University of Illinois at Urbana-Champaign Small Homes Council-Building Research Council COUNCIL NOTES ~,.Q. ::s C2.3 ILLINOIS LO-CAL HOUSE

Similar documents
University oflllinois at Urbana-Champaign Small Homes Council-Building Research Council COUNCIL NOTES I ~ (f.) G6.0 SUMMER COMFORT {I)

Sun11ner. Co111fort. Council Notes. Volume "12, Number 2. College of Fine and Applied Arts -University of Illinois. Building Research Council

University of Illinois at Urbana-Champaign Small Homes Council-Building Research Council COUNCIL NOTES. ::s >

ENERGY CRISIS LIVING WITH THE MATERIAL IN THIS CIRCULAR BY SEICHI KONZO AND WAYNE L. SHICK

HEATING THE HOME UNIVERSITY 0 F ILLINOIS BULLETIN REVISED BY DONALD E. BROTHERSON, A. I. A.

ENERGY CONSERVATION IN

Windo-w Planning Principles

ED ROOM l?lanning STANDARDS

Energy: Home Energy Audit

Building and Remodeling to Save Energy 1

Effect of Moisture on Building Systems!

FUELS BURNERS UNIVERSITY 0 F ILLINOIS BULLETIN REVISED BY W. S. HARRIS AND S. KONZO DEPARTMENT OF MECHANICAL ENGINEERING

The Art of Building Science

Simple Solar. Heating & Cooling

Bathroom SAVING ENERGY AROUND THE. If you go on vacation, turn the temperature selector to the lowest setting.

Adelaide Homes Design Guide 3 - Shading

17 Interior Climate Control

NAHB Green Home Building Guidelines. 3.1 Prerequisites. ResCheck. Energy Efficiency

HVAC Equipment Access Equipment Location

Energy Conservation. Meet Mr.A and Mr.B. They have both received their electricity bill. One of them is happy and one of them is not.

Pro Eco-Energy. Home Assessment

Supplement A- Improving Forced Air Heating Systems

Energy Efficiency Practices for the Low- Income Population

Joe Konopacki 10/26/2016. Attic & Crawlspace Ventilation. What results from poor ventilation? Attic & Crawlspace Ventilation. Overview Why ventilate?

FAQ. (Frequently Asked Questions) What is required to convert my unfinished basement to finished space?

Bathroom SAVING ENERGY AROUND THE. If you go on vacation, turn the temperature selector to the lowest setting.

iclicker Question iclicker Question Continuing Chapter 7 Overview of Chapter 7

Ventilation for New Low-Rise Residential Buildings July 20, 2015

SAVING ENERGY AROUND THE

Condensation On Windows

Attic Condensation. Presented by: Joan Maisonneuve Technical Services

Bedroom 100. True or False: Space heaters are more energy efficient and inexpensive to heat large areas than central heating systems.

Energy: Synthesis and Analysis

101 EASY WAYS TO SAVE ENERGY AND MONEY.

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on

energy-saving tips for all seasons

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

Commercial load calculator instructions (all measurements are imperial)

101 Low-Cost /No-Cost. Home Energy-Saving Measures

Vermont Energy Partnership Issues 101 Energy Saving Tips to Keep Money in Your Pocket and the Heat off Your Back

Adelaide Homes Design Guide 4 - Winter warming

Uniform Dwelling Code 2017 Updates SPS 323

SOLAR THERMAL HEATING: ALIVE AND WELL

you We are CONSERVING dedicated to serving more efficiently. 101 Low-Cost No-Cost Home Energy-Saving Measures That s the cooperative difference.

- Murdoch University, Western Australia.

Natural Ventilation for Poultry

The Heating System and Ventilation and Combustion Air

SH, VH & SE Models. SH, VH & SE Series Heat & Energy Recovery Ventilators IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

Energy problems in small apartment buildings

Powerful Money Saving Ideas BROUGHT TO YOU BY TVA AND YOUR LOCAL POWER COMPANY

Passive building in Hot and Humid Climates

PROTECTING FIRE SPRINKLER SYSTEM PIPES FROM FREEZING IN CHAPTER FACILITIES

1 Exam Prep Energy Efficient Building Construction in Florida Questions

101 EASY WAYS TO SAVE ENERGY AND MONEY TOGETHERWESAVE.COM

Equipment Specifications and Required Information Quantity Rebate

NEW HOME CERTIFICATION PROGRAM 2018 PROGRAM GUIDE

Address Account # Member # Equipment Specifications Quantity Rebate. ENERGY STAR Appliances

COST EFFECTIVE PASSIVE SOLAR FOR NEW HOME CONSTRUCTION

Asurity 1. Property Inspection Report S Gurd Rd., Hastings, MI Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski -

, 'I... " ENTILATION FOR SWINE / I / / I / I / UNIVERSITY OF flunois / I / SGRICULTUR~.uBRM~ '" ""'... I I \ / I I. , I \ CIRCULA~~G COpy I 1// 1\\

ENERGY PERFORMANCE SCORE

Moisture Condensation

Julie Klump, POAH Rick Fenuccio, Tom Hartman Marc Rosenbaum Melpet preliminary heat loss and energy model results and implications

DO IT YOURSELF ENERGY AUDIT

Home Energy Assessment Report

Land sea ping for Energy Conservation

Energy Conservation TIPS for the RESIDENTIAL MARKET

MAKING IT GREEN AND SAVING ENERGY WITH NSP

Energy efficiency: Present and Future. Paul Kando Midcoast Green Collaborative

HOME ENERGY SAVINGS GUIDE

Triple E New Construction. Doug Manthey Conservation Technologies Chad Trebilcock Minnesota Power

Exploring Energy Efficiency and Alternatives. Healthy Homes. Energy Management for Home. Home Energy Use Missouri. Energy Consumption in U.S.

We will help you find ways to save energy and money, while keeping your home comfortable. energy matter$

buildingscience.com Windows and Occupant Comfort EEBA Building Solutions 2003 Lincolnshire, IL

Ways to Save. Energy efficiency tips to help you lower your monthly power bill. 1 Ways To Save

WHY IS BUILDING SCIENCE IMPORTANT?

Optimal Use of Air Conditioner

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

Your floor to ceiling guide

This publication will describe the causes of excess moisture, how condensation occurs, and methods used to correct moisture problems.

EC Window Treatments for Energy Efficiency

RESNET HERS Rater Sample Test Questions 2

1 Save Energy and Money Today 2 Your Home s Energy Use 4 Insulation and Sealing Air Leaks 10 Heating and Cooling 16 Water Heating 18 Windows 20

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS

Moisture Movement. By Ben Gromicko

Home Cooling Fact Sheet. Stay Cool, Comfortable, and Cut Costs.

Guide. Do-It-Yourself. Virginia Energy Sense. Energy Saving Tips From. Do-It-Yourself Guide. VirginiaEnergySense.org

Residential Energy Use ME 416/516

Zero Energy Home Design Project

HOUSING Energy saving for windows

INDEX. ADDITIONS AND ALTERATIONS Defined Requirements ADMINISTRATION AND ENFORCEMENT... Chapter 1 AIR ECONOMIZERS

Rebate Catalog. Save money on qualified Home Cooling Systems, Appliances and more. Read about rebates for your home and business at mid.

Habitability Guidelines

1. Dial Down. 10 Energy Saving Tips for the Home

50% 80% 7 Years. Filter. Ventilation Solutions IAQ Canada. Ventilate. of our time is spend indoors. Limited warranty on motors

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT

Ventilation in Humid Climates: Data from Field Experiments

How to save money on energy at home

Home Energy Efficiency Part 2

Transcription:

University of Illinois at Urbana-Champaign Small Homes Council-Building Research Council COUNCIL NOTES N ~,.Q El ::s z C2.3 ILLINOIS LO-CAL HOUSE

THE "ILLINOIS LO-CAL HOUSE" ~~ - The increasing scarcity of fuels makes it imperative to include more energy-conserving features in our housing. This publication describes the design, construction, and predicted performance of a house which uses about one-half the energy needed to heat a house of the same size which was built to meet 1974 insulation standards (U.S. Department of Housing and Urban Development standards for houses located in areas having a heating season of between 4500 and 8000 degree-days). Because of its low energy requirements for heating, it has been called the "Illinois Lo-Cal House." If the Lo-Cal House is compared to the typical house of 1950, the savings are even more dramatic. A comparison with a house built to the 1980 HUD standards is also included. It should be noted that the level of insulation recommended in the new minimum standards is approaching the super-insulation recommended in the first Lo-Cal publication in 1976, which was considered extreme at the time. The major features which account for the exceptional reduction in energy usage are: Superior insulation Solar orientation COUNCIL NOTES VolumeS Number2 Fall, 1981 @1976, 1981 by The Board of Trustees of the University of illinois Revised by Michael T. McCulley, SHC-BRC Original Edition by Wayne L. Shick and Rudard A. Jones, FAIA Consultants: WarrenS. Harris and Seichi Konzo illustrations: John B. Sadowski Design: Joan R. Zagorski Editor: Henry R. Spies Renderings: Donna L. Milner All rights reserved. No part of this publication may be reproduced in any form without permission in writing from the publisher. Published quarterly by the Small Homes Council-Building Research Council, Onivers1ty of illinois at Urbana-Champaign, One East Saint Mary' s Road, Champaign, illinois 61820. This publication is one of a series written for the homeowner. A complete list of publications is available upon request.. Of the reduction, about 90% is due to the extra insulation. The remaining reduction is due to the location of most of the windows in the south wall, where they act as solar collectors. DESIGN AND CONSTRUCTION FEATURES Insulation Heavy ceiling insulation Heavy wall insulation Improved floor and crawl-space insulation Triple-glazed windows Complete vapor retarder (barrier) Tight construction to minimize air leakage Solar Major axis of house oriented east-west Roof overhang designed for solar control No windows on the east and west walls Major glass areas on the south wall General Features Can be built with standard, readily available building materials No new technology or labor skills required Design conforms to current practice Design adapts to various lot orientations Benefits Low-cost heating system Low energy use for heating Low-cost cooling system Low energy use for cooling Favorable ratios of benefit to cost Improved acoustic performance CONSTRUCTION DETAILS This design is considered appropriate for most areas of the United States having a heating season of 4500 degree-days or more. Page 2 University of Illinois SHC-BRC

BR BR L 56'-0" Design A. The basic plan was designed for use on a lot with the street on the north. 1. The living room and bedrooms are arranged on the south side of the house. 2. The family-kitchen area is on the north; however, it opens to the living room, from which it receives solar benefits. 3. The entrance vestibule, baths, utility and storage areas are also on the north. Roof-Ceiling Construction The roof-ceiling construction is designed with the bottom of the overhang (soffit) at the same level as the ceiling of the house. This simple modification of the usual roof-ceiling framing provides space to extend the thick ceiling insulation over the outside wall and still maintain adequate ventilation space above the insulation. Twelve inches of insulation, combined with the ceiling structure, provides a total thermal resistance (R) of 38, compared with an R of 19 for the 1974 house and nearly equal to the R-33 of the 1980 HUD house. A complete vapor retarder (barrier) is located immediately below the ceiling insulation. This may be a 4-mil polyethylene film or an aluminum foil on the back of the ceiling finish material. Outside Wall Construction The outside wall is composed of a double-framed wall with staggered studs 24 inches on center and spaced so that it is 81/2 inches from the back of the sheathing to the back of the interior finish. This provides space for insulation which, combined with the other elements of the wall, results in a total thermal resistance (R) of about 30. This is more than twice the insulating value of the 1974 house and about 11/2 times the 1980 standard for a house with electrical resistance heating. 4. Most of the windows (85%) are located on the south wall. The remaining windows are to meet code requirements for light and ventilation. There are no windows in the east and west walls. This is the best arrangement for thermal efficiency of the house. East and west windows should be used only when view is a prevailing requirement. In such cases, the windows should Qe small and well shaded in the summer. A vapor retarder (barrier) must be provided at the interior surface of the inner stud wall. Polyethylene film or foil-backed gypsum drywall is suitable for this application. Either blanket- or fill-type insulation may be used. The thickness of the wall may be varied in accordance with the climate and energy costs. There are several benefits of using a double wall. Since the studs do not touch, there is minimal heat lost through the framing. During construction, electric wires can be run between the double walls without drilling, reducing insulation damage and possibly labor costs. The slot between the top plates of the wall permits any moisture which gets into the wall to vent into the attic space. The thick, insulated wall and tripleglazed windows also reduce sound transmission. Floor-Foundation Insulation The most effective way to reduce the heat loss through the floor is to insulate both the floor of the house and the outside wall of the closed crawl space. The Lo-Cal design uses R-19 insulation in the floor and R-10 insulation on the perimeter wall of the crawl space. When practical, hot-water pipes and heating ducts (if any) should be above the floor insulation. A polyethylene vapor retarder should cover the dirt surface. If heating ducts are in the crawl space, then it should be C2.3 Illinois Lo-Cal House Page3

Roof truss with ceiling and soffit at same level allows thick insulation and air space for ventilation Roof overhang designed for solar control 7 Continuous soffit and ridge vents allow moisture from the attic space to escape and also reduce attic air temperature Vapor retarder (barrier) Triple-glazed windows * If ductwork is run in the crawl space: 1) Use no floor insulation; 2) Seal all duct joints well; 3) Increase the perimeter insulation of the crawl space to at least R-19; 4) Seal the crawl space, including vents. 1_. Double wall for thick insulation-----------~ HORIZONTAL SECTION OF WALL Perimeter insulation of foundation wall for crawl space or basement. See Circular F4.4, Crawl-Space Houses, or F2.0, Basement Construction VERTICAL SECTION OF HOUSE Page 4 University of Illinois SHC-BRC

treated as a heated space. The outside wall should be insulated to at least R-19 from the bottom of the floor to at least 24 inches below ground level, and R-10 from that point to the bottom of the wall. Window Design The triple-glazed windows of the Lo-Cal house are designed for low heat loss and optimum solar gain in winter and for reduced heat gain in summer. The design is based on a study which shows that the solar heat gain minus the heat loss of south-facing, triple-glazed windows can average up to 200-400 Btu per square foot per day. In the one-story plan, 85% of the window area is on the south wall. Small windows on other walls may be installed for view or ventilation. Triple-glazing consists of three panes of glass, and can be a standard window with sealed insulating glass plus a storm window, or a factorysealed triple unit. For the Lo-Cal House, a 50-inch high window was chosen. This height matches a roof overhang which is 16 inches above the top of the window and extends 30 inches out to the edge of the gutter. The south windows are exposed to sunlight in the winter and are shaded in the summer. In late summer and early fall, when the window is only partly shaded, shade screens or other devices can reduce heat gain. Since the house is so well-insulated, the 122 square feet of south windows provides enough solar gain while reducing heat losses at night and during bad weather. The south glass area is about 8% of the total floor area of the house. A Tight House Air infiltration or air leakage can be one of the most significant factors influencing the heating load. Infiltration around windows, doors, and gaps in the construction becomes more important as the heat loss through the other parts of the house becomes smaller. As the tables show, the house must be built tighter to get the maximum benefit from the extra insulation. TABLE 1 DESIGN HEAT LOSS (Btu per hour) 1974 1980 Lo-Cal Components House House House Ceiling (1568 s.f.) 5,762 3,528 2,940 Wall (1160 s.f.) 6,090 3,914 2,958 Floor (1568 s.f.) 3,245 2,069 2,069 Windows (144 s.f.) 5,972 5,972 3,942 Doors (40 s.f.) 267 267 267 Infiltration 16,929 12,696 10,125 Total 38,265 28,446 22,301 Heat Loss Calculations Table 1 summarizes the heat lost through the five component surfaces and from air infiltration from the 1974 house, a house built according to therequirements of the 1980 HUD standards, and the Lo-Cal House. These calculations are made in accordance with accepted engineering practice and do not include solar gains or internal heat gains. Heating System In the weather simulation for Rantoul, Illinois (1957, 5890 degree-days), the maximum heat loss of the Lo-Cal House is computed to be 20,990 Btu per hour. A number of options are available for the heating system. The system with the lowest installation cost would be individual room electric heating, such as baseboard units located under the windows. These units would have a total rated output of only 7 kilowatts, and the advantage of individual room thermostatic control. A natural-gas-fired central system or heat pump would cost more to install but, depending upon economics, might have the lowest 10-year cost. Cooling System For mechanical cooling, small, individual room units could easily cool the house. Although they offer the advantage of individual room control, they are noisier than a central cooling system. A central system using an outdoor air-cooled condenser can be provided at fairly low cost. The cooled air can be distributed through an overhead duct located in the central hallway. At a higher cost, the air-handling system can be designed to bring outdoor air into the system when outdoor air cooling is adequate. Exhaust Fans Kitchen and bathroom exhaust fans, either manually or automatically controlled, will remove excess heat and moisture from cooking and bathing. In colder regions where the tightest construction is used, air-to-air heat exchangers should be considered to maintain air quality and conserve energy. Solar Mechanics Sunlight through the windows heats the interior surfaces of the house; the structure and furnishings absorb heat and warm the air; insulation keeps the heat in the house, even after sundown. With maximum insulation and major south windows of insulating glass, the house itself becomes a cost-effective solar collector. C2.3 Illinois Lo-Cal House Page 5

The net heat gain (or loss) of a window varies with the latitude, month, window orientation, solar transmission, heat transmission, outdoor temperature, atmospheric conditions and percent of sunlight, reflected sunlight, and shading of the window. With the seasonal change of sun angle, the direct ray solar gain of south-facing windows is highest of all in winter, moderate in spring and fall, and lowest in summer. The daily solar gain of a south-facing, tripleglazed window may exceed the average 24-hour heat loss through the window; this net heat gain may be as much as 400 Btu per sq. ft. per day during the heating season. In some regions with more sunshine and snow cover, the gain may be higher. Generally, this benefit of triple-glazed windows applies to the cold areas of the United States. In climates with less than 4500 degreedays, south-facing double-glazed windows have similar benefits. Shading. While the south-facing windows provide solar heat for the house from October to April, the windows should be shaded to minimize solar gain from June to October. Trees. Deciduous trees are most useful because they are in leaf during the warm season of the year when shading is needed. They do not interfere with winter solar gain since their leaves have fallen before the heating season. Roof Overhang. With the seasonal change in sun angle, the roof overhang above the south windows can be designed to achieve the amount of shading or sun exposure desired. Other Shading Devices. Awnings, shade screens, shutters, blinds, foils, or draperies can limit solar gain of windows. For example, in conjunction with a roof overhang, shade screens over the lower half of windows can stop most of the solar gain of south-facing windows in August and September. The illustration shows the sun angle for a latitude of 39 with the profile of the roof overhang and south windows of the Lo-Cal House. At 43 latitude, the south windows are over 90 /o exposed to the sun from October 21 to February 21. From April 21 to August 21, the south windows are shaded 80% or more. The roof overhang could be designed to shade the window all summer; ho~ever, this is not desirable since it would also shade the windows and seriously reduce the solar gain during the spring heating season. Therefore, some other shading device should be used to block the sunlight during August and September. S~e Circular 3.2, Solar Orientation, for shading angles at other locations. PREDICTED PERFORMANCE Actual heating costs for the Lo-Cal House are being verified by building and testing a demonstration house under controlled, monitored conditions. Full-scale confirmation of predicted results will require the building of a number of lived-in houses in widespread areas of the United States and Canada. Since, as yet, demonstration house studies are not completed, the best alternative is to make a thorough engineering analysis, taking into account all energy inputs to the Lo-Cal House. For this purpose, a predictive computer program* was used, and weather data for Rantoul, Illinois, in 1957 was selected as having typical characteristics. Assumed Conditions Calculations of energy requirements for all three houses are based on the same conditions of weather, range of internal temperature, and internal heat gains. The HUD 1974 house was calculated on the basis of an air infiltration rate of 1 air change per hour, the 1980 house at 0.75 and the Lo-Cal House at 0.6 air changes per hour due to its tight construction. In both standard houses, the windows were placed with one-third of the total window area on each of the north and south walls and one-sixth on each of the east and west walls. * U. S. Army Corps of Engineers, Construction Engineering Research Laboratory "Building Loads Analysis and Systems Thermodynamics" (BLAST) program. Shading of south windows at 43 latitude (Casper, WY; Madison, WI; Buffalo, NY; Manchester, NH) Page 6 University of Illinois SHC-BRC

TABLE 2. CALCULATED HEATING AND COOLING LOADS Heating Load, Btu/Year Infiltration Loss, Btu/Year Max. Heat. Load; Btu/Hr. 1974 House 57,530,000 35,794,000 36,610 1980 House 37,260,000 25,600,000 26,770 Lo-Cal House 24,290,000 18,280,000 20,990 Cooling Load, Btu/Year Infiltration Gain, Btu/Year Max. Cool. Load, Btu/Hr. 1974 House 9,795,000 758,500 16,710 1980 House 10,350,000 569,000 15,310 Lo-Cal House 9,263,000 453,000 11,930 Comfort Conditions For all three houses, the room-air temperature was allowed to vary between 70 F and 78 F. Most people will accept air temperatures a few degrees above or below 72 F, especially when energy is saved. Winter Performance The heating analysis of the house can be expressed as: HEAT INPUT= HEAT LOSS The heat inputs are: (1) internal gains from persons, lighting, refrigerator, range, television, water heating, etc.; (2) solar gains, mainly from windows; and (3) input from heating ystem which uses fuel or electricity. The heat losses are made up of: (1) transmission losses through the house shell (ceiling, walls, windows, doors, and floors); (2) air infiltration; and (3) building overheating which must be vented. Since, as yet, demonstration house studies are not completed, the best alternative is to make a thorough engineering analysis, taking into account all energy inputs to the Lo-Cal House. For this purpose, a predictive computer program was used and weather data for Rantoul, Illinois, was selected. The heating degree-days for the test year were 5890. In this analysis, the assumed internal heat gain was equal to 15 kwh per day, which, when added to occupant gains, amounts to 61,000 Btu per day. The computer analysis is summarized in Table 2. In order to heat the Lo-Cal House for a year, the owner would need to buy (assuming 75 /o efficiency for gas and oil): 239 gallons of fuel oil, or 242 therms of natural gas, or 7144 kwh of electrical resistance heating. The owner of a house built to the 1974 standards would have to buy about twice the above amounts each heating season, and the requirements of the 1980 house would be about 50% higher than the Lo-Cal House. Summer Performance Because of the extra insulation, the Lo-Cal House gains heat very slowly and the summer cooling load is never high. With the assumed internal heat gain of 61,000 Btu per day, the maximum cooling requirement is about 12,000 Btu per hour in the Rantoul, Illinois, climate. For energy conservation, internal heat gains should be kept as low as possible during warm weather. For example, a large gathering of people in the house would substantially increase the cooling load. For the computer analysis, the cooling season was considered to be from May 1 through October 31. The total cooling load (including internal heat gains) for the period was computed to be 9.3 million Btu. Assuming that 1 kwh of electricity will deliver at least 6000 Btu of cooling, the energy required for cooling would be about 1550 kwh. At five cents per kwh, the cost for cooling would be $78 for the season. This cost could be reduced by using additional shading of the south windows during August and September, and could be further reduced by using night air cooling when the outdoor air temperature and humidity are suitable. Cooling System Selection For the predicted maximum hourly cooling load of 11,930 Btu per hour (Table 2), a central unit with a capacity of one ton or 12,000 Btu per hour would be enough on most days. A larger unit would handle those times when the hourly load is extreme, but the normal operation would be off-and-on, and the humidity would vary and cause discomfort. Better comfort is obtained from a cooling unit which is slightly undersized so that it operates continuously. If occasional unusually large cooling loads are anticipated, such as a large gathering of people in hot weather, an auxiliary cooling unit might be desirable, or the house could be pre-cooled to a lower temperature to control the short overload. C2.3 Illinois Lo-Cal House Page7

ALTERNATE DESIGNS Design B. This incorporates a basement and a fireplace in the basic design. Double sliding glass door units can be used instead of windows. Design C. This is more appropriate when the street is on the south or east of the lot. The entrance is moved to the end of the house and the garage is relocated. Design D. This plan shows how the principles may be applied to a two-story dwelling unit. Second Floor North Principal glass areas Variations in Plot Plan. The principles demonstrated in the design of the Lo-Cal House can be used in the design of all types of hqusing. I t- The plot plan shows the use of the various designs in a typical subdivision having a rectilinear street pattern. It is obvious that monotony and sameness need not be a problem. Page 8 University of Illinois SHC-BRC