended bearing life, relubricate at least once every two years with a lithium base grease, such as Alvania 3 (Shell Oil), Chev ron BRB2 (Standard Oil) or Regal AFB2 (Texas Oil). Use a hand grease gun for relubrication. Add only enough grease to purge through the bearings so that a bead of grease appears at the seal lip contacts. The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal in jury or death. Filters All G24 200 filters are installed external to the unit. Filters should be inspected monthly and cleaned or replaced when necessary to assure proper furnace operation. If optional filter box is used, see figures 3 or 4 for replace ment directions. The filter box contains four 16x25 inch (406mmx635mm) filters. NOTE Replacement filters must be U.L.C. certified or equivalent for use in Canada. Flame Rollout Safety Switches Your Lennox furnace is equipped with two sets of flame rollout safety switches (one in each heat section). Each switch shuts off the gas supply to the heat section it con trols when blockage occurs to its heat exchanger. If the furnace fails to operate due to the functioning of one or both of these safety switches, DO NOT attempt to place the furnace into operation. Contact a qualified service technician. Page 6

G24 200 UNIT REAR RETURN AIR FILTER BOX With Top or Side Filter access TOP FILTER ACCESS PANEL Burners (Both heat sections) Inspect the burners and burner flame at the beginning of each heating season. If necessary, clean the burners as indicated below: 1 Turn off the electrical and gas supply to the furnace. 2 Remove the burner box top. 3 Remove the burner retaining bracket. 4 Remove the burners. 5 Clean the inside of each burner with a bottle brush as shown in figure 5. FILTER BOX CLEANING BURNERS SIDE FILTER ACCESS PANEL FOUR FILTERS (Filters may also be installed through top of filter box) BURNER BOTTLE BRUSH G24 200 UNIT FOUR FILTERS (Filters may also be installed through side of filter box) FRONT FILTER ACCESS PANEL FIGURE 3 BOTTOM RETURN AIR FILTER BOX With Front or Side Filter access FIGURE 4 SIDE FILTER ACCESS PANEL FIGURE 5 6 Check the electrode gap using appropriately sized twist drills or feeler gauges. Gap should be between 0.110 and 0.140 inches (2.79 to 3.56mm). 7 Replace the burners and the burner retaining brack et. Make sure that the burners are properly seated in their slots in the tray and that each burner and man ifold orifice is aligned properly. 8 Reinstall the burner box top. 9 Carefully check all piping connections (factory and field) for gas leaks. Use a leak detecting solution or other pre ferred means. IMPORTANT Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use matches, candles, flame or other sources of igni tion to check for gas leaks. 10 Restore electrical power and gas supply to the furnace. Follow lighting instructions on the front of the unit. Check the appearance of the burner flame, burner pressure, gas flow, and temperature rise. If necessary, make ad justments. See the other unit adjustments section. Page 7

Flue And Chimney Check the flue pipe, chimney and all connections for tight ness and to make sure there is no blockage. Heat Exchangers (Both) Periodically inspect the heat exchanger tubes and flue box for corrosion. If necessary, clean as indicated below: 1 Turn off the electrical and gas supply to the furnace. 2 Disconnect the wiring to the combustion air fan. 3 Remove the screws securing the flue box to the fur nace. Clean the flue box with a wire brush (brass bristle brush recommended). 4 Disconnect the gas supply piping and the ignitor and sensor wires. Remove the burner assembly from the furnace. 5 Pull a large bore wire brush (brass bristle brush recom mended) through each heat exchanger tube to clean. 6 Reinstall the flue box using a new gasket. 7 Reconnect the combustion air fan wiring. 8 Reinstall the burner box, ignitor and sensor wires and the gas supply piping. 9 Follow step 10 in the burners section above. Electrical 1 Check all wiring for loose connections. 2 Check for the correct voltage at the furnace (furnace operating). 3 Check amp draw on blower motor. Motor service factor amps Nameplate Actual Repair Parts List The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA international. rating plate Example: G24 200. Refer to page 4 and 5 for parts identification. Cabinet Parts Electrical Parts Heating Parts Blower Parts Front louver door (2) Transformer(s) Heat exchanger (2) Wheel (2) Blower access panel (2) Ignition control board (2) Main burners Motor Cabinet cap Door interlock (2) Main burner orifices Cut off plate (2) Cabinet top rear Ignition cable (2) Gas manifold/burner Shaft box assembly (2) Cabinet bottom rear Ignitor (2) Gas valve (2) Motor pulley Flue adapter (2) Flame sensor (2) Flue box (2) Wheel pulley Roll out switch (2) Combustion air blower (2) Belt Primary limit (2) Flexible gas connector Bearing (2) Pressure switch (2) Vibration isolators (4) Blower timing control board Locating rods (2) Accessory relay Blower operation relays Contactor Combustion air blower operation relays Page 8