Document TM777030, rev. B. Initial release: 22 January 2008 Current release: 16 February 2010

Similar documents
Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

Addendum. HART Communication with the FlexSonic Acoustic Detector. 1.1 Rev: 1/

AutroFlame X33AF. Addendum. Multi-spectrum IR flame detector. Protecting life, environment and property...

FlameGard 5 UV/IR HART

FlameGard 5 MSIR HART

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Rosemount 3051S MultiVariable Transmitter

FLAME DETECTORS & HART

SharpEye Flame Detector Selection Guide

User Guide OI/FEX100HART EN Rev. A. WaterMaster FEX100 HART Field Device Specification

Instructions AutroVu Explosion-Proof Universal Display AV20

Instructions. FlexVu Explosion-Proof Universal Display Unit Model UD Rev: 6/

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

Flame Detection Jon Sarfas

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

WinHost Configuration and Diagnostic Software. User Guide

MO n : 12JMC rév A

SAFEYE XENON 700. Hydrocarbons and ethylene detection. Heated optics. 10-year Warranty for the Xenon flash bulb. SIL 2 according to IEC 61508

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

The SharpEye 40/40I (IR3) Flame Detection

CTT8 TEMPERATURE MONITOR DEVICE

Toxic Gas Detection. Model F12. Toxic Gas Detection

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

SafEye OPEN-PATH GAS DETECTION SYSTEM XENON 700. We INVENTED it... We PERFECTED it! Patent No. US 5,281,816; US 6,061,141; EP

The SharpEye 40/40L4-L4B (UV/IR) Flame Detection

HigH Performance Low cost flame Detection. Courtesy of Foster + Partners. The New 20/20M MINI FLAME DETECTOR SERIES

RPM1600 Series Room Pressure Monitors

Model D12-IR. Digital Gas Transmitter...

Power Flame Incorporated

Dryer Controller M720

FIRERAY 5000 range USER GUIDE

SafEye OPEN-PATH GAS DETECTION SYSTEM XENON 700S

Model 20/20MI Mini Triple IR (IR3) Flame Detector

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

40/40 Series UV/IR Flame Detector Models 40/40L, LB and 40/40L4, L4B

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

The SharpEye 40/40M (Multi IR) Flame Detection

DET-TRONICS. SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION FEATURES

The SharpEye 40/40I (IR3) Flame Detection

Modbus RTU RS485 Manual

Ultra Fast UV/IR Flame Detector Model 40/40UFL

F Technical Bulletin SC 370 SMART Modbus Interface

Deltapilot S FMB70. Functional Safety Manual. Level and Pressure Measurement with Output Signal ma

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

CCTV Model Flame Detector. User and Maintenance Manual TM , Rev. A January 2005

Instructions Electrochemical Toxic Gas Detector GT3000 Series Includes Transmitter (GTX) and Sensor Module (GTS) 5.

Configuration Data Sheet

SCAN20 Series Gas Detection Controller

Turbimax CUE21 / CUE22

The Most Versatile Flame Detectors in the World. Optical Flame Detection Solutions

STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT Revision 4 September 2017

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

Radar Transmitters SITRANS LR400 (HART/PROFIBUS PA) Quick Start Manual 03/2013 SITRANS

F&G detection system for LNG plants

Products no longer available

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

The SharpEye 40/40R (IR) Flame Detection

Model 3300 Technical Support and Installation Manual

Laptop / PC Programming Manual

Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

3600 Series UV Flame Detector Models 3600U and UB

Each burner shall be equipped with a Micro-Processor Based Burner Management Flame Safeguard and Parallel Positioning Control System.

Danfoss gas detection units

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

The Most Versatile Flame Detectors in the World. Optical Flame Detection Solutions

Configuration and Operation Manual for the Unipos

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

Rosemount 644H and 644R Smart Temperature Transmitters

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

OEM REFRIGERANT GAS SENSORS for Leak Detection & Measurement

The EN54 Part 2 & 4 Fire System

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

Motorised Infrared Optical Beam Smoke Detector. User Guide

Mini Triple IR (IR3) Flame Detector. User and Maintenance Manual

UNC100 Integra Manual

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

STEAMPAK Series BurnerPAK BMS Burner Management Systems

User s Manual DCU 305 R3 DCU 305 R3 LT. Diesel Engine Control Unit. Auto-Maskin

Compod. Instruction Manual IM-COMPOD Revision: C.1, November 2010

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Tender Document. MR 193/ Design, Supply & Commission New Control Panel for Ruston 16RK270 Generator

Installation Guide and Operating Manual MAN0932_V1_ _Rev B_08-12

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

SCAN200E USER S MANUAL

ZITON RADIO LOOP MODULE

Modbus TCP/IP Option Instruction Manual

Pump-Down Controller MODEL 4052

3600 Series UV/IR Flame Detector Models

Ultra Fast UV/IR Flame Detector

Mass Sensors, Inc. Profile. Applications. Technology Baur Blvd, St. Louis, MO (314)

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

Model OI-6000K Sensor Assembly

SMS GSM Alarm Messenger

Transcription:

Peckman Industrial Park, 218 Little Falls Road, Cedar Grove, NJ 07009 Tel. 973-239-8398 Fax 973-239-7614 Email: spectrex@spectrex-inc.com HART Communication With the SharpEye Flame Detector Document TM777030, rev. B Initial release: 22 January 2008 Current release: 16 February 2010 HART is a registered trademark of the HART Communication Foundation SharpEye is a registered trademark of Spectrex inc.

HART Host Specification: SharpEye revision B TABLE OF CONTENTS 1. Introduction... 3 1.1 Scope... 3 1.2 Purpose... 3 1.3 Who should use this document?... 3 1.5 References... 3 2. Product Overview... 3 3. Inreconncting the HART Communicator with the Detector... 4 4. HART Device Description Language... 5 5. HART Menu structure... 6 5.1 SharpEye Root Menu... 7 5.2 Status Menu... 8 5.3 Device Setup Menu... 9 5.4 HART Output Menu... 10 5.4.1 HART Status Menu... 11 Annex A. Field Device Status... 12 Annex B. Fire Detection Sensor Type Codes... 13 Annex C. Revision History... 14-2 -

HART Host Specification: SharpEye revision B 1. INTRODUCTION 1.1 Scope Digital communication with the SharpEye Flame Detector allows the operator to monitor the status of the detector, determine factory settings and initiate field tests. This document provides guidance for establishing HART communication and describe the HART menu structure when using the SharpEye with a HART Handheld Communicator, PC or other process interface device that supports DDL. 1.2 Purpose This specification is designed to compliment other documentation (e.g., the SarpEye user manual) by providing a complete, unambiguous description of the HART Host Application and Communication. 1.3 Who should use this document? The specification is designed to be a technical reference for System Integrators and End Users. 1.4 References HART Field Communications Protocol Specification, HCF_SPEC-12, Available from the HCF. SharpEye Triple IR (IR3) Flame Detector Model 20/20SI User's and Maintenance Manual, TM 784100, Available from 2. PRODUCT OVERVIEW The SharpEye is a family of Flame Detectors, which incorporate advanced optical spectral analysis of flames. SharpEye Flame Detectors operate reliably in the harsh conditions of offshore drilling and production platforms, FPSO vessels, fuel loading facilities, LNG and LPG plants, oil refineries, aircraft hangars, paint spray booths, gas turbine power stations, chemical and petrochemical plants. These detectors employ the latest UV (Ultra Violet), IR (Infrared), UV/IR (Ultra Violet & Infrared), IR 3 (Triple IR patented multi-spectrum detection) and CCTV Flame Detection technologies. Depending on the specific model, the SharpEye flame detector can include the following interfaces: 4-20mA current output, HART communication (FSK), relays, RS485 ModBus communication, status LEDs. - 3 -

HART Host Specification: SharpEye revision B 3. INTERCONNECTING THE HART COMMUNICATOR WITH THE DETECTOR The host connects to the device via the two-wire 4-to-20mA current loop. Refer to the User s and Maintenance Manual for connection details. This is the only output from this device, representing the Fire Detection channel. This output corresponds to the Primary Variable (PV). HART Communication is supported on this loop. Point-to-Point Mode. The HART Communicator can connect to SharpEye at any wiring termination point in the analog output signal loop. Connect the HART communicator in parallel with 500 Ohm load resistor. The HART connections are non-polarized. Switch on the HART Communicator. If a device is found, the HART Communicator displays the Main Menu. If no device is found, check the connections and verify the presence of a 500 ohms load resistance in series in the loop. Multidrop Mode Optical flame detectors are life safety devices and require the 4-20 ma loop for transmitting important detector status data. They should not be used in conjunction with multidrop mode, If multidrop mode required, the alarm and fault relay contacts must be connected directly to the safety system or fire panel for signaling purposes. SharpEye Flame Detector 4-20 out A R L HART Modem PC with appropriate software GND Figure 1: HART Connection block diagram. - 4 -

HART Host Specification: SharpEye revision B 4. HART DEVICE DESCRIPTION LANGUAGE The HART protocol incorporates a concept called the Device Description Language (DDL) that enables all suppliers of HART instruments to define and document their products in a single consistent format. This format is readable by handheld communicators, PCs and other process interface devices, regardless of manufacturer, allowing full functionality from any HART device. NOTE For full compliance of the Flame Detector with the HART Host application a SharpEye Device Description should be installed on your machine. A complete listing of the HCF DD library is available for download in manufacturer and device type sequence at the HCF home page. SharpEye Device Description allows presenting the HART menu in a graphical mode, this option is not supported by all hosts manufacturers, for using the graphical mode please refer to HART host literature. - 5 -

HART Host Specification: SharpEye revision B 5. HART MENU STRUCTURE The changeable options of the menu is bolded, the sub menus are underlined and buttons are marked with (b) Sharp Eye Root Menu 3. Dev. ID 4. Dev. Model 5. PV Snsr s/n 6. Tag 7. Long Tag 8. Descriptor 9. Message 10. Final asmbly num 11. Date 12. Status (b) 13. Self Test 14. Status Menu 15. Device Setup Menu 16. HART Output Menu Status Menu 1. 4-20 Value 2. Internal Temperature 3. Input Voltage 4. Heater Control 5. Heater State 6. Operating Time 7. Status (b) 8. Self Test Device Setup Menu 3. Dev ID 4. Config. Changed Counter 5. Enable Alarm Latch 6. Activate ACC relay on Warning 7. Enable Auto BIT 8. Activate ACC relay on Successful BIT 9. Activate Alarm on Successful BIT 10. ACC as E.O.L 11. Sensitivity 12. Alarm Delay 13. Heater Mode 14. Heater On Temp. 15. Poll Address 16. Loop Current Mode HART Output Menu 1. Num. Req. Preams. 2. Num. Resp.Preams. 3. Universal Rev. 4. Fld. Dev Rev. 5. Software Rev. 6. PV % rnge. 7. PV LRV 8. PV URV 9. PV Class 10. PV PDQ 11. PV LS 12. PV LSL 13. PV USL 14. PV Min. Span 15. PV Damp 16. HART Status Menu HART Status Menu (b) 1. Reset 'Configuration Changed' flag - 6 -

HART Host Specification: SharpEye revision B 5. 1 SharpEye ROOT MENU When HART communication is established, the first menu displayed is the Sharp Eye Root Menu. Sharp Eye Root Menu 3. Dev. ID 4. Dev. Model 5. PV Snsr s/n 6. Tag 7. Long Tag 8. Descriptor 9. Message 10. Final asmbly num 11. Date 12. Status 13. Self Test 14. Status Menu 15. Device Setup Menu 16. HART Output Menu 1 Manufacturer Read 2 Model Sharp Eye. Read 3 Dev ID Device unique identification number. Read 4 Dev. Model Device sensor type (see Annex B, Table B1: Fire Read Detection Sensor Type Codes). 5 PV Snsr s/n Serial Number of this device. Read 6 Tag Text that is associated with the field device installation R/W (16 chars). This text can be modified and used by the operator any way. 7 Long Tag Text that is associated with the field device installation R/W (32 chars). This text can be modified and used by the operator any way. 8 Descriptor Text associated with the field device that can be used R/W by the operator in any way. 9 Message Text associated with the field device that can be used by the operator in any way. R/W 10 Final asmbly num A number that is used for identification purposes, and is R/W associated with the overall field device. 11 Date Any Date chosen by the operator to be used for any R/W purpose. 12 Status Indicates a field device condition see Annex A Read 13 Self Test Internal tests are performed and any detected problems Button are reported in "Status". 14 Status Menu Current operating status and diagnostic information. Menu 15 Device Setup Menu Provides Access to various setup and configurations. Menu 16 HART Output Menu HART Specific Variables Menu - 7 -

HART Host Specification: SharpEye revision B 5. 2 STATUS MENU Sharp Eye Root Menu 3. Dev. ID 4. Dev. Model 5. PV Snsr s/n 6. Tag 7. Long Tag 8. Descriptor 9. Message 10. Final asmbly num 11. Date 12. Status 13. Self Test 14. Status Menu 15. Device Setup Menu 16. HART Output Menu Status Menu 1. 4-20 Value 2. Internal Temperature 3. Input Voltage 4. Heater Control 5. Heater State 6. Operating Time 7. Status 8. Self Test 1 4-20 Value The actual analog output of the Fire Detection Channel. Read 2 Internal Actual integral temperature of the detector (in deg C). Read Temperature 3 Input Voltage Actual detector's supply voltage. Read 4 Heater Control Indicates if the heater control is manual or automatic. Read 5 Heater State Indicates the current state of the heater (ON or OFF). Read 6 Operating Time Displays the total detector's operating time from last Read power up. 7 Status Indicates a field device condition see Annex A Read 8 Self Test Internal tests are performed and any detected problems are reported in "Status". Button - 8 -

HART Host Specification: SharpEye revision B 5. 3 DEVICE SETUP MENU Sharp Eye Root Menu 3. Dev. ID 4. Dev. Model 5. PV Snsr s/n 6. Tag 7. Long Tag 8. Descriptor 9. Message 10. Final asmbly num 11. Date 12. Status 13. Self Test 14. Status Menu 15. Device Setup Menu 16. HART Output Menu Device Setup Menu 3. Dev ID 4. Config. Changed Counter 5. Enable Alarm Latch 6. Activate ACC relay on Warning 7. Enable Auto BIT 8. Activate ACC relay on Successful BIT 9. Activate Alarm on Successful BIT 10. ACC as E.O.L 11. Sensitivity 12. Alarm Delay 13. Heater Mode 14. Heater On Temp. 15. Poll Address 16. Loop Current Mode Manufacturer Read Model Sharp Eye. Read Dev ID Device unique identification number. Read Config. Changed The number of Device Configuration changes since the Read Counter manufacture. Enable Alarm Enable alarm relay to stay energized after exiting the R/W Latch Alarm Mode. Activate ACC relay Activates ACC relay during Warning status. R/W on Warning Enable Auto BIT Enables automatic self test. R/W Activate ACC relay Activates ACC Relay after successful self test. R/W on Successful BIT Activate Alarm on Activates Alarm after successful self test R/W Successful BIT ACC as E.O.L Accessory Relay is Activated at Power on continuously. R/W Sensitivity Detectors Sensitivity setting. R/W Alarm Delay Defines delay between Fire Detection and Alarm. R/W Heater Mode 3 Heater Modes available- Auto, On, Off. R/W Heater on Temp. This option is active in Heater Auto mode it allows the R/W operator to set the temperature at which the optics heater begins operating. Poll Address Address used by the host to identify a field device. R/W Loop Current Mode Enables to choose between fixed or not fixed current R/W mode. - 9 -

HART Host Specification: SharpEye revision B 5. 4 HART OUTPUT MENU Sharp Eye Root Menu 3. Dev. ID 4. Dev. Model 5. PV Snsr s/n 6. Tag 7. Long Tag 8. Descriptor 9. Message 10. Final asmbly num 11. Date 12. Status 13. Self Test 14. Status Menu 15. Device Setup Menu 16. HART Output Menu HART Output Menu 1. Num. Req. Preams. 2. Num. Resp.Preams. 3. Universal Rev. 4. Fld. Dev Rev. 5. Software Rev. 6. PV % rnge. 7. PV LRV 8. PV URV 9. PV Class 10. PV PDQ 11. PV LS 12. PV LSL 13. PV USL 14. PV Min. Span 15. PV Damp 16. HART Status Menu 1 Num. Req. Preams HART specific synchronization messages. Read 2 Num. Resp. Preams. HART specific synchronization messages. Read 3 Universal Rev. HART protocol revision. Read 4 Fld. Dev Rev. Field Device hardware revision. Read 5 Software Rev. Field Device software revision. Read 6 PV % rnge. Percent of Range. The variable that tracks the Digital Read Value representation with respect to the range defined by the Lower Range and Upper Range Value, for normal operating modes. The units of this variable are always in percent. 7 PV LRV PV Upper Range Value. Read 8 PV URV PV Lower Range Value. Read 9 PV Class Not Classified Read 10 PV PDQ Indicates the status of the Primary Variable Read 11 PV LS Indicates if the Primary Variable is limited. Read 12 PV LSL "Good" Status Lower Range Value. Read 13 PV USL "Good" Status Upper Range Value. Read 14 PV Min Span PV Upper Range Value - PV Lower Range Value. Read 15 PV Damp. The time takes to PV to change his value. Read - 10 -

HART Host Specification: SharpEye revision B 5. 4. 1 HART STATUS MENU Sharp Eye Root Menu 3. Dev. ID 4. Dev. Model 5. PV Snsr s/n 6. Tag 7. Long Tag 8. Descriptor 9. Message 10. Final asmbly num 11. Date 12. Status 13. Self Test 14. Status Menu 15. Device Setup Menu 16. HART Output Menu HART Output Menu 1. Num. Req. Preams. 2. Num. Resp.Preams. 3. Universal Rev. 4. Fld.Dev Rev. 5. Software Rev. 6. PV % rnge. 7. PV LRV 8. PV URV 9. PV Class 10. PV PDQ 11. PV LS 12. PV LSL 13. PV USL 14. PV Min. Span 15. PV Damp 16. HART Status Menu HART Status Menu 1. Reset 'Configuration Changed' flag 1 Reset 'Configuration Changed' flag Clears the "Configuration Changed" bit. Button - 11 -

HART Host Specification: SharpEye revision B ANNEX A: FIELD DEVICE STATUS Field Device Status N B BIT FAULT IR UV W A F Explanation Normal State Self test is performed Self test failed Infra Red Detection Ultraviolet Detection Fire Warning Fire Alarm General Fault - 12 -

HART Host Specification: SharpEye revision B ANNEX B: Fire Detection Sensor Type Codes B1. Fire Detection Senor Type Codes Code 0x0066 0x0067 0x0068 0x0166 0x0190 0x0191 0x0192 0x0193 0x0194 0x0195 0x0196 0x0197 0x0198 0x0290 0x0291 0x0292 0x0293 0x0294 0x0295 0x0296 0x0297 0x0298 0x0366 0x0390 0x0391 0x0392 0x0393 0x0394 0x0395 0x0396 0x0397 0x0398 0x0466 Definition 20/20SI 20/20CTIN 20/20CTIP 20/20XI-1 40/40I-1 40/40R-1 40/40LB-1 40/40L-1 40/40U-1 40/40M-1 40/40UB-1 40/40L4-1 40/40L4B-1 40/40I-2 40/40R-2 40/40LB-2 40/40L-2 40/40U-2 40/40M-2 40/40UB-2 40/40L4-2 40/40L4B-2 20/20XI-3 40/40I-3 40/40R-3 40/40LB-3 40/40L-3 40/40U-3 40/40M-3 40/40UB-3 40/40L4-3 40/40L4B-3 20/20SH - 13 -

HART Host Specification: SharpEye revision B ANNEX C: REVISION HISTORY C1. Revision 1.0 Initial Revision. C2. Revision B Updated to comply with the third release of the DD. The changes made to stand along with 375 demands. 1. Device Setup Menu -> Configuration Changed y/n was canceled 2. In HART status menu, everything besides Reset Configuration Changed Flag was canceled. - 14 -