ELSEMA MD2010. Application Controls automatic doors or gates when a vehicle is present. Description

Similar documents
MD12-1 Vehicle Loop Detector

MD12-2 Vehicle Loop Detector

MVP-D-TEK Vehicle Loop Detector 9 Volts DC to 240 Volts AC. Operating Instructions

Operating Instructions

Eclipse MC240. Double & Single Gate Controller with Eclipse Operating System (EOS) 3rd Edition. MC240 for Double and Single Gates.

D-TEK -MS Vehicle Loop Detector. Operating Instructions

Operating Instructions

Operating Instructions

For more information, please visit or call toll free at

ENGINEERED PARKING SYSTEMS MODEL 3416D

QA16 Addressable System

D-TEK O P E R A T I N G I N S T R U C T I O N S V E HI C L E L O O P DETECTOR Johnston Parkway, Cleveland, Ohio 44128

MTRA-FSP Level Control Relay. Installation & Operation Manual

SMARTWALK DEMENTIA WANDERING SYSTEM

MULTIGUARD MULTIGUARD USERS MANUAL TYPE S3/240W 26/01/2010

ELECTRO-FENCE TM. Fence Protection System. Installation Manual. EF_Install_V2

DSP-13 Tri-Axis Detection (TRIAD TM ) System

Operating Instructions

User instructions. Wingo 3524 HS Swing gate operator

Installation, Operating and Maintenance Manual

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Product Data Sheet. Merlin GDP2. Gas Safety Products. Merlin GDP2. Installation, operating and maintenance 23/08/2016. S&S Northern Ltd 1

LUX Hardwired - Installation Notes

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016

CM-RQE70 PIR REQUEST TO EXIT DETECTOR

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance 23/08/2016. Merlin 1000BH Gas Proving/Gas Detection System

Conventional Fire Alarm System 2014 V1.2

CM-RQE70A PIR REQUEST TO EXIT DETECTOR

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

ARROWHEAD ALARM PRODUCTS Ltd. 344b Rosedale Rd, Albany, Auckland. Ph Fax v1.0

DIGITAL ALARM UNIT Model ALU-AP

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

SECURIT 700L USER MANUAL

User s Information Guide R2A

RONDISH DoorWatcher EASY INSTALL STRIP DOOR MONITOR

AED Alarm System Model Operations Manual

TBR 40 1 GD Blood Refrigerator Instruction Manual. for BLOOD STORAGE REFRIGERATORS MODEL TBR 40 1 GD. (40 x 500ml Blood Bag Capacity)

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

Section 1: General Description. Section 2: Features. Section 3: Operation. CM-RQE70 PIR REQUEST TO EXIT DETECTOR Installation Instructions.

Intruder alarm panel Terxon MX Operating instructions

Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Control Panel User Guide

ANTI SLEEP ALARM INTRODUCTION

Gas Safety Products. Installation, operating and maintenance. Merlin 1000BH Gas Proving/Gas Detection System

U ser's Guide PC6010

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

WIRING DIAGRAM AND INSTRUCTIONS

Using Your. Security System With LED Keypad S5030, S5031, S5032

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

Master Code Arming Auto-Bypass Option - Home-Away Arming Entry Delay Off Arming

Remote switching machines with a SMS text from your mobile phone! Remote Monitoring your assets in the worldwide by your mobile Phone!

STANDARD FEATURES SPECIFICATIONS

Control Panel Engineering and Commissioning Instructions

Digital Electronic Thermostat With RF

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

DOLKPS1KB Programming & Installation Manual

WM3000 WIRELESS MODULES

For silent arm / disarm use BUTTON 2.

Secure WANDERING INSTALLATION AND USAGE GUIDE

v Model No: TIMER Multi-function Timer Module Please note: * eeee on the display indicates a non valid dip-switch setting.

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor

Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

2G & 3G GSM Portable PIR Alarm

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

ZLM4 OEM Technical Manual

Elite. GJD022 /GJD023 35m External PIR. Multi Beam Lens Data

5 Sounds and Indications

Wireless D.I.Y. Alarm Kit

EDW500 / EDW503. Electronic Controls for Dishwashers

ORP (mv) Controller Model: ORP-XP2. UP DOWN ENTER Time & Date Main Menu Alarm Reset

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

SOLO Installation manual STAND-ALONE PROXIMITY ACCESS CONTROL SYSTEM

GSM RFID VOICE Alarm System

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

MOBILE CALL GSM Alarm System User s Manual

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

CONTROL DEVICE SLIDETRONIC HD

2G & 3G GSM Wireless Beam Alarm

Refrigerated air dryers

705 Emmett Street Bristol, CT DynaLock MODEL 3101C-TJ101 DELAY EGRESS SYSTEM WIRING INSTRUCTIONS

USER MANUAL FOR OPERATING SYSTEM

INSTRUCTION MANUAL FOR. Remote Control Car Alarm with Impact Sensor, Mini-Battery Backup Siren & Engine Immobiliser

Digital Electronic Thermostat With RF

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

Wireless Call Point ( )

TO ARM/DISARM ALARM The alarm is activated by pressing BUTTON 1 on the remote control transmitter once. The blinkers will flash once, and the

"Pegaso" wireless alarm system

DCS2000 DEMENTIA CARE SYSTEM USER GUIDE. For Software Version 1.2 1

FIRE STROBE 2000 INSTALLATION INSTRUCTIONS

User Guide ems25plus. Page 1. Normal operation. Product interface

MODEL KP-200 VANDAL RESISTANT & WEATHERPROOF FLUSH MOUNT DIGITAL KEYPAD DESIGNED FOR ACCESS CONTROL APPLICATIONS


ZM1 User Manual JVA TECHNOLOGIES.

SPACEMOTION SERIES SMM 01

Transcription:

Loop Detector is used to detect metal objects such as motor vehicles, motor bikes or trucks. ELSEMA Features Wide supply range: 12.0 to 24 Volts DC 16.0 to 24 Volts AC Selectable sensitivity Pulse or Presence setting for relay output. Power up and loop activation LED indicator Application Controls automatic doors or gates when a vehicle is present. Description Loop detectors in recent years have become a popular tool having innumerable applications in policing, right from surveillance operations to traffic control. Automation of gates and doors has become a popular usage of the loop detector. The digital technology of the loop detector enables the equipment to sense a change in the inductance of the loop as soon as it detects the metal object in its path. The inductive loop which detects the object is made of insulated electrical wire and is arranged either as a square or rectangle shape. The loop consists of several loops of wire and consideration should be giving to the loop sensitivity when installing on different surfaces. Setting the correct sensitivity allows the loops to operate with maximum detection. When detection occurs, the detector energises a relay for the output. This energising of the relay can be configured, to three different modes, by selecting the output switch on the detector. Sensing Loop Position A safety loop should be positioned where the largest amount of metal of the vehicle will be present when that vehicle is in the path of the moving gate, door or boom pole. Be aware that metal gates, doors or poles could activate the loop detector if they pass within range of the sensing loop. A free exit loop should be positioned +/- one and a half car lengths away from the gate, door or boom pole, on the approach side for traffic exiting. In cases where more than one loop is installed ensure there is at least a distance of 2m between the sensing loops to prevent cross-talk interference between the loops. (Also see Dip-switch 1 option and number of turns around the loop) 1

LOOP Elsema stocks pre-made loops for easy installation. Our pre-made loops are suitable for all types of installations. Either for cut-in, concrete pour or direct hot asphalt overlay. see www.elsema.com/auto/loopdetector.htm Detector position and installation Install the detector in a weatherproof housing. The detector should be as close to the sensing loop as possible. The detector should always be installed away from strong magnetic fields. Avoid running high voltage wires near the loop detectors. Do not install the detector on vibrating objects. When the control box is installed within 10 metres of the loop, normal wires can be used to connect the control box to the loop. More than 10 metres requires the use of a 2 core shielded cable. Do not exceed 30 metres distance between control box and loop. Dip-switch Settings Frequency setting (Dip switch 1) Dip switch 1 ON High Frequency Low Frequency Dip switch 1 OFF This setting is used in cases where two or more loop detectors and sensing loops have been installed. (The sensing loops and detectors should be positioned at least 2m apart). Set one detector to high frequency and the other set to low frequency to minimize the effects of cross-talk between the two systems. 2

Loop Sensitivity (Dip switch 2&3) Low sensitivity 1% of loop frequency Dip switch 2 & 3 OFF Low to medium sensitivity 0.5% of loop frequency Medium to high sensitivity 0.1% of loop frequency Dip switch 2 ON & 3 OFF Dip switch 2 OFF & 3 ON This setting determines the necessary change to the loop frequency to trigger the detector, as metal passes across the sensing loop area. High sensitivity 0.02% of loop frequency Dip switch 2 & 3 ON Boost mode is OFF Boost mode is On (Active) Boost Mode (Dip switch 4) Dip switch 4 OFF Dip switch 4 ON If boost mode is ON the detector will immediately switch to high sensitivity once activated. As soon as the vehicle is no longer being detected the sensitivity reverts back to what has been set on dipswitch 2 and 3. This mode is used when the height of the undercarriage of a vehicle increases as it passes over the sensing loop. 3

Permanent presence or limited presence mode (When presence mode selected. See dip-switch 8) (Dip switch 5) This setting determines how long the relay remains active when a vehicle is stopped within the sensing loop area. With limited presence mode, the detector will only activate the relay for 30 min. Dip switch 5 OFF If the vehicle has not moved out of the loop area after Limited presence mode 25 min, the buzzer will sound to alert the user that the relay will deactivate after another 5 min. Moving the vehicle across the sensing loop area again, will reactivate the detector for 30 min. Permanent presence mode Dip switch 5 ON The relay will remain active for as long as a vehicle is detected within the sensing loop area. When the vehicle clears the sensing loop area, the relay will deactivate. Relay Response (Dip switch 6) Relay response 1 Dip switch 6 OFF Relay activates immediately when the vehicle is detected in the sensing loop area. Relay response 2 Dip switch 6 ON Relay activates immediately after the vehicle leaves the sensing loop area. Filter ON Dip switch 7 ON Filter (Dip switch 7) This setting provides a 2 sec delay between detection and relay activation. This option is used to prevent false activations when small or fast moving objects pass through the loop area. This option can be used where an electric fence nearby is the cause of false activations. If the object does not remain in the area for 2 sec the detector will not activate the relay. 4

Pulse mode or Presence mode (Dip switch 8) Pulse mode Dip switch 8 OFF Pulse mode. Relay will activate for 1 sec only on entry or exit of sensing loop area as set by dip-switch 6. To re-activate the vehicle must leave the sensing area and re-enter. Presence mode Dip switch 8 ON Presence mode. Relay will remain active, as per dipswitch 5 selection, for as long as a vehicle is within the loop sensing area. Reset (Dip switch 9) The must be reset every time a setting change is made to the Dip-switches Reset Dip switch 9 ON/OFF To reset, switch dip-switch 9 on for approximately 2 seconds and then off again. The detector then completes the loop test routine. *Please note: The must be reset every time a setting change is made to the Dip-switches Relay status: Presence mode Pulse mode Relay Vehicle Present No vehicle present Loop faulty No Power N/O Closed Open Closed Closed N/C Open Closed Open Open N/O Closes for 1 sec Open Open Open N/C Opens for 1 sec Closed Closed Closed Power up or Reset (Loop testing) On power up the detector will automatically test the sensing loop. Ensure the sensing loop area has been cleared of all loose pieces of metal, tools and vehicles before powering up or resetting the detector! 5

Loop status is showed in the below table: ELSEMA Loop Status Fault LED Buzzer Loop is open or loop frequency too low 3 flashes after every 3sec Continues Until loop is corrected 3 beeps after every 3sec Repeats 5 times and stops Detect LED - - Solution 1. Check if loop is open. 2.Increase the loop frequency by adding more turns of wire Loop is short circuited or loop frequency too high 6 flashes after every 3sec Continues Until loop is corrected 6 beeps after every 3sec Repeats 5 times and stops 1. Check for short circuit in the loop circuit 2. Reduce the number wire turns around the loop to reduce the loop frequency Good loop All three the Detect LED, Fault LED and the buzzer will beep/flash (count) between 2 and 11 times to indicate the loop frequency. 1 count = 10KHz 3 counts x 10KHz = 30 40KHz Power up or Reset Buzzer and LED indications) Buzzer and LED indication: Detect LED 1 sec flashes 1 sec apart No vehicle (metal) detected in loop area On permanently Vehicle (metal) detected in loop area Fault LED 3 flashes 3 sec apart Loop wire is open circuit. Use Dip-switch 9 after any change has been done. 6 flashes 3 sec apart Loop wire is short circuited. Use Dip-switch 9 after any change has been done. Beeps when vehicle is present Continuous beep with no vehicle in the loop area Buzzer Buzzer beeps to confirm the first ten detections Loose wiring in loop or power terminals Use Dip-switch 9 after any change has been done. Elsema Pty Ltd 31 Tarlington Place, Smithfield NSW 2164 Ph: 02 9609 4668 Fax: 02 9725 2663 Website: www.elsema.com 6 Distributed by: