Fire Alarm System Fundamentals

Similar documents
NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

Fire Alarm Wiring. Circuit types, styles and limitations

Unified Fire Authority - Fire Prevention Bureau

Changes in NFPA

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

El Reno Fire Department Fire Alarm Plan Review Worksheet

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Questions/Comments for Richard Roux from Webinar on 7/11/13

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights

NFPA 72 Code Changes vs 2013

2018 NICET Code Transition Changes

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

2019 COURSE CATALOG (rev )

The 2013 National Fire Alarm and Signaling Code

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

Interfacing Fire Alarm, Sprinkler and Elevator Systems

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

Division 28 - Electronic Safety and Security

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code 2010

NFPA Changes

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Fire Alarm System Inspection and Testing Report

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

rpsa FIRE PROTECTION ENGINEERS

Fire Alarm System Fundamentals Presented By: Shamim Rashid-Sumar, Vice President Middle East Operations Rolf Jensen and Associates, Inc.

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

Advanced Fire Alarm Systems Training Program Outline (5 Day)

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces

Multiple Input and Output Modules

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

NFPA Changes

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

IN2 Digital, Addressable Fire-alarm System

MNEC NFPA 72 WHITE PAPER

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition

Addressable Fire Alarm Control Panel

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

FIRE DETECTION & ALARM SYSTEM BASICS

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA

Applying Performance-based Fire Alarm System Design Part 4

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

16721 FIRE ALARM AND DETECTION SYSTEMS

Fire Alarm and Life Safety System Inspection Certificate

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

3.1 Introduction. 3.1 Introduction

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017

Functional Performance Test

SECTION FIRE ALARM SYSTEMS

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

Hospital Fire Alarm Systems Recurring Misapplications and Misused Requirements

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800)

SECTION ADDRESSABLE FIRE ALARM SYSTEM

HARRIS COUNTY HOUSING AUTHORITY

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

PROTECTED PROPERTY. City: State: Zip Code: ALARM SERVICE COMPANY. City: State: Zip Code: COMMENTS AND CLARIFICATIONS ALARM SYSTEM DESCRIPTION

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices.

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

MD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

THE BASICS OF FIRE ALARM PLAN REVIEW

Fire Protection Coffee Break Training May 2016


Rancho Cucamonga Fire Protection District Prevention Bureau Standard

16721 FIRE ALARM AND DETECTION SYSTEMS

1.3 REFERENCE STANDARDS

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Pakenham Branch Library Section MacFarlane Street MULTIPLEX FIRE ALARM SYSTEM Project No Page 1 of 12

Fire alarm system specification for multiple tenant retail buildings

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Case Study Media Contact Beth Welch, or

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION INTRUSION DETECTION

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

Case Study Media Contact Beth Welch, or

Transcription:

Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom offers a full line of fire panels from conventional to intelligent FACP s ranging from 6 points of protection to over 500,000. As well, we manufacture a full line of mass notification systems, area of refuge, telephone entry/intercom systems, access control, and nurse call systems.

Introduce Yourself Hi, my name is My employer is I ve been in this industry for I m here because 2

Building Emergency Plan 3

Roster, hot beverages, baños, smokers, lunch, etc.

Goals and Objectives To review Basic Fire Alarm Systems, including their purpose, their operation, and their pieces & parts. Attendees must attend the entire seminar to receive a Certificate of Attendance. 5

Outline Codes and Standards History and Terminology Hardware FACU, Adders, Annunciators, Power Supplies, etc. Wiring Methods and Materials Devices Automatic and Manual Initiating Devices & Modules Appliances Horns, Bells, Buzzers, Chimes, Strobes, & Speakers Holistic Fire Protection 6

Referenced Publications International Building Code, 2012 edition NFPA 72-2013 National Fire Alarm & Signaling Code

History 1. The evolution of Codes and Standards Code of Hammurabi (1760 BC); The Rebuilding of London Act (1670); London Building Act (1844); BOCA/ICBO/SBCCI (1915/1922/1941); IBC (2000 to present) NBFU 70 (1883 to present) NBFU 72 (1896 to present 2. Early alarm and detection 3. Modern addressable analog systems 8

Codes and Standards Why are fire alarm systems installed? Where do Building and Fire Codes fit? What about Installation Standards? Let s get ready to RUMBLE! 9

Approved. Terminology Acceptable to the authority having jurisdiction. NFPA 72-2013 3.2.1* Authority Having Jurisdiction (AHJ). An organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure. NFPA 72-2013 3.2.2* 10

Terminology Listed. Equipment, materials, or services included in a list published by an organization that is acceptable to the AHJ and concerned with evaluation of products or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the equipment, material, or service meets appropriate designated standards or has been tested and found suitable for a specified purpose. NFPA 72-2013 3.2.5* 11

Terminology Nationally Recognized Testing Laboratory (NRTL) 12

13

Terminology Qualified. A competent and capable person or company that has met the requirements and training for a given field acceptable to the authority having jurisdiction. NFPA 72-2013 3.3.222* *Qualified might also mean that the person has knowledge of the installation, construction, or operation of apparatus and the hazards involved. 14

Terminology Device refers to an input (e.g. automatic fire detector, manual box, waterflow switch, etc.) Appliance refers to an output (e.g. horn, bell, chime, strobe, speaker, etc.). Module refers to an addressable input or output (e.g. monitor module, control module etc.) 15

Terminology Circuit refers to an electrical interface, (e.g. IDC, SLC, and NAC). Zone refers to an area, which may include devices and/or appliances. Circuit Class refers to its fault tolerance or how the circuit will perform during a fault condition, by labeling it Class A, B, C, D, E, or X. 16

Hardware Fire Alarm Control Panel Adder Modules Remote Annunciators Remote Power Circuits and Pathways 17

Fire Alarm Control Panel Fire Alarm Control Unit (FACU). A component of the fire alarm system, provided with primary and secondary power sources, which receives signals from initiating devices or other fire alarm control units, and processes these signals to determine part or all of the required fire alarm system output function(s). NFPA 72-2013 3.3.102* 18

Signal A message indicating a condition, communicated by electrical, visible, audible, wireless, or other means. NFPA 72-2013 3.3.257 Condition. A situation, environmental state, or equipment state of a fire alarm or signaling system. Condition Signal Response NFPA 72-2013 A.3.3.57 19

Condition Signal Response Alarm Condition. An abnormal condition that poses an immediate threat to life, property, or mission. Alarm Signal. A signal that results from the manual or automatic detection of an alarm condition. Alarm Response. The response to the receipt of an alarm signal. 20

Condition Signal Response Supervisory Condition. An abnormal condition in connection with the supervision of other systems, processes, or equipment. Supervisory Signal. A signal that results from the detection of a supervisory condition. Supervisory Response. The response to the receipt of a supervisory signal. 21

Condition Signal Response Trouble Signal. A signal that results from the detection of a trouble condition. Trouble Condition. An abnormal condition in a system due to a fault. Trouble Response. The response to the receipt of a trouble signal. 22

Hardware Adder Modules Network Card Conventional, Non-addressable Circuits Loop Adders (SLC) Graphic Driver 23

Transmitters Digital Alarm Communicator Systems. Radio Systems. NFPA 72-2013 26.6 A.26.6.2.2 It is not the intent of Section 26.6 to limit the use of listed equipment using alternate communications methods, provided these methods demonstrate performance characteristics that are equal to or superior to those technologies described in Section 26.6... 24

Remote Annunciators Distribute Control 25

Remote Power Supplies Distribute Power 26

Secondary Power Supply Sized to operate the system for 24 hours in the non-alarm condition and then for 5 or 15 minutes in the alarm condition. (Emergency Voice/Alarm Communication systems for 15 minutes at full load.) NFPA 72-2013 10.6.7.2 27

Battery-set Size Calculation 3-step Process Step 1: Total quiescent (non-alarm) load times 24 hours plus; Step 2: Total alarm load times 5 minutes (15 minutes for EVAC systems) plus; Step 3: A 20% safety margin NFPA 72-2013 10.6.7.2 28

Circuits and Pathways Pathway Class Designations. Pathways shall be designated as Class A, Class B, Class C, Class D, Class E, or Class X, depending on their performance. NFPA 72-2013 12.3* 29

ALARM SUPERVISORY TROUBLE FIRE ALARM CONTROL UNIT End-of-line Resistor Class B Initiating Device Circuit alarm and trouble condition 30

ALARM SUPERVISORY TROUBLE FIRE ALARM CONTROL UNIT Class A Initiating Device Circuit alarm and trouble condition 31

Compatibility All devices and appliances that receive their power from the initiating device circuit or signaling line circuit of a control unit shall be listed for use with the control unit. NFPA 72-2013 10.3.3 This requirement does not apply to notification appliance circuits. NFPA 72-2013 A.10.3.3 32

Addressable Device A fire alarm system component with discrete identification that can have its status individually identified or that is used to individually control other functions. NFPA 72-2013 3.3.8 Devices are polled and changes in condition are reported; alarm, supervisory, and trouble. 33

SLC Supervision 4 13 3 12 1 2 5 11 Addressable Fire Alarm Control Panel 6 7 8 9 10 Signaling Line Circuit (SLC)

Analog Initiating Device (Sensor) An initiating device that transmits a signal indicating varying degrees of condition as contrasted with a conventional initiating device, which can only indicate an on off condition. NFPA 72-2013 3.3.132.1 35

Analog Addressable System Certain systems are able to upwardly adjust sensor alarm threshold automatically to avoid a nuisance alarm resulting from hostile environments. This type of system will identify the affected detector when the limit of compensation is reached. NFPA 72-2013 23.8.5.4.2 36

Analog Addressable System Node 1 Loop 2 Device #101 Smoke Detector Dirty 37

Conventional vs. Addressable Initiating Device Circuit (IDC) 1 1 1 1 1 1 EOL Resistor Conventional Fire Alarm Control Panel 4 3 13 12 1 2 5 11 Addressable Fire Alarm Control Panel 6 7 8 9 10 Signaling Line Circuit (SLC)

ALARM SUPERVISORY TROUBLE FIRE ALARM CONTROL UNIT - + + - + - + - End-of-line Resistor Class B Notification Appliance Circuit trouble condition 39

ALARM SUPERVISORY TROUBLE - FIRE ALARM CONTROL UNIT + + + - + - + - - Class A Notification Appliance Circuit trouble condition 40

Bringing it all Together Primary Power Dedicated 120VAC Transmitter Supervising Station Initiating Device Circuits (IDC) S S S S Smoke Detectors P H P Manual Boxes Fire Alarm Control Panel Remote Annunciator H H H Heat Detectors Secondary Power Battery-set Event Printer / Hyperterminal HS HS HS Notification Appliance Circuits HS HS (NAC)

Fire Alarm System Wiring Methods Fire alarm systems are unique. Circuits are either supervised, redundant, or both. Therefore, their wiring methods are a bit different than that for light, power, and other limited-energy electrical systems. Install IAW NFPA 70, Article 760. NFPA 72-2013 12.2.4.3 Installation and Use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. NFPA 70-2014 110.3(B) 42

Wiring Methods and Materials NFPA 70-2011 Chapter 3 I. General Requirements 300.1 Scope. (A) All Wiring Installations. This article covers wiring methods for all wiring installations unless modified by other articles. 43

Voltage Drop Equipment shall be designed so that it is capable of performing its intended functions under the following conditions: (1)*At 85% and at 110% of the nameplate primary (main) and secondary (standby) input voltage(s) (2) At ambient temperatures of 32 F and 120 F (3) At a relative humidity of 85% and an ambient temperature of 86 F NFPA 72-2013 10.3.5 44

Circuit Fundamentals ALARM SUPERVISORY TROUBLE Source Load FIRE ALARM CONTROL UNIT - + Circuit Conductors + - End-of-line Resistor 45

Voltage Drop Is a function of current and resistance. Resistance is a function of conductor length and size. AWG DC Resistance /1000 10 1.24 12 1.98 14 3.07 16 4.89 18 7.77 NFPA 70-2011, Chapter 9, Table 8 Conductor Properties 46

End-of-line Method Total circuit length = distance x 2 ALARM SUPERVISORY TROUBLE Distance FIRE ALARM CONTROL UNIT - + + - End-of-line Resistor 47

Devices Automatic; Smoke, heat, flame, gas, waterflow Manual Boxes; single action, double action Supervisory Signal Valve Position, Air Pressure, Fire Pump Addressable Modules Monitor (input), SO (output), Relay 48

Heat-Sensing Fire Detectors NFPA 72-2013 17.6

Smoke-Sensing Fire Detectors NFPA 72-2013 17.7

Radiant Energy-Sensing Fire Detectors NFPA 72-2013 17.8

Gas Detection NFPA 72-2013 17.10

Manually Actuated Alarm-Initiating Devices NFPA 72-2013 17.14

Manually Actuated Alarm-Initiating Devices Each manual fire alarm box shall be securely mounted. The operable part of each manual fire alarm box shall be not less than 42 in. and not more than 48 in. above floor level. Manual fire alarm boxes shall be installed so that they are conspicuous, unobstructed, and accessible. NFPA 72-2013 17.14

55

Fire Extinguisher Electronic Monitoring Device NFPA 72-2013 17.15

Supervisory Signal Initiating Devices NFPA 72-2013 17.16

Notification Appliances NFPA 72-2013 18.1

Public Mode Audible Requirements To ensure the audible public mode signals are clearly heard, they shall be: 15 dba above average ambient or; 5 dba above maximum (having a duration of at least 60 seconds) Whichever is greater, in the area required to be served by the system on the A-weighted scale (dba). NFPA 72-2013 18.4.3.1* 59

Average Ambient Sound Level Business Occupancies... Education Occupancies... Industrial Occupancies... Institutional Occupancies... Mercantile Occupancies... Piers & Water Surrounded Structures... Places of Assembly... Residential Occupancies... 55 dba 45 dba 80 dba 50 dba 40 dba 40 dba 55 dba 35 dba NFPA 72-2013 Table A.18.4.3 60

Sleeping Area Requirements Where audible appliances provide signals for sleeping areas, they shall have a sound level of at least 15 db above the average ambient sound level or 5 db above the maximum sound level having a duration of at least 60 seconds or a sound level of at least 75 dba, whichever is greater, measured at the pillow on the A-weighted scale (dba). NFPA 72-2010 18.4.5.1 61

Visible Notification Appliance NFPA 72-2013 18.5

Visible Signaling Requirements Visible notification appliances shall be installed in accordance with Table 18.5.5.4.1(a) or Table 18.5.5.4.1(b) using one of the following: (1) A single visible notification appliance. (2) *Two groups of visible notification appliances, where visual appliances of each group are synchronized, in the same room or adjacent space within the field of view. This shall include synchronization of strobes operated by separate systems. (3) More than two visible notification appliances or groups of synchronized appliances in the same room or adjacent space within the field of view that flash in synchronization. NFPA 72-2013 18.5.5.4.2 63

Visible Signaling Requirements 1. Wall-mounted appliance location The entire lens 80-96 above the finished floor (except sleeping areas) 2. Ceiling-mounted appliances Within 30 of the finished floor 3. Sleeping areas 177cd within 2 of ceiling 110cd more than 2 below ceiling NFPA 72-2013 18.5 64

Textual Audible Appliance NFPA 72-2013 18.8

Annunciator Formats 66

Emergency Communication System (ECS) One-Way Emergency Communications System. Distributed Recipient Mass Notification System (DRMNS). In-Building Fire Emergency Voice/Alarm Communications System. In-Building Mass Notification System. Wide-Area Mass Notification System. Two-Way Emergency Communications System. 67

Survivability For systems employing relocation or partial evacuation, a Level 2 or Level 3 pathway survivability shall be required. NFPA 72-2013 24.3.6.4.1 68

Survivability Pathway survivability Level 2 shall consist of one or more of the following: (1) 2-hour fire-rated circuit integrity (CI) cable (2) 2-hour fire-rated cable system [electrical circuit protective system(s)] (3) 2-hour fire-rated enclosure or protected area (4) 2-hour performance alternatives approved by the authority having jurisdiction NFPA 72-2013 12.4.3 69

Survivability Pathway survivability Level 3 shall consist of pathways in buildings that are fully protected by an automatic sprinkler system in accordance with NFPA 13, and one or more of the following: (1) 2-hour fire-rated circuit integrity (CI) cable (2) 2-hour fire-rated cable system [electrical circuit protective system(s)] (3) 2-hour fire-rated enclosure or protected area (4) 2-hour performance alternatives approved by the authority having jurisdiction NFPA 72-2013 12.4.4 70

Balanced Fire Protection Alarm and Detection To provide occupant early warning Sprinkler System To suppress and extinguish Fire and Smoke Barriers To provide tenability 71

NFPA 72-2013 21.1 Emergency Control Function Interfaces Elevator Recall for Fire Fighters Service Elevator Shutdown Fire Service Access Elevators Occupant Evacuation Elevators HVAC Systems Door and Shutter Release Electrically Locked Doors Exit Marking Audible Notification Systems 72

Emergency Control Functions and Interfaces Maintain Path of Egress Maintain Areas of Refuge Provide Clear Approach for Firefighters Minimize Fire and Smoke Damage 73

74

Elevator Recall for Firefighters Service When sprinklers are installed in elevator pits, install automatic fire detection to initiate elevator recall IAW ASME A17.1 2.27.3.2.1(c) (1) Where sprinklers are located above the lowest level of recall, locate the fire detection device at hoistway top. (2) Where sprinklers are located in the bottom of the hoistway (the pit), fire detection device(s) shall be installed in the pit in accordance with Chapter 17. (3) Outputs to the elevator controller(s) shall comply with 21.3.14 [Satisfy ASME A17.1]. NFPA 72-2013 21.3.7* 75

Elevator Code Phase I Emergency Recall Operation by Fire Alarm Initiating Devices Fire alarm initiating devices shall be installed in conformance with NFPA 72, and located: At each floor served by the elevator; In the associated elevator machine room; In the elevator hoistway, when required. ASME A17.1 2.27.3.2 76

Elevator Recall for Firefighters Service Smoke detectors shall not be installed in unsprinklered elevator hoistways unless they are installed to activate the elevator hoistway smoke relief equipment. NFPA 72-2013 21.3.6 If ambient conditions prohibit installation of automatic smoke detection, other automatic fire detection shall be permitted. NFPA 72-2010 21.3.9* 77

Smoke Control Systems Smoke control, as required by the building code, is intended to: 1. Limit the spread of smoke 2. Direct the smoke out of the building NFPA 92A Smoke Control Systems Standard NFPA 92B Smoke Management Systems Standard 78

Smoke Control Methods Natural The use of windows, panels and/or hatches so that smoke will flow directly to the outside. Mechanical The use of building HVAC equipment to exhaust smoke and bring in outside air. 79

Smoke Detectors for Control of Smoke Spread Classifications. Smoke detectors installed and used to prevent smoke spread by initiating control of fans, dampers, doors, and other equipment shall be classified in the following manner: (1) Area detectors that are installed in the related smoke compartments (2) Detectors that are installed in the air duct systems (3) Video image smoke detection that is installed in related smoke compartments NFPA 72-2013 17.7.5* 80

Smoke Detectors for Control of Smoke Spread 81

Emergency Control Functions Emergency control function interface devices shall be located within 3 ft (1 m) of the component controlling the emergency control function. NFPA 72-2013 21.2.4* 82

Exit Marking Audible Notification Systems NFPA 72-2013 21.10

Discussion Questions What NFPA chapter governs commercial fire alarm systems? What NFPA chapter governs fire alarm electrical circuits and wiring? What NFPA chapter governs the standard for Smoke Control Systems? *Bonus* What IBC chapter governs commercial fire protection systems?

In Conclusion