DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

Similar documents
LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

INSTRUCTION MANUAL A131 High Level Audible Warning System / Battery backup

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Door Release Power Supply

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

New Silent Alert Fire Safe System

Gas Safety Products. Installation, operating and maintenance 28/10/2015. Merlin CT1250 Gas Interlock System. S&S Northern Ltd 1

Silent Alert Fire Safe System

1 Dimensions Installation Mains/boosted cold water inlet Connection to the system Drain Dimension for fixing 6

LEAKSTOPPER 1 Single zone water leak detection system

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

Installation, Operation and Maintenance Manual

Installation and user manual for the BiWire / Conventional Repeater Panel

GAS SUPRESSION CONTROL PANEL:

LEAKSTOPPER RANGE Multizone water leak detection systems

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Installation, Operating and Maintenance Manual

LeakSafe. solutions. WaterSwitch2. Installation Instructions

LeakSafe. solutions. WaterSwitch2. Installation Instructions

Please read this sheet as it contains important information

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

LMS-188-4P-BMS 4 POINT DIGITAL MONITOR/ALARM WITH PROTOCOL CONVERTER OPERATING INSTRUCTIONS

Intelligent Security & Fire Ltd

Product Data Sheet. Merlin GDP2. Gas Safety Products. Merlin GDP2. Installation, operating and maintenance 23/08/2016. S&S Northern Ltd 1

Smoke Vent Control Panel PCB4 V4 Installation Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

Leak Detection System Leak Minder Model: LDA-1 Instruction Manual

Noby-448 User Operating Manual & Log Book Page 1 of 12. Fire Control Panel. User Operating Manual & Log Book

ELECTRIC FIRE PUMP CONTROLLER

AS DIGITAL FIRE PUMP CONTROLLER

Excellence in Level Measurement

5000 INSTALLATION GUIDE

CERAMIC HEATER MODEL NO: DEVIL 350B 230V/110V OPERATING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS GC ISS 1

Premier Hazard STC Instructions

OPERATION AND INSTALLATION MANUAL

UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016

Accessible Toilet Alarm

Panel Functions & Indicators - Key to Icons General & Zone Fire LEDs ACCEPT SOUNDERS START/ STOP RESET BUZZER MUTE KEYSWITCH DELAY ON/OFF ITEM SELECT

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

THX-DL Data Logger USER & INSTALLATION MANUAL V

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

10yr O2NE & Safe-Ox. User Manual

Flopurge TS. Operation Manual

QA16 Addressable System

AquiTron. AT-LDM Liquid Detection Module INSTALLATION INSTRUCTIONS

Flostop TS D7E and A8E. Operation Manual

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

INSTRUCTION MANUAL A131 High Level Audible Warning System

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

400 SERIES REMOTE SIREN WITH REMOTE ROTARY CONTROL PANEL ETSA481RSR - 100W ETSA482RSR - 200W

Beacon 800 Gas Monitor Operator s Manual

Conventional Fire Alarm System 2014 V1.2

Strikemaster ES Engineering Manual

BC-4000 Bilge Monitor/Controller Installation Manual

Control Panel Engineering and Commissioning Instructions

AlertMaxx2. Installation & Operating Manual. Ground Water (DMS-298) Pump Station High Level Alarm

USER MANUAL & MAINTENANCE GUIDE OG OO

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

HT-2 / 9600 Series Control Contents

Beacon 110 Gas Monitor Operator s Manual

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

OPERATING and SERVICE GUIDE USA - Coin in / Ticket out Feature.

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

TECHNICAL MANUAL EDITION 1.0 VANDAL RESISTANT AUDIO AND VIDEO DOOR ENTRY SYSTEMS

Pakton Technologies Pty Ltd ABN Ferrier Road, Narangba Qld 4504

Operation and Maintenance Manual

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL

THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH.

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL

MULTIFUNCTION ALARM SYSTEM TYPE ED510 FIRE LEVEL GAS ZONE 1 ZONE 2 ZONE 1 ZONE 2 SENSOR 1 SENSOR 2 ALARM FAULT TEST ON TEST OFF

Four Channel Gas Detection System AGDS 4. The Home of Control & Automation in Ireland

Pioneer-R16 Gas Monitor Operator s Manual

Control Panel User Guide (TO BE RETAINED BY THE USER)

Troubleshooting Guide

BiWire Flexi. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI Installation Manual

WARNING FIRE DOOR CLOSING

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

EATON DFDAP-M / FDAP-M Remote Alarm Panels

2200 and 2200L ALARM CONTROL SYSTEMS

HGM300/RDM800 PREVENTATIVE MAINTENANCE AND TECHNICAL SUPPORT. SECTION 1 HGM300 CPU reset, RDM800 CPU reset, WARM UP notes and HGM300 Self Test

ZSC100 Gas Detection and Alarm System Controller

TECHNICAL DATA OBSOLETE

Cat No. 099A. Digital Programmable Thermostat for Weekday/Weekend Setting. User Maunal

Transcription:

CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 DMWD 1 to 4 Zone Water Detection with Distance to Leak Measurement Installation and Operation Manual

Contents 1) Display and Control 2) Operation 3) Water leak detected Test 4) Water Detected 5) Sensor Fault 6) Water Detection Sensitivity Adjustment 7) Installation 8) Positioning the water detection cable 9) Fitting Cable clips 10) Water Valve 11) Water Valve Override Procedure 12) Beacon and beacon sounder 13) Fitting the battery backup 14) Commissioning 15) Fault Diagnosis 16) Installation Drawing 17) Housing Size 2

1) Display and Control Zone Status Display Mute Push Button Zone Sensitivity Adjustment see Item 6 below Removable Terminal Block for connection to the water detection cable or sensor Valve Override & Display Cable Length Button Display Screens a) All detection cables are connected correctly and a water leak has not detected b) The detection cable has been disconnected, unplugged, damaged or cut 3

c) When the display is rotating between the above two windows, water has been detected and the unit is calculating the distance to the leak d) After (c) above, the display will change to show the distance to the leak from the start of the water detection cable. e) A leak has been detected but the zone is either not set for a distance reading, was unable to calculate the cable length on power up due to water or contaminants in the cable, or encountered a problem in determining the distance to the leak. 2) Operation In normal operation with no alarms or faults, the audible warning device will be OFF and the display will be showing The System has no s or Faults. If one or more of the zones has a disconnected or damaged cable, the audible warning device will sound and the display will show Zone (1-2-3-4) Damaged or Disconnected Cable. If the detection cable detects water, the audible warning device will sound and the display will alternate between WATER LEAK DETECTED ZONE (1-2-3-4) Please Wait and WATER LEAK DETECTED Distance Coming Soon until the final display window showing the distance to the leak WATER LEAK DETECTED ZONE (1-2-3-4) At 8 Metres. The display window WATER LEAK DETECTED AT ZONE (1-2-3-4) will be displayed on powering up if the system cant determine the total detection cable length due to water or contaminants touching the cable. This window will also be displayed if the system cant determine the distance to the leak or the zone is not set for distance measurement. If water shutoff valves are fitted, if a zone detects water, the appropriate valve will close and the associated internal Closed lamp will illuminate. The system will automatically open the valve allowing water to flow once the zone stops detecting water. This shutdown can be overridden, See Item 11 below. The length of the water detection cable can be checked providing the system has no alarms or faults as shown in screen (a) on page 3. To check the cable lengths press the Override / View push button. Each cable length will be displayed one at a time. If the system has multiple alarms, the screen will automatically scroll between each alarm one after the other providing the current alarm has been muted. This scrolling can be stopped at any time by continually pressing the Mute push button. If multiple alarms occur at the same time, each alarm will need acknowledging by the press of the Mute button. i.e. zones 1 & 2 go into water detected alarm at 4

the same time, the audible warning will be going with Zone 1 water detected on display. Pressing Mute will stop the audible warning but it will immediately start again only this time the display will be showing Zone 2 water detected. This second alarm will also need the mute button operated to silence the audible warning. For ease of installation and fault diagnoses both individual zone and Fault lamps have been provided internally on the top PCB. 3) Water leak detected Test To test that the unit is functioning correctly, pressing the red Test Zone button to put the system into a Water detected alarm. Using the test facility will operate the alarm relays generating a BMS alarm, and if fitted activate of the remote beacon/sounder and close the water shutoff valve. The resulting screen can be either (d) or (e) as shown on page 3. The displayed distance if any will be fictional. 4) Water Detected When the detection cable comes into contact with water anywhere along its length, the audible warning device will start, the common alarm and if fitted, the zone alarm relay will close and the display will show the zone number and distance to the leak from the start of the detection cable. To stop the audible warning press the Mute button. The system will remain in this state until the water has been removed from the cable when the alarm relay will automatically turn OFF. 5) Sensor Fault Because of the exposure of the detection cable on the floor, the system monitors for any breaks in the detection cable including the interconnection cable between the control unit and the detection cable. If a break within the cable is found, the audible warning device will start, the fault relay will operate and the display will show the zone number. To stop the audible warning press the Mute push button. The system will remain in this state until the sensor fault is repaired when the display and common fault relay will revert back to normal. If the controller detects a break in the cable, the system will continue to detect water up to the point of the break. 6) Water Detection Sensitivity Adjustment To increase the sensitivity of the cable turn the potentiometer ANTICLOCKWISE, to de-crease the sensitivity turn CLOCKWISE. Increase Sensitivity Decrease Sensitivity The sensitivity adjustment is provided to allow the point at which the system goes into alarm to be adjusted. Once the system is in alarm the cable will need to be dry before any reset. It is recommended that the sensitivity be set so that the arrow on the white plastic circle as shown above is pointing at the 3:00 clock position 5

7) Installation THIS EQUIPMENT SHOULD ONLY BE CONNECTED AND WORKED ON BY A QUALIFIED ELECTRICIAN. To mount the unit to a wall, first remove the front cover to expose the internal equipment. In each corner of the housing positioned below/above the front cover fixings will be found the mounting holes. Plastic glands have been provided for incoming power and outgoing signal cables. The large gland requiring a 20mm hole within the housing is for the power cable and the smaller gland requiring a 13mm hole within the housing is for the signal cable. Care should be taken when drilling the holes to ensure no damage occurs to the electronic equipment. A suitably rated 230VAC power cable supply should be run from a fused spur to the unit and terminated to the internal terminal block marked L, E & N. The fuse within the fused spur should be rated at 5 Amps. Distance Measuring Signal Cable Connections White signal cable Red wire to "A +", Black wire to "B -", Yellow wire to C, Blue wire to D Terminate the Red, Black, Yellow and Blue wires to the terminals within The alarm housing as shown above Signal cable used to connect the water detection cable to the alarm unit terminals. Water leak detection Cable run around the area to be protected Signal cable to Water detection cable connectors End of line Terminator Plug MUST Be fitted at the end of the detection cable 6

Non Distance Measuring Signal Cable Connections White signal cable Red wire to "A +", Black wire to "B -" Water leak detection Cable run around the area to be protected End of line Terminators Plug MUST Be fitted at the end of the detection cable Signal cable to Water detection cable connectors Terminate the Red and Black wires to the terminals within The alarm housing as shown above Signal cable used to connect to the water detection cable to the alarm unit terminals Power, Valves and BMS Connections 230VAC SUPPLY 230VAC To Zone 1 Valve 230VAC To Zone 2 Valve 230VAC To Zone 3 Valve 230VAC To Zone 4 Valve Zone 1 Output Contact Zone 2 Output Contact Zone 3 Output Contact Zone 4 Output Contact Common Output Contact Common Fault Output Contact 7

Output Volt Free contacts for use by a Building Management System. Function Required Fitted as Standard Relay Output Terminals Zone 1 alarm No Z1 Zone 2 alarm No Z2 Zone 3 alarm No Z3 Zone 4 alarm No Z4 Water detected alarm any zone Yes Common Cable Disconnected Yes Common Fault Power Fault Yes Common Fault All Zone wiring and volt free alarm / fault relays wiring is to removable screw type terminal blocks. 8) Positioning the water detection cable The detection cable is susceptible to damage and should not be fitted to areas where the cable is likely to be damaged or walked on. If fitting the cable around Air Conditioning Units with humidifiers, ensure that cable is positioned at least one metre from the ACU to stop intermittent alarms being generated from over humidity or water droplets from the AHU. Having positioned the detection cable, ensure that the End of line terminator is plugged into the end of the cable (see drawing above). 9) Fitting Cable Clips If Cable Clips are required, to protect the small sensor wires and to stop false water detected alarms from occurring insulating tape should be first applied around the detection cable before the clip tongue is closed. Clips should be fitted approximately every 1 to 1.5 metres apart. When using clips make sure that the cable touches the floor between the clips, DO NOT tighten the cable so that the cable does not touch the floor. Insulating Tape Under the fixing clip tongue 10) Water Valve If the system is supplied with water shutoff valves, once a water leak has been detected the unit will remove the 230V supply holding open the valve thereby closing it and stopping the flow of water. Once the leak has been rectified the detection cable may take some hours to dry out. During the dry out period the valve can be opened and closed using the procedure outlined in Item 11 below. 8

Connection of Water Ball Valve The 230VAC supply to the valves is generated from within the alarm unit. 15 to 25mm valves are supplied with a red and black cable whilst larger valves are red and green. For good practice connect live to the red wire and neutral to the black or green wire. The Valve is supplied with a short length of cable that will need extending back to the Valve terminals within the alarm unit. WARNING, In order to shut properly, this type of valve need powering for at least 3 minutes. Connection of Water Solenoid Valve The 230VAC supply to the valves is generated from within the alarm unit. Having removed and opened the 3 pin socket, connect live to terminal 1, neutral to terminal 2 and Earth to the earth terminal PLEASE NOTE; The type of valve MUST be fitted with the arrow on its body facing the direction of flow, if not, the valve will not stop the flow of water. 11) Water Valve Override Procedure This future will only work if there is a current water leak detected alarm, the zone has not already been overridden and the alarm has been Muted. To put the system into shutdown override and re-open the water valve, press and keep pressed the Override push button. On pressing the button the unit will start beeping. Keeping the finger on the button and wait until the beeping to stops. Once this happens stop pressing the Mute button. The system will automatically cancel the override once the zone stops detecting a water leak. If the Override needs cancelling and the valve needs to be closed again, Press the Override button again and following the same procure will cancel the override and close the shutdown valve. 9

Zone 1-2-3 & 4 valve closed lamps 12) Beacon and beacon sounder If a beacon or beacon sounder is supplied connect to the three terminals identified as Sounder Beacon as follows. Sounder Beacon terminal block 12a) Non Mutable Beacon or beacon sounder If the beacon or the beacon sounder is to be active (On all the time) until the water leak alarm has cleared, connect as follows Terminal reference Connect Beacon / beacon sounder terminals to the following terminals +V Beacon +V or Strobe /Tone + terminal BOV Beacon -V or Strobe /Tone - terminal SOV NO connection to this terminal 12b) Mutable Beacon or beacon sounder If the beacon or the beacon sounder is to turn off when the Mute push button is pressed connect as follows. Terminal reference Connect Beacon / beacon sounder terminals to the following terminals +V Beacon +V or Strobe /Tone + terminal BOV NO connection to this terminal SOV Beacon -V or Strobe /Tone - terminal 12c) Mutable sounder Beacon on all the time If the beacon is to remain alight all the time an alarm is current but the sounder is to be turned off when the Mute push button is pressed connect as follows. Terminal reference Connect Beacon / beacon sounder terminals to the following terminals +V Strobe and Tone + terminal BOV Strobe - terminal SOV Tone - terminal Warning; if the above option 12c is required, remove the electrical link connected between the second (Strobe -) & third terminals (Tone -) terminals within the sounder. 10

13) Fitting the battery backup The battery should be fitted connected after the system as been commissioned. Place the battery within the housing in the space provided. Connect the small BLACK cable to the battery terminal and the RED with black dots wire to the batteries + terminal. If the battery is misconnected, the battery fuse located on the small PCB will blow. 14) Commissioning The unit will automatically calculate the total cable length each time it is power up. For this reason the unit MUST be clear of all alarms and faults. If the total cable length cant be calculated due to contaminants or water in the detection cable, the system will revert back to a standard water detection system with NO measurement to the leak. However, once the cable dries out the system will again automatically calculate the total detection cable length without the need of powering down the unit. Having connected the unit as described above, turn on the mains power to the unit. The display should display the following screen. If not, refer to the Fault Diagnostics below. If the unit powers up with the audible warning going, press the mute button and wait to see if the alarm clears. If the alarm remains after approximately 20 seconds, refer to the Fault Diagnostics below. Note; Before the system can be commissioned and tested, the alarm unit must be displaying this screen. With the unit powered and displaying the above screen, press the Override / View push button and check each zones cable length is correct. Next unplug the End of line terminator positioned at the end of the detection cable. The controller should display Zone (1-2-3-4) Damaged or Disconnected Cable and the audible warning device should sound, if not refer to the Fault Diagnostics below, press the Mute button, the audible warning device should stop. Replace the End of line terminator to return the system to normal. Using a cup of CLEAN water, immerse a small area (75mm long) of cable into the water. The controller should alternate between the following two screens. 11

Once the unit calculates the distance to the leak, the display will change to the following and the audible warning device should sound, if not refer to the Fault Diagnostics below. Press the Mute button the audible warning device should stop. Remove the water and wipe the cable with some tissue paper. Repeat for all other zones. 15) Fault Diagnoses To help with fault diagnoses individual and Fault lamps are provided so show the status of each zone. 12

Fault Display is OFF and the unit appears dead The Water Detected statement remains in the screen all the time. The display appears dead and does not show Water Detected even though the system has a water detected alarm and the audible warning device is sounding. Possible Reason 1) No power to the control unit. Test with a meter 2) The power fuse has blown. Test the fuse with a meter 1) The cable needs drying out after detecting water. Using tissue paper dry the cable. 2) The cable has a short between the sensors due to Contaminants. Clean the cable using water and tissue paper dry out afterwards 3) The cable has been damaged. Visually check the cable for damage. 4) The sensitivity of the detection system is too sensitive. Remove the lid from the small plastic box connected to the detection cable and turn the potentiometer until the system resets. 5) System fault. Return to manufacture 1) System fault. Return to manufacture The system will not record a water detected alarm, the Display and audible warning device do not react to water on the cable. The display shows faulty or disconnected cable all the time. Horn not working 1) Sensitivity could be too low or a Possible system fault. Remove the lid from the small plastic box connected to the detection cable and turn the potentiometer until the system goes into alarm. 2) System fault. Return to manufacture 1) The detection or signal cable is broken or disconnected. Check for cable faults or breaks. 2) Detection module fault. Dip part of the detection cable into a cup of water and see if it sets up an alarm. 3) Controller fault. Press the test button to setup an alarm. 4) System fault. Return to manufacture 1) System fault. Return to manufacture 2) The battery will not power the system 1) Battery discharged, disconnect a lead and test with meter. 2) Battery fuse blow, see item 10 3) Charger fault, disconnect a battery lead & check for 13.5V 13

16) Installation Drawings Water Leak Unit S0V B0V +V - + Beacon or Beacon Sounder See Item 12 above for more information L E N ZONE 1 ZONE 2 ZONE 3 ZONE 4 C A B N/O COM N/C N/O COM N/C N/O COM N/C N/O COM N/C N/O COM N/C N/O COM N/C L E N Z1 Valve D C A L E N Z2 Valve B L E N Z3 Valve D C A L E N Z4 Valve Z1 B D C A Z2 Z1 Z2 B D Common Common Fault Signal Cable ZONE 4 Water Detection Cable S P S P Socket/Plug Socket/Plug 240vac 5amp Supply Volt free contacts to a BMS system C A + B - D Yellow to "C" Red to "A+" Black to "B-" Blue to "D" repeat for all zones Zone 1 Valve 230VAC Zone 2 Valve 230VAC Zone 3 Valve 230VAC Zone 4 Valve 230VAC + - + - + - + - System using Water Detection Cable. Not all the shown devises may be available on your system 14

17) Housing Sizes Main control unit and Outstation type OS4V 15